While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reaching
the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this
reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for
the connection of alarm transmission wiring, communications,
signaling, and/or power. If detectors are not so located, a devel-
oping fire may damage the alarm system, crippling its ability to
report a fire.
Audible warning devices such as bells may not alert people if
these devices are located on the other side of closed or partly
open doors or are located on another floor of a building. Any
warning device may fail to alert people with a disability or those
who have recently consumed drugs, alcohol or medication.
Please note that:
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear
a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to
conduct fire drills and other training exercise to make people
aware of fire alarm signals and instruct them on the proper
reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
LimWarLg.p65 01/10/2000
Page 3
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
1.3: Controls and Indicators ...............................................................................................................................13
2.6: Installation of Optional Modules.................................................................................................................25
2.6.1: CAC-4 Class A Converter Module (MS-4 only) ..............................................................................25
4.3: Status LEDs.................................................................................................................................................40
4.4.1: Fire Alarm Response.........................................................................................................................42
4.4.2: Fire Alarm Restoral...........................................................................................................................42
4.4.3: System Supervisory Condition Response .........................................................................................42
4.4.4: System Supervisory Restoral Response ............................................................................................42
5.4.2: Selecting and Locating Batteries.......................................................................................................47
6
MS-2/MS-4 P/N: 51512:D 10/18/04
Page 7
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility DocumentDocument #15384
411 Digital Alarm Communicator/TransmitterDocument #50921
411UD Digital Alarm Communicator/Transmitter Document #50759
MS-2/MS-4 PN 51512:D 10/18/047
Page 8
IDC (4.7 KΩ, ½ watt ELR)
NAC (4.7KΩ, ½ watt ELR)
2.5A max.
B-
B+
24 VDC
Resettable Power
500 mA max.
- 24 VDC
+ 24 VDC
MS-2(E) Main Circuit Board
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
Trouble Relay (fail-safe)
2 amps @ 30 VAC
Common
Trouble (Normally Open)
Normal (Normally Closed)
Alarm Relay
2 amps @ 30 VAC
Common
Normally Closed
Normally Open
JP3 - Cut to disable
Ground Fault
detection (only with
approval of AHJ)
J7 Transformer
Connector
120 VAC, 2.3A or
220/240 VAC, 1.15A
Earth
Neutral
Hot
(supervised)
J3 and J5
4XTMF Option
Module
Connectors
ms2bord.cdr
SW1, SW2 and SW3
Programming DIP Switches
Module Placement Supervision (if installed)
JP1 - cut to supervise module on J3 & J5
J8 Battery Connector
18 Amp Hour max.
Charger Fault LED
Battery Fault LED
Earth Fault LED
8MS-2/MS-4 PN 51512:D 10/18/04
Page 9
IDC (4.7 KΩ, ½ watt ELR) TB3
NAC (4.7KΩ, ½ watt ELR)
TB2 2.5A max. per NAC
NAC 2 B-
NAC 2 B+
NAC 1 B-
NAC 1 B+
24 VDC Power TB1
500 mA per circuit
- Reset
+ Reset
- Nonreset
+Nonreset
MS-4(E) Main Circuit Board
Zone 4 B-
Zone 4 B+
Zone 3 B-
Zone 3 B+
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
Trouble Relay TB5 (fail-safe)
2A @ 30 VAC
Common
Trouble (Normally Open)
Normal (Normally Closed)
Alarm Relay TB6
2A @ 30 VAC
Common
Normally Closed
Normally Open
Supv. Relay TB7
2A @ 30 VAC
Common
Normally Closed
Normally Open
TB1
+ - + -
Nonreset Reset
J9
TRANSFORMER 1TRANSFORMER 2
J7
J7 Transformer
Connector
J9 Transformer
(optional)
120 VAC, 2.3A or
220/240 VAC, 1.15A
Hot
Neutral
Earth
(supervised)
TB2
B+ B- B+ B NAC 1 NAC 2
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
POWER
ACK
TB8
HOT NEUT EARTH
J8 Battery Connector
18 Amp Hour max.
1
TB3
NAC
DISABLE
B+ B- B+ B ZONE 1 ZONE 2
Converter Module
ZONE 1
SUPERVISORY
ZONE 2
SUPERVISORY
ZONE 3
SUPERVISORY
ZONE 4
SUPERVISORY
NAC
ZONE
FAULT
DISABLE
ALARM
SILENCE
ZONE
ENABLE/D ISABLE
2
B+ B- B+ B ZONE 3 ZONE 4
Class A
TROUBLE
TROUBLE
TROUBLE
TROUBLE
POWER
SYSTEM
TROUBLE
TROUBLE
RESET
3
EARTH BATT CHG
J8
BATTERY
C TRBL NORM
TROUBLE
CLASS A
CONVERTER
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
ALARM
WAL K
SILENCE
TEST
WAL K
TEST
4
JP2
12345678
SW1
Charger Fault LED
Battery Fault LED
Earth Fault LED
TB5
C NC NO
J1
TB6
ALARMSUPV
C NC NO
JP3 - Cut to disable
Ground Fault
J3
detection (only with
approval of AHJ)
J5
TB7
JP3
J3 and J5
Option Module
Connectors
J4
JP1
12345678
ON
SW2 SW3
J6
12345678
ON
ON
J4 and J6
Option Module
Connectors
ms4bord.cdr
SW1, SW2 and SW3
Programming DIP Switches
Module Placement Supervision (if installed)
JP1 - cut to supervise module on J3 & J5
JP2 - cut to supervise module on J4 and J6
MS-2/MS-4 PN 51512:D 10/18/049
Page 10
Product DescriptionProduct Features
SECTION 1Product Description
The MS-2 is a two zone FACP (Fire Alarm Control Panel) and the MS-4 is a four zone
FACP. The information in this manual refers to both the MS-2 and MS-4 unless
otherwise specified. These control panels provide reliable fire signaling protection for
small to medium sized commercial, industrial and institutional buildings. The FACP is
compatible with System Sensor’s I
conventional smoke detectors that can transmit a maintenance trouble signal to the
FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the
ambient temperature falls below the detector rating (refer to System Sensor’s I
Installation and Maintenance Instructions document I56-1800-00 for device
specifications). In addition, the control panel is compatible with conventional input
devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations,
waterflow devices, tamper switches and other normally-open contact devices. Refer to
Fire•Lite Device Compatibility Document for a complete listing of compatible devices.
Outputs include one NAC (Notification Appliance Circuit) on the MS-2 and two NACs
on the MS-4. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC
resettable power. In addition, the MS-4 has a Form-C Supervisory relay and a
nonresettable power output. The FACP supervises wiring, AC voltage and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating
device will activate audible and visual signaling devices, illuminate an indicating LED,
sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an
optional module used to notify a remote station or initiate a auxiliary control function.
The MS-2E and MS-4E offer the same features as the MS-2 and MS-4 but allows
connection to 220/240 VAC.
3
detectors which are microprocessor-based
3
Note: Unless otherwise specified, the terms MS-2 and MS-4 are used in this manual to
refer to the MS-2 and MS-2E as well as the MS-4 and MS-4E FACPs respectively.
1.1 Product Features
•Style B (Class B) IDC (Initiating Device Circuit)
•Style Y (Class B) NAC (Notification Appliance
•Form-C Alarm Relay
•Form-C Trouble Relay
•Form-C Supervisory Relay (MS-4 only)
•3.0 amps total system current standard for MS-2 and MS-4
•6.0 amps total system current available for MS-4 with optional second
•Optional Dress Panel DP-MS2/4
•Optional Trim Ring P/N: TR-1-R for semi-flush mounting the cabinet
one zone programmable for combination
supervisory and waterflow
MS-2 - two IDCs
MS-4 - four IDCs
Circuit)
MS-2- one NAC
MS-4 - two NACs
transformer
MS-4
ZONE 1
TROUBLE
MAINTENANCEFIRE ALARM
SUPERVISORY
ZONE 2
TROUBLE
MAINTENANCE
SUPERVISORY
FIRE ALARM
ZONE 3
SUPERVISORY
TROUBLE
MAINTENANCE
FIRE ALARM
ZONE 4
SUPERVISORY
TROUBLE MAINTENANCE
FIRE ALARM
AC
POWER
ALARM
NAC
ZONE
SYSTEM
POWER
WALK
NAC
SILENCE
FAULT
TROUBLE
DISABLE
TROUBLE
TEST
DISABLE
10MS-2/MS-4 PN 51512:D 10/18/04
Page 11
Product FeaturesProduct Description
•Control Buttons
ACK (Acknowledge)
Alarm Silence
Reset
Walkt est
Zone Enable/Disable (one per zone)
•LED Indicators
Fire Alarm (one per zone)
Supervisory (one per zone)
Trouble (one per zone)
Maintenance (one per zone)
AC Power
NAC Disable
Zone Disable
NAC Fault
System Trouble
Power Trouble
Walkt est
Alarm Silence
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
•Piezo sounder for alarm, trouble and supervisory
•24 volt operation
•Low AC voltage sense
•Alarm Verification
•NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•Automatic battery trickle charger
•Silent or audible walktest capabilities
•Optional NAC Class A converter module (MS-4 only)
•Optional 4XTMF Transmitter Module (MS-2 and MS-4)
•Optional 4XZMF Zone Relay Module (MS-4 only)
•Optional 4XLMF Module for RZA-4XF Remote LED Annunciator (MS-4 only)
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can
be housed in the FACP cabinet. Larger batteries require a separate battery box such
as the Fire•Lite BB-17F)
Initiating Device Circuits - TB3
Alarm Zones 1 & 2 (MS-2 and MS-4)
Alarm Zones 3 & 4 (MS-4 only)
Power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 4 mA
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB2
One NAC on MS-2, two NACs on MS-4
Operation: Style Y (Class B)
Power-limited Circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 2.5 amps total with standard transformer. 5.0 amps
total (2.5 amp maximum per NAC) with optional transformer on MS-4 only
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke
detectors (see note 1)
Power-limited Circuitry
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Power - TB1 (MS-4 only)
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. Total current for resettable power and one Notification Appliance Circuit must
not exceed 3.0 amps for the MS-2. Total current for nonresettable power,
resettable power and two Notification Appliance Circuits must not exceed 6.0
amps for the MS-4 (requires optional second transformer)
12MS-2/MS-4 PN 51512:D 10/18/04
Page 13
Controls and IndicatorsProduct Description
1.3 Controls and Indicators
Front Panel Membrane Buttons
•Acknowledge
•Alarm Silence
•Reset
•Walktest
•Zone Enable/Disable - Zone 1
•Zone Enable/Disable - Zone 2
•Zone Enable/Disable - Zone 3 (MS-4 only)
•Zone Enable/Disable - Zone 4 (MS-4 only)
LED Indicators
•Fire Alarm Zone 1 - red LED
•Fire Alarm Zone 2 - red LED
•Fire Alarm Zone 3 - red LED (MS-4 only)
•Fire Alarm Zone 4 - red LED (MS-4 only)
•Supervisory Zone 1 - yellow LED
•Supervisory Zone 2 - yellow LED
•Supervisory Zone 3 - yellow LED (MS-4 only)
•Supervisory Zone 4 - yellow LED (MS-4 only)
•Trouble Zone 1 - yellow LED
•Trouble Zone 2 - yellow LED
•Trouble Zone 3 - yellow LED (MS-4 only)
•Trouble Zone 4 - yellow LED (MS-4 only)
•Maintenance Zone 1 - yellow LED
•Maintenance Zone 2 - yellow LED
•Maintenance Zone 3 - yellow LED (MS-4 only)
•Maintenance Zone 4 - yellow LED (MS-4 only)
•AC Power - green LED
•NAC Disable - yellow LED
•Zone Disable - yellow LED
•NAC Fault - yellow LED
•System Trouble - yellow LED
•Power Trouble - yellow LED
•Walktest - yellow LED
•Alarm Silence - yellow LED
•Earth Fault - yellow LED (on main circuit board)
•Battery Fault - yellow LED (on main circuit board)
•Charger Fault - yellow LED (on main circuit board)
MS-2/MS-4 PN 51512:D 10/18/0413
Page 14
Product DescriptionCircuits
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance
and supervisory conditions as follows:
•Alarm - on steady
•Trouble - pulse 1 second on and 1 second off
•Maintenance - pulse ½ second on and ½ second off
•Supervisory - pulse ½ second on and ½ second off
1.4 Circuits
Input Circuits
Two input IDCs (Initiating Device Circuits) on the MS-2 and four IDCs on the MS-4
provide Style B (Class B) configurations. All IDCs accept I
conventional two-wire smoke detectors, four-wire smoke detectors and normally-open
contact devices.
