Flowserve 10-45 User Manual

Worcester Controls
When shipped for field installation, the limit switch (proximity sensor) assembly will be broken down into subassemblies. The subassemblies are: (1) the switch (sensor) operator assembly, consisting of the switches (sensors), bracket, springs and bottoms; (2) the probes; and (3) the enclosure and cover. Hardware items and O-rings are packaged separately. Retaining rings and O-rings have to be assembled to the probes. Lubricate O-rings prior to assembly.
NOTE: Revision R3 End-Mounted Limit Switch and Proximity Sensor Kits fit Revision R2 and later 39 actuators. Included in the End­Mounted Limit Switch Kits is a Rebuild/Accessory Addition Label which is to be marked and applied to actuator after switch has been installed.
1. The End-Mounted Limit Switch (Proximity Sensor) assembly will be mounted on the left-hand (as viewed from actuator nameplate) end cap only, with conduit connection normally at the top of the enclosure.
NOTE: If it is necessary to have the conduit connection at the bottom of the enclosure, the switch enclosure can be inverted. See caution note in Step 2. Be sure that conduit connection will not interfere with piping.
The “standard” mounting configuration of the 39 Actuator to the valve is in-line, fail-closed. In this configuration, SW-1 (SEN-1), as described in the wiring diagram, will give indication when the actuator is in the open position, or CCW limit of rotation. SW-2 (SEN-2) gives indication of the closed position, or CW limit of rotation.
Actuator failure position may be changed by either inverting the actuator or mounting cross-line. In these cases, the limit switch (proximity sensor) must be mounted the same as described above, but SW-1 (SEN-1) and SW-2 (SEN-2) indication will be reversed from that above. If there is question as to which switch is going to indicate a given position, the actuator should be operated, and SW-1 (SEN-1) and SW-2 (SEN-2) checked to verify which switch (sensor) will give the desired indication.
2. Remove cover from enclosure. Carefully insert assembled probe assemblies through holes in bottom of enclosure.
CAUTION: The longer probe must go into the left-hand through-hole (looking at the housing with the conduit hole at top). If enclosure must be inverted to place the conduit connection at the bottom, the longer probe still must go into the left-hand port on the actuator end cap, as viewed with the actuator shaft in normal vertical position. (Both probes are the same length for the 1039 ELK only!)
3. Install O-rings into grooves in bottom side of enclosure. Assemble the enclosure, with probe assemblies, to the actuator. Secure with four cap screws and lockwashers. Check the probes for freedom of movement by moving them back and forth slightly.
4. With assembly complete to this point, it is convenient to make conduit connections and bring wiring through enclosure. It should be noted that the successful use of this device in hazardous atmospheres or other detrimental environments depends on proper conduit construction techniques.
5. When the switch (sensor) package is assembled, one of the probes will make contact with the switch (sensor) button. Simply press the switch (sensor) package until the mounting screws can be engaged. Tighten mounting screws until bracket is secure.
6. Switches (sensors) have been factory adjusted but should be rechecked after installation. Adjustment is as follows:
A. Limit Switches:
With actuator mounted in “standard” configuration (see Step 1), set actuator in closed position with the adjustment screw near its loose limit, adjust closed position switch SW-2 (see wiring diagram) by tightening the adjusting screw until switch contacts click. Then for SPDT switch, tighten adjustment screw two additional turns. For DPDT switch, tighten adjustment screw additional
1
/
4 turn only. Change actuator to its full open position
and adjust open position switch SW-1 in the same manner.
B. Proximity Sensors:
Sensors have to be wired per proximity wiring diagram for adjustment. With actuator mounted in “standard” configuration (see Step 1) and the adjustment screw near its loose limit, set actuator in closed position and adjust closed position sensor SEN-2 (see wiring diagram) by tightening the adjustment screw until load indication is observed; then tighten the adjustment screw an additional
1
/
2 turn. Change actuator to its full open
position and adjust open position sensor SEN-1 in the same manner.
NOTE: If actuator is mounted in any configuration other than “standard,” consult Step 1 of installation instructions to insure proper orientation of probes and switches (sensors).
7. Wiring instructions for limit switches and proximity sensors. Refer to Step 1 for any actuator-mounting configuration other than “standard.”
A. Limit Switches:
Make electrical connections in accordance with the wiring diagram on inside of cover.
WCAIM2051
(Part 19296)
10-45 39 End-Mounted Limit Switch and Proximity Sensor (Revisions R1 and R3)
Installation, Operation and Maintenance Instructions
B. Proximity Sensors:
See wiring diagrams above; diagrams are also on printed inside of the unit’s cover.
a WARNING: A load must be used when power is applied to sensors. Wiring without a load will cause sensor failure.
1) Wiring of AC proximity sensors is as follows: “AC in” connects to the blue lead; “AC out” connects to the brown lead.
The outside load is connected in series with either the blue or the brown lead.
Electrical Characteristics:
Supply Voltage - 20-140 VAC. Load Current - 200 mA maximum continuous.
2) Wiring of DC proximity sensors is as follows: The power supply positive (+) lead connects to the common (c) terminal; the negative (-) lead connects to the normally closed (n.c.) terminal.
The outside load is connected between the normally open (n.o.) terminal and the positive (+) lead.
Electrical Characteristics:
Supply Voltage - 9.6-55 VDC. Load Current - 200 mA maximum continuous. Current Consumption (excluding load) up to 10 mA.
8. Place the O-Ring in the groove in the housing flange first. Secure cover to enclosure with four cap screws. Cover must be assembled tightly for proper performance. The assembly is now complete.
Flow Control Division
Worcester Controls
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide operations or offices.
For more information about Flowserve Corporation, contact www.flowserve.com or call USA 1-800-225-6989.
FLOWSERVE CORPORATION FLOW CONTROL DIVISION
1978 Foreman Drive Cookeville, Tennessee 38501 USA Phone: 931 432 4021 Facsimile: 931 432 3105 www.flowserve.com
© 2003 Flowserve Corporation, Irving, Texas, USA. Flowserve and Worcester Controls are registered trademarks of Flowserve Corporation. WCAIM2051 10/03 Printed in USA
Wiring Diagram
Item Qty Description
1 2 SWITCH (SENSOR) 2 1 ENCLOSURE 3 1 COVER 4 1 BRACKET 5 2 PIVOT HOOK-SWITCH 6 2 BUTTON-SWITCH 7 2 SPRING-SWITCH 8 1 SPACER-SWITCH 9 2 SCREW-BRACKET MTG. 10 1 SCREW-SWITCH MTG. 11 2 SCREW-ADJUSTING 12 1 NUT 13 1 LOCKWASHER 14 4 SCREW-ENCLOSURE MTG. 15 4 SCREW-COVER 16 4 LOCKWASHER 17 1 NAMEPLATE 18 4 DRIVE SCREW 19 2 O-RING 20 1 ROD PROBE 21 1 PISTON PROBE 22 2 O-RING
Item Qty Description
23 2 RETAINING RING 24 1 O-RING 25* 1 26 2 SPACER 27 1 CAUTION LABEL
* Wiring diagram not shown.
Loading...