Flowserve 1400 User Manual

Valtek Logix 1400
Digital Positioner
GENERAL INFORMATION
The following instructions are designed to assist in unpacking, installing and performing maintenance as required on Valtek® Logix™ 1400 digital positioners. Series 1000 is the term used for all the positioners herein; however, specific numbers indicate features specific to a model (i.e. Logix 1400 digital positioner indicates that the positioner uses FOUNDATION™ fieldbus protocol). Prod- uct users and maintenance personnel should thoroughly review this bulletin prior to installing, operating, or per­forming any maintenance on the valve.
More detailed operation instructions are included in other manuals in the owner’s manual binder; refer to them when more information is needed.
Separate Flowserve Installation, Operation, Maintenance instructions cover the valve (IOM 1 or IOM 27) and actuator (IOM 2 or IOM 31) portions of the system and other accessories. Refer to
Installation & Reference Guide
implementation. Refer to the appropriate instructions when this information is needed.
To avoid possible injury to personnel or damage to valve parts, users must strictly adhere to WARNING and CAUTION notes. Modifying this product, substituting non-factory or inferior parts, or using maintenance procedures other than outlined could drastically affect performance or be hazardous to personnel and equipment and may void existing warranties.
Logix 1400 Digital Positioner
for details on fieldbus
WARNING: Standard industry safety practices must be adhered to when working on this or any other process control product. Specifically, personal protective and lifting devices must be used as warranted.
Unpacking
1. While unpacking the Logix 1400 positioner, check the packing list against the materials received. Lists describing the system and accessories are included in each shipping container.
2. When lifting the system from the shipping container, position lifting straps in a way that avoids damaging mounted accessories. Systems with valves up to six inches may be lifted by actuator lifting ring. On larger systems, lift unit using lifting straps or hooks through the yoke legs and outer end of body.
WARNING: When lifting a valve/actuator assem­bly with lifting straps, be aware the center of gravity may be above the lifting point. Therefore, support must be given to prevent the valve/ actuator from rotating. Failure to do so can cause serious injury to personnel or damage to nearby equipment.
3. In the event of shipping damage, contact the shipper immediately.
4. Should any problem arise, contact a Flowserve representative.
Valtek Part No. 164713 46-1
Table of Contents
General Information .................................................... 1
Unpacking .................................................................. 1
Logix 1400 Digital Positioner Overview ...................... 2
Specifications ............................................................. 3
Positioner Operation ................................................... 3
Tubing Positioner to Actuator ..................................... 4
Wiring and Grounding Guidelines ................................ 4
Driver Module Assembly ............................................. 5
Spool Valve Cover ...................................................... 6
Regulator .................................................................... 7
Internal Coalescing Filter ............................................ 7
Main PCB Assembly .................................................. 7
Collector Board ........................................................... 7
Field Terminations ...................................................... 8
Stem Position Sensor................................................. 8
LED Indicators ............................................................ 9
Re-Cal Button ............................................................. 9
Checking or Setting Internal Regulator Pressure ...... 10
Checking or Setting the Driver Module
Minimum Pressure ............................................... 10
Linear Mark I Valve Mounting................................... 11
Standard Rotary Mounting Procedure ....................... 12
Optional Rotary Mounting Procedure ........................ 13
Troubleshooting the Logix 1400 Digital Positioner .... 13
Theory of Operation.............................................. 13
Mounting and Installation ......................................... 15
Calibration ................................................................ 16
Control and Tuning ................................................... 16
Alarms ...................................................................... 18
Alerts ........................................................................ 19
Travel Accumulator .................................................. 20
Cycle Counter ........................................................... 20
Position Deviation ..................................................... 20
Advanced Features .................................................. 20
Glossary and Definitions ........................................... 23
Transducer Block Signature Parameters .................. 24
Exploded View of Positioner..................................... 27
Available Spare Parts Kits ....................................... 28
Troubleshooting Tables ............................................ 29
Positioner Mounting Kits........................................... 32
Logix 1400 Digital Positioner
Logix 1400 Digital Positioner Overview
The Logix 1400 digital positioner is a two-wire, FOUNDATION fieldbus compliant, digital valve positioner. The Logix 1400 digital positioner also utilizes the fieldbus protocol to allow two-way remote communications with the posi­tioner. The Logix 1400 digital positioner can control both double- and single-acting actuators with linear and rotary mountings.