Output Circuits
•24 VDC resettable power output - 500 mA
•24 VDC nonresettable power output (MS-4 only) - 500 mA
•24 volt battery charger (up to 18 Amp Hour batteries)
3
detectors as well as
1.5 Components
Notification Appliance Circuits
One NAC (Notification Appliance Circuit) Style Y (Class B) on the MS-2
Two NACs Style Y (Class B) on the MS-4
The main circuit board contains the system’s CPU, power supply, other primary
components and wiring interface connectors. Optional modules plug in and are
mounted to the main circuit board.
Cabinet
The cabinet is red and the backbox measures 14.5” (36.8 cm) x 15.218” (38.65 cm) x
2.875” (7.3 cm) and provides space for two batteries (up to 7 Amp Hours). Also
available is an optional dress panel which mounts inside the cabinet.
Transformer Assembly
One 100VA transformer is provided standard with the FACP. An optional second
100VA transformer is available for the MS-4 to provide maximum accessory power.
Batteries
The cabinet provides space for two 7 Amp Hour batteries (larger batteries up to 18 Amp
Hour, require use of a UL listed battery box such as the Fire•Lite BB-17F). Batteries
must be ordered separately.
14MS-2/MS-4 PN 51512:D 10/18/04
Page 15
Optional Modules and AccessoriesProduct Description
1.6 Optional Modules and Accessories
CAC-4 Class A Converter Module (MS-4 only)
The CAC-4 Module can be used to convert the Style B (Class B) Initiating Device
Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to
Style Z (Class A). The module connects to J1 on the MS-4 main circuit board.
4XTMF Transmitter Module (MS-2 and MS-4)
The 4XTMF provides a supervised output for local energy municipal box transmitter
and alarm and trouble reverse polarity. It includes a disable switch and disable trouble
LED. A module jumper option allows the reverse polarity circuit to open with a system
trouble condition if no alarm condition exists. The 4XTMF mounts to the MS-2 main
circuit board option module connectors J3 & J5 or the MS-4 main circuit board,
occupying one of the two sets of option module connectors J3 & J5 or J4 & J6.
4XLMF LED Interface Module (MS-4 only)
The LED Interface Module supports the RZA-4XF Remote Annunciator module.
Annunciator wiring is supervised for open conditions by this module. The 4XLMF
mounts to the MS-4 main circuit board option module connectors J3 and J5 only
RZA-4XF Remote Annunciator (MS-4 only)
The Remote Annunciator mounts on a standard single-gang electrical box and provides
LED indication of the following:
.
•Alarm Zone 1 (red LED)
•Alarm Zone 2 (red LED)
•Alarm Zone 3 (red LED)
•Alarm Zone 4 (red LED)
•System Trouble (yellow LED)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is
supervised for open conditions. Any open condition will cause the System Trouble
LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The RZA-4XF Remote Annunciator requires the use of the LED Interface Module
(4XLMF).
4XZMF Zone Relay Module (MS-4 only)
The Zone Relay Module provides Form-C relay contacts for the following:
•Alarm Zone 1
•Alarm Zone 2
•Alarm Zone 3
•Alarm Zone 4
•System Alarm
•System Trouble
As a jumper option, the first four relays described above can be made silenceable. The
4XZMF mounts to the MS-4 main circuit board, occupying one of the two sets of
option module connectors.
Dress Panel DP-MS2/4
A dress panel DP-MS2/4 is available as an option. The dress panel restricts access to
the system wiring while allowing access to the membrane switch panel.
MS-2/MS-4 PN 51512:D 10/18/0415
Page 16
Product DescriptionOptional Modules and Accessories
Battery Box
The Fire•Lite BB-17F battery box may be used to house two batteries greater than 7
Amp Hour to a maximum of 18 Amp Hour. The battery box mounts directly below the
control panel cabinet, centered to the main circuit board. The BB-17F is red and is
provided with knockouts.
411 and 411UD Digital Alarm Communicator/Transmitter
The three input/channel 411 and the four input/channel 411UD are dual line, digital
alarm communicator/transmitters which can be used as slave communicators with the
MS-4 FACP. The inputs/channels are compatible with normally open relay contacts,
require ELRs (End-of-Line Resistors), are supervised and are fully programmable. The
communicators interface with the public switched telephone network and are
compatible with most central station receivers. Power supplied must be 12 or 24 volts,
filtered and nonresettable. The communicators are mounted in a small metal enclosure,
providing a variety of mounting options. Refer to the 411 or 411UD manual for
additional information.
16MS-2/MS-4 PN 51512:D 10/18/04
Page 17
Backbox MountingInstallation
SECTION 2Installation
The cabinet can be surface mounted or semi-flush mounted using the optional Trim
Ring P/N: TR-1-R. The door is removable during the installation period by opening
and lifting if off the hinges. The cabinet mounts using two key slots at the top of the
backbox and two additional 0.250” diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Select a location for the
cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The area should be readily accessible with sufficient room to easily install
and maintain the control panel. Locate the top of the cabinet approximately five feet
above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed and
determine the appropriate knockouts. All wiring must be in accordance with the
National and/or Local codes for fire alarm systems and power supplies.
2.1 Backbox Mounting
1. Mark and predrill holes for the top two keyhole mounting bolts
2. Install two upper fasteners in the wall with the screw heads protruding
approximately ¼”
3. Using the upper keyholes, mount the backbox over the two screws
4. Mark the lower two holes, remove the backbox from the wall and drill the
mounting holes
5. Mount the backbox, install the remaining fasteners and tighten all screws
2.875” (7.3 cm)
0.75”(1.9 cm)
Height=15.000”
(38.10 cm)
10.375”
(26.35 cm)
Backbox = 14.5”
(36.8 cm)
9.1” (23.1 cm)
Pem Studs
Backbox Mounting Holes
Top
Depth = 3.000”
(7.62 cm)
2.7”
(6.86cm)
ms2-4cab.cdr
Bottom
1.125” (2.868 cm)
Figure 2.1 Backbox Mounting Dimensions
MS-2/MS-4 PN 51512:D 10/18/0417
Page 18
InstallationBackbox Mounting
Door = 15.342“ (38.97 cm)
Bottom
To p
Door = 14.677 “ (37.28 cm)
Depth = 2.875" (7.3 cm)
Depth = 3.050“
(7.75 cm)
Battery Box = 8.5“ (21.59 cm)
When batteries larger than 7 Amp Hour, up to 18 Amp Hour, are being used, the
BB-17F battery box (or UL listed equivalent) must be installed. To install the BB-17F:
1. Mount the FACP cabinet to the wall
2. Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F
3. Using conduit, hang the BB-17F from the FACP cabinet making sure there is at
least ½” of clearance between the two cabinets
4. Anchor the BB-17F to the wall
Depth = 4.75
(12.065 cm)
ms-4cabb.cdr
Battery Box = 14.5“
(37.384 cm)
Figure 2.2 Backbox and Battery Box
18MS-2/MS-4 PN 51512:D 10/18/04
Page 19
Operating PowerInstallation
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel.
