1 Firelite Place Northford, CT 06472-1653 USA TEL: (203) 484-7161
C
Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free installation
with long-term reliability: WARNING - Several different sources of power can be connected
to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit
and associated equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate
this unit until manuals are read and understood. CAUTION - System Re-acceptance T est after
Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or wiring. All
components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified. This
system meets NFP A requirements for operation wi thin the range of 0°C-49°C (32°F-120°F) or
humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful
life of the system's standby batteries and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it is recommended that this system
and its peripherals be installed in an environment with a normal room temperature of 15-27º
C/60-80º F. Verify that wir e sizes ar e adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged
when subjected to lightning induced transients. Although no system is completely immune
from lightning transients and interference, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered. Remove DC power prior to removing or inserting circuit boards.
Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When possible, make all cable entries from the
sides or rear. Before making modifications, verify that they will not interfere with battery,
transformer, or printed circuit board location. Do not tighten scr ew terminals more than 9 inlbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and
difficulty with screw terminal removal. Fire alarm control panels contain static-sensitive
components. Always ground yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. Use static suppressive packaging to protect
electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Equipment used in the system may not be technically compatible with the control. It is
essential to use only equipment listed for service with your control panel. Telephone lines
needed to transmit alarm signals from a premise to a central monitoring station may be out of
service or temporarily disabled. The most common cause of fire alarm malfunctions,
however, is inadequate maintenance. All devices and system wiring should be tested and
maintained by professional fire alarm installers following written procedures supplied with
each device. System inspection and testing should be scheduled monthly or as required by
National and/or local fire codes. Adequate written records of all inspections should be kept.
1.1Overview of Basic System ....................................................................................................................... 1-1
1.1.1 Hardware Features .......................................... .................................................................................. 1-1
1.1.2 Software Features .............................................................................................................................1-1
1.2About this Manual ....................................................................................................................................1-2
1.2.1 Terms Used in this Manual ...............................................................................................................1-2
Before You Begin Installing ............................................................................................... 3-1
3.1What’s in the Box? ...................................................................................................................................3-1
3.6.1.1 Current Draw Worksheet for MS-25 UL 864 ........................................................................ 3-6
3.6.1.2 Current Draw Worksheet for MS-25C ULC ........................................... ...............................3-8
3.6.2 Maximum Battery Standby Load for UL 864 .................................................................................3-10
3.6.3 Maximum Battery Standby Load for ULC ..................................................................................... 3-10
Section 4
Control Panel Installation ......................................................................................................4-1
4.1Mounting the Control Panel Cabinet ....................................................................................................... 4-1
4.1.1 Preventing Water Damage ................................................................................................................4-1
4.1.2 Removing the MS-25 Assembly from the Housing ..........................................................................4-1
4.1.3 Dead Front Installation and removal ................................................................................................4-2
4.1.3.1 Installing the Dead Front ........................................................................................................ 4-2
1
Contents
4.1.3.2 Dead Front Removal .............................................................................................................. 4-3
4.2AC Power Connection .............................................................................................................................4-4
4.2.1 AC Power Connection for UL 864 applications ...............................................................................4-4
4.2.2 AC Power Connection for Canadian Applications ...........................................................................4-5
5.1List of SLC Devices .................................................................................................................................5-1
5.2Maximum Number of Devices .................................................................................................................5-1
5.3Wiring Requirements for SLC Devices ................................................... ................................................5-2
5.3.1 Wiring SLC in Style 4 (Class B) Configuration .................................. ............................................. 5-2
6.6.1 System Options .................................................................................................................................6-6
6.6.1.1 Synchronized Strobes Active When Horns Silenced ............................................................. 6-6
7.2Lamp Test ................................................................................................................................................ 7-1
7.5Viewing Active Alarm Points ............................................................ ......................................................7-1
7.6Viewing Active Supervisory Points .........................................................................................................7-2
7.7Viewing Active Trouble Points ................................................................................................................ 7-2
7.8Walk Test ......................................... ........................................................................................................7-2
7.12 Loss of AC power ....................................................................................................................................7-3
7.16 Phone Line Monitoring ...........................................................................................................................7-4
7.21.1 Conduct a Fire Drill ..........................................................................................................................7-7
7.21.2 Conduct an Indicator Test .................................................................................................................7-7
7.21.3 Silence alarms or troubles .................................................................................................................7-7
9.1.2 View Active Points ............................................ ............................................................................... 9-1
9.1.3 Disable Or Re-Enable A Zone ..........................................................................................................9-1
9.1.4 Silence the Board PZT ......................................................................................................................9-1
9.1.5 Silence the Notification Appliances .................................................................................................9-1
9.1.6 To Initiate a Fire Drill .......................................................................................................................9-2
9.1.7 For a Dialer Test ........................................................... ....................................................................9-2
9.1.8 For a Lamp Test ................................................................................................................................9-2
9.1.9 AC LED ............................................................................................................................................9-2
9.1.10 Walk Test ............................................. .............................................................................................9-2
9.2Web Server Menus ...................................................................................................................................9-3
9.2.1 To add a smoke detector: ..................................................................................................................9-3
9.2.2 To add a notification appliance (fire bell) ........................................................................................9-3
9.2.3 To add a Remote Annunciator (DIP switch address 1 or 2) ............................................................. 9-3
9.2.4 To add custom Zone name ................................................................................................................ 9-4
9.2.5 To trip an SLC notification appliance ...............................................................................................9-4
9.2.6 To trip a Door Holder .......................................................................................................................9-4
Manufacturer Warranties and Limitation of Liability
Model MS-25/MS-25C/MS-25E Basic Operating Instructions
5
MS-25 Installation and Operation Manual
6
Section 1
Introduction
The MS-25 Fire Alarm Control / Communicator is an addressable fire control system that
meets the requirements of UL 864, ULC 527, and ULC 559. Unless otherwise indicated, all
references to MS-25 also refer to MS-25C and MS-25E.
1.1Overview of Basic System
1.1.1Hardware Features
•The MS-25 has one signaling line circuit (SLC) that supports 25 SLC devices (See
Section 5.1), and one SBUS circuit that supports two remote annunicators.
•2.0A of output power is available through 2 sets of terminals for notification appliance
circuits or 1.0A for auxiliary power applications. Each circuit is power limited per UL 864
and can source up to 2.0A.
Note: Total output power for all three circuits must not exceed 2.0A.
•Built-in dual phone line, digital alarm communicator/transmitter (DACT).
•Reports events to central station by zone.
•Two general purpose Form C programmable relays.
•One Form C Trouble Relay.
1.1.2Software Features
•The MS-25 is an addressable panel that operates like a 5 zone conventional panel.
•Advanced addressable smoke detector features:
–Automatic drift compensation
–Maintenance alert region
–Point status meets calibrated smoke test requirements for NFPA 72
•Auto learn “JumpStart” feature for easy programming.
•A choice of output patterns available for notification outputs, including ANSI 3.41
temporal signal.
®
•Built-in synchronization appliance support for Amseco, Gentex
Sensor ®.
, Wheelock®, or System
536881-1
Model MS-25 Installation and Operation Manual
1.2About this Manual
This manual is intended to be a complete reference for all installation and operation tasks for
the MS-25. Please let us know if the manual does not meet your needs in any way.
We value your feedback!
1.2.1Terms Used in this Manual
The following terminology is used with the MS-25 system:
TermDescription
SLCSignaling Line Circuit
Input PointAn addressable sensing device, such as a smoke or heat detector
or a contact monitor device.
Input ZoneA protected area made up of input points.
Output Point
(or Output Circuit)
Output (or “Cadence”) PatternThe pattern that the output will use, for example, Constant or
A notification point or circuit for notification appliances. Relay
circuits and auxiliary power circuits are also considered output
points.
ANSI 3.41.
1.3Compatible Products
See Section 5.1 for a list of compatible SLC devices for use with the MS-25.
See Appendix A for a list of compatible notification appliances.
1-253688
Introduction
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected
premise following the recommendations of the current edition of the National Fire Protection
Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes,
and the recommendations contained in Guide for the Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. A study by the Federal
Emergency Management Agency (an agency of the United States government) indicated that
smoke detectors may not go off or give early warning in as many as 35% of all fires. While
fire alarm systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons. For example:
•Particles of combustion or smoke from a developing fire may not reach the sensing
chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or
smoke flow.
Smoke particles may become cold, stratify, and not reach the ceiling or upper walls where
detectors are located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires
developing on another level.
•The amount of smoke present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density levels
are not created by a developing fire at the location of detectors, the detectors will not go
into alarm.
•Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photo electronic sensing chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast flaming fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide adequate warning of a fire.
•Smoke detectors are subject to false alarms and nuisance alarms and may have been
disconnected by users. For example, a smoke detector located in or near a kitchen may go
into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or
steamy environments may cause a smoke detector to falsely alarm. If the location of a
smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect
the smoke detector; call a professional to analyze the situation and recommend a solution.
•Smoke detectors cannot be expected to provide adequate warning of fires caused by arson,
children playing with matches (especially within bedrooms), smoking in bed, violent
explosions (caused by escaping gas, improper storage of flammable materials, etc.).
536881-3
Model MS-25 Installation and Operation Manual
•Heat detectors do not sense particles of combustion and are designed to alarm only when
heat on their sensors increases at a predetermined rate or reaches a predetermined level.
Heat detectors are designed to protect property, not life.
•Warning devices (including horns, sirens, and bells) may not alert people or wake up
sleepers who are located on the other side of closed or partially open doors. A warning
device that activates on a different floor or level of a dwelling or structure is less likely to
awaken or alert people. Even persons who are awake may not notice the warning if the
alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by
passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to
alert people with a disability, deep sleepers, people who have recently used alcohol or
drugs, or people on medication or sleeping pills.
Please note that:
i)Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not
respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercises to make people aware of fire
alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent
hearing loss.
•Telephone lines needed to transmit alarm signals from a premises to a central station may
be out of service or temporarily out of service. For added protection against telephone line
failure, backup radio transmission systems are recommended.