Since the positioner is insensitive to supply pressure changes and can handle supply pressures from 35 to 150 psig, a supply regulator is usually not required; however, an air filter is required due to the close clearances in the spool assembly.
NOTE: The air supply should conform to ISA Standard S7.3 (a dew point at least 18° Fahrenheit less than ambient temperature, particle size below one micron, and oil content not to exceed one part per million).
46-2 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Specifications
Electrical Specifications
ylppuSrewoPsubdleif,eriw-owT
ylppuS.B.FCDV0.23-0.9
wardtnerrucmumixaMAm22
snoitacinummoCFNOITADNUO subdleif
NI Configurator Software Specifications
retupmoCrossecorp68408muminiM
,TNro59swodniWgninnur BM-23(yromemlatotBM-61
BM-02,)dednemmocer
evirdyppolfhcni-5.3
rotacinummocBF
drac
)snoitporofINtcatnoc(
Positioner Specifications
dnabdaeDelacslluf%1.0<
siseretsyHelacslluf%2.0<
ytilibataepeRelacslluf%5.0<
ytiraeniL,)yrator(%5.0<
tanoitpmusnoCriA
)grab4(gisp06
MFCS%3.0<
3
mN5.0(
)rh/
Physical Specifications
gnitarepO
egnaRerutarepmeT
gnisuoHdetniap-redwop,tsaC
thgieW)gk9.3(sdnuop5.8
o
04-
o
04-(
o
581+otF
F
o
58+otC
)C
leetssselniats,munimula
sdnuop5.02munimula
leetssselniats)gk3.9(
Hazardous Area Certifications
foorPnoisolpxE,1viD,1ssalCASC/MF
gnidnep,D,C,BspuorG
eno,ecapsksiddrahelbaliava
evidnecninoN,2viD,1ssalCASC/MF
gnidnep,D,C,B,AspuorG
rotarugifnocINhtiwdeilppuS
efaSyllacisnirtnI,1viD,1ssalCASC/MF
gnidnep,D,C,B,AspuorG
CE Mark Qualifications
evitceriDCME
CEE/633/98
22055NE
elacslluf)raenil(%8.0
evitceriDDVLelbacilppAtoN
04105VNE,2-4-00016NE
1-18005NE,4-4-00016NE
1-18005NE,2-28005NE
CDV57<;CAV05<sitinU
Positioner Operation
The Logix 1400 positioner is an electric feedback instru­ment. Figure 1 shows a Logix 1400 positioner installed on a double-acting actuator for air-to-open action. Position­ing is based on a balance of two signals: one proportional to the command input signal and the other proportional to the valve stem position.
The supply pressure for the positioner pressure modula­tor is tapped off the main supply and is filtered as it passes through a field-replaceable, coalescing filter element in the module. This air passes through an internal pressure regulator that regulates it to approxi­mately 22 psig. The air then passes through an orifice that restricts the flow and air consumption.
The pressure modulator further controls the air from 6-12 psig, using a spring-diaphragm flapper that is attracted by an electromagnet to a nozzle. A temperature compen-
sated hall effect sensor mounted on a circuit board senses the spool valve position. The hall effect sensor and circuitry create an inner feedback loop, which deter­mines how much current to send to the electromagnet for a desired spool valve position. The electromagnet in the feedback loop varies the nozzle-flapper spacing, which regulates the output pressure between 6 and 12 psig, proportional to the digital positioning algorithm.
When the command and stem position signals are equal, the system will be in equilibrium and the valve stem will be in the position called for by the command signal. If these opposing signals are not equal, the spool valve will move up (or down) and, by means of the pressure modulator, change the output pressures and flow rate. This will cause the actuator piston to move until the signal of the position sensor equalizes with the command signal.