Disconnect all sources of power before servicing. The panel and associated equipment
may be damaged by removing and/or inserting cards, modules or interconnecting
cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power
source for the panel is 120 VAC, 50/60 Hz, 2.3 amps for the MS-2/MS-4 or 240 VAC,
50 HZ, 1.15 amps for the MS-2E/MS-4E. Run a pair of wires (with ground conductor)
from the protected premises main breaker box to TB8 of the main circuit board. As per
the National Electrical Code, use 14 AWG (2.00 mm
wire with 600V insulation. No other equipment may be connected to this circuit. In
addition, this circuit must be provided with overcurrent protection and may not contain
any power disconnect devices. A separate Earth Ground connection must be made to
ensure proper panel operation and lightning and transient protection. Connect the Earth
Ground wire [minimum 14 AWG (2.00 mm
2
)] to the transformer mounting stud. Do
not use conduit for the Earth Ground connection since this does not provide reliable
protection.
Secondary Power Source (Batteries)
2
, 1.6 mm O.D.) or heavier gauge
!
Optional second transformer
shown installed
Standard transformer
Earth ground wire shown
connected to transformer
mounting stud
Observe polarity when connecting the battery. Connect the battery cable to J8 on the
main circuit board using the plug-in connector and cable provided. The battery charger
is current-limited and capable of charging sealed lead acid batteries. The charger shuts
off when the system is in alarm.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin
and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately
flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
CLASS A
CONVERTER
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
WALK
TEST
C TRBL NORM
TROUBLE
ALARM
SILENCE
WALK
TEST
4
JP2
SW1
J1
JP1
SW2 SW 3
TB5
C NC NO
ALARMSUPV
J3
J5
J4
J6
12345678ON12345678ON12345678
ON
TB6
C NC NO
TB7
JP3
TB1
B+ B- B+ B-
+ - + -
NAC 1 NAC 2
TB8
HOT NEUT EARTH
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
DISABLE
POWER
ACK
1
J9
TRANSFORMER 1TRANSFORMER 2
J7
Nonreset Resettable
SIGNAL TRANSFORMER
XX-XXX-XXXXXX Rev X
SIGNAL TRANSFORMER
XX-XXX-XXXXXX Rev X
B+ B- B+ B ZONE 1 ZONE 2
NAC
DISABLE
SILENCE
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
ZONE
ALARM
2
ZONE 1
ZONE 2
ZONE 3
ZONE 4
NAC
FAULT
ZONE
ENABLE/DISABLE
BATTERY
B+ B- B+ B ZONE 3 ZONE 4
TROUBLE
TROUBLE
TROUBLE
TROUBLE
POWER
SYSTEM
TROUBLE
TROUBLE
RESET
3
EARTHBATT CHG
J8
TB3
TB2
ms4powr.cdr
Figure 2.3 Operating Power Connections
MS-2/MS-4 PN 51512:D 10/18/0419
Page 20
InstallationInput Circuits
2
2.3 Input Circuits
The MS-2 has two IDCs (Initiating Device Circuits) and the MS-4 has four IDCs. Each
circuit is compatible with System Sensor’s I
maintenance signal when the detector becomes dirty and a separate supervisory ‘freeze’
signal when ambient temperature falls below the detector rating. The maximum loop
resistance limit for each IDC is 100 ohms. The field wiring for each zone is supervised
for opens, shorts and ground faults. All conditions are visually and audibly
annunciated.
Each circuit is configured for Style B (Class B) operation and will accept I
detectors, any normally-open contact devices as well as conventional 2-wire or 4-wire,
24 VDC smoke detectors. In addition, Zone 1 (IDC 1) on the MS-2 and Zone 2 (IDC2)
on the MS-4 can be programmed as combination supervisory and waterflow zones.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
MS-4 Initiating Device Circuits can be converted to Style D (Class A) by installing the
optional Class A Converter module. Refer to "CAC-4 Class A Converter Module
(MS-4 only)" on page 25.
Class B Initiating Device Circuits (supervised and power-limited)
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
UL listed compatible 4-wire smoke detector
3
smoke detectors which generate a
4.7 KΩ, ½ watt resistor P/N:71252
3
smoke
UL listed
compatible
2-wire smoke
detectors
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
TB1
+ - + -
Nonreset Reset
manual pull stations
TB2
B+ B- B+ B NAC 1 NAC
Figure 2.4 IDC Connections
heat detectors
TB3
B+ B- B+ B ZONE 1 ZONE 2
Dummy load all
unused circuits - 4.7
KΩ, ½ watt resistor
(P/N: 71245)
ms-4idc.cdr
B+ B- B+ B ZONE 3 ZONE 4
Note: Zones 3 & 4
on MS-4 only
20MS-2/MS-4 PN 51512:D 10/18/04
Page 21
Input CircuitsInstallation
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between
an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the
same circuit. The following figure illustrates the wiring of Zone 2 as a Style B (Class
B) Waterflow/Supervisory circuit. Note that only
Zone 1 on the MS-2 and Zone 2 on
the MS-4 can be configured in this manner.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch
(tamper)
Supervisory Switch
(tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
TB3
B+ B- B+ BZONE 1 ZONE 2
B+ B- B+ BZONE 3 ZONE 4
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
Note: Zones 3 & 4
on MS-4 only
Figure 2.5 Style B Combination Circuit on Zone 2 of the MS-4
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch(es) must connect to the FACP Initiating Device
Circuit before the In-Line Resistor as shown in Figure 2.5
The Waterflow Supervisory Switch(es) must connect to the FACP Initiating
Device Circuit after the In-Line Resistor as shown in Figure 2.5
Program the FACP Initiating Device Circuit #1 on the MS-2 or Circuit #2 on
the MS-4 as a Combination circuit by placing SW1 DIP switch 8 to the ON
position as described in "SW1 DIP Switch Settings" on page 34
ms-4zon1.cdr
Waterflow Alarm Switch activation causes the panel to latch into alarm until
the alarm condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to track the supervisory
condition, that is, the panel will clear when the supervisory condition is
cleared (if FACP is programmed for Autoresettable Supervisory)
MS-2/MS-4 PN 51512:D 10/18/0421
Page 22
InstallationOutput Circuits
2.4 Output Circuits
2.4.1 Notification Appliance Circuits
The MS-2 provides one Style Y (Class B) NAC (Notification Appliance Circuit) while
the MS-4 provides two Style Y (Class B) NACs. Each circuit is capable of providing a
maximum of 2.5 amps of current. Total current drawn from these as well as other DC
power outputs cannot exceed 3.0 amps for the MS-2 or 6.0 amps for the MS-4 with the
optional second transformer installed (refer to battery calculations section). Each circuit
is supervised and power-limited. Refer to the Fire•Lite Device Compatibility
Document for a listing of compatible notification appliances.
The MS-4 NACs can be converted to Style Z (Class A) by installing the optional Class
A Converter module. Refer to "CAC-4 Class A Converter Module (MS-4 only)" on
page 25.
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Polarized Bell
Polarized Strobe
Polarized Horn
Notification Appliance Circuit
polarity shown in alarm condition
TB2
B+ B- B+ B-
NAC 1 NAC 2
Figure 2.6 NAC Connections
Polarized Bell
Polarized Horn-Strobe
Polarized Horn
Dummy load any unused
circuits (P/N: 71245)
ms-4nac.cdr
22MS-2/MS-4 PN 51512:D 10/18/04
Page 23
Output CircuitsInstallation
2.4.2 DC Power Output Connections
Resettable 24 VDC power is available on both the MS-2 and MS-4 control panels.
Nonresettable 24 VDC power is available only on the MS-4.
Nonresettable Power (500 mA) - MS-4 Only
24 VDC filtered, nonresettable power can be
obtained from these terminals (power-limited)
TB1
Figure 2.7 Auxiliary Power
2.4.3 Relays
The MS-2 and MS-4 control panels provide an alarm and fail-safe trouble relay and the
MS-4 also provides a supervisory relay. Each Form-C relay is rated for 2 amps @
30VAC (resistive).
Note that relay connections may be power-limited or nonpower-limited, provided that
0.25” minimum spacing is maintained between conductors of power-limited and
nonpower-limited circuits.
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors
can be obtained from these terminals (power-limited)
+ - + -
ms-4tb1.cdr
Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or
total power failure.
TROUBLE
C TRBL NORM
C NC NO
TB5
ALARM
SUPV
C NC NO
TB6
TB7
ms4relay.cdr
Figure 2.8 Relay Terminals
MS-2/MS-4 PN 51512:D 10/18/0423
Page 24
InstallationPower-limited Wiring Requirements
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the
cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away
from any nonpower-limited circuit wiring. Furthermore, all power-limited and
nonpower-limited circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring diagram for the MS-4 is illustrated below.
Power-limited Circuits
TB2
TB1
+ - + -
SIGNAL TRANSFORMER
XX-XXX-X XXXXX Rev X
Nonreset Res ettable
TB1
TB3
A+ A- A + ACLASS A CLASS A
NAC 1 NAC 2
A+ A - A+ A-
CLASS A CLASS A
ZONE 1 ZONE 2
A+ A- A + A-
CLASS A CLASS A
ZONE 3 ZONE 4
Nonpower-limited Circuits
TB5
C NC NO
ALARMSUPV
TB6
4XLB
C NC NO
TB7
CAC-4
Power-limited
ZONE 1
SUPERVISORY
FIRE ALA RM
SUPERVISORY
FIRE ALA RM
SUPERVISORY
FIRE ALA RM
SUPERVISORY
FIRE ALA RM
NAC
ACK
DISABLE
ZONE
DISABLE
ALARM
SILENCE
AC
POWER
SIGNAL TRANSFORMER
XX-XXX-XX XXXX Rev X
1
J9
TRANSFORMER 1TRANSFORMER 2
TB8
J7
HOT NEUT EARTH
ZONE 2
ZONE 3
ZONE 4
NAC
FAULT
ZONE
ENABLE/DISABLE
2
BATTERY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
SYSTEM
TROUBLE
J8
TROUBLE
RESET
3
EARTH BATT CHG
POWER
MAINTE NANCE
MAINTE NANCE
MAINTE NANCE
MAINTE NANCE
WAL K
TEST
JP2
WALK
TEST
4
1 2 345678
SW1
ALARM
SILENCE
ON
JP1
1 2 345678
1 2 345678
ON
SW2 SW3
4XLMF
ON
4XTMF
Circuits
Nonpower-limited
Circuit
ms4ulpwr.cdr
AC Power
Figure 2.9 Typical UL Power-limited Wiring Requirements
24MS-2/MS-4 PN 51512:D 10/18/04
Page 25
Installation of Optional ModulesInstallation
2.6 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or
wiring.