•System components, though designed to last many years, can fail at any time. As a
precautionary measure, it is recommended that smoke detectors be checked, maintained,
and replaced per manufacturer’s recommendations.
•System components will not work without electrical power. If system batteries are not
serviced or replaced regularly , they may not provide battery backup when AC power fails.
•Environments with high air velocity or that are dusty or dirty require more frequent
maintenance.
In general, fire alarm systems and devices will not work without power and will not function
properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate,
an alarm system is not a substitute for insurance.
Property owners should continue to act
prudently in protecting the premises and the people in their premises and should properly
insure life and property and buy sufficient amounts of liability insurance to meet their needs.
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection
equipment in all rooms and areas of the house or building in accordance with the requirements
1-453688
Introduction
and recommendations of the current edition of the National Fire Protection Association
Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’ s recommendations,
State and local codes and the recommendations contained in Guide for the Proper Use of
System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for
fire protection systems.
Requirements and Recommendations include:
•Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
•It is recommended that more than one smoke detector shall be installed in a hallway if it is
more than 30 feet long.
•It is recommended that there shall never be less then two smoke detectors per apartment or
residence.
•It is recommended that smoke detectors be located in any room where an alarm control is
located, or in any room where alarm control connections to an AC source or phone lines
are made. If detectors are not so located, a fire within the room could prevent the control
from reporting a fire.
•All fire alarm systems require notification devices, including sirens, bells, horns, and/or
strobes. In residential applications, each automatic alarm initiating device when activated
shall cause the operation of an alarm notification device that shall be clearly audible in all
bedrooms over ambient or background noise levels (at least 15dB above noise) with all
intervening doors closed.
•It is recommended that a smoke detector with an integral sounder (smoke alarm) be
located in every bedroom and an additional notification device be located on each level of
a residence.
•To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a
minimum the requirements of Chapter 14 of NFPA 72, 2010 Edition shall be followed. A
maintenance agreement should be arranged through the local manufacturer’s
representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is inadequate
maintenance. As such, the alarm system should be tested weekly to make sure all sensors and
transmitters are working properly.
536881-5
Model MS-25 Installation and Operation Manual
1-653688
Section 2
Agency Listings, Approvals, and Requirements
Install and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to
NFPA 72. End-of -line relays and resistors shall be placed within the electrical box located
and the end of the initiating circuit. Testing and maintenance should be performed according
to NFPA 72.
2.1Federal Communications Commission (FCC)
The following information must be provided to the telephone company before the MS-25 can
be connected to the phone lines:
AManufacturer:Honeywell International Inc.
BModel Number:MS-25
CFCC registration number:US: AC6AL05B205600
Ringer equivalence:0.5B
DType of jack:RJ31X
EFacility Interface Codes:Loop Start: 02LS2
Ground Start: 02GS2
FService Order Code:9.0F
1. This device may not be directly connected to coin telephone or party line services.
2. This device cannot be adjusted or repaired in the field. In case of trouble with the device,
notify the installing company or return to:
Fire-Lite Alarms
1 Firelite Place
Northford, CT 06472-1653
203-484-7161
3. If the MS-25 causes harm to the telephone network, the telephone company will notify the
user in advance that temporary discontinuance of service may be required. If advance
notice is not practical, the telephone company will notify the user as soon as possible.
Users have the right to file complaints, if necessary, with the Federal Communications
Commission.
536882-1
Model MS-25 Installation and Operation Manual
4. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone
company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:
(1) This device may not cause radio interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
a) This equipment complies with Part 68 of the FCC rules and the requirements adopted by
the ACTA. On the wiring diagram of this equipment is a label that contains, among other
information, a product identifier in the format US: AC6AL05B-205600. If requested, this
number must be provided to the telephone company.
b) See Section 4.8 for phone jack information.
c) A plug and jack used to connect this equipment to the premises wiring and telephone
network must comply with the applicable FCC Part 68 rules and requirements adopted by
the ACTA. A compliant telephone cord and modular plug is provided with this product. It
is designed to be connected to a compatible modular jack that is also compliant. See
installation instructions for details.
d) The REN is used to determine the number of devices that may be connected to a telephone
line. Excessive RENs on a telephone line may result in the devices not ringing in response
to an incoming call. In most but not all areas, the sum of RENs should not exceed five
(5.0). To be certain of the number of devices that may be connected to a line, as
determined by the total RENs, contact the local telephone company. For products
approved after July 23, 2002, the REN for this product is part of the product identifier that
has the format US: AC6AL05B-205600. The digits represented by ## are the REN
without a decimal point (e.g., 03 is a REN of 0.3). For earlier products, the REN is
separately shown on the label.
e) If this equipment MS-25 causes harm to the telephone network, the telephone company
will notify you in advance that temporary discontinuance of service may be required. But
if advance notice isn't practical, the telephone company will notify the customer as soon as
possible. Also, you will be advised of your right to file a complaint with the FCC if you
believe it is necessary.
f) The telephone company may make changes in its facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the telephone
company will provide advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
g) If trouble is experienced with this equipment MS-25, for repair or warranty information,
please contact FireLite. If the equipment is causing harm to the telephone network, the
telephone company may request that you disconnect the equipment until the problem is
resolved.
h) See warranty in back of this manual for repair and replacement information.
i)Connection to party line service is subject to state tariffs. Contact the state public utility
2-253688
Agency Listings, Approvals, and Requirements
commission, public service commission or corporation commission for information.
j)If your home has specially wired alarm equipment connected to the telephone line, ensure
the installation of this MS-25 does not disable your alarm equipment. If you have
questions about what will disable alarm equipment, consult your telephone company or
qualified installer.
Electrical Safety Advisory:
Parties responsible for equipment requiring AC power should consider including an advisory
notice in their customer information suggesting the customer use a surge arrestor. Telephone
companies report that electrical surges, typically lightning transients, are very destructive to
customer terminal equipment connected to AC power sources. This has been identified as a
major nationwide problem.
2.2Underwriters Laboratories (UL)
2.2.1Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on).
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use ONLY the addressable smoke detectors specified in Section 5.1 of this manual.
3. Use UL listed notification appliances compatible with the MS-25, choose from those specified in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
Restricted Options:
•The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 30 hours. For UL certified installations this number must be set from 1 to 3 hours.
•The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL
certified installations the setting must be a maximum of 60 seconds.
•Call forwarding shall not be used.
•Waterflow and Supervisory have to be set to Latching as shown in the restricted options
table in Section 6. See Table 6-1:.
536882-3
Model MS-25 Installation and Operation Manual
2.2.2Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the MS-25 sends an automatic
daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours.
2.3ULC Requirements
Install in accordance with the Canadian Electrical Code, C22.1, Part 1, Section 32.
2-453688
Section 3
Before You Begin Installing
This section of the manual is intended to help you plan your tasks to facilitate a smooth
installation. Please read this section thoroughly , especially if you are installing a MS-25 panel
for the first time.
3.1What’s in the Box?
The MS-25 ships with the following hardware:
•A cabinet with all hardware assembled
•Two keys for the front door
•Installation and Operation manual P/N 53688
•Ten 4.7K ohm end-of-line resistors
•A battery cable for batteries wired in series
3.2Environmental Specifications
It is important to protect the MS-25 control panel from water. To prevent water damage, the
following conditions should be AVOIDED when installing the units:
•Intended for indoor use in dry locations only
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the MS-25 control panel, the unit should be mounted
where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity outside the range of 10%-93% at 30°C (86°F) noncondensing.
536883-1
Model MS-25 Installation and Operation Manual
3.3Electrical Specifications
T able 3-1 list the electrical specifications for the MS-25 field wiring as well as a description of
the each individual terminal and their respective electrical rating. For location of the terminals
refer to 3.5. See also Section 4 for installation.
*Regulated for NAC circuits
*Special application when used for auxiliary power circuits.
3-253688
Before You Begin Installing
1/4” spacing must
be maintained
between power
limited and Nonpower limited
wiring
3.4Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with
telephone communication or cause false alarms. To avoid induced noise, follow these
guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one multiconductor cable for the entire panel. Instead, separate the wiring as follows:
High voltageAC power Terminals
SLC loopsPhone line circuits
Notification circuitsNAC1 through NAC2
Relay circuitsSBUS Wiring
•Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to earth ground at the panel. You must route high and low voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit
board where it could induce noise into the sensitive microelectronics or pick up unwanted
RF noise from the high speed circuits. See Figure 3-1 for an example.
•High frequency noise, such as that produced by the inductive reactance of a speaker or
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it
around a ferrite toroid.
Figure 3-1 Wire Routing Example
536883-3
Model MS-25 Installation and Operation Manual
Form C
Trouble Relay
On-board
Annunciator
BatteryConnector
AC PowerInput
Form C
Programmable
Relays
AC Power Input
Battery
Connector
24VDC
Ethernet
Programming Port
Mounting
screw
Location
mounting
pin
Mounting screws
Slide-In Stand-offs
SBUS
SLC Out
NAC/AUX
Power
Circuits
Phone Lines
3.5Board Assembly Diagram
Figure 3-2 Model MS-25 Assembly
Figure 3-2 shows the MS-25 circuit board stack. If you should need to remove the control
board for repair, remove the three mounting screws which hold the control board in the
cabinet, slide out of slot from slide-in standoff. Then lift the control board off the location
mounting pin and out of the cabinet.
3-453688
Before You Begin Installing
3.6Calculating Current Draw and Standby Battery
This section is for helping you determine the current draw and standby battery requirements
(Table 3-2).
3.6.1Worksheet Requirements
The following steps must be taken when determining MS-25 current draw and standby battery
requirements.
1. For the MS-25, the worst case current draw is listed for the panel and all addressable
devices. Fill in the number of addressable devices that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in the
Current Calculation Worksheet at Line A.
2. Add up the current draw for all auxiliary devices and record in the table at Line B.
3. Add up all notification appliance loads and record in the table at Line C.
4. For notification appliance circuits and auxiliary devices not mentioned in the manual,
refer to the device manual for the current ratings.