46-3Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Air-to-Open
Configuration
Flame Arrestors
Spool Valve
Exhaust
OUTPUT 1
Collector Board Pressure Sensor
Air Supply
Digital Position Algorithm
LED
Dis-
play
OUTPUT 2
Exhaust
OO
Stem Position Sensor
Hall Effect Sensor Electromagnetic Coil Nozzle
Flame Arrestor
Figure 1: Logix 1000 Digital Positioner Schematic
Detailed Sequence of Positioner Operations
The positioner operates on a pressure equilibrium prin­ciple with a spool valve apportioning supply to the actuator. An increase in the command signal causes the modulator pressure to increase, pushing the spool as­sembly upward from its equilibrium position. This opens the spool valve ports, supplying air to output 1 and exhausting air from output 2. This causes the actuator piston to move upward.
The upward motion of the piston is transmitted back to the positioner through the stem-position feedback link­age. The piston continues to stroke upward until the stem-position signal of the sensor increases sufficiently to counter the command signal being sent to the control algorithm. At this point, the spool is at its equilibrium position as the pressures in the cylinder stabilize and the air flow to the actuator decreases. The computer will then make small adjustments to fine-tune the desired position and compensate for changes in dynamic loading.
A decrease in the command signal reverses the described actions, causing a proportional downward movement of the actuator piston and stem.
Tubing Positioner to Actuator
Proper tubing orientation is critical for the positioner to function correctly and have the proper failure mode. Referring to Figure 1 note that for air-to-open valves, the output 1 port of the positioner manifold is tubed to the bottom side of the actuator. The output 2 port of the
Main PCB Tray
Ribbon Cable
Flame Arrestor
Filter
Regulator
Orifice
Flapper
positioner manifold is tubed to the top side of the actuator. For air-to-close valves the above configuration is reversed.
Wiring and Grounding Guidelines Input Cable Shielding (Figure 2)
The fieldbus signal to the Logix 1400 digital positioner should be in shielded cable. Shields must be tied to a ground at only one end of the cable to provide a place for environmental electrical noise to be removed from the cable. In general, shield wire should be connected at the source.
Cable Requirements
The Logix 1400 digital positioner utilizes the fieldbus communication protocol. Refer to Fieldbus Foundation document AG-140, Wiring and Installation 31.25 kbit/s, Voltage Mode, Wire Medium Application Guide for full information on wiring and building fieldbus networks.
Grounding Screw
The green grounding screw, located inside the termina­tion cap, should be used to provide the unit with an adequate and reliable earth ground reference.
This ground should be tied to the same ground as the electrical conduit. Additionally, the electrical conduit should be earth grounded at both ends of its run. The green grounding screw must not be used to terminate signal shield wires.
46-4 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Field Terminations
FB Connection Terminals
Housing EARTH Terminal
Shielded Cable
Ground
Fieldbus connection
Figure 2: Field Termination
Driver Module Assembly
The driver module assembly moves the spool valve by means of differential pressures on its diaphragm. Air is routed to the module from the interface plate through a hose that connects to the assembly through a hose barb with an integral orifice. Wires from the module connect the hall effect sensor and the pressure modulator coil to the collector board.
Driver Module Assembly Replacement
To replace the driver module assembly, refer to Figures 3 - 5, 7 and 19 then proceed as outlined below. The following tools are required:
1
/4-inch open-end wrench
1
/2-inch hex wrench Phillips screwdriver Driver Module removal tool
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the driver module cover, using a wrench (Figure 4). Do not force the cover. If undue resistance is encountered, use the slots to loosen cover.
4. Remove the spool valve cover by removing the screw and sliding the cover assembly backwards until the tab is clear of the slot. It is not necessary to remove the sheet metal cap from this assembly (Figure 7).
5. Being careful not to lose the nylon washers, remove the two phillips-head screws that attach the driver module to the main housing (Figure 5).
6. Remove the spool valve block by removing the two phillips-head screws and carefully sliding the block off the spool (Figure 5).
1
/2-inch hex
CAUTION: The spool (extending from the driver assembly) is easily damaged. Use extreme cau­tion when handling driver assembly.