2.6.1 CAC-4 Class A Converter Module (MS-4 only)
2.6.1.1 Installation
The CAC-4 Module can be used to convert the four Style B (Class B) Initiating
Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification
Appliance Circuits to Style Z (Class A). The module plugs into connector J1 which
is located at the top right of the MS-4 main circuit board.
Install the three supplied standoffs in the holes on the main circuit board as
indicated in the following figure. Carefully align the connector on the CAC-4 with
J1 on the FACP main circuit board and press the module securely into place. Make
certain the pins are properly aligned to prevent bending or breaking of any
connector pins.
Secure to Standoffs
TB1
+ - + -
Nonreset Reset
TB1
CLASS A CLASS A
NAC 1 NAC 2
TB2
B+ B- B+ B NAC 1 NAC 2
A+ A- A+ A-
A+ A- A+ A-
CLASS A CLASS A
ZONE 1 ZONE 2
A+ A- A+ A-
CLASS A CLASS A
ZONE 3 ZONE 4
CAC-4 Module
TB3
B+ B- B+ B ZONE 1 ZONE 2
B+ B- B+ B ZONE 3 ZONE 4
CLASS A
CONVERTER
J1 Connector
MS-4 Main Circuit Board
Figure 2.10 CAC-4 Module Installation
C TRBLNORM
TROUBLE
J1
Secure to Standoff
TB5
C NC NO
TB6
ALARMSUPV
C NC NO
TB7
JP3
ms4tocac.cdr
MS-2/MS-4 PN 51512:D 10/18/0425
Page 26
InstallationInstallation of Optional Modules
2.6.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB2 of the MS-4
and TB1 of the CAC-4 module. Wire the Style D (Class A) Initiating Device
Circuits using TB3 of the MS-4 and TB1 of the CAC-4. Make certain to observe
polarity when connecting the devices to the circuits. The B+ and A+ terminals must
comprise the feed and return for the positive side of a device and the B- and Aterminals must comprise the feed and return for the negative side of a device. To
configure any of the zones for Class B when the CAC-4 is installed, simply wire to
the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor
after the last device on the circuit. Do not wire to the corresponding A+ and Aterminals on the CAC-4 module. Note that Zone 1 IDC on the MS-2 and Zone 2
IDC on the MS-4 can be configured as a combination waterflow/supervisory circuit
as illustrated in the following figure.
(supervised and power-limited)
Circuit polarities
shown in alarm
condition
Class B (Style B)
IDC - 4.7 KΩ
½ watt ELR
resistor
P/N:71252
(supervised and
power-limited)
Class A (Style Z) NAC
Polarized
Bell
Polarized
Strobe
Polarized
Horn
TB2
B+ B- B+ B NAC 1 NAC 2
IMPORTANT!
All devices must be
within 20 feet of the
Class A portion of
the circuit and
wiring must be in
Ω
1.2 K
½ watt
In-Line
resistor
P/N:75579
TB3
conduit.
Tamper
Smoke
Tamper
Pull Station
Heat
Waterflow
B+ B- B+ B ZONE 1ZONE 2
Class A
(Style D) IDC
Combo Waterflow
& Supervisory
20KΩ, ½ watt ELR
resistor P/N:75477
(supervised and
power-limited)
Smoke
Pull Station
Heat
B+ B- B+ B ZONE 3ZONE 4
Class A
(Style D) IDC
(supervised and
power-limited)
Dummy load all unused
circuits - 4.7 K
½ watt ELR resistor
(P/N: 71245)
Circuit Board
Ω
MS-4
TB1
A+ A- A+ A-
CLASS A CLASS A
NAC 1 NAC 2
A+ A- A+ A-
CLASS A CLASS A
ZONE 1 ZONE 2
A+ A- A+ A-
CLASS A CLASS A
ZONE 3 ZONE 4
CAC-4 Class A Converter Module
ms4comba.cdr
Figure 2.11 Wiring NACs and IDCs for Class A Operation
26MS-2/MS-4 PN 51512:D 10/18/04
Page 27
Installation of Optional ModulesInstallation
2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules
MS-4: The 4XLMF LED Interface Module can only be plugged into connectors J3 and
J5 on the MS-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged
into connectors J3 and J5 or
of any two of the three modules can be installed.
MS-2: Only the 4XTMF module can be plugged into connectors J3 & J5 on the MS-2
main circuit board. (No other option modules can be installed on the MS-2).
The following steps must be followed when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6)
on the main circuit board to allow the control panel to supervise the placement of
any installed option module
3. Install the two supplied metal standoffs in the locations indicated. These
standoffs provide the required earth ground protection
J4 and J6 on the MS-4 main circuit board. A combination
ms4bord.cdr
J9
TRANSFORMER 1TRANSFORMER 2
J7
TB1
+ - + -
Nonreset Reset
TB2
B+ B- B+ B NAC 1 NAC 2
HOT NEUT EARTH
4. Carefully plug the connectors on the option module into connectors J3 and J5 or
J4 and J6 on the FACP main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the
supplied screws
6. When the installation has been completed, connect the wiring to the modules as
indicated in the following sections
7. Test system for proper operation
TB3
B+ B- B+ B ZONE 1 ZONE 2
ZONE 1
1
NAC
DISABLE
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
ZONE
DISABLE
ALARM
SILENCE
2
ZONE 2
ZONE 3
ZONE 4
NAC
SYSTEM
FAULT
TROUBLE
ZONE
ENABLE/DISABLE
BATTERY
TB8
AC
POWER
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
ACK
JP2 Jumper
Cut to install module on J4 & J6
B+ B- B+ B ZONE 3 ZONE 4
CLASS A
CONVERTER
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
POWER
TROUBLE
RESET
3
EARTH BATT CHG
J8
C TRBL NORM
TROUBLE
WALK
TEST
WALK
TEST
4
JP2
ALARM
SILENCE
12345678
SW1
J1
JP1
12345678
ON
SW2 SW3
ON
TB5
C NC NO
12345678
ON
TB6
C NC NO
ALARMSUPV
J3
J5
J4
J6
TB7
JP3
J3
J5
J4
J6
JP1 Jumper
Cut to install
module on J3 & J5
(when using
(when using
Standoffs
J3 & J5
Standoffs
J4 & J6
Figure 2.12 4X Option Module Connection to MS-4
MS-2/MS-4 PN 51512:D 10/18/0427
Page 28
InstallationInstallation of Optional Modules
2.6.2.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter
in addition to alarm and trouble reverse polarity. A jumper option allows the reverse
polarity circuit to open with a system trouble condition if no alarm condition exists. A
disable switch allows disabling of the transmitter output during testing to prevent
accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended
for connection to a polarity reversal circuit or a Remote Station receiving unit
having compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect)
position to prevent accidental activation of the municipal box. Note that a Disconnect
LED will illuminate after the module is installed in the FACP. In addition, the System
Trouble LED will turn on to indicate the Disconnect condition.
Note: 4XTMF Module is not suitable for
transmitting reverse polarity supervisory signal.
* Wiring from these terminals can
exit the protected premises.
Dummy load terminals 6 and 7
(4.7kΩ, ¼ watt resistor) if
Municipal Box is not connected.
4xtmf.cdr
Disconnect LED
Figure 2.13 4XTMF Transmitter Module
28MS-2/MS-4 PN 51512:D 10/18/04
Page 29
Installation of Optional ModulesInstallation
2.6.2.2 4XZMF Zone Relay Module (MS-4 only)
The 4XZMF provides four zone alarm, one system alarm and one system trouble
Form-C relays. Nonpower-limited and power-limited wiring must have a minimum
distance of 0.25”, wire to wire. If this module is used to drive nonpower-limited and
power-limited circuits, follow the instructions below:
Relay #1 through #4 will activate with Output #1 through
#4 and remain latched unless ‘LATCH’ jumper is cut.
1
NO
2
NC
Relay #1
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
}
}
}
}
}
}
Relay #2
Relay #3
Relay #4
Alarm
Trouble
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
4xzma.cdr
Use Disable Switch to
disconnect the relays
Cut jumper for nonlatching
(silenceable) relay operation
1) Skip a set of dry contacts to maintain the 0.25” required space between powerlimited and nonpower-limited circuits. The wiring of this module must follow the
requirements as specified in "Power-limited Wiring Requirements" on page 24.
OR
2) If this module is needed to drive power-limited and nonpower-limited relays that are
next to each other, refer to the following illustration which shows a typical connection:
Relay #1
Relay #2
Relay #3
Relay #4
{
{
{
{
NO
NC
NO
NC
NO
NC
NO
NC
power-limited circuit
C
C
C
C
no connection
}
power-limited circuit
}
nonpower-limited circuit
}
nonpower-limited circuit
}
4xzma.cdr
Figure 2.14 4XZMF Zone Relay Module
MS-2/MS-4 PN 51512:D 10/18/0429
Page 30
InstallationInstallation of Optional Modules
2.6.2.3 4XLMF LED Interface Module (MS-4 only)
The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this
module must follow the requirements as specified in "Power-limited Wiring
Requirements" on page 24.
4XLB
4XLMF Module
Important: The 4XLMF module can only
MS-4 main circuit board.
+24 VDC
1
Out #1
2
Out #2
3
Out #3
4
Out #4
5
System Trouble
6
Sound
7
Resound
8
Connect to corresponding terminals
of RZA-4XF Remote Annunciator
4xlma.cdr
be installed on connectors J3 and J5 of the
Note: Make wiring connections with
system power off. Maximum
wire impedance is 50 ohms per
wiring connection.
rza-4xbx.cdr
Single-gang Box
Front View of RZA-4XF
rza-4xfr.cdr
Side View
Figure 2.15 4XLMF LED Interface Module
30MS-2/MS-4 PN 51512:D 10/18/04
Page 31
Installation of Optional ModulesProgram Options via DIP Switch
1
SECTION 3Program Options via DIP Switch
This section describes the programming options available via DIP switch settings. The
FACP can be field programmed using option DIP switches SW1, SW2 and SW3 which
are located in the bottom right side of the main circuit board. Refer to the following
illustration for switch locations and DIP switch placement in the ON and OFF
positions.