5. Make sure that the total alarm current you calculated, including current for the panel itself,
does not exceed 2.0 A. This is the maximum alarm current for the MS-25 control panel.
If the current is above 2.0 A you will need to use a notification power expander(s) such as
the Fire-Lite FCPS-24FS6 (8) power supply to distribute the power loads so that the MS25 or the power expanders do not exceed their power rating.
6. Complete the remaining instructions in the Current Calculation Worksheet for determining
battery size requirements.
536883-5
Model MS-25 Installation and Operation Manual
3.6.1.1Current Draw Worksheet for MS-25 UL 864
Use Table 3-2 to determine amp-hour requirements during alarm/battery standby operation.
(Copy the page if additional space is required.) You can install up to 25 SLC devices and two
ANN-80 Remote Annunciator.
Table 3-2: Current Calculation Worksheet for SLC Devices
Device# of DevicesCurrent per Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
Auxiliary DevicesRefer to devices manual for current rating.
BAuxiliary Devices Current
Notification Appliance CircuitsRefer to device manual for current rating.
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
GMultiply lines E and F.Total standby AHAH
Table 3-2: Current Calculation Worksheet for SLC Devices
Device# of DevicesCurrent per Device
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
1. Use next size battery with capacity greater than required.
1
Total ampere hours
required
Standby
Current
Alarm
Current
H
AH
AH
536883-7
Model MS-25 Installation and Operation Manual
3.6.1.2Current Draw Worksheet for MS-25C ULC
Use to determine amp-hour requirements during alarm/battery standby operation. (Copy the
page if additional space is required.) You can install up to 25 SLC devices and two ANN-80C
Remote Annunciator. The maximum battery size for ULC installations is 18 Amp/hr.
Table 3-3: Current Calculation Worksheet for Devices for ULC
Device# of DevicesCurrent per Device
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from
battery)
Accessory Modules
ANN-80C Remote Annunicator
Addressable SLC Detectors
HFS-PA
HFS-PTAmAmA
HFS-DAmAmA
HFS-TAmAmA
SD355AmAmA
SD355TAmAmA
D355PLAmAmA
H355AmAmA
Addressable SLC Modules
HFS-MMA
BG-12LXStandby/Alarm 0.375 mA
HFS-MRAStandby/Alarm 0.255mAmAmA
MMF-301AStandby/Alarm 0.375 mA
CRF-300AStandby/Alarm 0.375 mA
I300A10 maxStandby/Alarm 0.45 mAmAmA
ATotal System Current
Auxiliary DevicesRefer to devices manual for current rating.
BAuxiliary Devices Current
Notification Appliance CircuitsRefer to device manual for current rating.
CNotification Appliances Current
DTotal current ratings of all devices in system (line A + line B + C)mAmA
ETotal current ratings converted to amperes (line D x .001):AA
FNumber of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):H
GMultiply lines E and F.Total standby AHAH
HAlarm sounding period in hours. (For example, 5 minutes = .0833 hours)H
Table 3-3: Current Calculation Worksheet for Devices for ULC
Device# of DevicesCurrent per Device
IMultiply lines E and H.Total alarm AH
J
Add lines G and I.
1. Use next size battery with capacity greater than required.
1
Total ampere hours
required
Standby
Current
Alarm
Current
AH
AH
536883-9
Model MS-25 Installation and Operation Manual
3.6.2Maximum Battery Standby Load for UL 864
Table 3-4 shows the standby load calculations for the MS-25 based on 24 hours of standby.
The standby load calculations of line D in the Current Draw Calculation Worksheet must be
less than the number shown in Table 3-4 for the selected battery size, standby hour and alarm
time. The numbers below have a built in 20% derating factor for the battery amp hour
capacity.
Table 3-4: Maximum Battery Standby loads for 24 Hour Standby
Rechargeable
Battery Size
7 AH226 mA213 mA206 mA
12 AH393 mA379 mA372 mA
18 AH593 mA579 mA572 mA
24 AH793 mA779 mA772 mA
33 AH1.09 A1.08 A1.07 A
24 hr Standby,
5 mins. Alarm
24 hr Standby,
15 min alarm
24 hr Standby,
20 min alarm
3.6.3Maximum Battery Standby Load for ULC
Table 3-5 shows the ULC standby load calculations for the MS-25C based on 24 hours of
standby. The standby load calculations of line D in the Current Draw Calculation Worksheet
must be less than the number shown in Table 3-5 for the selected battery size, standby hour
and alarm time. The numbers below have a built in 40% derating factor for the battery amp
hour capacity.
Table 3-5: Maximum Battery Standby loads for ULC 24 Hour Standby
Rechargeable
Battery Size
7 AH226 mA213 mA206 mA
12 AH393 mA379 mA372 mA
18 AH529 mA515 mA508 mA
24 hr Standby,
5 mins. Alarm
24 hr Standby,
15 min alarm
24 hr Standby,
20 min alarm
Warning
Fire-Lite does not support the use of batteries smaller than those listed in Table 3-4. If you use a battery too small
for the installation, the system could overload the battery resulting in the installation having less than the required
24 hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for your installation. It is recommended that you replace batteries every five years.
3-1053688
Section 4
Control Panel Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while
installing or servicing.
4.1Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the MS-25 panel.
The MS-25 cabinet dimensions are:
12-3/4” W x 15-1/8” H x 3-3/8” D (32.39 cm W x 38.42 cm H x 8.57 cm D).
The MS-25 panel should be located within a secured area, where it is accessible to main drop
wiring runs and where it can be easily tested and serviced. Building occupants are responsible
for maintaining the panel should be able to hear alarms and troubles. When selecting a
location, keep in mind that the panel itself is the main source of alarm and trouble
annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting
on concrete, especially when moisture is expected, attach a piece of 3/4 inch plywood to the
concrete surface and then attach the MS-25 to the plywood. Also mount any other desired
components to the plywood.
DO NOT flush-mount the MS-25 cabinet.
4.1.1Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.
4.1.2Removing the MS-25 Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for
repair, do so by removing the screws that hold the control panel in to the cabinet. Do not
attempt to disassemble the circuit boards.
536884-1
Model MS-25 Installation and Operation Manual
Dead Front
Panel
4.1.3Dead Front Installation and removal
This section provides instructions to install and or remove the dead front for the control panel
cabinet.
4.1.3.1Installing the Dead Front
Follow these steps to properly install the dead front panel into the control panel cabinet.
1. Remove the top two annunciator screws, do not discard them they will be reused. See
Figure 4-1 for annunciator screw location.
2. Set the dead front into the cabinet as shown in Figure 4-1.
3. Reinsert the two annunciator screws as shown in Figure 4-1.
Figure 4-1 Dead Front Installation and Removal
4-253688
Control Panel Installation
4.1.3.2Dead Front Removal
Follow these steps to properly remove the dead front panel from the control panel cabinet.
1. Remove the two annunciator screws, do not discard them. See Figure 4-1.
2. Tilt the dead front forward to clear the top of the cabinet and left the dead front out of the
cabinet. See Figure 4-1.
3. Reinsert the two annunciator screws. See Figure 4-1.
536884-3
Model MS-25 Installation and Operation Manual
Ground
To AC
Supervised
AC
Connection
4.2AC Power Connection
4.2.1AC Power Connection for UL 864 applications
At installation, connect the AC terminals to the power source as shown in Figure 4-2. It may
be necessary for a professional electrician to make this connection. Connect black and white
wires from transformer to 120V power . Connect ground wire from 120V power to screw
labeled G on the MS-25 circuit board.
The AC power input is rated at 120 VAC, 60 Hz, 1.5A for MS-25 and 230 VAC, 50/60Hz,
.75A for MS-25E.
Figure 4-2 120/230 VAC Power Connection
4-453688
Control Panel Installation
4.2.2AC Power Connection for Canadian Applications
For Canadian applications, an AC terminal block is supplied standard with the MS-25C. The
AC terminal block is factory installed on the left of the circuit board chassis as shown in
Figure 4-3.
Figure 4-3 AC terminal Block Connections
536884-5
Model MS-25 Installation and Operation Manual
Red
Battery Jumper
(P/N 140694)
Shippe d With Pa ne l
Black
Supervised
Battery 2Battery 1
12V Battery
12V Battery
Fire-Lite
PN BAT-1270
4.3Battery Connection
The control panel battery charge capacity is 7.0 to 33 AH or 18 AH for ULC installations. The
main control cabinet can house batteries up to 7 AH, larger capacity batteries can be housed in
a Remote Battery Box (P/N BB-26 or BB-55F). Use 12V batteries of the same AH rating.
Determine the correct AH rating as per your current load calculation (see Section 3.6).
Maximum charging current for batteries is 3.1A @ 27 VDC.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
The following steps and diagram explain how to connect the batteries.
1. Connect the black wire from the control panel negative (–) battery terminal to the negative
(–) side of Battery #2.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2
to the (–) negative side of Battery #1.
3. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of
Battery #1.
4-653688
Figure 4-4 Battery Connection
Control Panel Installation
4.4SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring
configurations (Class B).
4.4.1Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum
wiring distance that can be used with control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel,
it is necessary to calculate the total worst case current draw for all modules on a single 4conductor bus. The total worst case current draw is calculated by adding the individual worst
case currents for each module. The individual worst case values are shown in the table below.
Note: Total worst case current draw on a single SBUS cannot exceed 500 mA.
Model NumberWorst Case Current Draw
MS-25 Remote Fire Annunciator.04 amps
After calculating the total worst case current draw, Table 4-1 specifies the maximum distance
the modules can be located from the panel on a single wire run. The table insures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wire
gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more
than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in
the note below).
Table 4-1: Wire Distance Per Wire Gauge Using Copper Wire
Wiring Distance: SBUS Modules to Panel
Total W orst Case
Current Draw (amps)
0.1001852 ft.4688 ft.* 6000 ft.* 6000 ft.
0.200926 ft.2344 ft.3731 ft.5906 ft.
0.300617 ft.1563 ft. 2488 ft.3937 ft.
0.400463 ft.1172 ft.1866 ft.2953 ft.
0.500370 ft.938 ft.1493 ft.2362 ft.
