Fire-Lite MS-2E' MS-4E, MS-2, MS-4, MS-2E, MS-4E User Manual

Page 1
PN: 51512:D ECN 04-593
Fire Alarm Control Panel
MS-2 & MS-4
MS-2E & MS-4E
Document #51512
10/18/04 Revision:
D
Page 2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel-
oping fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the mean­ing of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
LimWarLg.p65 01/10/2000
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
Page 4
Notes
4 MS-2/MS-4 PN 51512:D 10/18/04
Page 5
Table of Contents
SECTION 1: Product Description ........................................................................................................................10
1.1: Product Features..........................................................................................................................................10
1.2: Specifications ..............................................................................................................................................12
1.3: Controls and Indicators ...............................................................................................................................13
1.4: Circuits ........................................................................................................................................................14
1.5: Components.................................................................................................................................................14
1.6: Optional Modules and Accessories .............................................................................................................15
SECTION 2: Installation .......................................................................................................................................17
2.1: Backbox Mounting......................................................................................................................................17
2.2: Operating Power..........................................................................................................................................19
2.3: Input Circuits...............................................................................................................................................20
2.4: Output Circuits ............................................................................................................................................22
2.4.1: Notification Appliance Circuits ........................................................................................................22
2.4.2: DC Power Output Connections.........................................................................................................23
2.4.3: Relays................................................................................................................................................23
2.5: Power-limited Wiring Requirements...........................................................................................................24
2.6: Installation of Optional Modules.................................................................................................................25
2.6.1: CAC-4 Class A Converter Module (MS-4 only) ..............................................................................25
2.6.1.1 Installation ...............................................................................................................................25
2.6.1.2 Wiring NACs and IDCs for Class A .......................................................................................26
2.6.2: 4XTMF, 4XLMF and 4XZMF Option Modules...............................................................................27
2.6.2.1 4XTMF Transmitter Module Installation ...............................................................................28
2.6.2.2 4XZMF Zone Relay Module (MS-4 only) ..............................................................................29
2.6.2.3 4XLMF LED Interface Module (MS-4 only) .........................................................................30
SECTION 3: Program Options via DIP Switch ..................................................................................................31
3.1: DIP Switch Settings ....................................................................................................................................32
3.1.1: SW1 DIP Switch Settings .................................................................................................................34
3.1.1.1 Silence Inhibit .........................................................................................................................34
3.1.1.2 Auto-silence ............................................................................................................................34
3.1.1.3 Temporal Coding ....................................................................................................................34
3.1.1.4 Selective Silence .....................................................................................................................34
3.1.1.5 Trouble Reminder ...................................................................................................................34
3.1.1.6 AC Trouble Delay ...................................................................................................................34
3.1.1.7 Autoresettable Supervisory .....................................................................................................34
3.1.1.8 IDC Combination Circuit ........................................................................................................34
3.1.2: SW2 DIP Switch Settings .................................................................................................................35
3.1.2.1 IDC1 Verification (MS-4 only) ..............................................................................................35
3.1.2.2 IDC1 Supervisory (MS-4 only) ...............................................................................................35
3.1.2.3 IDC1 Verification for MS-2 or IDC2 Verification for MS-4 .................................................35
3.1.2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4 .................................................35
3.1.2.5 IDC2 Verification for MS-2 or IDC3 Verification for MS-4 .................................................36
3.1.2.6 IDC2 Supervisory for MS-2 or IDC3 Supervisory for MS-4 .................................................36
3.1.2.7 IDC4 Verification (MS-4 only) ...............................................................................................36
3.1.2.8 IDC4 Supervisory (MS-4 only) ...............................................................................................36
3.1.3: SW3 DIP Switch Settings .................................................................................................................36
3.1.3.1 NAC1 Nonsilenceable .............................................................................................................36
3.1.3.2 NAC1 Disable .........................................................................................................................36
3.1.3.3 NAC2 Nonsilenceable (MS-4 only) ........................................................................................36
3.1.3.4 NAC2 Disable (MS-4 only) ....................................................................................................36
3.1.3.5 Strobe Synchronization ...........................................................................................................37
3.1.3.6 Nonsilenceable Waterflow for Combination Circuit ..............................................................37
3.1.3.7 Spares ......................................................................................................................................37
SECTION 4: Operating Instructions ....................................................................................................................38
MS-2/MS-4 P/N: 51512:D 10/18/04 5
Page 6
Table of Contents
4.1: Switch Functions in Normal Mode..............................................................................................................38
4.1.1: ACK - Acknowledge.........................................................................................................................38
4.1.2: Silence ...............................................................................................................................................38
4.1.3: Zone Enable/Disable .........................................................................................................................38
4.1.4: Reset/(Lamp Test) .............................................................................................................................38
4.1.5: Walktest.............................................................................................................................................39
4.2: Walktest .......................................................................................................................................................39
4.3: Status LEDs.................................................................................................................................................40
4.4: Operation .....................................................................................................................................................41
4.4.1: Fire Alarm Response.........................................................................................................................42
4.4.2: Fire Alarm Restoral...........................................................................................................................42
4.4.3: System Supervisory Condition Response .........................................................................................42
4.4.4: System Supervisory Restoral Response ............................................................................................42
4.4.5: Trouble Condition Response.............................................................................................................43
4.4.6: Trouble Condition Restoral...............................................................................................................43
SECTION 5: Power Supply Calculations .............................................................................................................44
5.1: Overview .....................................................................................................................................................44
5.2: Calculating the AC Branch Circuit..............................................................................................................44
5.3: Calculating the System Current Draw.........................................................................................................45
5.3.1: Overview ...........................................................................................................................................45
5.3.2: How to Use Table 5-3 on page 46 to Calculate System Current Draw.............................................45
5.4: Calculating the Battery Size ........................................................................................................................47
5.4.1: NFPA Battery Requirements .............................................................................................................47
5.4.2: Selecting and Locating Batteries.......................................................................................................47
6
MS-2/MS-4 P/N: 51512:D 10/18/04
Page 7
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384 411 Digital Alarm Communicator/Transmitter Document #50921 411UD Digital Alarm Communicator/Transmitter Document #50759
MS-2/MS-4 PN 51512:D 10/18/04 7
Page 8
IDC (4.7 K, ½ watt ELR)
NAC (4.7K, ½ watt ELR)
2.5A max.
B-
B+
24 VDC
Resettable Power
500 mA max.
- 24 VDC
+ 24 VDC
MS-2(E) Main Circuit Board
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
Trouble Relay (fail-safe) 2 amps @ 30 VAC
Common Trouble (Normally Open) Normal (Normally Closed)
Alarm Relay 2 amps @ 30 VAC
Common Normally Closed Normally Open
JP3 - Cut to disable Ground Fault detection (only with approval of AHJ)
J7 Transformer Connector
120 VAC, 2.3A or 220/240 VAC, 1.15A
Earth Neutral Hot (supervised)
J3 and J5
4XTMF Option
Module
Connectors
ms2bord.cdr
SW1, SW2 and SW3
Programming DIP Switches
Module Placement Supervision (if installed) JP1 - cut to supervise module on J3 & J5
J8 Battery Connector
18 Amp Hour max.
Charger Fault LED Battery Fault LED Earth Fault LED
8 MS-2/MS-4 PN 51512:D 10/18/04
Page 9
IDC (4.7 K, ½ watt ELR) TB3
NAC (4.7K, ½ watt ELR)
TB2 2.5A max. per NAC
NAC 2 B-
NAC 2 B+
NAC 1 B-
NAC 1 B+
24 VDC Power TB1
500 mA per circuit
- Reset + Reset
- Nonreset +Nonreset
MS-4(E) Main Circuit Board
Zone 4 B-
Zone 4 B+
Zone 3 B-
Zone 3 B+
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
Trouble Relay TB5 (fail-safe) 2A @ 30 VAC
Common Trouble (Normally Open) Normal (Normally Closed)
Alarm Relay TB6 2A @ 30 VAC
Common Normally Closed Normally Open
Supv. Relay TB7 2A @ 30 VAC
Common Normally Closed Normally Open
TB1
+ - + -
Nonreset Reset
J9
TRANSFORMER 1TRANSFORMER 2
J7
J7 Transformer Connector
J9 Transformer (optional)
120 VAC, 2.3A or 220/240 VAC, 1.15A
Hot
Neutral
Earth
(supervised)
TB2
B+ B- B+ B­ NAC 1 NAC 2
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
POWER
ACK
TB8
HOT NEUT EARTH
J8 Battery Connector
18 Amp Hour max.
1
TB3
NAC
DISABLE
B+ B- B+ B­ ZONE 1 ZONE 2
Converter Module
ZONE 1
SUPERVISORY
ZONE 2
SUPERVISORY
ZONE 3
SUPERVISORY
ZONE 4
SUPERVISORY
NAC
ZONE
FAULT
DISABLE
ALARM
SILENCE
ZONE
ENABLE/D ISABLE
2
B+ B- B+ B­ ZONE 3 ZONE 4
Class A
TROUBLE
TROUBLE
TROUBLE
TROUBLE
POWER
SYSTEM
TROUBLE
TROUBLE
RESET
3
EARTH BATT CHG
J8
BATTERY
C TRBL NORM TROUBLE
CLASS A CONVERTER
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
ALARM
WAL K
SILENCE
TEST
WAL K TEST
4
JP2
12345678
SW1
Charger Fault LED Battery Fault LED Earth Fault LED
TB5
C NC NO
J1
TB6
ALARM SUPV
C NC NO
JP3 - Cut to disable Ground Fault
J3
detection (only with approval of AHJ)
J5
TB7
JP3
J3 and J5
Option Module
Connectors
J4
JP1
12345678
ON
SW2 SW3
J6
12345678
ON
ON
J4 and J6
Option Module
Connectors
ms4bord.cdr
SW1, SW2 and SW3
Programming DIP Switches
Module Placement Supervision (if installed) JP1 - cut to supervise module on J3 & J5 JP2 - cut to supervise module on J4 and J6
MS-2/MS-4 PN 51512:D 10/18/04 9
Page 10
Product Description Product Features
SECTION 1 Product Description
The MS-2 is a two zone FACP (Fire Alarm Control Panel) and the MS-4 is a four zone FACP. The information in this manual refers to both the MS-2 and MS-4 unless otherwise specified. These control panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s I conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating (refer to System Sensor’s I Installation and Maintenance Instructions document I56-1800-00 for device specifications). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete listing of compatible devices.