J9
TRANSFORMER 1TRANSFORMER 2
J7
+ - + -
Nonreset Reset
TB2
TB1
B+ B- B+ B NAC 1 NAC 2
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
POWER
ACK
TB8
HOT NEUT EARTH
TB3
NAC
DISABLE
1
B+ B- B+ B ZONE 1 ZONE 2
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
NAC
ZONE
FAULT
DISABLE
ALARM
SILENCE
ENABLE/DISAB LE
2
B+ B- B+ B ZONE 3 ZONE 4
ZONE 1
TROUBLE
ZONE 2
TROUBLE
ZONE 3
TROUBLE
ZONE 4
TROUBLE
SYSTEM
TROUBLE
ZONE
BATTERY
1 2 3 4 5 6 7 8
SW
J8
ON
TROUBLE
RESET
3
EARTH BATT CHG
POWER
CLASS A
CONVERTER
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
WALK
TEST
JP2
C TRBL NORM
TROUBLE
J1
ALARM
SILENCE
WALK
TEST
4
JP1
12345678
12345678
ON
SW1
SW2
1 2 3 4 5 6 7 8
SW2
TB5
ON
SW3
ON
12345678
ON
TB6
C NC NO
ALARMSUPV
J3
J5
J4
J6
C NC NO
1 2 3 4 5 6 7 8
SW3
TB7
JP3
12345678
ON
Switches 1 through 7
shown in OFF position
ms4switc.cdr
ON
Switch 8 shown in
ON position
Figure 3.1 Field Programming DIP Switches
MS-2/MS-4 PN 51512:D 10/18/0431
Page 32
Program Options via DIP SwitchDIP Switch Settings
3.1 DIP Switch Settings
The following tables list the programmable features for the MS-2 and MS-4. Placing a
DIP switch in the ON position will select the feature while placing the DIP switch in the
OFF position will deselect the feature. The exceptions to this rule are SW3 DIP
switches 5 & 6. These two switches are used to select the Notification Appliance
Circuit synchronization feature. A detailed description of each feature is presented in
the following pages.
Important: When any programmable feature is changed by repositioning a DIP switch,
the FACP Reset button must be pressed to ensure that the control panel can read the
new switch position.
Table 3.1 MS-2 DIP Switch Settings
Switch NumberDIP Switch NumberDIP Switch ON
1Silence Inhibit
2Auto-silence
3Temporal Coding
4Selective Silence (if sync. enabled)
SW1
5Trouble Reminder
SW2
SW3
6AC Trouble Delay
7Autoresettable Supervisory
8IDC Combination Waterflow/
1not used
2not used
3IDC1 Verification
4IDC1 Supervisory
5IDC2 Verification
6IDC2 Supervisory
7not used
8not used
1NAC1 Nonsilenceable
2NAC1 Disable
3not used
4not used
5 & 6
used to select strobe
synchronization feature as
shown to the right
Supervisory Circuit
Switch 5Switch 6
No SynchronizationOFFOFF
System Sensor SynchronizationONOFF
Gentex SynchronizationOFFON
Wheelock SynchronizationONON
7Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)
8spare
32MS-2/MS-4 PN 51512:D 10/18/04
Page 33
DIP Switch SettingsProgram Options via DIP Switch
Table 3.2 MS-4 DIP Switch Settings
Switch NumberDIP Switch NumberDIP Switch ON
1Silence Inhibit
2Auto-silence
3Temporal Coding
4Selective Silence (if sync. enabled)
SW1
5Trouble Reminder
6AC Trouble Delay
7Autoresettable Supervisory
8IDC Combination Waterflow/
Supervisory Circuit
1IDC1 Verification
2IDC1 Supervisory
3IDC2 Verification
SW2
SW3
4IDC2 Supervisory
5IDC3 Verification
6IDC3 Supervisory
7IDC4 Verification
8IDC4 Supervisory
1NAC1 Nonsilenceable
2NAC1 Disable
3NAC2 Nonsilenceable
4NAC2 Disable
5 & 6
used to select strobe
synchronization feature as
shown to the right
7Nonsilenceable Waterflow for
Switch 5Switch 6
No SynchronizationOFFOFF
System Sensor SynchronizationONOFF
Gentex SynchronizationOFFON
Wheelock SynchronizationONON
Combination Circuit
(only if SW1 switch 8 is ON)
8spare
MS-2/MS-4 PN 51512:D 10/18/0433
Page 34
Program Options via DIP SwitchDIP Switch Settings
3.1.1 SW1 DIP Switch Settings
3.1.1.1 Silence Inhibit
Switch 1, placed in the ON position, selects the Silence Inhibit feature. This feature
prevents the silencing or resetting of the NACs (Notification Appliance Circuits) for
a period of one minute after initiation of an alarm. Placing switch 1 to the OFF
position deselects the Silence Inhibit feature. The factory default setting is switch 1
OFF for no Silence Inhibit.
3.1.1.2 Auto-silence
Switch 2, placed in the ON position, selects the Auto-silence feature. This feature
automatically silences all NACs, programmed for silenceable operation, ten
minutes after alarm activation. A new activation on another zone will resound the
NACs. The factory default setting is switch 2 OFF for no Auto-silence.
3.1.1.3 Temporal Coding
Switch 3, placed in the ON position, selects the Temporal Coding feature. This
feature causes the NACs to pulse,
second off,
½ second on, 1½ seconds off, continually repeating this pattern while
activated. The factory default setting is switch 3 OFF for no Temporal Coding,
which will cause the NACs to sound a steady signal when activated.
Note that Temporal Coding is disabled if Strobe Synchronization is enabled.
3.1.1.4 Selective Silence
Switch 4, placed in the ON position, selects the Selective Silence feature. This
feature allows the use of various manufacturer’s horn strobe mute protocols. When
Selective Silence is enabled and the Synchronization feature is selected (refer to
"Strobe Synchronization" on page 37), pressing the Silence button will turn off all
silenceable audible devices while leaving on the visual devices, such as strobes.
The factory default setting is switch 4 OFF for no Selective Silence.
Note: Enabling Selective Silence but not Synchronization will cause audible and
visual devices to be turned off when the Silence button is pressed.
½ second on, ½ second off, ½ second on, ½
3.1.1.5 Trouble Reminder
Switch 5, placed in the ON position, selects the Trouble Reminder feature. This
feature causes the FACP piezo to sound every 15 seconds for alarms and every two
minutes for troubles after the alarms or troubles have been silenced. In addition, the
piezo will resound 24 hours after a trouble has been silenced but not cleared. The
factory default setting is switch 5 OFF for Trouble Reminder disabled.
3.1.1.6 AC Trouble Delay
Switch 6, placed in the ON position, selects the AC Trouble Delay feature. This
feature allows the FACP to delay trouble activation for six hours following an AC
loss or brownout condition. The factory default setting is switch 6 OFF for no AC
Trouble Delay.
3.1.1.7 Autoresettable Supervisory
Switch 7, placed in the ON position, selects the Autoresettable Supervisory feature.
This feature causes the IDCs (Initiating Device Circuits), programmed as
supervisory circuits, to automatically reset (nonlatching) after the alarm condition
has been cleared. The factory default setting is switch 7 OFF for no Autoresettable
Supervisory.
3.1.1.8 IDC Combination Circuit
Switch 8, placed in the ON position, sets IDC #1 on the MS-2 or IDC #2 on the
MS-4 as a combination circuit. A combination zone can be used for monitoring
supervisory devices such as valve tamper switches and alarm devices such as
waterflow switches. Supervisory conditions, which latch via software, can be
silenced by pressing the Acknowledge and then Silence buttons. The factory
default setting is switch 8 OFF for no Combination circuit.
34MS-2/MS-4 PN 51512:D 10/18/04
Page 35
DIP Switch SettingsProgram Options via DIP Switch
3.1.2 SW2 DIP Switch Settings
3.1.2.1 IDC1 Verification (MS-4 only)
Switch 1 only on the MS-4, placed in the ON position, selects the Verification
feature for IDC (Initiating Device Circuit) #1. When Verification is selected the
following events will occur when a smoke detector activates:
1. FACP removes power from all zones for 6 seconds, resetting all smoke detectors
2. Power is reapplied and a 12 second retard period begins, allowing detectors to
stabilize
3. During the 18 second reset/retard periods of steps 1 & 2, subsequent alarms by
the same zone are ignored
4. Alarms detected on any other zone during the retard period will cause the FACP
to immediately process the alarm
5. A 60 second confirmation period follows the reset/retard period. If an alarm
occurs during the confirmation period, on the zone which initiated verification,
the FACP will immediately process the alarm. If no alarm is detected during this
confirmation period, the FACP returns to normal condition
Important! Circuits selected for verification must have only smoke detectors
installed
Detector Alarms on Different
Zone During First Detector's
Verification Period
RETARD
18 sec.
CONFIRMATION
Control Panel Processes Alarm if Same Detector is Still in Alarm
Control Panel Immediately Processes Alarm
6 sec.
RESET
Alarm Ignored
The factory default setting is switch 1 OFF for no IDC1 Verification.
3.1.2.2 IDC1 Supervisory (MS-4 only)
Switch 2 only on the MS-4, placed in the ON position, programs IDC #1 as a
Supervisory circuit. A supervisory zone can be used for monitoring supervisory
devices such as sprinkler tamper switches. A supervisory activation will pulse the
piezo sounder at a ˝ second rate and flash the zone supervisory LED at the same
rate. The factory default setting is switch 2 OFF for no IDC1 Supervisory.
3.1.2.3 IDC1 Verification for MS-2 or IDC2 Verification for MS-4
Switch 3, placed in the ON position, selects the Verification feature for IDC #1 on
the MS-2 or IDC #2 on the MS-4. The factory default setting is switch 3 OFF for no
Verification. Refer to IDC1 Verification (MS-4 only) for a description of this
feature.