0.600309 ft.781 ft.1244 ft.1969 ft.
0.700265 ft.670 ft.1066 ft.1687 ft.
0.800231 ft.586 ft.933 ft.1476 ft.
0.900206 ft.521 ft.829 ft.1312 ft.
1.000 (Max)185 ft.469 ft.746 ft.1181 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
536884-7
Model MS-25 Installation and Operation Manual
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (Feet) =
(6000 feet maximum)
where: Rpu = Ohms per 1000 feet for various wire gauges (see table below)
Table 4-2: Typical Wire Resistance per 1000 ft. using Copper Wire
Wire GaugeOhms per 1000 feet (Rpu)
2216.2
186.4
164.02
142.54
Maximum Resistance (Ohms)* 500
Rpu
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules:
1 - Module MS-25 Fire Annunciator
The total worst case current is calculated as follows:
MS-25 Current Draw= 1 x .04 amps= .04 amps
Total Worst Case Current Draw= .04 amps
Using this value, and referring to the Wiring Distance table, it can be found that the available
options are:
1852 feet maximum using 22 Gauge wire
4688 feet maximum using 18 Gauge wire
6000 feet maximum using 16 Gauge wire
6000 feet maximum using 14 Gauge wire
4-853688
4.4.2Wiring Configurations
Supervised
Power Limited
ANN-80
Figure 4-5 illustrates Class B configuration.
Control Panel Installation
Figure 4-5 SBUS Class B Wiring
536884-9
Model MS-25 Installation and Operation Manual
4.5ANN-80 Remote Annunciator Installation
The optional Model ANN-80 (red) and ANN-80-W (white) Remote Annunciator is shown in
Figure 4-6.
Figure 4-6 Model ANN-80 Remote Annunciator, Front View
ANN-80 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the ANN-80 in the desired location (see Section 4.5.1).
3. Connect the ANN-80 to the panel (see Section 4.6).
4. Use the DIP switches on the back of the ANN-80 to assign an ID# to the ANN-80 (see
Section 4.7.1).
5. The new ANN-80 module must be added to the system through programming.
JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.3.2). Select a name, if desired (see Section 7.3.1.1).
4-1053688
Control Panel Installation
Back Box
Inside Cover
LCD Display
4.5.1Mounting the ANN-80
This section of the manual describes mounting the remote annunciator. Figure 4-7 shows the
parts of the annunciator.
Figure 4-7 ANN-80 Annunciator Parts
The ANN-80 Series plastic enclosures can be surface or semi-flush mounted in a single,
double or 4” square electrical box.
To mount the ANN-80 Series enclosure:
1. Open the ANN-80 Series cover by turning the key switch counterclockwise to the ON
(Unlocked) position.
2. Push in the snap latch tab located on the right side while pulling the cover open.
3. Pull wire through 7/8” hole in backplate and feed through wire channel to lower left corner of backplate before routing to terminal block.
4. The cover must remain attached to the backplate while mounting the annunciator to the
electrical box/ wall. The cover cannot be reattached or removed after the annunciator has
been mounted.
5. Surface or Semi-flush mount the ANN-80 to a single, double or 4" square electrical box.
The ANN-SB80KIT(-R/-B/-W) is an available kit that contains two plastic backboxes that
can be used to surface mount the ANN-80.
536884-11
Model MS-25 Installation and Operation Manual
Supervised
Power Limited
4.6Model ANN-80 Connection to the Panel
Connect the ANN-80 to the panel as shown in Figure 4-8.
Figure 4-8 Model ANN-80 Connection to the Panel
4-1253688
Control Panel Installation
ID Number
(Address)
(not valid) 00
01
02
DIP Switch
4.7Configuring Module
This section describes how to configure the ANN-80 Annunciator that has been added to the
system. Each SBUS device requires a unique address. ANN-80 Series DIP switch S21 is used
to set the address. This address will be displayed on the LCD display as the Station ID
number.
4.7.1Assigning Module IDs
When installing the ANN-80 you must use the DIP switches on the module to assign an ID# to
the module. A maximum of 2 devices can be connected to the FACP SBUS communication
circuit. The SBUS device address needs to be set to 01or 02.
Note: Note that 00 is not a valid address.
Figure 4-9 shows the DIP switch positions and their correlation to a numerical ID.
Figure 4-9 DIP switch settings
536884-13
Model MS-25 Installation and Operation Manual
Use Minimum of 26
AWG Telephone
Line cord
4.8Telephone Connection
Connect the telephone lines as shown in Figure 4-10. The Model 7860 phone cord is available
from Fire-Lite for this purpose.
Figure 4-10 Connection of Telephone Lines
4-1453688
Control Panel Installation
4.9Notification Appliance/Auxiliary Power Circuits
The two outputs of the MS-25 can be programmed to be used as NACs or as Aux power.
This section of the manual explains how to install conventional notification appliances and
how these terminals can be used for auxiliary power.
4.9.1Conventional Notification Appliance Circuit
The MS-25 supports Class B (Style Y) configurations for notification appliance applications.
You must use an appliance from the list of compatible appliances in the Appendix A at the
back of this manual. Each circuit can source up to 2.0A. (total current for the system must not
exceed 2.0A)
To install a Class B notification appliance circuit:
1. Wire Class B Notification appliances as shown in Figure 4-11.
2. Configure the circuit through programming.
Figure 4-11 Class B Notification Appliance Circuit Wiring
536884-15
Model MS-25 Installation and Operation Manual
Non-Supervised
Power Limited
+
–
Special
Application
DC Circuit
4.9.2Auxiliary Power Installation
NAC Circuits 1 and 2 on the control panel can be used as auxiliary power circuits. The three
types of auxiliary power available are:
•Door Holder (see section 4.9.2.1)
•Constant (see section 4.9.2.2)
•Resettable Power (see section 4.9.2.3)
Auxiliary power circuits are power limited. Each circuit can source up to 1.0A (total current
for system must not exceed 2.0A).
To install an auxiliary power circuit:
1. Wire the NAC circuit(s) that will be used for auxiliary power . See 3.5 for location of NAC
circuits.
2. Configure the auxiliary power output through programming.
4.9.2.1Door Holder Power
Door holder power is intended for fire door applications. When there are no alarms in the
system and the panel has AC power, door holder circuits have 24 volt power present at their
terminals. Any alarm will cause power to disconnect. Power will be re-applied when the
system is reset. If AC power is off for more than 15 seconds, the auxiliary door holder power
will be disconnected to conserve the battery backup. When AC power is restored, power is
immediately restored to the door holder circuits.
Figure 4-12 Example of an Auxiliary Power For Door Holder
Use a UL listed door holder see list from Appendix A-3, for this application.
4-1653688
Control Panel Installation
4.9.2.2Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is
always present at Constant circuits.
4.9.2.3Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional
4-wire smoke detectors. For circuits selected as Resettable, 24 volt power is always present at
the terminals unless a system reset occurs. If a system reset occurs, power is disconnected
from the terminals for 30 seconds, then re-applied.
536884-17
Model MS-25 Installation and Operation Manual
4.10 On-Board Relays (Conventional, Power Limited)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays
are Form C rated at 2.5 A @ 24 VDC Resistive.
4.10.1 Common Trouble Relay
The control panel has a dedicated Form C trouble relay built into terminals labeled
TROUBLE. The relay provides a normally open and a normally closed contact. The trouble
relay will deactivate under any trouble condition. Form C rated at 2.5 A @ 24 VDC Resistive.
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no alarm or
trouble conditions.
4.10.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals labeled RELAY 1
or RELAY 2. Each relay provides a normally open and a normally closed contact.
To configure one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See 4.10.1 for the location of
the relay terminals.
2. Default programming causes Relay 1 to activate for any supervisory. Relay 2 will activate
for any alarm. For relay applications that require different behavior see Section 6.
4-1853688
Control Panel Installation
4.11 Remote Station Applications
4.11.1 City Box Connection Using the 5220 Module
This section describes how to connect the control panel to a municipal fire alarm box or “city
box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service.
The city (master) box is an enclosure that contains a manually operated transmitter used to
send an alarm to the municipal communication center which houses the central operating part
of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current
accounted for in control panel draw.)
Alarm Current:1 Amp for 1 second
Max Voltage:24 VDC
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-13. This drawing also shows how
to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program NAC1 as auxiliary and power constant on. Program NAC2 as a non-silencing,
constant on notification circuit.
536884-19
Model MS-25 Installation and Operation Manual
Note:
NAC Circuit 2 Used
as an Example.
Either NAC Circuit Can
Be Used.
Supervised for Opens
and Ground faults
only Non-Power
Limited
It is not possible to reset the remote indication until you clear the condition and reset the
control panel.
4-2053688
Figure 4-13 City Box Connection
Control Panel Installation
4.11.2 NFPA 72 Polarity Reversal
4.11.2.1 Alarm, Supervisory and Trouble Reverse Polarity Outputs
Three HFS-MR or CRF-300 modules are required to independently report alarm, supervisory
and trouble. SLC addresses 141, 143, and 147 must be used as shown in Figure 4-14.
Figure 4-14 Reverse Polarity output wiring
536884-21
Model MS-25 Installation and Operation Manual
4-2253688
Section 5
SLC Device Installation
Cautions!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the
control panel while installing or servicing.
5.1List of SLC Devices
The following SLC devices can be used with the control panel. See the device installation
instructions for more information. (packaged with the device)
•A MS-25 system supports a maximum of 25 SLC detectors and modules, in any
combination.
536885-1
Model MS-25 Installation and Operation Manual
5.3Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the
type of device you are installing for details.
5.3.1Wiring SLC in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid
or stranded as long as it meets the National Electric Code 760-121 requirements for power
limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 40 ohms to the farthest SLC device.
Maximum loop length depends on the wire gauge.
All SLC wiring is Supervised, and Power-limited.
The following figures show how length is determined for out and back tap and T-Tap style
wiring.
Figure 5-1 Calculating wire run length for a simple out and back
536885-3
Model MS-25 Installation and Operation Manual
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet.
This requirement must be met in addition to the maximum distance requirements for the
various wire gauges.