Outputs include one NAC (Notification Appliance Circuit) on the MS-2 and two NACs on the MS-4. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC resettable power. In addition, the MS-4 has a Form-C Supervisory relay and a nonresettable power output. The FACP supervises wiring, AC voltage and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate a auxiliary control function. The MS-2E and MS-4E offer the same features as the MS-2 and MS-4 but allows connection to 220/240 VAC.
3
detectors which are microprocessor-based
3
Note: Unless otherwise specified, the terms MS-2 and MS-4 are used in this manual to refer to the MS-2 and MS-2E as well as the MS-4 and MS-4E FACPs respectively.
1.1 Product Features
Style B (Class B) IDC (Initiating Device Circuit)
Style Y (Class B) NAC (Notification Appliance
Form-C Alarm Relay
Form-C Trouble Relay
Form-C Supervisory Relay (MS-4 only)
3.0 amps total system current standard for MS-2 and MS-4
6.0 amps total system current available for MS-4 with optional second
Optional Dress Panel DP-MS2/4
Optional Trim Ring P/N: TR-1-R for semi-flush mounting the cabinet
one zone programmable for combination
supervisory and waterflow
MS-2 - two IDCs
MS-4 - four IDCs
Circuit)
MS-2- one NAC
MS-4 - two NACs
transformer
MS-4
ZONE 1
TROUBLE
MAINTENANCEFIRE ALARM
SUPERVISORY
ZONE 2
TROUBLE
MAINTENANCE
SUPERVISORY
FIRE ALARM
ZONE 3
SUPERVISORY
TROUBLE
MAINTENANCE
FIRE ALARM
ZONE 4
SUPERVISORY
TROUBLE MAINTENANCE
FIRE ALARM
AC
POWER
ALARM
NAC
ZONE
SYSTEM
POWER
WALK
NAC
SILENCE
FAULT
TROUBLE
DISABLE
TROUBLE
TEST
DISABLE
10 MS-2/MS-4 PN 51512:D 10/18/04
Page 11
Product Features Product Description
Control Buttons
ACK (Acknowledge)
Alarm Silence
Reset
Walkt est
Zone Enable/Disable (one per zone)
LED Indicators
Fire Alarm (one per zone)
Supervisory (one per zone)
Trouble (one per zone)
Maintenance (one per zone)
AC Power
NAC Disable
Zone Disable
NAC Fault
System Trouble
Power Trouble
Walkt est
Alarm Silence
Earth Fault (on circuit board)
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
Automatic battery trickle charger
Silent or audible walktest capabilities
Optional NAC Class A converter module (MS-4 only)
Optional 4XTMF Transmitter Module (MS-2 and MS-4)
Optional 4XZMF Zone Relay Module (MS-4 only)
Optional 4XLMF Module for RZA-4XF Remote LED Annunciator (MS-4 only)
MS-2/MS-4 PN 51512:D 10/18/04 11
Page 12
Product Description Specifications
1.2 Specifications
AC Power - TB8
MS-2/MS-4: 120 VAC, 50/60 Hz, 2.3 amps MS-2E/MS-4E: 240 VAC, 50 Hz, 1.15 amps Wire size: minimum #14 AWG (2.0 mm
Battery (sealed lead acid only) - J8
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the Fire•Lite BB-17F)
Initiating Device Circuits - TB3
Alarm Zones 1 & 2 (MS-2 and MS-4) Alarm Zones 3 & 4 (MS-4 only) Power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA maximum Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Standby Current: 4 mA Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB2
One NAC on MS-2, two NACs on MS-4 Operation: Style Y (Class B) Power-limited Circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 2.5 amps total with standard transformer. 5.0 amps total (2.5 amp maximum per NAC) with optional transformer on MS-4 only End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays
Trouble Relay TB5 (fail-safe) Alarm Relay TB6 Supervisory Relay TB7 (MS-4 only) Relay Contact Ratings: 2 amps @ 30 VAC (resistive)
2
) with 600V insulation
1
Resettable Power - TB1
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note 1) Power-limited Circuitry Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Power - TB1 (MS-4 only)
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA (see note 1) Power-limited Circuitry Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. Total current for resettable power and one Notification Appliance Circuit must not exceed 3.0 amps for the MS-2. Total current for nonresettable power, resettable power and two Notification Appliance Circuits must not exceed 6.0 amps for the MS-4 (requires optional second transformer)
12 MS-2/MS-4 PN 51512:D 10/18/04
Page 13
Controls and Indicators Product Description
1.3 Controls and Indicators
Front Panel Membrane Buttons
Acknowledge
Alarm Silence
Reset
Walktest
Zone Enable/Disable - Zone 1
Zone Enable/Disable - Zone 2
Zone Enable/Disable - Zone 3 (MS-4 only)
Zone Enable/Disable - Zone 4 (MS-4 only)
LED Indicators
Fire Alarm Zone 1 - red LED
Fire Alarm Zone 2 - red LED
Fire Alarm Zone 3 - red LED (MS-4 only)
Fire Alarm Zone 4 - red LED (MS-4 only)
Supervisory Zone 1 - yellow LED
Supervisory Zone 2 - yellow LED
Supervisory Zone 3 - yellow LED (MS-4 only)
Supervisory Zone 4 - yellow LED (MS-4 only)
Trouble Zone 1 - yellow LED
Trouble Zone 2 - yellow LED
Trouble Zone 3 - yellow LED (MS-4 only)
Trouble Zone 4 - yellow LED (MS-4 only)
Maintenance Zone 1 - yellow LED
Maintenance Zone 2 - yellow LED
Maintenance Zone 3 - yellow LED (MS-4 only)
Maintenance Zone 4 - yellow LED (MS-4 only)
AC Power - green LED
NAC Disable - yellow LED
Zone Disable - yellow LED
NAC Fault - yellow LED
System Trouble - yellow LED
Power Trouble - yellow LED
Walktest - yellow LED
Alarm Silence - yellow LED
Earth Fault - yellow LED (on main circuit board)
Battery Fault - yellow LED (on main circuit board)
Charger Fault - yellow LED (on main circuit board)
MS-2/MS-4 PN 51512:D 10/18/04 13
Page 14
Product Description Circuits
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse ½ second on and ½ second off
Supervisory - pulse ½ second on and ½ second off
1.4 Circuits
Input Circuits
Two input IDCs (Initiating Device Circuits) on the MS-2 and four IDCs on the MS-4 provide Style B (Class B) configurations. All IDCs accept I conventional two-wire smoke detectors, four-wire smoke detectors and normally-open contact devices.
Output Circuits
24 VDC resettable power output - 500 mA
24 VDC nonresettable power output (MS-4 only) - 500 mA
24 volt battery charger (up to 18 Amp Hour batteries)
3
detectors as well as
1.5 Components
Notification Appliance Circuits
One NAC (Notification Appliance Circuit) Style Y (Class B) on the MS-2 Two NACs Style Y (Class B) on the MS-4
Relays
Alarm Relay Trouble Relay (fail-safe) Supervisory Relay (MS-4 only) Form-C contacts rated 2.0 amps @ 30 VAC (resistive)
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Cabinet
The cabinet is red and the backbox measures 14.5” (36.8 cm) x 15.218” (38.65 cm) x
2.875” (7.3 cm) and provides space for two batteries (up to 7 Amp Hours). Also available is an optional dress panel which mounts inside the cabinet.
Transformer Assembly
One 100VA transformer is provided standard with the FACP. An optional second 100VA transformer is available for the MS-4 to provide maximum accessory power.
Batteries
The cabinet provides space for two 7 Amp Hour batteries (larger batteries up to 18 Amp Hour, require use of a UL listed battery box such as the Fire•Lite BB-17F). Batteries must be ordered separately.
14 MS-2/MS-4 PN 51512:D 10/18/04
Page 15
Optional Modules and Accessories Product Description
1.6 Optional Modules and Accessories
CAC-4 Class A Converter Module (MS-4 only)
The CAC-4 Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J1 on the MS-4 main circuit board.
4XTMF Transmitter Module (MS-2 and MS-4)
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The 4XTMF mounts to the MS-2 main circuit board option module connectors J3 & J5 or the MS-4 main circuit board, occupying one of the two sets of option module connectors J3 & J5 or J4 & J6.
4XLMF LED Interface Module (MS-4 only)
The LED Interface Module supports the RZA-4XF Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module. The 4XLMF mounts to the MS-4 main circuit board option module connectors J3 and J5 only
RZA-4XF Remote Annunciator (MS-4 only)
The Remote Annunciator mounts on a standard single-gang electrical box and provides LED indication of the following:
.
Alarm Zone 1 (red LED)
Alarm Zone 2 (red LED)
Alarm Zone 3 (red LED)
Alarm Zone 4 (red LED)
System Trouble (yellow LED)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The RZA-4XF Remote Annunciator requires the use of the LED Interface Module (4XLMF).
4XZMF Zone Relay Module (MS-4 only)
The Zone Relay Module provides Form-C relay contacts for the following:
•Alarm Zone 1
•Alarm Zone 2
•Alarm Zone 3
•Alarm Zone 4
System Alarm
System Trouble
As a jumper option, the first four relays described above can be made silenceable. The 4XZMF mounts to the MS-4 main circuit board, occupying one of the two sets of option module connectors.
Dress Panel DP-MS2/4
A dress panel DP-MS2/4 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel.
MS-2/MS-4 PN 51512:D 10/18/04 15
Page 16
Product Description Optional Modules and Accessories
Battery Box
The Fire•Lite BB-17F battery box may be used to house two batteries greater than 7 Amp Hour to a maximum of 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board. The BB-17F is red and is provided with knockouts.
411 and 411UD Digital Alarm Communicator/Transmitter
The three input/channel 411 and the four input/channel 411UD are dual line, digital alarm communicator/transmitters which can be used as slave communicators with the MS-4 FACP. The inputs/channels are compatible with normally open relay contacts, require ELRs (End-of-Line Resistors), are supervised and are fully programmable. The communicators interface with the public switched telephone network and are compatible with most central station receivers. Power supplied must be 12 or 24 volts, filtered and nonresettable. The communicators are mounted in a small metal enclosure, providing a variety of mounting options. Refer to the 411 or 411UD manual for additional information.
16 MS-2/MS-4 PN 51512:D 10/18/04
Page 17
Backbox Mounting Installation
SECTION 2 Installation
The cabinet can be surface mounted or semi-flush mounted using the optional Trim Ring P/N: TR-1-R. The door is removable during the installation period by opening and lifting if off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional 0.250” diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Select a location for the cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the control panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed and determine the appropriate knockouts. All wiring must be in accordance with the National and/or Local codes for fire alarm systems and power supplies.
