Fire-Lite MS-10UD User Manual

Fire Alarm Control Panels
MS-5UD Series
MS-10UD Series
Manual
Document 52626 3/7/2014 Rev:
P/N 52626:C4 ECN 14-167
C4
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warn ing of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication met h­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association S tandard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http: // www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States governme nt) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smok e ” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designe d to ala rm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growt h, neither type of detector i s necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and al arm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector shoul d be tested at least once per year by a qualified fire protection specialist . Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment l
ist
ed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep t he entire life safety sys tem in excellent working order , ongoing mai ntenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dus t, dirt, or hig h air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthl y or as required by National and/or local fire codes and should be per­formed by authorized professional life safety system installers only . Adequate written reco rds of all inspecti ons should be kept.
Limit-D-1-2013
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauth orized use of this document is strictly prohibited.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

Table of Contents

Section 1: Product Description .............................................................................................13
1.1: Product Features ..........................................................................................................................................14
1.2: Specifications...............................................................................................................................................15
1.3: Controls and Indicators................................................................................................................................20
1.4: Digital Alarm Communicator/Transmitter ..................................................................................................21
1.5: Components.................................................................................................................................................21
1.6: Optional Modules and Accessories .............................................................................................................21
1.7: Telephone Requirements and Warnings.......................................................................................................23
1.7.1: Telephone Circuitry...........................................................................................................................23
1.7.2: Digital Communicator.......................................................................................................................23
1.7.3: Telephone Company Rights and Warnings.......................................................................................24
1.7.4: For Canadian Applications................................................................................................................24
Section 2: Installation.............................................................................................................26
2.1: Backbox Mounting ......................................................................................................................................26
2.2: Operating Power..........................................................................................................................................28
2.3: Input Circuits...............................................................................................................................................30
2.4: Output Circuits.............................................................................................................................................32
2.4.1: Notification Appliance Circuits.........................................................................................................32
2.4.2: Special Application DC Power Output Connections.........................................................................33
2.4.3: Relays - Programmable .....................................................................................................................33
2.4.4: Remote Synchronization Output .......................................................................................................34
2.5: Power-limited Wiring Requirements................................................................................ ...........................35
2.6: Digital Communicator.................................................................................................................................36
2.7: Installation of Optional Modules.................................................................................................................37
2.7.1: CAC-5X Class A Converter Module.................................................................................................37
Installation............................................................................................................................................37
Wiring NACs and IDCs for Class A....................................................................................................38
2.7.2: 4XTMF Option Module ....................................................................................................................39
4XTMF Transmitter Module Installation.............................................................................................39
2.7.3: ANN-SEC Option Card.....................................................................................................................40
2.8: ANN-BUS Devices......................................................................................................................................41
Guidelines.............................................................................................................................................41
2.8.1: ANN-BUS Wiring.............................................................................................................................41
Calculating Wiring Distance for ANN-BUS Modules.........................................................................41
Wiring Configuration ................................................ .................................. .........................................44
Powering ANN-BUS Devices from Auxiliary Power Supply .............................................................45
2.8.2: ANN-BUS Device Addressing ..........................................................................................................45
2.8.3: ANN-80(C) Remote Fire Annunciator/Indicator ..............................................................................46
Specifications .......................................................................................................................................46
Installation............................................................................................................................................46
Opening/Closing Annunciator..............................................................................................................46
Mounting ..............................................................................................................................................47
Wiring ANN-80 to FACP................................................................................. ....................................47
2.8.4: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................48
Specifications .......................................................................................................................................49
PRN-6F Printer Installation..................................................................................................................49
2.8.5: ANN-I/O LED Driver Module..........................................................................................................51
ANN-I/O Board Layout........................................................................................................................51
Specifications .......................................................................................................................................51
ANN-I/O Connection to FACP............................................................................................................52
.....
ANN-I/O Module LED Wiring.......................................................................................................