78 sec.
3.1.2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4
Switch 4, placed in the ON position, programs IDC #1 on the MS-2 or IDC #2 on
the MS-4 as a Supervisory circuit. A supervisory zone can be used for monitoring
supervisory devices such as sprinkler tamper switches. A supervisory activation
will pulse the piezo sounder at a ˝ second rate and flash the zone supervisory LED at
the same rate. The factory default setting is switch 2 OFF for no Supervisory.
MS-2/MS-4 PN 51512:D 10/18/0435
Page 36
Program Options via DIP SwitchDIP Switch Settings
3.1.2.5 IDC2 Verification for MS-2 or IDC3 Verification for MS-4
Switch 5, placed in the ON position, selects the Verification feature for IDC #2 on
the MS-2 or IDC #3 on the MS-4. The factory default setting is switch 5 OFF for no
Verification. Refer to "IDC1 Verification (MS-4 only)" on page 35 for a
description of this feature.
3.1.2.6 IDC2 Supervisory for MS-2 or IDC3 Supervisory for MS-4
Switch 6, placed in the ON position, programs IDC #2 on the MS-2 or IDC #3 on
the MS-4 as a Supervisory circuit. A supervisory zone can be used for monitoring
supervisory devices such as sprinkler tamper switches. A supervisory activation
will pulse the piezo sounder at a ˝ second rate and flash the zone supervisory LED at
the same rate. The factory default setting is switch 6 OFF for no Supervisory.
3.1.2.7 IDC4 Verification (MS-4 only)
Switch 7 only on the MS-4, placed in the ON position, selects the Verification
feature for IDC #4. The factory default setting is switch 7 OFF for no IDC4
Verification. Refer to "IDC1 Verification (MS-4 only)" on page 35 for a
description of this feature.
3.1.2.8 IDC4 Supervisory (MS-4 only)
Switch 8 only on the MS-4, placed in the ON position, programs IDC #4 as a
Supervisory circuit. A supervisory zone can be used for monitoring supervisory
devices such as sprinkler tamper switches. A supervisory activation will pulse the
piezo sounder at a ˝ second rate and flash the zone supervisory LED at the same
rate. The factory default setting is switch 8 OFF for no IDC4 Supervisory.
3.1.3 SW3 DIP Switch Settings
3.1.3.1 NAC1 Nonsilenceable
Switch 1, placed in the ON position, programs NAC #1 as a nonsilenceable circuit.
Selecting this feature will prevent the notification appliances on NAC #1 from
being silenced by the Autosilence feature or by pressing the Alarm Silence button.
The factory default setting is switch 1 OFF for silenceable circuit.
3.1.3.2 NAC1 Disable
Switch 2, placed in the ON position, will disable NAC #1, preventing the
notification appliances from activating. This feature may be used during
maintenance or while testing the system to prevent building evacuation. The FACP
will indicate an NAC disabled fault and system trouble while this feature is
selected. The factory default setting is switch 2 OFF for NAC1 enabled.
3.1.3.3 NAC2 Nonsilenceable (MS-4 only)
Switch 3 only on the MS-4, placed in the ON position, programs NAC #2 as a
nonsilenceable circuit. Selecting this feature will prevent the notification
appliances on NAC #2 from being silenced by the Autosilence feature or by
pressing the Alarm Silence button. The factory default setting is switch 3 OFF for
silenceable circuit.
3.1.3.4 NAC2 Disable (MS-4 only)
Switch 4 only on the MS-4, placed in the ON position, will disable NAC #2,
preventing the notification appliances from activating. This feature may be used
during maintenance or while testing the system to prevent building evacuation. The
FACP will indicate an NAC disabled fault and system trouble while this feature is
selected. The factory default setting is switch 4 OFF for NAC2 enabled.
36MS-2/MS-4 PN 51512:D 10/18/04
Page 37
DIP Switch SettingsProgram Options via DIP Switch
3.1.3.5 Strobe Synchronization
Switches 5 and 6 are used to program the Synchronization feature. This feature
controls the activation of notification appliances in such a way that all devices will
turn on and off at exactly the same time, This is particularly critical when activating
strobes which must be synchronized to avoid random activation and a potential
hazard or confusion. The FACP can be programmed to operate with a variety of
manufacturer’s devices. The following table lists the required switch settings to
accomplish synchronization:
Synchronization FeatureSwitch 5Switch 6
No SynchronizationOFFOFF
System Sensor SynchronizationONOFF
Gentex SynchronizationOFFON
Wheelock SynchronizationONON
The factory default setting is switches 5 and 6 OFF for No Synchronization.
3.1.3.6 Nonsilenceable Waterflow for Combination Circuit
If SW1 switch 8 is set to the ON position to select a Combination Waterflow/
Supervisory Circuit (refer to "IDC Combination Circuit" on page 34) and SW3
switch 7 is set to the ON position to select the Nonsilenceable Waterflow for the
Combination Circuit option, the following conditions will occur:
• MS-2 - NACs become nonsilenceable upon acitvation of IDC #1 (Combination
Circuit)
• MS-4 - NACs become nonsilenceable upon activation of IDC #2 (Combination
Circuit)
Notes:
1.If initial alarm activations are from IDCs other than the Combination Circuit,
the NACs will be either silenceable or nonsilenceable, depending on the
setting of SW3 switches 1 and 3 (refer to "NAC1 Nonsilenceable" on page 36
and "NAC2 Nonsilenceable (MS-4 only)" on page 36).
2.If alarm activation is from the Combination Circuit programmed for
nonsilenceable, all NACs will be nonsilenceable regardless of subsequent IDC
activations.
3.1.3.7 Spares
Switch 8 is a spare switch and has no function at this time. The switch should
therefore be left in the factory default setting of OFF.
MS-2/MS-4 PN 51512:D 10/18/0437
Page 38
Operating InstructionsSwitch Functions in Normal Mode
SECTION 4Operating Instructions
The MS-2 and MS-4 have two modes of operation which are Normal and Walktest
modes. Upon initial power-up, the system will be in Normal Mode. This section
discusses operation of the control panel in the Normal Mode.
4.1 Switch Functions in Normal Mode
4.1.1 ACK - Acknowledge
The Acknowledge button, which is located on the FACP membrane switch panel,
silences the system piezo sounder and changes all flashing system LEDs to on steady.
Pressing the Acknowledge button will have no effect on the Notification Appliance
Circuits. To activate, press and hold the Acknowledge button for a minimum of one
second.
4.1.2 Silence
Pressing the Silence button, which is located on the FACP membrane switch panel,
silences the system piezo sounder, turns off the silenceable Notification Appliance
Circuits and turns on the Alarm Silence LED. The Silence button will be ignored for nonsilenceable waterflows and NACs. Upon the occurrence of a subsequent event
(alarm or trouble), Silence is overridden and the control panel will respond to the new
event. To activate, press the Silence button for a minimum of one second.
Note: If Silence Inhibit has been enabled, NACs cannot be silenced for one minute
following initiation of an alarm.
4.1.3 Zone Enable/Disable
To disable a zone, press the corresponding Zone Enable/Disable button. The Zone
Disable and system Trouble LEDs will blink, as well as the Trouble LED for the
disabled zone. To enable the zone, press the Zone Enable/Disable button a second time.
4.1.4 Reset/(Lamp Test)
The system Reset button, which is located on the FACP membrane switch panel, resets
the system and any smoke detectors. Each press of the Reset button will cause the
following:
Clear all status LEDs
Turn off the Notification Appliance Circuits
Reset all zones by temporarily removing power
Silence the onboard piezo sounder
Restore all system relays to normal
Temporarily remove power from the resettable power output
Note: if Silence Inhibit is active, a panel reset cannot occur for one minute.
Any alarm, supervisory or trouble condition that exists after a system reset will resound
the system, reactivating appropriate system activity. Any zones that were disabled
before the reset will be disabled after the reset.
Lamp Test - When the Reset button is pressed and then released, the FACP will
perform a Lamp Test. All panel LEDs will be turned on and the piezo will sound for
approximately two seconds.
38MS-2/MS-4 PN 51512:D 10/18/04
Page 39
WalktestOperating Instructions
!
!
4.1.5 Walktest
The Walktest button, which is located on the FACP membrane switch panel, allows a
panel walktest to be performed. Pressing and holding the Walktest button for a
minimum of two seconds causes the FACP to enter audible walktest. Pressing the
Walktest button and then the Silence button and holding both for a minimum of two
seconds will cause the panel to enter silent walktest. Walktest can be exited by pressing
and holding the Walktest button for a minimum of three seconds or by pressing the
Reset button. Refer to “Walktest” for a complete description of this feature.
4.2 Walktest
Walktest allows the testing of all control panel IDCs (input zones). An audible or silent
walktest may be performed.
It is important to note that while the FACP is in Walktest mode, the control panel is in
!
an off-normal condition and does not provide fire protection.
It should also be noted that the trouble relay will be activated while the control panel is
in Walktest mode. Placing the control panel into Walktest mode will only be possible if
the system has no active alarms.
Prior to initiating a walktest, check to make certain that all system faults have been
cleared. Upon entering Walktest mode, the following conditions should occur:
•Trouble relay will activate
•Alarm relay will be disabled
•Supervision relay will be disabled (MS-4 only)
•Piezo sounder will be disabled
3
•I
smoke detectors will enter their own test mode causing their LEDs to flash
twice every five seconds (refer to the I
•All alarm conditions will be displayed as they occur by blinking zone alarm LED
•All zone troubles will be displayed as they occur by blinking zone trouble LED
3
specification document)
During walktest, the FACP zone LEDs will blink for the first activation on a zone.
Subsequent activations on the same zone will cause the corresponding zone LED to
blink the number of alarms on the zone since the start of the test, followed by a two
second pause and then a repeat of the sequence.
Note that following a zone activation, a 6 second reset for conventional and 60 second
reset for I
3
detectors is initiated. No new alarms or troubles will be detected during this
reset period.