2.1 Backbox Mounting
1. Mark and predrill holes for the top two keyhole mounting bolts
2. Install two upper fasteners in the wall with the screw heads protruding approximately ¼”
3. Using the upper keyholes, mount the backbox over the two screws
4. Mark the lower two holes, remove the backbox from the wall and drill the mounting holes
5. Mount the backbox, install the remaining fasteners and tighten all screws
2.875” (7.3 cm)
0.75”(1.9 cm)
Height=15.000”
(38.10 cm)
10.375”
(26.35 cm)
Backbox = 14.5”
(36.8 cm)
9.1” (23.1 cm)
Pem Studs
Backbox Mounting Holes
Top
Depth = 3.000”
(7.62 cm)
2.7”
(6.86cm)
ms2-4cab.cdr
Bottom
1.125” (2.868 cm)
Figure 2.1 Backbox Mounting Dimensions
MS-2/MS-4 PN 51512:D 10/18/04 17
Page 18
Installation Backbox Mounting
Door = 15.342“ (38.97 cm)
Bottom
To p
Door = 14.677 “ (37.28 cm)
Depth = 2.875" (7.3 cm)
Depth = 3.050“
(7.75 cm)
Battery Box = 8.5“ (21.59 cm)
When batteries larger than 7 Amp Hour, up to 18 Amp Hour, are being used, the BB-17F battery box (or UL listed equivalent) must be installed. To install the BB-17F:
1. Mount the FACP cabinet to the wall
2. Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F
3. Using conduit, hang the BB-17F from the FACP cabinet making sure there is at least ½” of clearance between the two cabinets
4. Anchor the BB-17F to the wall
Depth = 4.75 (12.065 cm)
ms-4cabb.cdr
Battery Box = 14.5“ (37.384 cm)
Figure 2.2 Backbox and Battery Box
18 MS-2/MS-4 PN 51512:D 10/18/04
Page 19
Operating Power Installation
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the panel is 120 VAC, 50/60 Hz, 2.3 amps for the MS-2/MS-4 or 240 VAC, 50 HZ, 1.15 amps for the MS-2E/MS-4E. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB8 of the main circuit board. As per the National Electrical Code, use 14 AWG (2.00 mm wire with 600V insulation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
2
)] to the transformer mounting stud. Do
not use conduit for the Earth Ground connection since this does not provide reliable protection.
Secondary Power Source (Batteries)
2
, 1.6 mm O.D.) or heavier gauge
!
Optional second transformer shown installed
Standard transformer
Earth ground wire shown connected to transformer mounting stud
Observe polarity when connecting the battery. Connect the battery cable to J8 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
CLASS A CONVERTER
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
WALK TEST
C TRBL NORM TROUBLE
ALARM SILENCE
WALK TEST
4
JP2
SW1
J1
JP1
SW2 SW 3
TB5
C NC NO
ALARM SUPV
J3
J5
J4
J6
12345678ON12345678ON12345678
ON
TB6
C NC NO
TB7
JP3
TB1
B+ B- B+ B-
+ - + -
NAC 1 NAC 2
TB8
HOT NEUT EARTH
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
DISABLE
POWER
ACK
1
J9
TRANSFORMER 1TRANSFORMER 2
J7
Nonreset Resettable
SIGNAL TRANSFORMER
XX-XXX-XXXXXX Rev X
SIGNAL TRANSFORMER
XX-XXX-XXXXXX Rev X
B+ B- B+ B­ ZONE 1 ZONE 2
NAC
DISABLE
SILENCE
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
ZONE
ALARM
2
ZONE 1
ZONE 2
ZONE 3
ZONE 4
NAC FAULT
ZONE
ENABLE/DISABLE
BATTERY
B+ B- B+ B­ ZONE 3 ZONE 4
TROUBLE
TROUBLE
TROUBLE
TROUBLE
POWER
SYSTEM
TROUBLE
TROUBLE
RESET
3
EARTHBATT CHG
J8
TB3
TB2
ms4powr.cdr
Figure 2.3 Operating Power Connections
MS-2/MS-4 PN 51512:D 10/18/04 19
Page 20
Installation Input Circuits
2
2.3 Input Circuits
The MS-2 has two IDCs (Initiating Device Circuits) and the MS-4 has four IDCs. Each circuit is compatible with System Sensor’s I maintenance signal when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating. The maximum loop resistance limit for each IDC is 100 ohms. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept I detectors, any normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. In addition, Zone 1 (IDC 1) on the MS-2 and Zone 2 (IDC2) on the MS-4 can be programmed as combination supervisory and waterflow zones. Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
MS-4 Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to "CAC-4 Class A Converter Module (MS-4 only)" on page 25.
Class B Initiating Device Circuits (supervised and power-limited)
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
UL listed compatible 4-wire smoke detector
3
smoke detectors which generate a
4.7 K, ½ watt resistor P/N:71252
3
smoke
UL listed compatible 2-wire smoke detectors
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
TB1
+ - + -
Nonreset Reset
manual pull stations
TB2
B+ B- B+ B­ NAC 1 NAC
Figure 2.4 IDC Connections
heat detectors
TB3
B+ B- B+ B­ ZONE 1 ZONE 2
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
ms-4idc.cdr
B+ B- B+ B­ ZONE 3 ZONE 4
Note: Zones 3 & 4 on MS-4 only
20 MS-2/MS-4 PN 51512:D 10/18/04
Page 21
Input Circuits Installation
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit. Note that only
Zone 1 on the MS-2 and Zone 2 on
the MS-4 can be configured in this manner.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
Supervisory Switch (tamper)
Supervisory Switch (tamper)
In-Line-Resistor
1.2 K, ½ watt resistor P/N: 75579
Alarm Switch (waterflow)
TB3
B+ B- B+ B­ZONE 1 ZONE 2
B+ B- B+ B­ZONE 3 ZONE 4
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
Note: Zones 3 & 4 on MS-4 only
Figure 2.5 Style B Combination Circuit on Zone 2 of the MS-4
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch(es) must connect to the FACP Initiating Device
Circuit before the In-Line Resistor as shown in Figure 2.5
The Waterflow Supervisory Switch(es) must connect to the FACP Initiating
Device Circuit after the In-Line Resistor as shown in Figure 2.5
Program the FACP Initiating Device Circuit #1 on the MS-2 or Circuit #2 on
the MS-4 as a Combination circuit by placing SW1 DIP switch 8 to the ON position as described in "SW1 DIP Switch Settings" on page 34
ms-4zon1.cdr
Waterflow Alarm Switch activation causes the panel to latch into alarm until
the alarm condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to track the supervisory
condition, that is, the panel will clear when the supervisory condition is cleared (if FACP is programmed for Autoresettable Supervisory)
MS-2/MS-4 PN 51512:D 10/18/04 21
Page 22
Installation Output Circuits
2.4 Output Circuits
2.4.1 Notification Appliance Circuits
The MS-2 provides one Style Y (Class B) NAC (Notification Appliance Circuit) while the MS-4 provides two Style Y (Class B) NACs. Each circuit is capable of providing a maximum of 2.5 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed 3.0 amps for the MS-2 or 6.0 amps for the MS-4 with the optional second transformer installed (refer to battery calculations section). Each circuit is supervised and power-limited. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
The MS-4 NACs can be converted to Style Z (Class A) by installing the optional Class A Converter module. Refer to "CAC-4 Class A Converter Module (MS-4 only)" on page 25.
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
Polarized Bell
Polarized Strobe
Polarized Horn
Notification Appliance Circuit polarity shown in alarm condition
TB2
B+ B- B+ B-
NAC 1 NAC 2
Figure 2.6 NAC Connections
Polarized Bell
Polarized Horn-Strobe
Polarized Horn
Dummy load any unused circuits (P/N: 71245)
ms-4nac.cdr
22 MS-2/MS-4 PN 51512:D 10/18/04
Page 23
Output Circuits Installation
2.4.2 DC Power Output Connections
Resettable 24 VDC power is available on both the MS-2 and MS-4 control panels. Nonresettable 24 VDC power is available only on the MS-4.
Nonresettable Power (500 mA) - MS-4 Only 24 VDC filtered, nonresettable power can be obtained from these terminals (power-limited)
TB1
Figure 2.7 Auxiliary Power
2.4.3 Relays
The MS-2 and MS-4 control panels provide an alarm and fail-safe trouble relay and the MS-4 also provides a supervisory relay. Each Form-C relay is rated for 2 amps @ 30VAC (resistive).
Note that relay connections may be power-limited or nonpower-limited, provided that
0.25” minimum spacing is maintained between conductors of power-limited and nonpower-limited circuits.
4-Wire Smoke Detector Power (500 mA) 24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from these terminals (power-limited)
+ - + -
ms-4tb1.cdr
Note: Relay contacts are shown with power applied to the panel and no active troubles, alarms or supervisories. The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.
TROUBLE
C TRBL NORM
C NC NO
TB5
ALARM
SUPV
C NC NO
TB6
TB7
ms4relay.cdr
Figure 2.8 Relay Terminals
MS-2/MS-4 PN 51512:D 10/18/04 23
Page 24
Installation Power-limited Wiring Requirements
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-4 is illustrated below.
Power-limited Circuits
TB2
TB1
+ - + -
SIGNAL TRANSFORMER
XX-XXX-X XXXXX Rev X
Nonreset Res ettable
TB1
TB3
A+ A- A + A­CLASS A CLASS A NAC 1 NAC 2
A+ A - A+ A-
CLASS A CLASS A
ZONE 1 ZONE 2
A+ A- A + A-
CLASS A CLASS A
ZONE 3 ZONE 4
Nonpower-limited Circuits
TB5
C NC NO
ALARM SUPV
TB6
4XLB
C NC NO
TB7
CAC-4
Power-limited
ZONE 1
SUPERVISORY
FIRE ALA RM
SUPERVISORY
FIRE ALA RM
SUPERVISORY
FIRE ALA RM
SUPERVISORY
FIRE ALA RM
NAC
ACK
DISABLE
ZONE
DISABLE
ALARM
SILENCE
AC
POWER
SIGNAL TRANSFORMER
XX-XXX-XX XXXX Rev X
1
J9
TRANSFORMER 1TRANSFORMER 2
TB8
J7
HOT NEUT EARTH
ZONE 2
ZONE 3
ZONE 4
NAC
FAULT
ZONE
ENABLE/DISABLE
2
BATTERY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
SYSTEM
TROUBLE
J8
TROUBLE
RESET
3
EARTH BATT CHG
POWER
MAINTE NANCE
MAINTE NANCE
MAINTE NANCE
MAINTE NANCE
WAL K
TEST
JP2
WALK TEST
4
1 2 345678
SW1
ALARM
SILENCE
ON
JP1
1 2 345678
1 2 345678
ON
SW2 SW3
4XLMF
ON
4XTMF
Circuits
Nonpower-limited
Circuit
ms4ulpwr.cdr
AC Power
Figure 2.9 Typical UL Power-limited Wiring Requirements
24 MS-2/MS-4 PN 51512:D 10/18/04
Page 25
Installation of Optional Modules Installation
2.6 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.6.1 CAC-4 Class A Converter Module (MS-4 only)
2.6.1.1 Installation
The CAC-4 Module can be used to convert the four Style B (Class B) Initiating Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module plugs into connector J1 which is located at the top right of the MS-4 main circuit board.