2.8.6: ANN-LED Annunciator Module.......................................................................................................53
Specifications .......................................................................................................................................53
52
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 5
Table of Contents
Mounting/Installation ...........................................................................................................................54
ANN-LED Board Layout and Connection to FACP............................................................................54
2.8.7: ANN-RLY Relay Module..................................................................................................................54
Specifications........................................................................................................................................54
Mounting/Installation ...........................................................................................................................55
ANN-RLY Board Layout and Connection to FACP............................................................................56
2.9: ANN-BUS Audio Panel...............................................................................................................................56
Section 3: Programming........................................................................................................58
3.1: User Programming.......................................................................................................................................58
3.2: Initial Power-up............................................................................................................................................59
3.3: Programming Screens Description ..............................................................................................................59
3.4: Programming and Passwords.......................................................................................................................60
3.5: Master Programming Level .........................................................................................................................61
3.5.1: Input Zones........................................................................................................................................61
3.5.2: NAC (Notification Appliance Circuit) ..............................................................................................66
Enabled.................................................................................................................................................66
NAC Coding.........................................................................................................................................67
Silence...................................................................................................................................................68
Auto Silence..........................................................................................................................................69
Silence Inhibited...................................................................................................................................69
3.5.3: Relays ................................................................................................................................................69
3.5.4: System Setup .....................................................................................................................................69
Timers...................................................................................................................................................70
Banner...................................................................................................................................................72
Time-Date.............................................................................................................................................72
Trouble Reminder.................................................................................................................................74
Canadian Option...................................................................................................................................74
Charger Disable....................................................................................................................................74
3.5.5: Option Modules ................................................................................................................................75
ANN-BUS.............................................................................................................................................75
ANN-RLY Options Screen...................................................................................................................78
ANN-AUDIO Options Screen..............................................................................................................79
ANN-SEC Enable...................................... ................................................................. ..........................79
Onboard DACT ............................................................................................ ........................................79
3.5.6: History ...............................................................................................................................................90
View Events..........................................................................................................................................90
Erase History ........................................................... .................................. ...........................................91
3.5.7: Walktest.............................................................................................................................................91
3.5.8: Clear Program....................................................................................................................................92
Printer/PC .............................................................................................................................................92
3.5.9: Password Change...............................................................................................................................92
3.6: Maintenance Programming Level................................................................................................................93
3.6.1: Input Zones - Enable/Disable ............................................................................................................93
3.6.2: History ...............................................................................................................................................94
3.6.3: Walktest.............................................................................................................................................94
3.6.4: Time-Date..........................................................................................................................................95
Section 4: Operating Instructions.........................................................................................96
4.1: Panel Control Buttons..................................................................................................................................96
4.1.1: Acknowledge/Step.............................................................................................................................96
4.1.2: Alarm Silenced ..................................................................................................................................96
4.1.3: Drill/Hold 2 Sec.................................................................................................................................96
4.1.4: Reset ..................................................................................................................................................96
4.2: LED Indicators.............................................................................................................................................96
4.3: Normal Operation ........................................................................................................................................97
4.4: Trouble Operation........................................................................................................................................97
4.5: Alarm Operation ..........................................................................................................................................99
6 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Table of Contents
4.6: Supervisory Operation.................................................................................................................................99
4.7: Process Monitor Operation........................................................................................................................100
4.8: Hazard/Tornado Condition Operation .......................................................................................................100
4.9: Medical Alert Condition Operation...........................................................................................................101
4.10: Disable/Enable Operation........................................................................................................................101
4.11: Waterflow Circuits Operation..................................................................................................................101
4.12: Detector Functions................................... ................................................................. ... ............................102