7. Remove the tubing from the orifice in the driver module assembly. Using a
1
/4-inch open-end wrench,
remove the orifice from the driver module (Figure 4).
8. Remove the two wiring connections that link the driver module assembly to the collector board. (Figure 4).
9. Feed the wires back through the housing so they extend backward toward the driver module opening. This will allow the driver module to thread out without tangling the wires.
10. Grasp the driver module cap with the driver module removal tool and rotate the entire driver module counter clockwise to remove. After it is threaded out, carefully retract the driver module from the housing to avoid damaging the spool.
11. Take the new driver module and verify that the O-ring and boot are in place. Lay the wires back along the modulators as shown in Figure 3 and hold in place.
12. Gently direct the driver module into the housing bore, making sure the spool does not hit the housing. Turn driver module clockwise to thread it into the housing. Continue rotating the module until it bottoms out.
13. Once the threads are fully engaged, rotate the driver module counter clockwise until the flat on the driver module and the flat on the housing are aligned. This will align the screw holes for the next step (Figure 3).
14. Verify that nylon gaskets are in the counter bores in the driver module retaining screw holes as shown in Figure 5.
15. Insert two driver-to-housing screws into the driver housing through the counter-bored holes in the positioner main housing. Tighten evenly with a phillips screwdriver.
Collector Board
Pressure Modulator Connection
Hall Sensor Connection
Flat in Housing
Protective Boot
O-ring
Orient this flat parallel to flat in housing
Minimum Pressure Set Screw (factory calibrated)
Driver Module Assembly
Install orifice after driver module is in housing
Figure 3: Driver Module Assembly
46-5Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Orifice
Nylon Gaskets
Driver to Housing Screws
Spool
Spool Valve Screws
Driver Module Cover
Figure 4: Driver Module Orifice
16. Feed the driver module wires into the main chamber of the housing and connect them to collector board.
17. Verify that the three O-rings are in the counter-bores on the machined platform where the spool valve block is to be placed (Figure 19)
18. Carefully slide the block over the spool, using the machined surface of the housing base as a register (Figure 5). Slide the block toward the driver module until the two retaining holes line up with the threaded holes in the base.
19. Install two spool-valve screws and tighten securely with a phillips screwdriver.
20. Insert the orifice into the threaded hole in the driver module assembly. Tighten with a 1/4-inch open-end wrench (Figure 4). Attach the flexible tubing from the interface plate to this fitting.
21. Set the minimum pressure as described on page 10.
22. Thread driver module cover into driver module bore in the main housing.
Spool Valve Block
Housing
Figure 5: Spool and Block
5. Remove the molded filter element by pulling it straight out of chamber cover vent piece.
6. Install O-ring into base of chamber cover vent piece as shown in Figure 6.
7. Place new molded filter element into the chamber cover vent piece. This element provides part of the track to secure the O-ring installed in the last step.
8. Place spool valve shroud onto spool valve cover.
9. Place the spool valve cover assembly in place by setting it on the ramp and sliding it until the tab seats in the slot (Figure 7) and secure with No. 8-32 screw.
O-ring
Spool Valve Cover
The spool valve cover incorporates a coalescing filter element in a two-piece cover. This protects the spool valve chamber from moisture and provides a low back pressure vent for exhaust air from the spool valve.
Replacing Filter in Spool Valve Cover
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the spool cover by removing the screw and sliding the cover assembly backward until the tab is clear of the slot. The sheet metal cover may be removed and cleaned with a brush or by blowing out with compressed air (Figure 7).
4. Remove the O-ring from around hydrophobic filter element and set aside (Figure 6).
46-6 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Hydrophobic Filter
Spool Valve Cover
Spool Valve Shroud
Figure 6: Spool Valve Cover Assembly
Spool Valve Cover
Screw
Figure 7: Spool Valve Cover Assembly
Ribbon Cable Main PCB Assembly Screws (3)
Regulator
The regulator reduces the pressure of the incoming supply air to a level that the driver module can use.