Figure 5-2 Calculating Wire Run Length for a T-tap
5-453688
SLC Device Installation
Supervised
Power limited
5.4Wiring SLC Detectors
This section describes how to install heat and smoke detectors. All detectors ship with
installation instructions. Refer to the detector’s installation instructions for more detailed
information.
2. Set the address for each device as described in Section 5.5.
Figure 5-3 Heat and Smoke Detector Connection to the Panel.
536885-5
Model MS-25 Installation and Operation Manual
All dials labeled for ONES
or TENS position
Example 1: Device Set to 35
Example 2: Device set to 105
5.5Addressing SLC Devices
All SLC devices are addressed using the two rotary dials that appear on the device board. Use
the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS
rotary dial to set the tens place in a two digit number.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary
dial to 3 as shown in Figure 5-4.
Example 2: T o select device address 105, turn the ONES rotary dial to 5 and the TENS rotary
dial to 10 as show in Figure 5-4.
Figure 5-4 SLC Device Addressing Using Rotary Dials
5-653688
Section 6
Programming
This section of the manual describes how to change the control panel programming options
from the built-in web page of the control panel. All options described in this section are edited
via the panel’s built in web page
Important!
Before any customized programming is done, JumpStart should be run first. After JumpStart
is run, thoroughly test the system. The reason the system should be tested after JumpStart is
because JumpStart automatically programs the system, searching for and configuring all
SLC devices and SBUS annunciators it finds. JumpStart allows you to confirm the integrity
of the installation prior to performing any custom programming. After determining that the
hardware is properly installed, custom programming can be performed. Refer to Section 6.
6.1UL 864 Programming Requirements
Table 6-1: Standards in Requirements for Control Units and Accessories
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming OptionMenu Item
System OptionsLow AC Report DelayYes0–30 hours1–3
Zone OptionsSupervisoryYesLatching/NonLatching
Zone OptionsWaterflowYesLatching/NonLatching
System OptionsAlarm VerificationYes1-250 seconds60-250 seconds
Dialer Phone line Programming
option
Line Monitor EnabledYesY/NY*
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings Permitted in
UL 864
*Only needs to be enabled if using the DACT.
536886-1
Model MS-25 Installation and Operation Manual
6.2Control Panel Programming
The MS-25 is an addressable control panel that has the characteristics of a 5 zone
conventional fire alarm control panel.
6.3Default Control Panel Configuration.
The panel ships from the factory in a defaulted configuration that may allow the installer to
use the panel without doing any custom programming.
6.3.1Default Mapping of SLC Inputs to Outputs
The panel mapping configuration for the MS-25 is fixed with regards to SLC addresses, zone
assignments and output points. The relationship between input points and output points
follows the rules defined in 6.3.2 below. For input points, the SLC address determines the
zone assignment and alarm characteristics. For output points, the SLC address determines the
output function for the point.
Table 6-2 shows that any input SLC device with an address set within the range 1-15 will be
assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111
or 112 will activate for an alarm in zone 1.
6.3.3Default Mapping for the 2 built-in Notification
Circuits.
There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to
activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the
System Sensor synchronization pattern. To change the behavior of the default mapping of
these circuits refer to Section 6.5.
536886-3
Model MS-25 Installation and Operation Manual
6.3.4Maximum SLC address point count
The MS-25 control panel supports a maximum of 25 SLC points to be used within the 159
point address range. The points can be all inputs, all outputs or any combination of inputs and
output points. When more than 25 SLC devices are added to the control panel, any excess
points will indicate a trouble and not be recognized by the panel.
6.3.5Installer Code
The installer code is factory programmed as 123456. The installer code is required to learn
and remember which SLC devices are connected to the panel. The installer code can be
changed when a PC is used to modify the default programming options.
6.4JumpStart Auto Programming
Once the physical installation of SLC devices is finished, the panel will need to learn which
SLC devices and SBUS annunciators are present.
IMPORTANT!
There is no limit to how often you can run JumpStart. Each time you run this
process it starts fresh and does not remember previously installed devices
that are no longer present.
To run JumpStart:
1. Press and hold the “JumpStart” key,
2. Press the installer code after PIN is displayed.
3. During JumpStart, the panel will briefly light up all LEDs and then display “SLC Prg” on
the 7 segment display.
4. When complete the display will be off and programming is complete.
If changes are required that affect address settings for the SLC devices, device types or
number of SLC devices installed you will need to repeat JumpStart to re-learn which devices
are supposed to be present on the system.
6-453688
Programming
6.5Modifying Panel Programming using a PC
6.5.1Connecting the panel to a PC
Modifications to the default panel programming can only be done using the embedded web
server of the control panel. There are two ways to connect to the panel for the purpose of
programming. It can be connected through a DHCP (Dynamic Host Configuration Protocol)
router or it can also be plugged in using a Standard CAT5e Ethernet cable without a router.
Both methods of connecting the panel to the PC are for local connection only.
By default, the panel is configured to search for a DHCP server. If there is a DHCP server
present, the panel receives the IP configuration offered by the DHCP server and displays the
IP address on the seven segment display.
If the panel is connected to a PC without a router, it assigns itself a default class B IP address
of the format (169.254.X.X). Each panel will have a unique IP address and it will also be
displayed on the 7 segment display. When direct connected, it will normally take about 40
seconds to display the IP address. The panel displays “IP” while the IP address is being
determined during this 40 second search period.
A PC with the Windows operating system may take up to 1 minute to fallback to the APIPA
(Automatic Private IP Addressing) which enables the PC to communicate to the panel.
Whether using either the PC direct connect or the PC connected to the panel via DHCP router,
you are ready to view and edit the panel programming options once the panel shows the IP
address on the seven segment display.
The embedded web page programming tool is accessed by typing in the panel IP address in a
web browser . MS Internet explorer 6 and Mozilla Firefox 3.0.5 are the only two web browsers
tested and recommended.
536886-5
Model MS-25 Installation and Operation Manual
6.6Panel Programming Options
All customized programming options for the MS-25 control panel are described in this section
and are available to be edited using the embedded web server of the control panel.
6.6.1System Options
6.6.1.1Synchronized Strobes Active When Horns Silenced
The default configuration for this option is No. If set to Yes, strobes will remain on when
horns are silenced until a panel reset is issued.
6.6.1.2Silence/Reset Inhibit Enabled
The default configuration for this option is NO. If set to Yes, Pressing either Reset or Silence
Buttons will be ignored for the duration of the delay (set to 30 seconds). The inhibit feature
delay is only active for the first alarm/supervisory signal.
6.6.1.3Water Flow Delay
The water flow delay is a debounce time that is generally used to help reduce false alarms
during brief periods of water pressure fluctuation in a water riser. The default setting is 1
second which is the minimum debounce time. You can set the water flow delay within the
range 1-90 seconds.
6.6.1.4Installer Code (User ID)
This is the password used to lock the list of SLC devices found during the JumpStart auto
learn process. It is defaulted to 123456 and can be changed to any 4 to 8 digit number .
6.6.1.5Alarm Verification Time
Alarm verification is an optional false alarm prevention feature for smoke detectors that
verifies an alarm condition by resetting the smoke detector . The alarm verification time can be
set within the range of 1-250 seconds. For UL 864 installations this option must be greater
than 59 seconds. The default setting is 60 seconds.
6.6.1.6Auto Test
Enter the hour/minutes (in 24 hour format) that you desire the control panel to send the
automatic test report.
6.6.1.7Low AC Report Delay
This option determines the number of delay hours before a loss of AC is reported to the
central station. It is defaulted to 3 hours and must be within the range 0-30 hours. For U.L.
864 installation this option must be set within the range 1-3 hours.
6-653688
Programming
6.6.1.8Walk Test Reporting
The default configuration for this option is No. If set to Yes, the panel generates a TEST report
to the central station when the walk test begins. During a walk test, the panel’s normal fire
alarm function is completely disabled, placing the panel in a local trouble condition. All zones
respond as 1-Count zones (respond when a single detector is in alarm) during a walk test.
Each alarm initiated during the walk test will be reported.
6.6.1.9Walk Test duration
Enter the amount of time, in minutes, for the walk test duration. When the programmed
amount of time expires, the Walk Test will end automatically.
6.6.1.10 Walk Test NAC Time out
Enter the amount of time, in seconds, for the walk test NAC active duration. During a walk
test alarm activation, the NACs will automatically deactivate after the programmed amount of
time expires.
6.6.1.11 Clock Source
The panel’s AC line frequency is selectable for 60 Hz, 50 Hz, or Internal Clock Source. AC
frequency feature dictates how the control panel will calculate time based on the AC line
frequency used in the installation site. The “Internal Clock” option can be used in areas where
the AC line frequency is not dependable and you want the panel to calculate time from the
internal crystal. The internal crystal is not as accurate as the AC power source. The panel
defaults to the 60 HZ selection.
6.6.1.12 Auto Daylight Savings Time
Select this feature to “Yes” if you want the panel to automatically adjust the clock to track
with daylight savings time.
6.6.1.13 Remote Annunciator
Select this feature to “Yes” if a ANN-80 Remote Annunciator is to be used. A customized
banner can also be added to the Remote Annunciator . The Remote Annunciator allows for the
top 2 lines to be programmed as a custom banner.
536886-7
Model MS-25 Installation and Operation Manual
6.6.2Zone Programming
6.6.2.1SLC Addresses Within Each Zone
Each zone has 15 alarm SLC addresses and 5 supervisory SLC addresses assigned to it as
described in table 6.1. For each SLC address within a zone, the SLC device type choices are
Unused, Detector, Manual Pull Switch, Latching Water Flow Switch or Non-Latching Water
Flow Switch. The default setting is that all points are unused.
6.6.2.2Zone Silenceable
When an alarm occurs within a zone, there is a programming option that allows the outputs to
be silenceable or not. If you want the SILENCE key to be able to silence outputs triggered by
active alarms within the zone select YES for this option. The default setting is Yes.
6.6.2.3Zone Type
A zone can be either a one count zone or an alarm verification zone. The default setting is one
count. A one count zone has an immediate alarm when a single detector goes into alarm.