4.13: Time Functions: Real-Time Clock...........................................................................................................102
4.14: Coded Operation................................................................................... ...................................................102
4.15: Presignal .......................................................................................... ........................................................102
4.16: Positive Alarm Sequence.........................................................................................................................103
4.17: Special System Timers............................................................... ..............................................................103
4.17.1: Silence Inhibit Timer.....................................................................................................................103
4.17.2: Autosilence Timer ................................................ .................................. .......................................103
4.17.3: Trouble Reminder........................................................................................ ..................................103
4.17.4: Waterflow Retard Timer.............................................................................. ..................................104
4.17.5: Alarm Verification (None or One Minute)....................................................................................104
4.18: Walktest ..................................................................................... ..............................................................104
4.19: Read Status ....................................................... .......................................................................................105
4.19.1: Input Zones.................................................................................... ................................................105
4.19.2: NAC........................................................ .................................. .....................................................106
4.19.3: Relays ............................................................................................................. ...............................106
4.19.4: System Settings .......................... ................................................................. ..................................107
4.19.5: Timers....................................... ................................................................ .....................................107
4.19.6: Daylight Savings ....................................................... ....................................................................107
4.19.7: History................................ .................................. .........................................................................107
4.19.8: Print .......................................................... .....................................................................................107
4.19.9: ANN-BUS ........................................................................................... ..........................................108
4.19.10: Central Station.............................................................................................................................108
4.19.11: Phone Line...................................................................................................................................109
4.19.12: Service Terminal..........................................................................................................................109
Section 5: Central Station Communications......................................................................110
5.1: Transmittal Priorities.................................................................................................................................111
Section 6: Local/Remote Site Upload/Download...............................................................113
6.1: Remote Download .....................................................................................................................................113
6.2: Transferring a Program..............................................................................................................................114
6.2.1: Security Features .............................................................................................................................114
Section 7: Power Supply Calculations................................................................................116
7.1: Overview....................................................................................................................................................116
7.2: Calculating the AC Branch Circuit............................................................................................................116
7.3: Calculating the System Current Draw.......................................................................................................117
7.3.1: Overview .........................................................................................................................................117
7.3.2: How to Use Table 7.3 on page 118 to Calculate System Current Draw .........................................117
7.4: Calculating the Battery Size ......................................................................................................................119
7.4.1: NFPA Battery Requirements...........................................................................................................119
7.4.2: Selecting and Locating Batteries.....................................................................................................119
Appendix A: Ademco Contact ID Format Event Code Descriptions................................120
A.1: Transmission Format Between DACT and Receiver................................................................................120
A.2: Ademco Contact ID Typical Printout .......................................................................................................120
Appendix B: NFPA Standard-Specific Requirements .......................................................125
B.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................130
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 7
Table of Contents
Appendix C: FACP with Keltron..........................................................................................131
Appendix D: Wire Requirements.........................................................................................132
D.1: MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring.......................................................................................132
D.2: MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring................................................................................133
Appendix E: Default Programming .....................................................................................134
Appendix F: Canadian Application.....................................................................................136
F.1: ANN-LED Annunciator Installation for Canadian Applications...............................................................136
Index ......................................................................................................................................138
8 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S559 Standard for Equipment for Fire Signal Receiving Centers and
Systems
This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part I NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384 CHG-120F Battery Charger Manual Document #50888 CHG-75 Battery Charger Manual Document #51315 411UD Manual Document #50759 411UDAC Manual Document #51073 ANN-80 Product Installation Doc. Document #52749 ANN-(R)LED Product Installation Doc. Document #53032 ANN-I/O Product Installation Doc. Document #151416 ANN-RLY Product Installation Doc. Document #53033 ANN-S/PG Product Installation Doc. Document #151417 ACC-25/50 Series Audio Panel Document #51889
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 9
MS-5UD Series Main Circuit Board
S
W
1
Dummy load all unused circuits
with 4.7K, ½ watt End-of-Line
resistors
Style Z (Class A) NAC
Style D (Class A) IDC
Class A Converter Module
3 Programmable Relays
Nonsupervised relay contacts
Contact Ratings
2.0 amps @ 30 VDC (resistive)
0.5 amp @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble, or supervisory activity)
A Fail Safe Trouble relay switches
to the NC position during trouble
conditions and under loss of all
power.
(*Factory default relay
programming)
Alarm*
Trouble*
Supervisory*
Remote
Synchronization
Output (see note 2)
Special Application
Power
24 VDC filtered,
supervised, and power-
limited. 0.040 amp
maximum. Requires
4.7K ohm ELR.
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(C/E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): Refer to “Remote
Synchronization Output” on page 34.
3. 18 Amp Hour max. for MS-5UD-3(E)
26 Amp Hour max. for MS-5UD-7(E)
18 Amp Hour max. for MS-5UD-7C
Class A Converter Module
Remove jumper JP43 to
disable Ground Fault
Detection circuit (only with
approval of AHJ)
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
Relay when 4XTMF
module is installed
Auxiliary
Trouble Input
Kiss-off LED
Secondary Phone
Active LED
Primary Phone
Active LED
Primary
Secondary
ANN-SEC
option card connector
USB port for local programming using a
personal computer and PK-5X Utility
DACT Phone Line Jacks
Nonpower-Limited
Battery (see note 3)
24 VDC, supervised,
nonpower-limited
Basic System Connections
5-Zone Panel
Power Supply Connector
For more specific UL wiring
information, refer to page 35.
Important! Removing Ground Fault Disable
Jumper JP43 voids UL/NFPA Style/Class
indentifications for circuits. Remove jumper
JP43 only with the approval of the local AHJ
(Authority Having Jurisdiction).