Install the three supplied standoffs in the holes on the main circuit board as indicated in the following figure. Carefully align the connector on the CAC-4 with J1 on the FACP main circuit board and press the module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any connector pins.
Secure to Standoffs
TB1
+ - + -
Nonreset Reset
TB1
CLASS A CLASS A
NAC 1 NAC 2
TB2
B+ B- B+ B­ NAC 1 NAC 2
A+ A- A+ A-
A+ A- A+ A-
CLASS A CLASS A
ZONE 1 ZONE 2
A+ A- A+ A-
CLASS A CLASS A
ZONE 3 ZONE 4
CAC-4 Module
TB3
B+ B- B+ B­ ZONE 1 ZONE 2
B+ B- B+ B­ ZONE 3 ZONE 4
CLASS A CONVERTER
J1 Connector
MS-4 Main Circuit Board
Figure 2.10 CAC-4 Module Installation
C TRBL NORM TROUBLE
J1
Secure to Standoff
TB5
C NC NO
TB6
ALARM SUPV
C NC NO
TB7
JP3
ms4tocac.cdr
MS-2/MS-4 PN 51512:D 10/18/04 25
Page 26
Installation Installation of Optional Modules
2.6.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB2 of the MS-4 and TB1 of the CAC-4 module. Wire the Style D (Class A) Initiating Device Circuits using TB3 of the MS-4 and TB1 of the CAC-4. Make certain to observe polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed and return for the positive side of a device and the B- and A­terminals must comprise the feed and return for the negative side of a device. To configure any of the zones for Class B when the CAC-4 is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+ and A­terminals on the CAC-4 module. Note that Zone 1 IDC on the MS-2 and Zone 2 IDC on the MS-4 can be configured as a combination waterflow/supervisory circuit as illustrated in the following figure.
(supervised and power-limited)
Circuit polarities shown in alarm condition
Class B (Style B)
IDC - 4.7 K
½ watt ELR
resistor
P/N:71252
(supervised and
power-limited)
Class A (Style Z) NAC
Polarized
Bell
Polarized
Strobe
Polarized
Horn
TB2
B+ B- B+ B­ NAC 1 NAC 2
IMPORTANT! All devices must be within 20 feet of the
Class A portion of
the circuit and
wiring must be in
1.2 K ½ watt
In-Line
resistor
P/N:75579
TB3
conduit.
Tamper
Smoke
Tamper
Pull Station
Heat
Waterflow
B+ B- B+ B­ ZONE 1 ZONE 2
Class A
(Style D) IDC
Combo Waterflow
& Supervisory
20K, ½ watt ELR
resistor P/N:75477
(supervised and
power-limited)
Smoke
Pull Station
Heat
B+ B- B+ B­ ZONE 3 ZONE 4
Class A
(Style D) IDC
(supervised and
power-limited)
Dummy load all unused circuits - 4.7 K ½ watt ELR resistor (P/N: 71245)
Circuit Board
MS-4
TB1
A+ A- A+ A-
CLASS A CLASS A
NAC 1 NAC 2
A+ A- A+ A-
CLASS A CLASS A
ZONE 1 ZONE 2
A+ A- A+ A-
CLASS A CLASS A
ZONE 3 ZONE 4
CAC-4 Class A Converter Module
ms4comba.cdr
Figure 2.11 Wiring NACs and IDCs for Class A Operation
26 MS-2/MS-4 PN 51512:D 10/18/04
Page 27
Installation of Optional Modules Installation
2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules
MS-4: The 4XLMF LED Interface Module can only be plugged into connectors J3 and J5 on the MS-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged into connectors J3 and J5 or of any two of the three modules can be installed.
MS-2: Only the 4XTMF module can be plugged into connectors J3 & J5 on the MS-2 main circuit board. (No other option modules can be installed on the MS-2).
The following steps must be followed when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6) on the main circuit board to allow the control panel to supervise the placement of any installed option module
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide the required earth ground protection
J4 and J6 on the MS-4 main circuit board. A combination
ms4bord.cdr
J9
TRANSFORMER 1TRANSFORMER 2
J7
TB1
+ - + -
Nonreset Reset
TB2
B+ B- B+ B­ NAC 1 NAC 2
HOT NEUT EARTH
4. Carefully plug the connectors on the option module into connectors J3 and J5 or J4 and J6 on the FACP main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in the following sections
7. Test system for proper operation
TB3
B+ B- B+ B­ ZONE 1 ZONE 2
ZONE 1
1
NAC
DISABLE
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
ZONE
DISABLE
ALARM
SILENCE
2
ZONE 2
ZONE 3
ZONE 4
NAC
SYSTEM
FAULT
TROUBLE
ZONE
ENABLE/DISABLE
BATTERY
TB8
AC
POWER
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
ACK
JP2 Jumper
Cut to install module on J4 & J6
B+ B- B+ B ­ ZONE 3 ZONE 4
CLASS A CONVERTER
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
TROUBLE
MAINTENANCE
POWER
TROUBLE
RESET
3
EARTH BATT CHG
J8
C TRBL NORM TROUBLE
WALK TEST
WALK TEST
4
JP2
ALARM
SILENCE
12345678
SW1
J1
JP1
12345678
ON
SW2 SW3
ON
TB5
C NC NO
12345678
ON
TB6
C NC NO
ALARM SUPV
J3
J5
J4
J6
TB7
JP3
J3
J5
J4
J6
JP1 Jumper
Cut to install module on J3 & J5
(when using
(when using
Standoffs
J3 & J5
Standoffs
J4 & J6
Figure 2.12 4X Option Module Connection to MS-4
MS-2/MS-4 PN 51512:D 10/18/04 27
Page 28
Installation Installation of Optional Modules
2.6.2.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
Note: 4XTMF Module is not suitable for transmitting reverse polarity supervisory signal.
TBL Jumper
Disconnect Switch shown in disconnect position
TBL
J1
J2
Connect to:
• MS-4 Connectors J3 & J5 or
• MS-2 Connectors J3 & J5.
TB1
J4 & J6
Polarities are shown for module activation
1+ 2­3+ 4­5 6+ 7-
}Remote Alarm (power-limited)* }Remote Trouble (power-limited)*
No connection
}Municipal Box (nonpower-limited)*
* Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7k, ¼ watt resistor) if Municipal Box is not connected.
4xtmf.cdr
Disconnect LED
Figure 2.13 4XTMF Transmitter Module
28 MS-2/MS-4 PN 51512:D 10/18/04
Page 29
Installation of Optional Modules Installation
2.6.2.2 4XZMF Zone Relay Module (MS-4 only)
The 4XZMF provides four zone alarm, one system alarm and one system trouble Form-C relays. Nonpower-limited and power-limited wiring must have a minimum distance of 0.25”, wire to wire. If this module is used to drive nonpower-limited and power-limited circuits, follow the instructions below:
Relay #1 through #4 will activate with Output #1 through #4 and remain latched unless ‘LATCH’ jumper is cut.
1
NO
2
NC
Relay #1 C NO NC C NO NC C NO NC C NO NC C NO NC C
} }
}
}
} }
Relay #2
Relay #3
Relay #4
Alarm
Trouble
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
4xzma.cdr
Use Disable Switch to disconnect the relays
Cut jumper for nonlatching (silenceable) relay operation
1) Skip a set of dry contacts to maintain the 0.25” required space between power­limited and nonpower-limited circuits. The wiring of this module must follow the requirements as specified in "Power-limited Wiring Requirements" on page 24.
OR
2) If this module is needed to drive power-limited and nonpower-limited relays that are next to each other, refer to the following illustration which shows a typical connection:
Relay #1
Relay #2
Relay #3
Relay #4
{
{ {
{
NO
NC
NO
NC
NO
NC
NO
NC
power-limited circuit
C
C
C
C
no connection
}
power-limited circuit
}
nonpower-limited circuit
}
nonpower-limited circuit
}
4xzma.cdr
Figure 2.14 4XZMF Zone Relay Module
MS-2/MS-4 PN 51512:D 10/18/04 29
Page 30
Installation Installation of Optional Modules
2.6.2.3 4XLMF LED Interface Module (MS-4 only)
The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must follow the requirements as specified in "Power-limited Wiring Requirements" on page 24.
4XLB
4XLMF Module
Important: The 4XLMF module can only MS-4 main circuit board.
+24 VDC
1
Out #1
2
Out #2
3
Out #3
4
Out #4
5
System Trouble
6
Sound
7
Resound
8
Connect to corresponding terminals of RZA-4XF Remote Annunciator
4xlma.cdr
be installed on connectors J3 and J5 of the
Note: Make wiring connections with
system power off. Maximum wire impedance is 50 ohms per wiring connection.
rza-4xbx.cdr
Single-gang Box
Front View of RZA-4XF
rza-4xfr.cdr
Side View
Figure 2.15 4XLMF LED Interface Module
30 MS-2/MS-4 PN 51512:D 10/18/04
Page 31
Installation of Optional Modules Program Options via DIP Switch
1
SECTION 3 Program Options via DIP Switch
This section describes the programming options available via DIP switch settings. The FACP can be field programmed using option DIP switches SW1, SW2 and SW3 which are located in the bottom right side of the main circuit board. Refer to the following illustration for switch locations and DIP switch placement in the ON and OFF positions.