Replacing Regulator
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and unscrew the regulator from the interface plate, exercising caution not to damage the collector board (Figure 19).
4. Verify that the O-rings are in place on the base of the new regulator
5. Replace the regulator by threading into the port on the interface plate.
6. Check regulating pressure to ensure that it is set at 22 psi.
Internal Coalescing Filter
The internal coalescing filter ensures that supply air is clean and dry before it gets to the regulator. Because the air has already been filtered before this point, the element should not require extended maintenance.
Replacing Input Filter Element (Figure 19)
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and remove collector board by disconnecting the wiring and removing three screws that attach it to the housing. Each cable has its own unique connector to prevent improper connections.
4. Remove the four No. 6-32 hex screws from the filter housing and remove filter housing.
5. Remove the old coalescing filter from the bore in the interface plate.
Figure 8: Main PCB Assembly
6. Insert new coalescing filter into the bore on interface plate.
7. Verify that the O-ring is in place in filter housing.
8. Set filter housing over coalescing filter and secure with four No. 6-32 screws.
9. Replace collector board and reconnect wiring.
Main PCB Assembly
The main PCB assembly contains the circuit boards and processor that perform the control functions of the positioner. The boards are conformal-coated with a protective silicon coating. This module can be easily replaced if positioner upgrades are desired. None of the components are user-serviceable. This module is to be replaced as an entire unit.
Replacing Main PCB Assembly (Figure 8)
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and disconnect the ribbon cable from the collector board.
CAUTION: To avoid damaging any components, exercise caution by gently raising the locking tab to release the ribbon cable.
4. Remove the PCB assembly by removing the three No. 6-32 screws and lifting out of housing.
5. Place the new PCB assembly on bosses inside the positioner housing.
6. Insert three No. 6-32 screws through the boards, with the nylon washers on the bottom into the threaded bosses and tighten evenly, using a phillips screw­driver. Do not overtighten.
7. Reconnect the ribbon cable to the collector board.
46-7Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Collector Board
The collector board assembly provides a central routing for all electronic connections in the positioner, linking the pressure modulator coil, hall effect sensor and field inputs to the main electronics. The collector board assembly also serves as a mounting for the pressure sensors used on the advanced model of the positioner.
Removing Collector Board (Figure 19)
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and disconnect the wiring to the collector board. Each cable has its own unique connector to prevent mistakes in reconnecting.
4. Remove the three No. 8-32 screws holding the collector board to the housing.
5. Remove the collector board.
Replacing/Upgrading Collector Board
1. For the advanced collector board (Logix 1x1x), check that pressures sensors are in place on back of collector board. For the standard model (Logix 1x0x), make sure the adapter block is securely fastened to the collector board.
2. Make sure the O-rings are in place in the counterbores of the pressure ports.
3. Set collector board assembly in place.
4. Insert three No. 8-32 screws through collector boards into the threaded holes on sensor shelf and standoff.
5. Tighten all three screws.
6. Connect the main ribbon from electronics tray.
7. Reconnect wiring to the collector board.
Field Terminations
The field terminations board provides a connection point inside the explosion-proof housing for all hookups to the positioner. While the board is not likely to experience a failure, it can easily be replaced to upgrade the positioner.
Replacing Field Terminations Board
(Figure 19)
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and disconnect the field termination cable from collector board.
4. Remove the field terminations cover and the three No. 8-32 screws.
5. Remove field terminations board, carefully pulling wiring through bore.
6. Verify that the O-ring is in place in the counter bore in the positioner housing.
7. Feed wiring through passageway into main chamber of housing.
8. Set the circuit board in place and secure with three No. 8-32 screws.
9. Connect field termination cable to collector board.
Stem Position Sensor
The position feedback assembly transmits valve posi­tion information to the processor by means of a rotary position sensor that connects to the valve stem through a feedback linkage. The follower arm is biased against one side of the slot with a rotary spring to provide accurate tracking of the pin in the slot. This spring also automatically moves the position feedback assembly to its limit in the unlikely event of failure of any component in the linkage.
Stem Position Sensor Replacement
(Figure 9)
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and disconnect rotary posi­tion sensor wires from collector board.