Alarm verification is an optional false alarm prevention feature for smoke detectors that
verifies an alarm condition by resetting the smoke detector. If the alarm condition still exists
by the time the reset cycle has completed, the detector will go into alarm. If the detector is no
longer in alarm, the initial alarm is ignored. The alarm verification sequence for a detector
does not occur if the zone is already in alarm.
6.6.3Output Point Programming
For each output SLC address you can select that a device is present or unused. The default
setting for all output points is unused.
The two notification circuits are both defaulted to activate th e System Sensor synchronization
pattern when any of the five zones are in alarm. You can define each of the notification
circuits to be either a conventional notification circuit or an auxiliary power type circuit.
6.6.4.2Conventional Notification Circuit Mapping
When defined as a conventional notification circuit, the circuit can be configured to activate
for any combination of zone alarms and/or supervisories. Select all the categories you wish to
have the circuit activate under.
Conventional Notification Circuit Cadence Pattern
When a conventional notification circuit activates, it can be configured to produce one of six
output patterns.
1. Constant On - 24V DC power
2. ANSI - ANSI temporal pattern
3. AMSECO Sync - Strobe synchronization for AMSECO appliances
4. Gentex Sync - Strobe synchronization for Gentex appliances
5. System Sensor Sync - Strobe synchronization for System Sensor appliances
6. Wheelock Sync - Strobe synchronization for Wheelock appliances
Auxiliary Power Options
Each of the notification circuits can be configured as an auxiliary power circuit in one of three
options.
1. Constant - Always on, 24V DC power.
2. Door Holder - 24V DC when in standby, Off if any alarm device activates, or loss of AC
power.
3. Resettable - 24V DC except for 30 seconds off during panel reset.
536886-9
Model MS-25 Installation and Operation Manual
6.6.5Relay Programming Options
The two on board relays of the control panel can be selected to activate for general alarm,
general supervisory, resettable auxiliary power or door holder power. Relay 1 is defaulted to
activate for general supervisory. Relay 2 is defaulted to activate for general alarm.
6.6.5.1General System Relay Silence Option
This option defaults to silenceable. This option controls the silencing behavior for Relay 1,
Relay 2 and the general output relays at SLC addresses 141 through 148.
6.6.6Dialer Phone Line Programming Options
The programming options below are available for each of the two phone lines.
6.6.6.1Line Prefix
This option allows the insertion of digits, delays and special tone characters to be dialed
before the phone number stored in the account option is dialed. The default setting is to not
have any prefix.
6.6.6.2Dial Tone Detection
The default configuration for this option is “Enabled”. If set to “Disabled”, the dialer will not
check for the presence of dial tone on the associated phone line prior to making a call.
6.6.6.3Line Monitoring Enabled (Y/N)
This option is used to enable phone line voltage supervision. It defaults to No.
6.6.6.4Dialing Option
The dialer can use touch tone or pulse dialing when calling the central station. The options for
dialing are touch tone only, dial pulse only or alternating touch tone/dial pulse when multiple
attempts are used to connect with the central station. The default setting is touch tone only.
6.6.6.5Pulse Dialing Format
There are two duty cycle options for the pulse dialing. US format is 60/40. European format is
66/34. The default setting is the US format.
6-1053688
Programming
6.6.7Dialer Account programming Options
Up to two accounts can be used for reporting events to the central station. A typical reason to
use multiple reporting accounts might be to have one account for reporting alarms and a
different account for reporting supervisories and troubles. The programming options for each
account are described below.
6.6.7.1Account Number
Up to six digits allowed for SIA formats or up to four digits for contact ID format. Default
account numbers are blank.
6.6.7.2Phone Number
Enter the phone number to call the central station. Default setting is blank.
The following special characters are available:
Table 6-4: Special Dialing Characters
#Pound (or number) key on the telephone
*Star key on the telephone
,Comma (character for 2-second pause)
6.6.7.3Reporting Format
Choose SIA8 (up to 8 events per call), SIA20 (up to 20 events per call) or contact ID reporting
format. Default setting is contact ID.
6.6.7.4Reporting Filters
Selecting the Must option forces the event type to be reported to the account even if it was
already reported to another account. Selecting the Yes option will insure that the event type
gets to at least one account. Selecting the No option means that the event type will not be
reported to this account. The default setting is No.
Selecting No for all report filters in both accounts effectively disables the dialer.
536886-11
Model MS-25 Installation and Operation Manual
6-1253688
Section 7
System Operation
The operation of the MS-25 control panel is similar to a conventional 5 zone Fire Alarm
Control Panel. System status and control is segmented into zones even though the panel
supports addressable SLC devices for input and output functions.
7.1System Reset
To reset the system press the RESET key once. All LEDs will light while the system is being
reset. Alarms and Supervisories that were latched will be reset to their normal state. Outputs
that had been activated by any Alarms and Supervisories will be deactivated.
7.2Lamp Test
For Lamp test in accordance with ULC-527-99, see MS-25 Basic Operating Instructions.
7.3System Silence
To Silence the PZT and all silenceable outputs that are active, press the SILENCE key once.
Any silenceable trouble, supervisory or alarm that is silenced will automatically unsilence if left
silenced for 24 hours or if a new trouble, supervisory or alarm event occurs.
7.4Acknowledge
Use the ACK key to acknowledge alarm, supervisory and trouble events.
7.5Viewing Active Alarm Points
When one or more SLC points within a zone are in alarm, the alarm LED for that zone will
blink and outputs will activate that are mapped to alarms within the zone. To display the SLC
address of an input point that is in alarm, press the ALARM ID key once and use the PREV
(previous) or NEXT key to scroll through the alarm points. All points that are in alarm spanning
all zones on the control panel will be displayed when using the scroll keys.
536887-1
Model MS-25 Installation and Operation Manual
7.6Viewing Active Supervisory Points
When one or more SLC points within a zone are in supervisory alarm, the supervisory LED
for that zone will blink and outputs will activate that are mapped to supervisories within the
zone. To display the SLC address of an input point that is in supervisory, press the SUPERVS
ID key once and use the PREV (previous) or NEXT key to scroll through the supervisory
points. All points that are in supervisory spanning all zones on the control panel will be
displayed when using the scroll keys.
7.7Viewing Active Trouble Points
When one or more SLC points within a zone are in trouble, the trouble LED for that zone will
blink and outputs will activate that are mapped to troubles within the zone. T o display the SLC
address of an input point that is in trouble, press the TROUBLE ID key once and use the
PREV (previous) or NEXT key to scroll through the trouble points. All addressable points that
are in trouble throughout the control panel will be displayed when using the scroll keys.
Note: If there are any system level troubles active, the LED corresponding to the system level trouble will blink
also. However, system level troubles are not displayed on the 7 segment display after using the TROUBLE
ID key and the PREV or NEXT to scroll addressable troubles. Only point troubles are displayed.
7.8Walk Test
Walk test is enabled by holding the WALK TEST key until the PZT stops. This takes about 5
seconds. Once in walk test the 7 segment display will show that the walk test is active. During
walk test, inputs can be activated and the outputs that are mapped to the input will be activated
for 3 seconds. The input will automatically be reset when the outputs are deactivated.
The exit walk test, hold the WALK TEST key until the PZT stops. The panel is now in normal
standby mode.
7.9Fire Drill
A fire drill is activated by holding the DRILL key until the 7 segment display shows drl on.
All outputs will be active. To stop the fire drill, press the RESET key. If the reset key is not
pressed within 10 minutes, the fire drill will automatically reset.
7-253688
System Operation
7.10 Zone Disable Feature
T o disable a zone, press the disable zone key that corresponds to the zone number you wish to
disable. When a zone is disabled all alarm events that occur while the zone is disabled will be
ignored. Zones that are disabled will be in trouble. The PZT will sound the trouble cadence.
The trouble LED for the specific zone along with the general trouble LED will blink
indicating that the zone is in trouble. If the silence key is pressed after a zone is disabled, the
trouble LEDs will be continuously on and the PZT will silence.
To enable a zone which had been previously disabled, press the disable zone key that
corresponds to the zone number you wish to enable. Each pressing of the zone disable key will
toggle the disable/enable state for the zone.
Note: Followed by the Installers code in ULC installations. See Basic Operating Instructions.
7.11 Disabling Notification Circuits
There are 2 notification circuits on the MS-25 control panel (NAC1 and NAC2). You can
disable them individually by pressing the NAC1 or NAC2 disable keys. A disabled
notification circuit will cause a trouble on the circuit. The PZT will sound the trouble cadence.
The trouble LED for the circuit along with the general trouble LED will blink indicating
trouble. If the silence key is pressed, the trouble LEDs will be continuously on and the PZT
will silence.
Pressing the NAC disable key when the circuit is already disabled will enable the circuit. Each
pressing of a NAC disable key will toggle the disable/enable state for the circuit.
7.12 Loss of AC power
When AC is present and above the brown out threshold, the AC LED will be on continuously .
When AC power is off or below the brown out threshold, the AC LED will blink. The
GENERAL TROUBLE LED will blink also. The trouble relay will activate for loss of AC
once the reporting delay for reporting loss of AC power has been reached. The default setting
for this delay is 3 hours. If the silence key is pressed, the trouble LEDs will be continuously
on and the PZT will silence.
7.13 Remote Connection Feature (ULC Installations
Only)
T o disconnect the communication paths to the Central S tation and/or remote stations, press the
walk test button and the Acknowledge button at the same time. The PZT on the panel will
sound and the General Trouble LED will be flashing. This feature will remain active until you
press the Walk Test and Acknowledge buttons again.
536887-3
Model MS-25 Installation and Operation Manual
7.14 Low Battery
The battery voltage is continuously monitored during normal standby . When the battery is not
present or the voltage is too low , the control panel will indicate a low battery trouble. Both the
LOW BATTERY and GENERAL TROUBLE LED will blink when there is a low battery
condition. The PZT will also sound the trouble cadence. If the silence key is pressed, the
trouble LEDs will be continuously on and the PZT will silence.