J9
TRANSFORMER 1TRANSFORMER 2
J7
+ - + -
Nonreset Reset
TB2
TB1
B+ B- B+ B­ NAC 1 NAC 2
FIRE ALARM
FIRE ALARM
FIRE ALARM
FIRE ALARM
AC
POWER
ACK
TB8
HOT NEUT EARTH
TB3
NAC
DISABLE
1
B+ B- B+ B­ ZONE 1 ZONE 2
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
NAC
ZONE
FAULT
DISABLE
ALARM
SILENCE
ENABLE/DISAB LE
2
B+ B- B+ B­ ZONE 3 ZONE 4
ZONE 1
TROUBLE
ZONE 2
TROUBLE
ZONE 3
TROUBLE
ZONE 4
TROUBLE
SYSTEM
TROUBLE
ZONE
BATTERY
1 2 3 4 5 6 7 8
SW
J8
ON
TROUBLE
RESET
3
EARTH BATT CHG
POWER
CLASS A CONVERTER
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
WALK
TEST
JP2
C TRBL NORM TROUBLE
J1
ALARM
SILENCE
WALK TEST
4
JP1
12345678
12345678
ON
SW1
SW2
1 2 3 4 5 6 7 8
SW2
TB5
ON
SW3
ON
12345678
ON
TB6
C NC NO
ALARM SUPV
J3
J5
J4
J6
C NC NO
1 2 3 4 5 6 7 8
SW3
TB7
JP3
12345678
ON
Switches 1 through 7 shown in OFF position
ms4switc.cdr
ON
Switch 8 shown in ON position
Figure 3.1 Field Programming DIP Switches
MS-2/MS-4 PN 51512:D 10/18/04 31
Page 32
Program Options via DIP Switch DIP Switch Settings
3.1 DIP Switch Settings
The following tables list the programmable features for the MS-2 and MS-4. Placing a DIP switch in the ON position will select the feature while placing the DIP switch in the OFF position will deselect the feature. The exceptions to this rule are SW3 DIP switches 5 & 6. These two switches are used to select the Notification Appliance Circuit synchronization feature. A detailed description of each feature is presented in the following pages.
Important: When any programmable feature is changed by repositioning a DIP switch, the FACP Reset button must be pressed to ensure that the control panel can read the new switch position.
Table 3.1 MS-2 DIP Switch Settings
Switch Number DIP Switch Number DIP Switch ON
1 Silence Inhibit
2 Auto-silence
3 Temporal Coding
4 Selective Silence (if sync. enabled)
SW1
5 Trouble Reminder
SW2
SW3
6 AC Trouble Delay
7 Autoresettable Supervisory
8 IDC Combination Waterflow/
1 not used
2 not used
3 IDC1 Verification
4 IDC1 Supervisory
5 IDC2 Verification
6 IDC2 Supervisory
7 not used
8 not used
1 NAC1 Nonsilenceable
2 NAC1 Disable
3 not used
4 not used
5 & 6
used to select strobe
synchronization feature as
shown to the right
Supervisory Circuit
Switch 5 Switch 6
No Synchronization OFF OFF
System Sensor Synchronization ON OFF
Gentex Synchronization OFF ON
Wheelock Synchronization ON ON
7 Nonsilenceable Waterflow for
Combination Circuit (only if SW1 switch 8 is ON)
8spare
32 MS-2/MS-4 PN 51512:D 10/18/04
Page 33
DIP Switch Settings Program Options via DIP Switch
Table 3.2 MS-4 DIP Switch Settings
Switch Number DIP Switch Number DIP Switch ON
1 Silence Inhibit
2 Auto-silence
3 Temporal Coding
4 Selective Silence (if sync. enabled)
SW1
5 Trouble Reminder
6 AC Trouble Delay
7 Autoresettable Supervisory
8 IDC Combination Waterflow/
Supervisory Circuit
1 IDC1 Verification
2 IDC1 Supervisory
3 IDC2 Verification
SW2
SW3
4 IDC2 Supervisory
5 IDC3 Verification
6 IDC3 Supervisory
7 IDC4 Verification
8 IDC4 Supervisory
1 NAC1 Nonsilenceable
2 NAC1 Disable
3 NAC2 Nonsilenceable
4 NAC2 Disable
5 & 6
used to select strobe
synchronization feature as
shown to the right
7 Nonsilenceable Waterflow for
Switch 5 Switch 6
No Synchronization OFF OFF
System Sensor Synchronization ON OFF
Gentex Synchronization OFF ON
Wheelock Synchronization ON ON
Combination Circuit (only if SW1 switch 8 is ON)
8spare
MS-2/MS-4 PN 51512:D 10/18/04 33
Page 34
Program Options via DIP Switch DIP Switch Settings
3.1.1 SW1 DIP Switch Settings
3.1.1.1 Silence Inhibit
Switch 1, placed in the ON position, selects the Silence Inhibit feature. This feature prevents the silencing or resetting of the NACs (Notification Appliance Circuits) for a period of one minute after initiation of an alarm. Placing switch 1 to the OFF position deselects the Silence Inhibit feature. The factory default setting is switch 1 OFF for no Silence Inhibit.
3.1.1.2 Auto-silence
Switch 2, placed in the ON position, selects the Auto-silence feature. This feature automatically silences all NACs, programmed for silenceable operation, ten minutes after alarm activation. A new activation on another zone will resound the NACs. The factory default setting is switch 2 OFF for no Auto-silence.
3.1.1.3 Temporal Coding
Switch 3, placed in the ON position, selects the Temporal Coding feature. This feature causes the NACs to pulse, second off,
½ second on, 1½ seconds off, continually repeating this pattern while
activated. The factory default setting is switch 3 OFF for no Temporal Coding, which will cause the NACs to sound a steady signal when activated.
Note that Temporal Coding is disabled if Strobe Synchronization is enabled.
3.1.1.4 Selective Silence
Switch 4, placed in the ON position, selects the Selective Silence feature. This feature allows the use of various manufacturer’s horn strobe mute protocols. When Selective Silence is enabled and the Synchronization feature is selected (refer to "Strobe Synchronization" on page 37), pressing the Silence button will turn off all silenceable audible devices while leaving on the visual devices, such as strobes. The factory default setting is switch 4 OFF for no Selective Silence.
Note: Enabling Selective Silence but not Synchronization will cause audible and visual devices to be turned off when the Silence button is pressed.
½ second on, ½ second off, ½ second on, ½
3.1.1.5 Trouble Reminder
Switch 5, placed in the ON position, selects the Trouble Reminder feature. This feature causes the FACP piezo to sound every 15 seconds for alarms and every two minutes for troubles after the alarms or troubles have been silenced. In addition, the piezo will resound 24 hours after a trouble has been silenced but not cleared. The factory default setting is switch 5 OFF for Trouble Reminder disabled.
3.1.1.6 AC Trouble Delay
Switch 6, placed in the ON position, selects the AC Trouble Delay feature. This feature allows the FACP to delay trouble activation for six hours following an AC loss or brownout condition. The factory default setting is switch 6 OFF for no AC Trouble Delay.
3.1.1.7 Autoresettable Supervisory
Switch 7, placed in the ON position, selects the Autoresettable Supervisory feature. This feature causes the IDCs (Initiating Device Circuits), programmed as supervisory circuits, to automatically reset (nonlatching) after the alarm condition has been cleared. The factory default setting is switch 7 OFF for no Autoresettable Supervisory.
3.1.1.8 IDC Combination Circuit
Switch 8, placed in the ON position, sets IDC #1 on the MS-2 or IDC #2 on the MS-4 as a combination circuit. A combination zone can be used for monitoring supervisory devices such as valve tamper switches and alarm devices such as waterflow switches. Supervisory conditions, which latch via software, can be silenced by pressing the Acknowledge and then Silence buttons. The factory default setting is switch 8 OFF for no Combination circuit.
34 MS-2/MS-4 PN 51512:D 10/18/04
Page 35
DIP Switch Settings Program Options via DIP Switch
3.1.2 SW2 DIP Switch Settings
3.1.2.1 IDC1 Verification (MS-4 only)
Switch 1 only on the MS-4, placed in the ON position, selects the Verification feature for IDC (Initiating Device Circuit) #1. When Verification is selected the following events will occur when a smoke detector activates:
1. FACP removes power from all zones for 6 seconds, resetting all smoke detectors
2. Power is reapplied and a 12 second retard period begins, allowing detectors to stabilize
3. During the 18 second reset/retard periods of steps 1 & 2, subsequent alarms by the same zone are ignored
4. Alarms detected on any other zone during the retard period will cause the FACP to immediately process the alarm
5. A 60 second confirmation period follows the reset/retard period. If an alarm occurs during the confirmation period, on the zone which initiated verification, the FACP will immediately process the alarm. If no alarm is detected during this confirmation period, the FACP returns to normal condition
Important! Circuits selected for verification must have only smoke detectors installed
0 sec.
Detector Alarm Verification (Reset/Retard + Confirmation)
Detector Goes Into Alarm
Detector Alarms on Different Zone During First Detector's Verification Period
RETARD
18 sec.
CONFIRMATION
Control Panel Processes Alarm if Same Detector is Still in Alarm
Control Panel Immediately Processes Alarm
6 sec.
RESET
Alarm Ignored
The factory default setting is switch 1 OFF for no IDC1 Verification.
3.1.2.2 IDC1 Supervisory (MS-4 only)
Switch 2 only on the MS-4, placed in the ON position, programs IDC #1 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ˝ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 2 OFF for no IDC1 Supervisory.
3.1.2.3 IDC1 Verification for MS-2 or IDC2 Verification for MS-4
Switch 3, placed in the ON position, selects the Verification feature for IDC #1 on the MS-2 or IDC #2 on the MS-4. The factory default setting is switch 3 OFF for no Verification. Refer to IDC1 Verification (MS-4 only) for a description of this feature.
78 sec.
3.1.2.4 IDC1 Supervisory for MS-2 or IDC2 Supervisory for MS-4
Switch 4, placed in the ON position, programs IDC #1 on the MS-2 or IDC #2 on the MS-4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ˝ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 2 OFF for no Supervisory.
MS-2/MS-4 PN 51512:D 10/18/04 35
Page 36
Program Options via DIP Switch DIP Switch Settings
3.1.2.5 IDC2 Verification for MS-2 or IDC3 Verification for MS-4
Switch 5, placed in the ON position, selects the Verification feature for IDC #2 on the MS-2 or IDC #3 on the MS-4. The factory default setting is switch 5 OFF for no Verification. Refer to "IDC1 Verification (MS-4 only)" on page 35 for a description of this feature.