4. Remove the two screws from the rotary position sensor, taking care not to lose the washers, and remove the sensor from the housing.
5. Turn position sensor shaft until the dot on the slot is aligned with the wires on the pot (Figure 9).
6. Insert the position sensor into the shaft with the wires pointing toward the main PCB assembly. Turn position sensor clockwise until the bolting slots align with the housing screw holes and the wires on the sensor protrude over the main PCB assembly tray.
7. Carefully center the position sensor on the shaft bore, insert and tighten the screws.
Do not over
tighten.
8. Route wires along the position sensor and reconnect to collector board.
Rotate Stem Position Sensor
slowly
Stem Position Sensor
Housing
Sensor Cable
Feedback Shaft
Bearing
Stem Position Sensor Dot
Figure 9:
Stem Position Sensor Orientation
46-8 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
LED Indicators
The Logix 1400 digital positioner has three LED indica­tors that are visible through a window in the main cover. Only one LED will blink at any given time. Each LED has a different color to convey basic information about the positioner status. Green indicates that the positioner is operating normally. Yellow indicates that a ‘customer defined limit’ or ‘alert’ has been reached. Red indicates that an error condition exists. A fieldbus configurator must be used to determine the specific reason for a yellow or red LED status.
During stroke and actuator calibration, no LED will blink. After calibration is complete, the green LED indicates that the calibration was completed successfully. If the yellow or red LED blinks after a calibration process, a warning or error was detected and the configurator must be used to identify the specific calibration error.
NOTE: If the LED indicator changes from green to yellow after a calibration process, the user may have set a warning limit (position alert, cycle counter alert, etc.). Use a fieldbus configurator to monitor status.
Re-Cal Button
If the fieldbus configurator is not available, Logix 1400 digital positioner has a Re-Cal feature that performs a stroke calibration and allows basic operation of the positioner.
NOTE:The Re-Cal operation retains all previously config­ured information. All settings remain unchanged except stroke calibration parameters. If the device is being installed for the first time, factory default parameters are used. The FB Configurator must be used the first time to configure the Logix 1400 digital positioner. The trans-
ducer block must be out of service for Re-cal to work.
The Re-Cal button is located on the collector board inside the main housing chamber as shown in Figure 10.
Warning: Accessing this function requires removal of the main cover. The user must take all necessary precautions if this operation is performed in explo­sion-proof areas.
Re-Cal Button
NOTE: DIP switches not used on Logix 1400 positioner
Figure 10: Re-Cal Button
Make the appropriate configuration settings, using FB Configurator and CONTROL_FLAGS variable. ATO/ATC selects air-to-open or air-to-close (this is determined by the mechanical tubing of the actuator). The Actuator Style check box allows the user to select linear or rotary feedback linkage. If activates custom characterization.
Press Re-Cal button and hold for five seconds. If the button is released before five seconds have elapsed, no action will be taken. After five seconds, the positioner will begin a stroke calibration. Release the Re-Cal button once calibration has started. The positioner will automatically stroke the valve. No LED will blink during this process.
Upon completion of calibration:
•A blinking green LED indicates the valve is in control mode and calibration was successful.
•A blinking yellow LED immediately after a stroke calibration usually indicates that the valve did not stroke. Check the air supply and cable connections.
• The red LED will blink if a calibration error occurred. The cause of a red LED is generally a stem position linkage/feedback sensor alignment problem. For linear linkage, the active electrical feedback angle is 65 degrees. For rotary linkage, the active electrical feedback angle is 95 degrees. The red LED indicates that the mechanical travel is not centered within the electrical sensor travel. If a red LED is blinking after a stroke calibration, loosen the feedback sensor mounting screws as shown in Figure 9. Turn the stem position sensor slowly while watching the LED indica­tors. Try small movements, both clockwise and counter­clockwise. If the yellow LED begins to blink, the feedback sensor has been correctly moved into range. Tighten the feedback sensor mounting screws and repeat the Re-Cal procedure. If the LED remains red even after moving the full length of the sensor slot, verify the following items: under the CONTROL_FLAGS parameter ‘Actuator Style’ (checked is rotary, unchecked is linear), stem clamp and take-off arm height.