7.15 Ground Fault
The control panel monitors the SLC and notification circuits for wiring shorts to earth ground.
If any wire from these circuits is connected to earth ground the control panel will indicate a
ground fault by blinking both the GROUND FAULT and GENERAL TROUBLE LED. The
PZT will also sound the trouble cadence. If the silence key is pressed, the trouble LEDs will
be continuously on and the PZT will silence.
7.16 Phone Line Monitoring
The control panel monitors the phone line voltage at TELCO1 and TELCO2 when line
monitoring is enabled (see programming section 6.5.6.3). When line monitoring is enabled
and there is not sufficient voltage at TELCO1 or TELCO2, the 7 segment display will indicate
“Ln1” and/or “Ln2” for phone line 1 and phone line 2 troubles.
7.17 Reporting Account Monitoring
When the control panel is configured to use the dialer, the reporting accounts will indicate
trouble if the panel has failed to communicate to the central station after 10 attempts. Account
1 trouble is indicated on the 7 segment display as “AC1”. Account 2 trouble is indicated on
the 7 segment display as “AC2”. Once the communication path to the central station is
restored, the account troubles will self restore.
7.18 SLC Fault
In the event that the SLC circuit is shorted or drawing too much current, the panel will
indicate this by displaying “SLC err” on the 7 segment display. Remove the fault and the
trouble will self restore.
7.19 Dialer Error
In the event that the dialer microprocessor is unable to communicate with the main
microprocessor the panel will indicate this by displaying “dlr” on the 7 segment display . If this
trouble is ever displayed, the panel needs to be returned to the factory for repair.
7-453688
System Operation
7.20 Annunciator Description
Operation of the Remote Annunciator is simple. This section of the manual is an overview of
the operation of the Remote Annunciator. Please read this entire section carefully before
operating the Remote Annunciator. Figure 7-1 shows the Remote Annunciator.
Figure 7-1 ANN-80 Remote Annunciator
7.20.1 LCD Displays
The Remote Annunciator's LCD displays system messages, annunciates alarms, supervisories
and troubles; provides status information; and prompts for input. These messages can be up to
80 characters, displaying over four lines of 20 characters each. Annunciator keys beep when
they are pressed.
536887-5
Model MS-25 Installation and Operation Manual
Text of Internal Banner
Custom Banner example
7.20.2 Banner
The banner is the message that displays on the Annunciator when the system is in normal
mode (no alarm, trouble or supervisory condition exists). You can create a customized
message that will display instead of the internal (default) message. See 6.6.1.13 for
information on customizing the banner.
Figure 7-2 Banner Display Examples
7-653688
System Operation
7.21 Basic Operation
7.21.1 Conduct a Fire Drill
1. Activate the key by turning it to the ON position.
2. Press and hold the Drill key for 2 seconds.
3. The drill will begin after the key has been held down for 2 seconds.
4. Press the Reset key to end the Fire Drill. (If you do not press the Reset Key to end the Fire
Drill manually, it will time out automatically after 10 minutes).
7.21.2 Conduct an Indicator Test
The indicator test checks the annunciator LEDs, PZT, and LCD display.
1. Activate the key by turning it to the ON position.
2. Press the Reset Key to conduct an indicator test. The system turns on all LEDs for several
seconds, beeps the PZT, and displays a message on the LCD display. A problem is
indicated if any of the following occurs:
•An LED does not turn on.
•You do not hear the beep.
•The LCD is unable to annunciate the message correctly.
7.21.3 Silence alarms or troubles
1. Activate the key by turning it to the ON position.
2. Press the Silence Key.
Note: Alarm and trouble signals that have been silenced but the detector remains un-restored and will un-silence
every 24 hours until it is restored.
7.21.4 Reset alarms
1. Activate the key by turning it to the ON position.
2. Press the Reset key.
7.21.5 View Alarms or Troubles
When the system is in alarm or trouble, you can press the Down key to view the location of an
alarm or trouble. The Point ID, and time stamp of when the condition occurred will also be
displayed.
536887-7
Model MS-25 Installation and Operation Manual
7.22 Operation Mode Behavior
The remote annunciator can be in one of six conditions at any given moment: Normal, Alarm,
Supervisory, Trouble, Silenced, and Reset. Table 7-1 describes the behavior of the Remote
Annuciator in each of these modes.
Table 7-1: Operation Modes of Remote Annunciator
Operation
Mode
NormalNo alarm or
AlarmA smoke
SupervisoryThe system
Occurs WhenSystem BehaviorIn This Mode You Can
trouble condition
exists.
detector goes
into alarm or a
pull station is
activated.
detects a
supervisory
condition.
AC POWER LED is on.
The All Systems Normal display indicates
that the system is in normal mode.
The current date and time display on the
last line of the LCD.
The dialer seizes control of the phone line
and calls the central station.
The Remote Annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).
ALARM LED flashes.
The LCD displays a screen similar to this
one.
The dialer seizes control of the phone line
and calls the central station.
The Remote Annunciator sounds a loud,
pulsing beep in the sequence one second
on, one second off.
SUPERVISORY LED flashes.
The LCD displays a screen similar to this
one.
The LCD displays a screen similar to this
one.
Press the down arrow to view the alarm. A screen
similar to this one displays.
Activate the key by turning it to the ON position
then press the Silence key to silence the Remote
Annunciator (and any notification devices attached
to the system).
When the alarm condition clears, activate the key
and press Reset to restore the panel to normal.
Press down arrow to view the supervisory condition.
A screen similar to this one displays.
Activate the key by turning it to the ON position
then press the Silence key to silence the Remote
Annunciator.
Once the supervisory condition has been corrected,
the system will restore itself automatically.
7-853688
Table 7-1: Operation Modes of Remote Annunciator
System Operation
Operation
Mode
TroubleA system trouble
Reset
SilencedAn alarm or
Occurs WhenSystem BehaviorIn This Mode You Can
condition occurs.
The
button is pressed
while the key is
activated.
trouble condition
has been silenced
but still exists.
To silence alarms
and troubles,
The dialer seizes control of the phone line
and calls the central station.
The remote annunciator sounds a loud,
pulsing beep in the sequence one second
on, nine seconds off.
TROUBLE LED flashes.
The LCD displays a screen similar to this
one.
All LEDs are on briefly then the LCD
displays “RESET IN PROGRESS”. If the
reset process completes normally, the date
and time normal mode screen displays.
SILENCE LED is on. TROUBLE,
SUPERVISORY or GENERAL ALARM
LED (depending on condition) is on. The
annunciator (and any notification devices
attached to the system) will be silenced.
Press down arrow to view the trouble. A screen
similar to this one displays.
Activate the key by turning it to the ON position
then press the Silence key to silence the Remote
Annunciator.
Once the trouble condition has been fixed, the
system will restore itself automatically.
Press down arrow to view the location of the alarm
or trouble. When the condition no longer exists, the
SYSTEM SILENCED and SYSTEM TROUBLE
LED, SUPERVISORY or GENERAL ALARM
LEDs turn off.
press
while the key is
activated.
536887-9
Model MS-25 Installation and Operation Manual
7-1053688
Section 8
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes
sent by the control panel for SIA and Contact ID formats.
8.1Receivers Compatible with the Control Panel
Table 8-1 shows receivers compatible with the control panel.
Table 8-1: Receivers Compatible with the Control Panel
ManufacturerModelFormat
Silent KnightModel 9800SIA and Contact ID
Model 9000 (SIA formats)SIA
AdemcoModel MX8000 (Contact ID)Contact ID
Sur-GardSG-MLR2-DG (V. 1.64 or higher)SIA and Contact ID
Osborne HoffmanQuickalertSIA and Contact ID
8.2Reporting Formats Dialer Outputs
SIA Reporting FormatContact ID Reporting Format
Event Description
System Events
AC power restoreTrouble System EventAR330100000
AC power lostTrouble System EventAT130100000
Short circuit removed from SLC communication loop
Short circuit detected on SLC communication loop
Fire drill has begunTestSystem EventFI160400000
Fire drill endedT estSystem EventFK360400000
Panel date has been changedTrouble System EventJD162500000
Event
Family
System events are reported when either “Report by Zone” is selected.
Trouble System EventER33333200Exp. ID
Trouble System EventET33133200Exp. ID
Event Class
(System, Zone,
or Point)
Module
ID #
(if any)
SIA
Event
Code
Parameter
(if any)
Qualifier
Event
Code
Group#Contact
#
Panel time has been changedTrouble System EventJT162500000
Local programming beginTrouble System EventLB162700000
536888-1
Model MS-25 Installation and Operation Manual
Phone line 1 trouble restoreTrouble System EventLR1335100001
Phone line 2 trouble restoreTrouble System EventLR2335200002
Phone line 1 trouble detectedTrouble System EventLT1135100001
Phone line 2 trouble detectedTrouble System EventLT2135200002
Periodic test event – normalTestSystem EventRP160200000
Periodic test event – off normalTestSystem EventRY160800000
Initial power upTrouble System EventRR130500000
Unable to report to an accountTrouble System EventRTAcct #1354Acct #Acct #
User has initiated dialer testTestSystem EventRX160100
Walk test endTestSystem EventTE360700000
Walk test beginTestSystem EventTS160700000
Auto dialer test communication troubleTrouble System EventYCLine #135000Line #
Report to an account successfulTrouble System EventYKAcct #3354Acct #Acct #
Auto dialer test communication trouble
restore
Ground fault condition detectedTrouble System EventYP34131000Exp. ID
Ground fault condition restoreTrouble System EventYQ34331000Exp. ID
Battery voltage restoreTrouble System EventYR34330200Exp. ID
Battery voltage lowTrouble System EventYT34130200Exp. ID
This section of the manual offers suggestions for troubleshooting hardware problems. Please read
this section if you encounter a problem when installing the control panel. If these suggestions do
not solve your problem or if you encounter a problem that is not listed here, contact FireLite
Technical Support for assistance.
9.1.1JumpStart
Jumpstart will learn all of the SLC devices and SBUS annunciators attached to the system. Do a
JumpStart first and any customization second.