3.1.2.6 IDC2 Supervisory for MS-2 or IDC3 Supervisory for MS-4
Switch 6, placed in the ON position, programs IDC #2 on the MS-2 or IDC #3 on the MS-4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ˝ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 6 OFF for no Supervisory.
3.1.2.7 IDC4 Verification (MS-4 only)
Switch 7 only on the MS-4, placed in the ON position, selects the Verification feature for IDC #4. The factory default setting is switch 7 OFF for no IDC4 Verification. Refer to "IDC1 Verification (MS-4 only)" on page 35 for a description of this feature.
3.1.2.8 IDC4 Supervisory (MS-4 only)
Switch 8 only on the MS-4, placed in the ON position, programs IDC #4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ˝ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 8 OFF for no IDC4 Supervisory.
3.1.3 SW3 DIP Switch Settings
3.1.3.1 NAC1 Nonsilenceable
Switch 1, placed in the ON position, programs NAC #1 as a nonsilenceable circuit. Selecting this feature will prevent the notification appliances on NAC #1 from being silenced by the Autosilence feature or by pressing the Alarm Silence button. The factory default setting is switch 1 OFF for silenceable circuit.
3.1.3.2 NAC1 Disable
Switch 2, placed in the ON position, will disable NAC #1, preventing the notification appliances from activating. This feature may be used during maintenance or while testing the system to prevent building evacuation. The FACP will indicate an NAC disabled fault and system trouble while this feature is selected. The factory default setting is switch 2 OFF for NAC1 enabled.
3.1.3.3 NAC2 Nonsilenceable (MS-4 only)
Switch 3 only on the MS-4, placed in the ON position, programs NAC #2 as a nonsilenceable circuit. Selecting this feature will prevent the notification appliances on NAC #2 from being silenced by the Autosilence feature or by pressing the Alarm Silence button. The factory default setting is switch 3 OFF for silenceable circuit.
3.1.3.4 NAC2 Disable (MS-4 only)
Switch 4 only on the MS-4, placed in the ON position, will disable NAC #2, preventing the notification appliances from activating. This feature may be used during maintenance or while testing the system to prevent building evacuation. The FACP will indicate an NAC disabled fault and system trouble while this feature is selected. The factory default setting is switch 4 OFF for NAC2 enabled.
36 MS-2/MS-4 PN 51512:D 10/18/04
Page 37
DIP Switch Settings Program Options via DIP Switch
3.1.3.5 Strobe Synchronization
Switches 5 and 6 are used to program the Synchronization feature. This feature controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time, This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices. The following table lists the required switch settings to accomplish synchronization:
Synchronization Feature Switch 5 Switch 6
No Synchronization OFF OFF
System Sensor Synchronization ON OFF
Gentex Synchronization OFF ON
Wheelock Synchronization ON ON
The factory default setting is switches 5 and 6 OFF for No Synchronization.
3.1.3.6 Nonsilenceable Waterflow for Combination Circuit
If SW1 switch 8 is set to the ON position to select a Combination Waterflow/ Supervisory Circuit (refer to "IDC Combination Circuit" on page 34) and SW3 switch 7 is set to the ON position to select the Nonsilenceable Waterflow for the Combination Circuit option, the following conditions will occur:
• MS-2 - NACs become nonsilenceable upon acitvation of IDC #1 (Combination
Circuit)
• MS-4 - NACs become nonsilenceable upon activation of IDC #2 (Combination
Circuit)
Notes:
1.If initial alarm activations are from IDCs other than the Combination Circuit, the NACs will be either silenceable or nonsilenceable, depending on the setting of SW3 switches 1 and 3 (refer to "NAC1 Nonsilenceable" on page 36 and "NAC2 Nonsilenceable (MS-4 only)" on page 36).
2.If alarm activation is from the Combination Circuit programmed for nonsilenceable, all NACs will be nonsilenceable regardless of subsequent IDC activations.
3.1.3.7 Spares
Switch 8 is a spare switch and has no function at this time. The switch should therefore be left in the factory default setting of OFF.
MS-2/MS-4 PN 51512:D 10/18/04 37
Page 38
Operating Instructions Switch Functions in Normal Mode
SECTION 4 Operating Instructions
The MS-2 and MS-4 have two modes of operation which are Normal and Walktest modes. Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel in the Normal Mode.
4.1 Switch Functions in Normal Mode
4.1.1 ACK - Acknowledge
The Acknowledge button, which is located on the FACP membrane switch panel, silences the system piezo sounder and changes all flashing system LEDs to on steady. Pressing the Acknowledge button will have no effect on the Notification Appliance Circuits. To activate, press and hold the Acknowledge button for a minimum of one second.
4.1.2 Silence
Pressing the Silence button, which is located on the FACP membrane switch panel, silences the system piezo sounder, turns off the silenceable Notification Appliance Circuits and turns on the Alarm Silence LED. The Silence button will be ignored for nonsilenceable waterflows and NACs. Upon the occurrence of a subsequent event (alarm or trouble), Silence is overridden and the control panel will respond to the new event. To activate, press the Silence button for a minimum of one second.
Note: If Silence Inhibit has been enabled, NACs cannot be silenced for one minute following initiation of an alarm.
4.1.3 Zone Enable/Disable
To disable a zone, press the corresponding Zone Enable/Disable button. The Zone Disable and system Trouble LEDs will blink, as well as the Trouble LED for the disabled zone. To enable the zone, press the Zone Enable/Disable button a second time.
4.1.4 Reset/(Lamp Test)
The system Reset button, which is located on the FACP membrane switch panel, resets the system and any smoke detectors. Each press of the Reset button will cause the following:
Clear all status LEDs
Turn off the Notification Appliance Circuits
Reset all zones by temporarily removing power
Silence the onboard piezo sounder
Restore all system relays to normal
Temporarily remove power from the resettable power output
Note: if Silence Inhibit is active, a panel reset cannot occur for one minute.
Any alarm, supervisory or trouble condition that exists after a system reset will resound the system, reactivating appropriate system activity. Any zones that were disabled before the reset will be disabled after the reset.
Lamp Test - When the Reset button is pressed and then released, the FACP will perform a Lamp Test. All panel LEDs will be turned on and the piezo will sound for approximately two seconds.
38 MS-2/MS-4 PN 51512:D 10/18/04
Page 39
Walktest Operating Instructions
!
!
4.1.5 Walktest
The Walktest button, which is located on the FACP membrane switch panel, allows a panel walktest to be performed. Pressing and holding the Walktest button for a minimum of two seconds causes the FACP to enter audible walktest. Pressing the Walktest button and then the Silence button and holding both for a minimum of two seconds will cause the panel to enter silent walktest. Walktest can be exited by pressing and holding the Walktest button for a minimum of three seconds or by pressing the Reset button. Refer to “Walktest” for a complete description of this feature.
4.2 Walktest
Walktest allows the testing of all control panel IDCs (input zones). An audible or silent walktest may be performed.
It is important to note that while the FACP is in Walktest mode, the control panel is in
!
an off-normal condition and does not provide fire protection.
It should also be noted that the trouble relay will be activated while the control panel is in Walktest mode. Placing the control panel into Walktest mode will only be possible if the system has no active alarms.
Prior to initiating a walktest, check to make certain that all system faults have been cleared. Upon entering Walktest mode, the following conditions should occur:
Trouble relay will activate
Alarm relay will be disabled
Supervision relay will be disabled (MS-4 only)
Piezo sounder will be disabled
3
•I
smoke detectors will enter their own test mode causing their LEDs to flash
twice every five seconds (refer to the I
All alarm conditions will be displayed as they occur by blinking zone alarm LED
All zone troubles will be displayed as they occur by blinking zone trouble LED
3
specification document)
During walktest, the FACP zone LEDs will blink for the first activation on a zone. Subsequent activations on the same zone will cause the corresponding zone LED to blink the number of alarms on the zone since the start of the test, followed by a two second pause and then a repeat of the sequence.
Note that following a zone activation, a 6 second reset for conventional and 60 second reset for I
3
detectors is initiated. No new alarms or troubles will be detected during this
reset period.
Disabled zones will not respond during Walktest. A zone may be disabled while in Walktest mode, should a faulty device be detected. This allows the user to return the system to Normal mode, enabling all other zones while preventing the faulty zone from triggering a false alarm.
Audible Walktest
To perform an audible Walktest, press and hold the Walktest button for a minimum of two seconds. The Trouble and Walktest LEDs will blink at a ¼ second rate.
While testing input devices, the first initiating device activated on a zone will cause the NACs to sound for four seconds. Subsequent device activations on the same zone will cause the NACs to turn on for one second. Any smoke detectors that are activated will automatically be reset by the panel. Zone faults (open circuits) will cause the NACs to remain on steadily until the fault is cleared.
During an audible walktest, if a device remains latched in alarm (such as a Pull Station that is not reset after activation), subsequent testing of devices on the same zone will not
trigger the NACs. Be certain to reset or clear each device after testing.
MS-2/MS-4 PN 51512:D 10/18/04 39
Page 40
Operating Instructions Status LEDs
Silent Walktest
To perform a silent Walktest, press the Walktest button, then press the Alarm Silence button and hold both for a minimum of two seconds. The Trouble, Walktest and Alarm Silence LEDs will blink at a ¼ second rate.
A silent walktest will not activate the control panel Notification Appliance Circuits. All alarm and trouble conditions must be observed using the LEDs at the control panel as described in the previous sections.
Exiting Walktest Mode
Walktest mode can be exited by pressing and holding the Walktest button for a minimum of three seconds or by pressing the Reset button. The time-out feature will
cause the control panel to automatically exit Walktest mode if no button presses have occurred for one hour.
4.3 Status LEDs
AC Power LED
A green LED that remains on while the AC power supply is within correct limits. If this indicator fails to light under normal conditions, service the system immediately.
NAC Disable LED
A yellow LED that blinks to indicate that a Notification Appliance Circuit has been disabled using the main circuit board DIP switches. The LED will turn on steady when the Acknowledge or Alarm Silence button is pressed.
Zone Disable LED
A yellow LED that blinks to indicate that one or more alarm zones have been disabled using the Zone Enable/Disable buttons. The disabled zone’s trouble LED will also be on. The Acknowledge or Alarm Silence button does not affect the Zone Disable LED.
NAC Fault LED
A yellow LED that blinks to indicate that an NAC trouble condition exists in the system. The LED turns on steady when the Acknowledge or Alarm Silence button is pressed.