Disabled zones will not respond during Walktest. A zone may be disabled while in
Walktest mode, should a faulty device be detected. This allows the user to return the
system to Normal mode, enabling all other zones while preventing the faulty zone from
triggering a false alarm.
Audible Walktest
To perform an audible Walktest, press and hold the Walktest button for a minimum of
two seconds. The Trouble and Walktest LEDs will blink at a ¼ second rate.
While testing input devices, the first initiating device activated on a zone will cause the
NACs to sound for four seconds. Subsequent device activations on the same zone will
cause the NACs to turn on for one second. Any smoke detectors that are activated will
automatically be reset by the panel. Zone faults (open circuits) will cause the NACs to
remain on steadily until the fault is cleared.
During an audible walktest, if a device remains latched in alarm (such as a Pull Station
that is not reset after activation), subsequent testing of devices on the same zone will
not
trigger the NACs. Be certain to reset or clear each device after testing.
MS-2/MS-4 PN 51512:D 10/18/0439
Page 40
Operating InstructionsStatus LEDs
Silent Walktest
To perform a silent Walktest, press the Walktest button, then press the Alarm Silence
button and hold both for a minimum of two seconds. The Trouble, Walktest and Alarm
Silence LEDs will blink at a ¼ second rate.
A silent walktest will not activate the control panel Notification Appliance Circuits.
All alarm and trouble conditions must be observed using the LEDs at the control panel
as described in the previous sections.
Exiting Walktest Mode
Walktest mode can be exited by pressing and holding the Walktest button for a
minimum of three seconds or by pressing the Reset button. The time-out feature will
cause the control panel to automatically exit Walktest mode if no button presses have
occurred for one hour.
4.3 Status LEDs
AC Power LED
A green LED that remains on while the AC power supply is within correct limits. If
this indicator fails to light under normal conditions, service the system immediately.
NAC Disable LED
A yellow LED that blinks to indicate that a Notification Appliance Circuit has been
disabled using the main circuit board DIP switches. The LED will turn on steady when
the Acknowledge or Alarm Silence button is pressed.
Zone Disable LED
A yellow LED that blinks to indicate that one or more alarm zones have been disabled
using the Zone Enable/Disable buttons. The disabled zone’s trouble LED will also be
on. The Acknowledge or Alarm Silence button does not affect the Zone Disable LED.
NAC Fault LED
A yellow LED that blinks to indicate that an NAC trouble condition exists in the
system. The LED turns on steady when the Acknowledge or Alarm Silence button is
pressed.
System Trouble LED
A yellow LED that blinks to indicate that a system fault or abnormal condition exists
and that the fire alarm system may be inoperative. It turns on steady when the
Acknowledge or Alarm Silence button is pressed.
Power Trouble LED
A yellow LED that blinks to indicate an AC power, battery or charger trouble condition.
It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Walktest LED
A yellow LED that blinks to indicate that the control panel is in Walktest mode. The
Acknowledge and Alarm Silence buttons do not affect the Walktest LED.
Alarm Silence LED
A yellow LED that turns on to indicate that an Alarm condition exists in the system but
the Notification Appliance Circuits and the local piezo sounder have been silenced.
Zone Fire Alarm LED
A red LED for each zone that blinks to indicate that an alarm exists on the
corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button
is pressed.
40MS-2/MS-4 PN 51512:D 10/18/04
Page 41
OperationOperating Instructions
Zone Supervisory LED
A yellow LED for each zone that blinks if the zone has been programmed for
supervisory and a supervisory condition exists on the corresponding zone. It turns on
steady when the Acknowledge or Alarm Silence button is pressed.
Note that an I
3
smoke detector freeze condition is displayed as a supervisory condition.
The zone does not have to be programmed as a supervisory for this to occur.
Zone Trouble LED
A yellow LED for each zone that blinks to indicate that a trouble exists on the
corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button
is pressed.
Zone Maintenance LED
A yellow LED for each zone that blinks to indicate that a I
3
smoke detector on the
corresponding zone is dirty or in need of maintenance. It turns on steady when the
Acknowledge or Alarm Silence button is pressed.
Earth Fault LED (on main circuit board)
A yellow LED that blinks to indicate a ground fault condition on the system. A ground
fault occurs when a low resistance between the FACP and earth ground exists. The
LED turns on steady when the Acknowledge or Alarm Silence button is pressed.
4.4 Operation
Battery Fault LED (on main circuit board)
A yellow LED that blinks to indicate a low battery or no battery condition on the FACP.
It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Charger Fault LED (on main circuit board)
A yellow LED that blinks to indicate a battery charger fault. It turns on steady when
the Acknowledge or Alarm Silence button is pressed.
Normal mode is the standard mode of operation. In this mode, the panel continuously
monitors system status. When no alarm or trouble conditions exist, the control panel
will be in the following state:
•all LEDs will be off (except the AC Power LED)
•the Notification Appliance Circuits will be off
•all relays are in their normal state
•the onboard piezo sounder will be off
•I3 smoke detectors will be polled for maintenance and freeze conditions on initial
entry into Normal mode. Thereafter, each device will be polled every hour for
freeze and every four hours for maintenance conditions
All alarm and system trouble conditions are annunciated on the control panel’s LEDs.
Note: To ensure that the system is functioning properly, the FACP will perform a freeze
check five minutes after the panel is reset, followed by a maintenance check. If there is
no freeze or maintenance condition, the panel will continue to monitor for freeze
conditions every hour and maintenance conditions every four hours.
MS-2/MS-4 PN 51512:D 10/18/0441
Page 42
Operating InstructionsOperation
4.4.1 Fire Alarm Response
The control panel will, upon detection of an alarm condition, cause the following:
•Latch the alarm condition - requires panel reset to clear alarm condition
•Blink the Zone Alarm LED one second On and one second Off
•Turn on remote annunciator alarm LED and piezo sounder
•Turn the Notification Appliance Circuit(s) on
•Turn the FACP piezo sounder on steady
•Turn on the alarm relay
•Start the Silence Inhibit, Auto-silence and Trouble Reminder functions if enabled
4.4.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system
reset button has been pressed (pull stations have been reset, smoke detectors have reset
and no smoke is present, waterflow has stopped). The control panel will perform the
following upon restoral of all active alarms:
•Turn off the FACP Zone Alarm LED
•Turn off remote annunciator alarm LED and piezo sounder
•Turn off the Notification Appliance Circuit(s)
•Turn off the FACP piezo sounder
•Turn off the alarm relay
•I3 smoke detectors will be polled for maintenance and freeze conditions on initial
entry into Normal mode. Thereafter, each device will be polled every hour for
freeze and every four hours for maintenance conditions
4.4.3 System Supervisory Condition Response
Zones can be programmed for supervisory in applications where a waterflow sensing
device has been employed and a sprinkler tamper switch is to be monitored. An I
detector in a ‘freeze’ condition (detected abnormally low ambient temperature) will
also generate a supervisory condition on its alarm zone (refer to the I
3
specification
sheet for temperature threshold). Any supervisory condition will cause the control
panel to perform the following functions:
•Blink the FACP Zone Supervisory LED ½ second On and ½ second Off
•Pulse the piezo sounder ½ second On and ½ second Off
•Turn on the supervisory relay (MS-4 only)
3
4.4.4 System Supervisory Restoral Response
When the supervisory condition has been cleared, the control panel will perform the
following:
•Turn off the FACP Zone Supervisory LED
•Turn off the piezo sounder
•Turn off the supervisory relay (MS-4 only)
42MS-2/MS-4 PN 51512:D 10/18/04
Page 43
OperationOperating Instructions
4.4.5 Trouble Condition Response
The control panel, upon detection of one or more trouble conditions, well perform the
following:
•Blink the FACP System Trouble LED one second On and one second Off
•Blink the FACP Zone Trouble LED one second On and one second Off
•Turn on remote annunciator Trouble LED and pulse the piezo sounder
•Pulse the FACP piezo sounder one second On and one second Off
•Transfer fail-safe Trouble relay
•Additional LEDs will turn on or blink according to the specific trouble
NAC Disable LED if NAC has been disabled
Zone Disable LED if a zone has been disabled
NAC Fault LED if a fault is detected on an NAC
Power Trouble LED if an AC, battery or charger fault is detected
AC Power LED will turn off
if AC fail or brownout occurs
Alarm Silence LED if Silence button is pressed after an alarm or trouble
Walktest LED if Walktest mode is entered
Zone Maintenance LED if a I
3
smoke detector needs servicing
Earth Fault LED if a ground fault occurs
Battery Fault LED if low or no battery condition occurs
Charger Fault LED if a charger trouble occurs
4.4.6 Trouble Condition Restoral
The control panel performs the following upon restoral of all trouble conditions:
•Turn off the FACP System Trouble LED
•Turn off the FACP Zone Trouble LED
•Turn off the remote annunciator Trouble LED and piezo sounder
•Turn off the piezo sounder
•Transfer the fail-safe Trouble relay
•Turn off additional LEDs corresponding to specific troubles
MS-2/MS-4 PN 51512:D 10/18/0443
Page 44
Power Supply CalculationsOverview
SECTION 5Power Supply Calculations
5.1Overview
This section contains instructions and tables for calculating power supply currents in
alarm and standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the
system
2. Calculating the power supply load current for non-fire and fire alarm conditions
and calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power
loss occurs
4. Selecting the proper batteries for your system
5.2Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which
must be labeled FIRE ALARM. This branch circuit must connect to the line side of
the main power feed of the protected premises. No other non-fire alarm equipment may
be powered from the fire alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the control panel.
Overcurrent protection for this circuit must comply with Article 760 of the National
Electrical Codes as well as local codes. Use 14 AWG (2.00 mm
insulation for this branch circuit.
Use Table 5-1 , to determine the total amount of current, in AC amperes (A), that must
be supplied to the system.