Special Application
DC Power Outputs 24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay
EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.5 amp maximum) to
smoke detectors (IDC). Supervision
required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC
filtered, power-limited (0.5 amp maximum).
Supervision required. Nonresettable
Power suitable for powering smoke
detectors.
Configure TB9, Terminals 1 & 2 as
Resettable or Nonresettable Power.
• Resettable Power - jumper JP31 pins 2
& 3
• Nonresettable Power - jumper JP31 pins
1 & 2 (as shown)
4
3
2
1
{
{
Notification Appliance Circuits (see note 1)
Special Application Power
NAC #1, #2, #3, & #4, Style Y (Class B) (Supervised, Power-
Limited) (See Style Z illustra ted near right edge of board.)
4.7Kohm, ½ watt End-of-Line Resistor
PN 71252
NAC #1 NAC #2 NAC #3 NAC #4
Special Application
Power
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power-Limited) (See
Style D illustrated near
right edge of board.)
4.7Kohm, ½ watt End-of-
Line Resistor
PN 71252
Initiating Device Circuits
Push switch down to
upgrade software
ms-5udlayout.wmf
10 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
4
6
6
4
T
B
6
Z
O
N
E
6
Z
O
N
E
7
Z
O
N
E
8
Z
O
N
E
9
Z
O
N
E
1
0
S
W
1
TB4
/
T
B
6
1
/
6
2
/73/85/
1
0
4
/
9
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(C/E) = 3 amps max. per
NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page34.
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(E)
18 Amp Hour max. for MS-10UD-7C
Dummy load all unused circuits
with 4.7K, ½ watt End-of-Line
resistors
Style Z (Class A) NAC
Style D (Class A) IDC
Class A Converter Module
3 Programmable Relays
Nonsupervised relay contacts
Contact Ratings
2.0 amps @ 30 VDC (resistive)
0.5 amp @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble, or supervisory activity)
A Fail Safe Trouble relay switches to
the NC position during trouble
conditions and under loss of all
power.
(*Factory default relay programming)
Alarm*
Trouble*
Supervisory*
Remote
Synchronization
Output (see note 2)
Special Application Power
24 VDC filtered, supervised,
and power-limited. 0.040 amp
maximum. Requires 4.7K
ohm ELR.
Class A Converter Module
Remove jumper JP43 to
disable Ground Fault
Detection circuit (only with
approval of AHJ)
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
Relay when 4XTMF
module is installed
Auxiliary
Trouble Input
Kiss-off LED
Secondary Phone
Active LED
Primary Phone
Active LED
Primary
Secondary
ANN-SEC
option card connector
USB port for local programming using a
personal computer and PK-5X Utility
DACT Phone Line Jacks
Nonpower-Limited
Battery (see note 3)
24 VDC, supervised,
nonpower-limited
Basic System Connections
10-Zone Panel
Power Supply Connector
For more specific UL wiring
information, refer to page 35.
Important! Removing Ground Fault Disable
Jumper JP43 voids UL/NFPA Style/Class
indentifications for circuits. Remove jumper
JP43 only with the approval of the local AHJ
(Authority Having Jurisdiction).
Special Application
DC Power Outputs 24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay
EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.5 amp maximum) to
smoke detectors (IDC). Supervision
required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC
filtered, power-limited (0.5 amp maximum).
Supervision required. Nonresettable
Power suitable for powering smoke
detectors.
Configure TB9, Terminals 1 & 2 as
Resettable or Nonresettable Power.
• Resettable Power - jumper JP31 pins 2
& 3
• Nonresettable Power - jumper JP31 pins
1 & 2 (as shown)
4
3
2
1
{
{
Notification Appliance Circuits (see note 1)
Special Application Power
NAC #1, #2, #3, & #4, Style Y (Class B) (Supervised, Power-
Limited) (See Style Z illustrated near right edge of board.)
4.7Kohm, ½ watt End-of-Line Resistor
PN 71252
NAC #1 NAC #2 NAC #3 NAC #4
Special Application
Power
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power-Limited) (See
Style D illustrated near
right edge of board.)
4.7Kohm, ½ watt End-of-
Line Resistor
PN 71252
Initiating Device Circuits
Push switch down to
upgrade software
Special Application Power
IDCs 1 through 5, Style B
(Class B) (Supervised, Power-
Limited) (See Style D
illustrated near right edge of
board.)