System Trouble LED
A yellow LED that blinks to indicate that a system fault or abnormal condition exists and that the fire alarm system may be inoperative. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Power Trouble LED
A yellow LED that blinks to indicate an AC power, battery or charger trouble condition. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Walktest LED
A yellow LED that blinks to indicate that the control panel is in Walktest mode. The Acknowledge and Alarm Silence buttons do not affect the Walktest LED.
Alarm Silence LED
A yellow LED that turns on to indicate that an Alarm condition exists in the system but the Notification Appliance Circuits and the local piezo sounder have been silenced.
Zone Fire Alarm LED
A red LED for each zone that blinks to indicate that an alarm exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
40 MS-2/MS-4 PN 51512:D 10/18/04
Page 41
Operation Operating Instructions
Zone Supervisory LED
A yellow LED for each zone that blinks if the zone has been programmed for supervisory and a supervisory condition exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Note that an I
3
smoke detector freeze condition is displayed as a supervisory condition.
The zone does not have to be programmed as a supervisory for this to occur.
Zone Trouble LED
A yellow LED for each zone that blinks to indicate that a trouble exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Zone Maintenance LED
A yellow LED for each zone that blinks to indicate that a I
3
smoke detector on the corresponding zone is dirty or in need of maintenance. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Earth Fault LED (on main circuit board)
A yellow LED that blinks to indicate a ground fault condition on the system. A ground fault occurs when a low resistance between the FACP and earth ground exists. The LED turns on steady when the Acknowledge or Alarm Silence button is pressed.
4.4 Operation
Battery Fault LED (on main circuit board)
A yellow LED that blinks to indicate a low battery or no battery condition on the FACP. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Charger Fault LED (on main circuit board)
A yellow LED that blinks to indicate a battery charger fault. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Normal mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When no alarm or trouble conditions exist, the control panel will be in the following state:
all LEDs will be off (except the AC Power LED)
the Notification Appliance Circuits will be off
all relays are in their normal state
the onboard piezo sounder will be off
I3 smoke detectors will be polled for maintenance and freeze conditions on initial entry into Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions
All alarm and system trouble conditions are annunciated on the control panel’s LEDs.
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five minutes after the panel is reset, followed by a maintenance check. If there is no freeze or maintenance condition, the panel will continue to monitor for freeze conditions every hour and maintenance conditions every four hours.
MS-2/MS-4 PN 51512:D 10/18/04 41
Page 42
Operating Instructions Operation
4.4.1 Fire Alarm Response
The control panel will, upon detection of an alarm condition, cause the following:
Latch the alarm condition - requires panel reset to clear alarm condition
Blink the Zone Alarm LED one second On and one second Off
Turn on remote annunciator alarm LED and piezo sounder
Turn the Notification Appliance Circuit(s) on
Turn the FACP piezo sounder on steady
Turn on the alarm relay
Start the Silence Inhibit, Auto-silence and Trouble Reminder functions if enabled
4.4.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system reset button has been pressed (pull stations have been reset, smoke detectors have reset and no smoke is present, waterflow has stopped). The control panel will perform the following upon restoral of all active alarms:
Turn off the FACP Zone Alarm LED
Turn off remote annunciator alarm LED and piezo sounder
Turn off the Notification Appliance Circuit(s)
Turn off the FACP piezo sounder
Turn off the alarm relay
I3 smoke detectors will be polled for maintenance and freeze conditions on initial entry into Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions
4.4.3 System Supervisory Condition Response
Zones can be programmed for supervisory in applications where a waterflow sensing device has been employed and a sprinkler tamper switch is to be monitored. An I detector in a ‘freeze’ condition (detected abnormally low ambient temperature) will also generate a supervisory condition on its alarm zone (refer to the I
3
specification sheet for temperature threshold). Any supervisory condition will cause the control panel to perform the following functions:
Blink the FACP Zone Supervisory LED ½ second On and ½ second Off
Pulse the piezo sounder ½ second On and ½ second Off
Turn on the supervisory relay (MS-4 only)
3
4.4.4 System Supervisory Restoral Response
When the supervisory condition has been cleared, the control panel will perform the following:
Turn off the FACP Zone Supervisory LED
Turn off the piezo sounder
Turn off the supervisory relay (MS-4 only)
42 MS-2/MS-4 PN 51512:D 10/18/04
Page 43
Operation Operating Instructions
4.4.5 Trouble Condition Response
The control panel, upon detection of one or more trouble conditions, well perform the following:
Blink the FACP System Trouble LED one second On and one second Off
Blink the FACP Zone Trouble LED one second On and one second Off
Turn on remote annunciator Trouble LED and pulse the piezo sounder
Pulse the FACP piezo sounder one second On and one second Off
Transfer fail-safe Trouble relay
Additional LEDs will turn on or blink according to the specific trouble
NAC Disable LED if NAC has been disabled
Zone Disable LED if a zone has been disabled
NAC Fault LED if a fault is detected on an NAC
Power Trouble LED if an AC, battery or charger fault is detected
AC Power LED will turn off
if AC fail or brownout occurs
Alarm Silence LED if Silence button is pressed after an alarm or trouble
Walktest LED if Walktest mode is entered
Zone Maintenance LED if a I
3
smoke detector needs servicing
Earth Fault LED if a ground fault occurs
Battery Fault LED if low or no battery condition occurs
Charger Fault LED if a charger trouble occurs
4.4.6 Trouble Condition Restoral
The control panel performs the following upon restoral of all trouble conditions:
Turn off the FACP System Trouble LED
Turn off the FACP Zone Trouble LED
Turn off the remote annunciator Trouble LED and piezo sounder
Turn off the piezo sounder
Transfer the fail-safe Trouble relay
Turn off additional LEDs corresponding to specific troubles
MS-2/MS-4 PN 51512:D 10/18/04 43
Page 44
Power Supply Calculations Overview
SECTION 5 Power Supply Calculations
5.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
5.2 Calculating the AC Branch Circuit
The control panel requires connection to a separate, dedicated AC branch circuit, which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm branch circuit. The branch circuit wire must run contin­uously, without any disconnect devices, from the power source to the control panel. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm insulation for this branch circuit.
Use Table 5-1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system.
TABLE 5-1:120 VAC Branch Circuit Requirements
Device Type
MS-2/MS-4
or
MS-2E/MS-4E
Number of
Devices
1X
[ ] X =
[ ] X [ ] =
Sum Column for AC Branch Current Required =
Current Draw
(AC amps)
2.3
1.15
2
) wire with 600 volt
Total C u r re n t
per Device
=
44 MS-2/MS-4 PN 51512:D 10/18/04
Page 45
Calculating the System Current Draw Power Supply Calculations
5.3 Calculating the System Current Draw
5.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when primary power is applied, use Calculation Column 1 in Table 5-3 on page 46. The control panel must support a larger load current during a fire alarm condition. To calculate the fire alarm load on the power supply, use Calculation Col­umn 2 in Table 5-3 on page 46. The secondary power source (batteries) must be able to power the system during a primary power loss. To calculate the non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 5-3 on page 46.
When calculating current draw and the battery size, note the following:
• ‘Primary’ refers to the main power source for the control panel
• ‘Secondary’ refers to the control panel’s backup batteries
• All currents are given in amperes (A). Table 5-2 shows how to convert milliam­peres and microamperes to full amperes.
TABLE 5-2:Converting to Full Amperes
To convert... Multiply Example
Milliamperes (mA) to amperes (A)
Microamperes ( amperes (A)
µA) to
mA x 0.001 3 mA x 0.001 = 0.003A
µA x 0.000001 300 µA x 0.000001 = 0.0003 A
5.3.2 How to Use Table 5-3 on page 46 to Calculate System Current Draw
Use Table 5-3 on page 46 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns
2. Enter the current draw where required. Refer to the Fire-Lite Device Compati­bility Document for compatible devices and their current draw
3. Calculate the current draws for each in all columns
4. Sum the total current for each column
5. Copy the totals from Column 2 and Column 3 to Table 5-4 on page 47
Following are the types of current that can be entered into Table 5-3 on page 46:
Calculation Column 1 - The primary supply current load that the control
panel must support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control
panel must support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in
a non-fire alarm condition during a loss of AC power.
MS-2/MS-4 PN 51512:D 10/18/04 45
Page 46
Power Supply Calculations Calculating the System Current Draw
Table 5-3 contains three columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5-4 on page 47.
TABLE 5-3:System Current Draw Calculations
Calculation Column 1
Device Type
Main Circuit Board
MS-2
or
MS-4
CAC-4 [ ] X[0.001]= [ ] X[0.001]= X[0.001]=
4XTMF [ ] X[0.005]= [ ]
4XZMF [ ] X[0.004]= [ ] X[0.008]= X[0.004]=
4XLMF/RZA-4XF pair
2-wire Detector Heads [ ]
4-wire Detector Heads [ ]
Power Supervision
Current Draw from
TB1 (nonalarm
Sum each column7 for
4
Relays
5
NAC #1
NAC #2 [ ] X[ ]=
totals Primary Non-Alarm = Primary Alarm = Secondary Alarm =
Primary, Non-Fire Alarm Current (amps)
Qty X[current draw]= Total Qty X [current draw] = Total Qty X[current draw]= Total
1
[ ]
1 pair max.
[ ] X[0.025]= [ ] X[0.025]= X[0.025]=
6
)
X[0.080]=
X[0.085]=
X[0.004]= [ ] X[0.019]= X[0.004]=
2
=
X[ ]
3
X[ ]
=
[ ]= [ ]= [ ]=
Calculation Column 2 Primary, Fire Alarm Current (amps)
1
=
0. 1
[ ] X[ ]= X[ ]=
[ ] X[ ]= X[ ]=
[ ] X[ ]=
X[0.112]
X[0.175]
X[0.011]1=
1
=
Calculation Column 3 Secondary, Non-Fire Alarm Current (amps)
0. 1
X[0.080]=
X[0.085]=
X[0.005]=
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps.
2. Refer to the Device Compatibility Document for standby current.
3. Refer to the Device Compatibility Document for standby current.
4. Must use compatible listed Power Supervision Relay.
5. Current limitation of Terminal TB2 circuits is 2.50 amps per NAC (MS-4 requires optional transformer for max. current)
6. The total standby current must include both the resettable (TB1 Terminals 3 & 4) and nonresettable for MS-4 only (TB1 Termi­nals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maxi­mum ratings specified. Current limitations of TB1, Terminals 1 & 2 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10
, nonresettable power and TB1, Terminals 3 & 4 = 0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10mV
mV
RMS
RMS
resettable power.