1. Press and hold the JumpStart key until “PIN” is displayed.
2. Enter the installers code on the 10 digit keypad.
3. “SLC” “Prg” will be displayed until the JumpStart is complete.
9.1.2View Active Points
View Active Points (alarm, non-system trouble, and supervisory conditions).
Press the corresponding ID key (e.g. Alarm ID).
Use Prev and Next to view more active points of that type.
9.1.3Disable Or Re-Enable A Zone
1. Press the Zone x Disable button on the keypad.
2. The PZT will sound a trouble.
Can be silenced by pressing Signal Silence (ALL points in that zone are affected).
9.1.4Silence the Board PZT
Press ACK
9.1.5Silence the Notification Appliances
1. Press SIGNAL SILENCE
2. If Silence/Reset Inhibit Enabled is selected in programming, that button and the SYSTEM
RESET button are ignored for the first 30 seconds of the first alarm or supervisory signal.
536889-1
Model MS-25 Installation and Operation Manual
9.1.6To Initiate a Fire Drill
1. Press Drill until “DRL” is displayed.
2. Press SYSTEM RESET to end the drill.
9.1.7For a Dialer Test
Press JumpStart and Next at the same time.
9.1.8For a Lamp Test
Press JumpStart and Prev at the same time.
9.1.9AC LED
The AC LED will blink for the loss of AC and the Trouble Relay will activate after the
programmed delay time (default = 3 hours).
9.1.10 Walk Test
1. Press and hold Walk Test for about 5 seconds to start a walk test.
2. Press SYSTEM RESET to end the test.
9.1.11 Seven Segment Display
On the 7 segment display:
“AC1” indicates dialer account 1 failed to report
“AC2” indicates dialer account 2 failed to report
“drl” indicates a problem with the dialer. The panel must be returned to the factory for repair
“drL” indicates a fire drill is taking place
“Ln1” indicates low/no voltage on phone line 1
“Ln2” indicates low/no voltage on phone line 2
“CE1” indicates Autotest Comm Error Line 1
“CE2” indicates Autotest Comm Error Line 2
“SLC err” indicates an over current condition on the SLC loop
“bAt” indicates battery trouble
“rA1” indicates remote annunciator 1 trouble
“rA2” indicates remote annunciator 2 trouble
“gnd” indicates ground fault trouble
9-253688
Trouble Shooting and Quick Tips
“AC” indicates AC power supply trouble
“nC1” indicates notification appliance circuit 1 trouble
“nC2” indicates notification appliance circuit 2 trouble
“tSt” indicates a trouble for the duration of a walk test
Correct the fault and the trouble will restore
9.2Web Server Menus
The System Summary and Mapping Table sections are not editable, but are populated based
on the entries in the other sections.
9.2.1To add a smoke detector:
Which zone will it be in? (e.g. the Lunchroom, Zone 2)
1. Click on Zone Programming, under Zone 2
2. Click Alarm Points
3. Find an Unused SLC Address and click on the detector type (e.g. address 24 Photo)
4. Click Accept
Note: Remember to choose to Download to Panel after all of your changes are done AND set the rotary switches
on the back of the smoke detector. (e.g. tens=2 and ones=4)
9.2.2To add a notification appliance (fire bell)
1. Click on NAC Programming
2. Click on the NAC circuit you want to activate (e.g. NAC 1)
3. Click to check the box for either Alarm and/or Supervisory events to cause that NAC to
activate.
9.2.3To add a Remote Annunciator (DIP switch address 1
or 2)
1. Click on System Options
2. Click on yes option for Remote Annunciator Installed 1/ Remote Annunciator Installed 2.
3. Click Accept
Note: Remember to choose to Download to Panel after all of your changes are done.
536889-3
Model MS-25 Installation and Operation Manual
9.2.4To add custom Zone name
1. Click on Zone Programming
2. Click on Zone Options. Enter custom Zone name (20 characters max) in the corresponding
field.
3. Click Accept
Note: Remember to choose to Download to Panel after all of your changes are done.
9.2.5To trip an SLC notification appliance
1. Click on Output Point Programming
2. Click on the tab for the event type you want to activate the notification appliance.
3. Click the circle for Present across from one or both of the SLC device(s) addresses for the
Zone which has the initiation devices that you want to trip the appliance.
Note: Be sure to set your SLC notification device address to match.
9.2.6To trip a Door Holder
1. Click on Output Point Programming
2. Click on the System tab
3. Click on the circle for Present across from the SLC Address of the door holder. (e.g. 158)
4. Set the Door Holder device address accordingly. (e.g. 158)
The Door Holder will provide 24VDC when in standby, 0V during alarms or loss of AC.
An on board relay can also be used for Door Holder power. See Section 6.6.5.
Help to reduce false alarms
In the System Options section, Water Flow Delay can be adjusted to account for brief periods
of water pressure fluctuation.
Alarm Verification Time verifies an alarm condition by resetting the smoke detectors before
activating alarms (UL 864 installations must not exceed 60 seconds).
9-453688
Appendix A
Compatible Devices
A.1Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL
resistor on each loop. All supervised notification appliances used with the control panel must
be polarized.
Note:Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen
will work with this feature. This control is UL listed for panel wide Synchronization.
Table A-1 below lists notification appliances compatible with the fire alarm control panel.
Appliances which can be synchronized indicate the type of SYNC available in the columns
marked Audio and/or Visual.
CHRChime
CHWChime
CHSR2-Wire Chime/Strobe
CHSW2-Wire Chime/Strobe
HRHorn
HWHorn
HRKHorn
P2R2-Wire Horn/Strobe
P2R-P2-Wire Horn/Stro be
PC2R2-Wire Horn/Strobe
PC2R-P2-Wire Horn/Strobe
P2RH2-Wire Horn/Strobe High Candela
P2RH-P2-Wire Horn/Strobe High Candela
PC2RH2-Wire Horn/Strobe High Candela
PC2RH-P2-Wire Horn/Strobe High Candela
System Sensor
P2W2-Wire Horn/Strobe
P2W-P2-Wire Horn/Strobe
PC2W2-Wire Horn/Strobe
PC2W-P2-Wire Horn/Strobe
P2WH2-Wire Horn/Strobe High Candela
P2WH-P2-Wire Horn/Strobe High Candela
PC2WH2-Wire Horn/S trobe High Candela
PC2WH-P2-Wire Horn/Strobe High Candela
P2RK2-Wire Horn/Strobe
PC2RK2-Wire Horn/Strobe
P2RHK2-Wire Horn/Strobe High Candela
PC2RHK2-Wire Horn/Strobe High Candela
P4R4-Wire Horn/Strobe
PC4R4-Wire Horn/Strobe
P4RH4-Wire Horn/Strobe High Candela
P4W4-Wire Horn/Strobe
536883
Model MS-25 Installation and Operation Manual
ManufacturerModelAudioVisualType
PC4W4-Wire Horn/Strobe
P4WH4-Wire Horn/Strobe High Candela
PC4WH4-Wire Horn/S trobe High Candela
P4RK4-Wire Horn/Strobe
PC4RK4-Wire Horn/Strobe
P4RHK4-Wire Horn/Strobe High Candela
PC4RHK4-Wire Horn/Strobe High Candela
PC4RH4-Wire Horn/Strobe High Candela
SRStrobe
SR-PStrobe
SCRStrobe
SCR-PStrobe
SRHStrobe High Candela
System Sensor
SRH-PStrobe High Candela
SCRHStrobe High Candela
SCRH-PStrobe High Candela
SWStrobe
SW-PStrobe
SCWStrobe
SCW-PStrobe
SWHStrobe High Candela
SWH-PStrobe High Candela
SCWHStrobe High Candela
SCWH-PStrobe High Candela
SRKStrobe
SCRKStrobe
SRHKStrobe High Candela
SCRHKStrobe High Candela
RSSWP-24MCWHStrobe Weatherproof
ZRS-MCWHStrobe
ZRS-24MCCStrobe
ZRS-24MCCHStrobe
MB-G6-24 Motor Bell
MB-G10-24 Motor Bell
MB-G6-12 Motor Bell
MB-G10-12 Motor Bell
MIZ-24-R Mini-Horn
MT-12/24-R Multitone Horn
MT4-12/24 Multitone Horn
ZRS-MCWStrobe
MTWPR-24MCCHMultitone Horn Strobe
NH-12/24RHorn
HSRHorn/Strobe
HSWHorn/Strobe
STRStrobe
STWStrobe
HNRHorn
HNWHorn
System Sensor B112LPBase0.1236
System Sensor B114LPBase**
System Sensor B404BBase**
System Sensor DH100ACDCPhotoelectric0.150.70
System Sensor DH100ACDCLPPhotoelectric0.150.70
System Sensor DH100ACDCLWPPhotoelectric0.150.70
System Sensor DH400ACDCI
System Sensor DH400ACDCP
System Sensor 1112/24/DIonization0.0550
System Sensor 1424Ionization0.1041
System Sensor 1451 (w/B402B Base)Ionization0.1039
System Sensor 2112/24ATRPhotoelectric0.5060/70
System Sensor 2112/24AITRPhotoelectric0.5060/70
System Sensor 2112/24/DPhotoelectric0.0550
System Sensor 2112/24RPhotoelectric0.5060/70
System Sensor 2112/24TRPhotoelectric0.5060/70
System Sensor 2112/24T/DPhotoelectric w/135° Thermal0.0550
System Sensor 2112/24TSRBPhotoelectric w/135° Thermal
System Sensor 2312/24TBPhotoelectric0.1250
System Sensor 2412 (12 volt)Photoelectric0.1277
System Sensor 2412AT (12 volt)Photoelectric0.1258
System Sensor 2412TH (12 volt)Photoelectric0.1277
System Sensor 2424
System Sensor 2424TH
System Sensor 2451Photoelectric0.1039
System Sensor 2451TH (with/B402B Base)Photoelectric0.1039
System Sensor 2W-MODLoop Test/Maintenance Mod.3050
System Sensor 4W-B (12/24 Volt)
System Sensor4WT-B (12/24 Volt)
System Sensor 4WTA-B (12/24 Volt)