TABLE 5-1:120 VAC Branch Circuit Requirements
Device Type
MS-2/MS-4
or
MS-2E/MS-4E
Number of
Devices
1X
[ ]X=
[ ]X[ ]=
Sum Column for AC Branch Current Required=
Current Draw
(AC amps)
2.3
1.15
2
) wire with 600 volt
Total C u r re n t
per Device
=
44MS-2/MS-4 PN 51512:D 10/18/04
Page 45
Calculating the System Current DrawPower Supply Calculations
5.3Calculating the System Current Draw
5.3.1 Overview
The control panel must be able to power all internal and external devices continuously
during the non-fire alarm condition. To calculate the non-fire alarm load on the system
power supply when primary power is applied, use Calculation Column 1 in Table 5-3
on page 46. The control panel must support a larger load current during a fire alarm
condition. To calculate the fire alarm load on the power supply, use Calculation Column 2 in Table 5-3 on page 46. The secondary power source (batteries) must be able to
power the system during a primary power loss. To calculate the non-fire alarm load on
the secondary power source, use Calculation Column 3 in Table 5-3 on page 46.
When calculating current draw and the battery size, note the following:
• ‘Primary’ refers to the main power source for the control panel
• ‘Secondary’ refers to the control panel’s backup batteries
• All currents are given in amperes (A). Table 5-2 shows how to convert milliamperes and microamperes to full amperes.
TABLE 5-2:Converting to Full Amperes
To convert...MultiplyExample
Milliamperes (mA) to
amperes (A)
Microamperes (
amperes (A)
µA) to
mA x 0.0013 mA x 0.001 = 0.003A
µA x 0.000001300 µA x 0.000001 = 0.0003 A
5.3.2 How to Use Table 5-3 on page 46 to Calculate System Current Draw
Use Table 5-3 on page 46 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Fire-Lite Device Compatibility Document for compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 5-4 on page 47
Following are the types of current that can be entered into Table 5-3 on page 46:
Calculation Column 1 - The primary supply current load that the control
panel must support during a non-fire alarm condition, with AC power
applied.
Calculation Column 2 - The primary supply current load that the control
panel must support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in
a non-fire alarm condition during a loss of AC power.
MS-2/MS-4 PN 51512:D 10/18/0445
Page 46
Power Supply CalculationsCalculating the System Current Draw
Table 5-3 contains three columns for calculating current draws. For each column,
calculate the current and enter the total (in amperes) in the bottom row. When finished,
copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5-4 on
page 47.
Calculation Column 2
Primary, Fire Alarm Current
(amps)
1
=
0.1
[ ]X[ ]=X[ ]=
[ ]X[ ]=X[ ]=
[ ]X[ ]=
X[0.112]
X[0.175]
X[0.011]1=
1
=
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
0.1
X[0.080]=
X[0.085]=
X[0.005]=
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005
amps.
2. Refer to the Device Compatibility Document for standby current.
3. Refer to the Device Compatibility Document for standby current.
4. Must use compatible listed Power Supervision Relay.
5. Current limitation of Terminal TB2 circuits is 2.50 amps per NAC (MS-4 requires optional transformer for max. current)
6. The total standby current must include both the resettable (TB1 Terminals 3 & 4) and nonresettable for MS-4 only (TB1 Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. Current limitations of TB1, Terminals 1 & 2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10
7. Total current draw listed above cannot exceed 3.0 amps with only standard transformer installed or, for the MS-4, 6.0 amps with
both the standard and optional transformers installed.
0.
,
46MS-2/MS-4 PN 51512:D 10/18/04
Page 47
Calculating the Battery SizePower Supply Calculations
5.4Calculating the Battery Size
Use Table 5-4 to calculate the total Standby and Alarm load in ampere hours (AH).
This total load determines the battery size (in AH), required to support the control panel
under the loss of AC power. Complete Table 5-4 as follows:
1. Enter the totals from Table 5-3 on page 46, Calculation Columns 2 and 3 where
shown
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’
below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and
Alarm ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size
(in AH)
5. Write the ampere hour requirements on the Protected Premises label located
inside the cabinet door
TABLE 5-4:Total Secondary Power Requirements at 24 VDC
Primary Alarm Load
(total from Table 5-3 Calculation
Column 2)
[ ]
Sum of Standby and Alarm Ampere Hours= AH
Multiply by the Derating FactorX 1.2
Battery Size, Total Ampere Hours Required= AH
Required Standby Time
(24 or 60 hours)
X[ ]= AH
Required Alarm Time
(for 5 min., enter 0.084,
for 10 min., enter 0.168)
X[ ]
= AH
5.4.1 NFPA Battery Requirements
• NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of
standby power followed by 5 minutes in alarm
• NFPA 72 Auxiliary and Remote Station require 60 hours of standby followed by
5 minutes in alarm. Batteries installed in a system powered by a generator need
to provide at least 4 hours of standby power
5.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 5-4 . The
control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of housing batteries up to 7 AH. Batteries larger than 7 AH require the
BB-17F or other UL listed external battery cabinet.
MS-2/MS-4 PN 51512:D 10/18/0447
Page 48
Notes
48MS-2/MS-4 PN 51512:D 10/18/04
Page 49
Index
Numerics
411 16
411UD 16
4XLMF
installation 27, 30
see also LED Interface Module 15
see also LED interface module 30
specifications 30
wiring to RZA-4XF 30
4XTMF
installation 27, 28
operation 28
see also Transmitter Module 15
see also transmitter module 28
specifications 28
4XZMF
installation 27, 29
see also Zone Relay Module 15
see also zone relay module 29
specifications 29
A
AC power 19
AC Power LED 40
AC power rating 12
AC power requirements 44
AC trouble delay 34
accessories 15
ACK
see also Acknowledge 11
Acknowledge 11, 13
Acknowledge button 38
alarm
see also Class A Converter Module 9, 15
charger 14
charger capacity 12
Charger Fault LED 41
circuits 10
Class A 15, 20, 26
Class A Converter Module 9, 15
installation 25
Class B 10, 12, 14, 20
coding
NACs 34
combination circuit 10, 21
see also waterflow/tamper 34
combination waterflow/supervisory 10, 20, 21
requirements 21
wiring 21
compatibility
see also device compatibility 10
control buttons 11
controls 13
current
maximum system 12
nonresettable power 23
resettable power 23
see also system current 10
total output 22
current requirements for system 45, 46
D
description 10
device compatibility 10
Digital Alarm Communicator/Transmitter
see also 411 & 411UD 16
dimensions
backbox 14, 17
DIP switch options
see also programming 31
DIP switch settings 32
see also programming 31
disable
see also zone enable/disable 11
disable NAC 36
dress panel 10, 15
E
Earth Fault LED 41
earth ground 19
MS-2/MS-4 PN 51512:D 10/18/0449
Page 50
Index
enable
see also zone enable/disable 11
End-of-Line resistor
IDC 12, 20, 21
NAC 12, 22
F
fail-safe
trouble relay 23
fail-safe relay
see also trouble relay 14
features 10
fire alarm response 42
fire alarm restoral 42
Form-C 15, 29
see also relay 10, 14
freeze 20
freeze signal
see also smoke detector monitoring 10
G
Gentex synchronization 37
Ground Fault
disable 8, 9
I
I3 detectors 14, 20
IDC 9, 10, 12, 14, 20
alarm current 12
compatibility 20
End-of_Line resistor 21
End-of-Line resistor 12, 20
maximum loop resistance 12, 20
see also Initiating Device Circuit 8
short circuit current 12
standby current 12
wiring 20
indicators 13
see also LED 11
Initiating Device Circuit 8, 9, 10, 12, 14, 20
Class A 26
In-Line resistor
IDC combination circuit 21
installation 17
4XLMF 27
4XTMF 27, 28
4XZMF 27
CAC-4 25
Class A Converter Module 25
option modules 25, 27
J
J3 and J5
option module connectors 27
J4 and J6
option module connectors 27
JP1 jumper
placement supervision 27
JP2
placement supervision 27
L
Lamp Test 38
LED 11, 13
AC Power 11, 13, 40
Alarm Silence 11, 13
alarm silence 40
Battery Fault 11, 13
battery fault 41
Charger 11, 13
charger fault 41
Earth Fault 11, 13
earth fault 41
Fire Alarm 11, 13
main circuit board 8, 9
Maintenance 11, 13
NAC Disable 11, 13
NAC disable 40
NAC Fault 11, 13
NAC fault 40
Power Trouble 11, 13
power trouble 40
Supervisory 11, 13
System Trouble 11, 13
system trouble 40
Trouble 11, 13
Walktest 11, 13
walktest 40
Zone Disable 11, 13
zone disable 40
zone fire alarm 40
zone maintenance 41
zone supervisory 41
zone trouble 41
LED Interface Module 15
installation 27
see also 4XLMF 30
M
main circuit board
see also MS-2 8
see also MS-4 9
maintenance 20
piezo pulse rate 14
maintenance signal
see also smoke detector monitoring 10
modes of operation
see also normal and walktest 38
mounting
cabinet 17
MS-2 Main Circuit Board 8
MS-4 Main Circuit Board 9
municipal box 28
municipal box transmitter
see also 4XTMF 15
N
NAC 9, 10, 12, 14, 22
coding 34
current 22
50MS-2/MS-4 PN 51512:D 10/18/04
Page 51
Index
disable 36
End-of-Line resistor 12, 22
maximum current 12
nonsilenceable 36
see also Notification Appliance Circuit 8
wiring 22
NAC Disable LED 40
NAC Fault LED 40
nonpower-limited wiring 24
nonresettable power 9, 10, 12, 14, 23
current 23
maximum current 12
nonsilenceable NAC 36
normal mode 38
Notification Appliance Circuit 8, 9, 10, 12, 14, 22
Zone 1 20
Zone Disable LED 40
Zone Enable/Disable 11, 13
Zone Fire Alarm LED 40
Zone Maintenance LED 41
zone relay module 15
see also 4XZMF 29
Zone Supervisory LED 41
Zone Trouble LED 41
Index
52MS-2/MS-4 PN 51512:D 10/18/04
Page 53
Notes
MS-2/MS-4 PN 51512:D 10/18/0453
Page 54
Notes
54MS-2/MS-4 PN 51512:D 10/18/04
Page 55
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.
LimWarLg.p65 01/10/2000
Page 56
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.