7. Total current draw listed above cannot exceed 3.0 amps with only standard transformer installed or, for the MS-4, 6.0 amps with both the standard and optional transformers installed.
0.
,
46 MS-2/MS-4 PN 51512:D 10/18/04
Page 47
Calculating the Battery Size Power Supply Calculations
5.4 Calculating the Battery Size
Use Table 5-4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 5-4 as follows:
1. Enter the totals from Table 5-3 on page 46, Calculation Columns 2 and 3 where shown
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below)
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH)
5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door
TABLE 5-4:Total Secondary Power Requirements at 24 VDC
Secondary Standby Load (total from Table 5-3 Calculation Column 3) [ ]
Primary Alarm Load (total from Table 5-3 Calculation Column 2)
[ ]
Sum of Standby and Alarm Ampere Hours = AH
Multiply by the Derating Factor X 1.2
Battery Size, Total Ampere Hours Required = AH
Required Standby Time (24 or 60 hours)
X[ ] = AH
Required Alarm Time (for 5 min., enter 0.084, for 10 min., enter 0.168)
X[ ]
= AH
5.4.1 NFPA Battery Requirements
• NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm
• NFPA 72 Auxiliary and Remote Station require 60 hours of standby followed by 5 minutes in alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power
5.4.2 Selecting and Locating Batteries
Select batteries that meet or exceed the total ampere hours calculated in Table 5-4 . The control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabi­net is capable of housing batteries up to 7 AH. Batteries larger than 7 AH require the BB-17F or other UL listed external battery cabinet.
MS-2/MS-4 PN 51512:D 10/18/04 47
Page 48
Notes
48 MS-2/MS-4 PN 51512:D 10/18/04
Page 49
Index
Numerics
411 16 411UD 16 4XLMF
installation 27, 30 see also LED Interface Module 15 see also LED interface module 30 specifications 30 wiring to RZA-4XF 30
4XTMF
installation 27, 28 operation 28 see also Transmitter Module 15 see also transmitter module 28 specifications 28
4XZMF
installation 27, 29 see also Zone Relay Module 15 see also zone relay module 29 specifications 29
A
AC power 19 AC Power LED 40 AC power rating 12 AC power requirements 44 AC trouble delay 34 accessories 15 ACK
see also Acknowledge 11 Acknowledge 11, 13 Acknowledge button 38 alarm
piezo pulse rate 14 alarm relay 8, 9, 10, 14, 23
contact rating 12 Alarm Silence 11, 13 Alarm Silence LED 40 alarm verification 35, 36
timing graph 35 annunciator, remote
see also RZA-4XF 30 applications 10 audible Walktest 39 autoresettable supervisory 34 auto-silence 34 auxiliary power 23
B
backbox
dimensions 14, 17
mounting 17 battery 14, 19
precautions 19
rating 12 battery box 16
mounting 18 battery calculations 47 battery connector 8, 9
Battery Fault LED 41 BB-17F 18
see also battery box 16
buttons 13
see also control buttons 11
C
cabinet
dimensions 17, 18 mounting 17 see also backbox 14
CAC-4 20
installation 25
see also Class A Converter Module 9, 15 charger 14 charger capacity 12 Charger Fault LED 41 circuits 10 Class A 15, 20, 26 Class A Converter Module 9, 15
installation 25 Class B 10, 12, 14, 20 coding
NACs 34 combination circuit 10, 21
see also waterflow/tamper 34 combination waterflow/supervisory 10, 20, 21
requirements 21
wiring 21 compatibility
see also device compatibility 10 control buttons 11 controls 13 current
maximum system 12
nonresettable power 23
resettable power 23
see also system current 10
total output 22 current requirements for system 45, 46
D
description 10 device compatibility 10 Digital Alarm Communicator/Transmitter
see also 411 & 411UD 16 dimensions
backbox 14, 17 DIP switch options
see also programming 31 DIP switch settings 32
see also programming 31 disable
see also zone enable/disable 11 disable NAC 36 dress panel 10, 15
E
Earth Fault LED 41 earth ground 19
MS-2/MS-4 PN 51512:D 10/18/04 49
Page 50
Index
enable
see also zone enable/disable 11
End-of-Line resistor
IDC 12, 20, 21 NAC 12, 22
F
fail-safe
trouble relay 23
fail-safe relay
see also trouble relay 14 features 10 fire alarm response 42 fire alarm restoral 42 Form-C 15, 29
see also relay 10, 14 freeze 20 freeze signal
see also smoke detector monitoring 10
G
Gentex synchronization 37 Ground Fault
disable 8, 9
I
I3 detectors 14, 20 IDC 9, 10, 12, 14, 20
alarm current 12
compatibility 20
End-of_Line resistor 21
End-of-Line resistor 12, 20
maximum loop resistance 12, 20
see also Initiating Device Circuit 8
short circuit current 12
standby current 12
wiring 20 indicators 13
see also LED 11 Initiating Device Circuit 8, 9, 10, 12, 14, 20
Class A 26 In-Line resistor
IDC combination circuit 21 installation 17
4XLMF 27
4XTMF 27, 28
4XZMF 27
CAC-4 25
Class A Converter Module 25
option modules 25, 27
J
J3 and J5
option module connectors 27 J4 and J6
option module connectors 27 JP1 jumper
placement supervision 27 JP2
placement supervision 27
L
Lamp Test 38 LED 11, 13
AC Power 11, 13, 40 Alarm Silence 11, 13 alarm silence 40 Battery Fault 11, 13 battery fault 41 Charger 11, 13 charger fault 41 Earth Fault 11, 13 earth fault 41 Fire Alarm 11, 13 main circuit board 8, 9 Maintenance 11, 13 NAC Disable 11, 13 NAC disable 40 NAC Fault 11, 13 NAC fault 40 Power Trouble 11, 13 power trouble 40 Supervisory 11, 13 System Trouble 11, 13 system trouble 40 Trouble 11, 13 Walktest 11, 13 walktest 40 Zone Disable 11, 13 zone disable 40 zone fire alarm 40 zone maintenance 41 zone supervisory 41 zone trouble 41
LED Interface Module 15
installation 27 see also 4XLMF 30
M
main circuit board
see also MS-2 8 see also MS-4 9
maintenance 20
piezo pulse rate 14
maintenance signal
see also smoke detector monitoring 10
modes of operation
see also normal and walktest 38
mounting
cabinet 17 MS-2 Main Circuit Board 8 MS-4 Main Circuit Board 9 municipal box 28 municipal box transmitter
see also 4XTMF 15
N
NAC 9, 10, 12, 14, 22
coding 34
current 22
50 MS-2/MS-4 PN 51512:D 10/18/04
Page 51
Index
disable 36 End-of-Line resistor 12, 22 maximum current 12 nonsilenceable 36 see also Notification Appliance Circuit 8
wiring 22 NAC Disable LED 40 NAC Fault LED 40 nonpower-limited wiring 24 nonresettable power 9, 10, 12, 14, 23
current 23
maximum current 12 nonsilenceable NAC 36 normal mode 38 Notification Appliance Circuit 8, 9, 10, 12, 14, 22
Class A 26
O
operating instructions 38 operation 41 option modules 15
connector 8, 9
connectors 27
installation 25, 27
placement supervision 27
P
piezo 14
alarm 14
maintenance 14
see also sounder 11
supervisory 14
trouble 14 polarity reversal circuit
see also 4XTMF 28 power 12, 19, 23
maximum system 12
primary 19
secondary
see also battery 19
see also resettable and nonresettable power 9 power supply calculations 44 Power Trouble LED 40 power-limited wiring 24 programming 31, 32
chart 32
DIP switches 31
feature chart 32
supervisory 35 programming DIP switches 31
R
relay 8, 9, 10, 14, 15, 23, 29
contact rating 12, 23 Remote Annunciator
see also RZA-4XF 15 remote station service 28 Reset 11 Reset button 38 resettable power 8, 9, 10, 12, 14, 23
current 23 maximum current 12
reverse polarity circuit
see also 4XTMF 15
RZA-4XF
see also Remote Annunciator 15 see also remote annunciator 30 wiring to RXLMF 30
S
selective silence 34 silence
selective 34 Silence button 38 silence inhibit 34 silent walktest 40 sounder 11, 14 status LEDs 40 strobe synchronization
see also synchronization 37 Style B 12, 14, 20
see also Class B 10 Style D 15, 20, 26 Style Y 12, 14
see also Class B 10 Style Z 15, 26 supervision
option module placement 27 supervisory
piezo pulse rate 14
see also programming supervisory 35, 36 supervisory relay 9, 10, 14, 23
contact rating 12 supervisory response 42 supervisory restoral 42 switch functions 38 synchronization
Gentex 37
see also strobe synchronization 37
System Sensor 37
Wheelock 37 system current 10 system current calculations 45 System Sensor synchronization 37 System Trouble LED 40
T
temporal coding 34 transformer assembly 14
rating 14 Transmitter Module 15 transmitter module
see also 4XTMF 28 trouble
piezo pulse rate 14 trouble relay 8, 9, 10, 14, 23
contact rating 12
fail-safe 23 trouble reminder 34
MS-2/MS-4 PN 51512:D 10/18/04 51
Page 52
trouble response 43 trouble restoral 43
U
UL
wiring requirements 24
V
verification
alarm timing graph 35 see also alarm verification 35
W
Walktest 11, 13 Walktest LED 40 Walktest Mode 38 Walktest mode 39
audible 39 exiting 40
silent 40 waterflow/tamper circuit 34 Wheelock synchronization 37 wiring
CAC-4 26
Class A Converter Module 26
Class A IDC 26
Class A NAC 26
combination waterflow/supervisory 21
IDC 20
NAC 22
nonpower-limited 24
power-limited 24
UL requirements 24
Z
Zone 1 20 Zone Disable LED 40 Zone Enable/Disable 11, 13 Zone Fire Alarm LED 40 Zone Maintenance LED 41 zone relay module 15
see also 4XZMF 29 Zone Supervisory LED 41 Zone Trouble LED 41
Index
52 MS-2/MS-4 PN 51512:D 10/18/04
Page 53
Notes
MS-2/MS-4 PN 51512:D 10/18/04 53
Page 54
Notes
54 MS-2/MS-4 PN 51512:D 10/18/04
Page 55
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of original purchase by the manufacturer's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired, or serviced by anyone other than the manufacturer or its authorized distributors, or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its products. The manufacturer does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
LimWarLg.p65 01/10/2000
Page 56
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...