Custom
is selected, the positioner
Rotary
check box setting
NOTE:If the stroke stops in the closed position, the error occurred when the position sensor/linkage was at closed position. If the stroke stops in the open position, the error occurred when position sensor/linkage was at the open position. No calibration parameters are saved if an error occurs. If the power to the positioner is removed, the unit will power-up with the previous configuration parameters. A successful calibration will save parameters.
If the valve does not stroke after pressing the Re-Cal button, this may be an indication that the internal regu­lator pressure and/or the driver module minimum pres­sure is low. Refer to the following instructions to check and set the internal regulator and minimum pressure settings.
Note that the tools and equipment used in the next two procedures are from indicated vendors.
46-9Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
This port is Internal Regulator Output. This should be tubed to orifice on Driver Module.
Check pressure through No. 10-32 x
1
/16 Barb fitting
Regulator Pressure Test Port
Internal Regulator Set Screw
Figure 11: Internal Regulator
Checking or Setting Internal Regulator Pressure
1. Disconnect the air supply from the positioner.
2. Remove the main cover. The regulator pressure set port is factory plugged with a No. 10-32 hex plug (Figure 11). Replace hex plug with a No. 10-32 x
1
/16-inch barb fitting.
3. Attach a 0 to 30 psi pressure gauge (with some
1
/16-inch flexible tubing) to the barb fitting shown in
Figure 11.
4. Reconnect the air supply to the positioner and read the internal regulator pressure on the 0 to 30 gauge (the internal regulator should be set to 22.0 psi). Adjust the regulator pressure by turning the set screw with a small flat screwdriver.
5. Once the regulator pressure is set, remove the air supply to the positioner, and replace the No. 10-32 x
1
/16-inch barb fitting with the No. 10-32 hex plug.
Checking or Setting the Driver Module Minimum Pressure
Once the internal regulator pressure is set to 22.0 psi, the driver module minimum pressure can be checked. To do this, refer to Figure 12, and proceed as follows:
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect power from the positioner.
3. Remove the main cover and remove the flexible tubing from the orifice.
1
/16-inch
4. Obtain a No. 10-32 x swivel elbow (Pneumadyne part No. SFL-10 or equivalent).
5. Remove No. 10-32 x .016 orifice (Figure 4) from the driver module, and screw in No. 10-32 x swivel elbow.
6. Direct the swivel elbow so the minimum pressure test port is accessible.
7. Screw a No. 10-32 x
1
/16-inch barb fitting into the test port, and screw the No. 10-32 x .016 orifice into the end of the elbow as shown.
8. Connect the tubing from the internal regulator output port to the orifice.
9. Using some
1
/16-inch flexible tubing, connect a 0 to
30 gauge to the minimum pressure set port.
10. Once the gauge is connected, reapply the positioner air supply. The minimum pressure should now be registering on the gauge and must be 3.8 to 4.2 psi. If the minimum pressure is not correct, use a
9
/64-inch Allen wrench to turn the minimum pressure set screw located at the bottom of the driver module (Figure 3) until the pressure is in the range indicated. Cycle the positioner air supply several times and recheck the minimum pressure and readjust, if necessary, to ensure that the pressure has settled within the range specified.
11. When the pressure is set, remove the air supply.
12. Remove the No. 10-32 x
1
/16-inch barb and orifice from
the swivel elbow and then remove the swivel elbow.
13. Replace the orifice as shown in Figure 4 and reconnect the
1
/16-inch tubing from the internal regu­lator output port to the orifice. Reconnect the posi­tioner air supply and power. The positioner should now be ready to calibrate.
Minimum Pressure Test Port
No.10-32 x
1
/16-inch
barb
No.10-32 x Swivel ELL Pneumadyne
Part No. SFL-10 No.10-32 x .016
Orifice Pressure from
Internal Regulator to be tubed to this orifice
Figure 12: Driver Module
46-10 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Loading...
+ 22 hidden pages