4.7Kohm, ½ watt End-of-Line
Resistor
PN 71252
Initiating Device Circuits
ms-10udlayout.wmf
MS-10UD Series Main Circuit Board
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 11
-
+-+
JP1
JP3
SW1
JP4
TB3
TB4
TB2
ENABLE
AC DELAY
16 HR DELAY
TENS
ONES
CUT FOR 240VAC
GND FLT DISABLE
AM-1 ENABLE
ADDRESS
ON OFF
AM-1
JP5
JP2
F1
F2
J4
J1 J2
J3
F3
TB1
HOT
OUT
+
BAT
+
OUT
-
BAT
-
EARTH
NEUT
1
5
1
5
A- B- A+ B+
NC NO C
043
9
261578121315
14
10
1104
3
9
261
578
121315
14
10
11
TB1
TBL
J1
J2
7 6 5 1
POWER LIMITED
Sw1
P1
P2
P3
P4
110
11
20
21 30
31
40
1 2 3 4 5
ALARM
TROUBLE
FIRE ALARM ANNUNCIATOR
A
C
K
S
T
E
P
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB6
TB3
TB5
TB4
TB2
Alarm
Silenced
Earth Fault
ZONE 1
ALM
TBL
SUP
1
ZONE 6
ALM
TBL
SUP
6
NAC 1
Fault
Battery
Fault
ZONE 2
ALM
TBL
SUP
2
ZONE 7
ALM
TBL
SUP
7
NAC2
Fault
Charger
Fault
ZONE 3
ALM
TBL
SUP
3
ZONE 8
ALM
TBL
SUP
8
FIRE ALARM ANNUNCIATOR
NAC 4
Fault
ZONE 5
ALM
TBL
SUP5ALM
TBL
SUP
NAC 3
Fault
Disabled
ZONE 4
ALM
TBL
SUP
4
ZONE 9
ALM
TBL
SUP
9
F
ROM AP PHONE PS
TN TO AP
O
UT NC
OUT N
O
INPUT TAMPER GND +12/24
V
P4CN2P5P6
P7P
8
P9P10
P11P1
2
CHG-120 Charger
Doc. #
ANN-BUS - TB3
Battery Connector - J12
510udperi.wmf
ANN-80(C)
LCD Text Annunciator/Indicator
Doc. #
ANN-I/O
LED Driver
Doc. #
ANN-S/PG
Printer Driver
Doc. #
CHG-75 Charger
Doc. # 51315
ANN-(R)LED
LED Display
Doc. #
ANN-RLY
10 Form-C Relay Card
Doc. #
4XTM
Reverse Polarity Module
J4 & J5
IPDACT
Internet Communicator
Doc. #53109
J8 & J9 Telephone Connections
USB
Local PC
12 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Section 1: Product Description

The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone F ACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise specified. The combination control and digital communicator panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s i transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervi­sory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately
o
F (refer to System Sensor i3 Installation and Maintenance Instructions). In addition, the control
45 panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Fire•Lite Device Compatibility Document for a complete listing of compati­ble devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application reset­table and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery level and telephone line integrity. Available accessories include local and remote upload/download soft­ware, remote annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone net­work. Local programming interrogation is also possible using the PS-Tools and the USB port on the FACP. Any personal computer with Windows of 2400 baud and PS-Tools may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.
3
detectors which are conventional smoke detectors that can
®
XP or newer, compatible modem with a speed
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, display alarm informa­tion on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 13
Product Description Product Features
The following versions of the MS-5UD and MS-10UD are available:
FACP Version Description
MS-5UD-3 Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-5UD-7 Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
MS-5UD-7C Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current. Includes built-in ANN-LED Annunciator . This panel is approved for Canadian applications
MS-5UD-3E Five Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-5UD-7E Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
MS-10UD-3 Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-10UD-3E Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-10UD-7 Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
MS-10UD-7C Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current. Includes built-in ANN-LED Annunciator . This panel is approved for Canadian applications.
MS-10UD-7E Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
NOTE: Unless otherwise specified, the information in this manual applies to all versions of the panels.

1.1 Product Features

Built-in DACT (Digital Alarm Communicator/Transmitter)
Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD - five programmable IDCsMS-10UD - ten programmable IDCs
Four Style Y (Class B) NAC (Notification Appliance Circu it) ­special application power
Three programmable Form-C relays
Built-in Programmer
Touchtone/Rotary dialing
Programmable Make/Break Ratio
Optional Dress Panel: DP-51050
A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED Annunciator module
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
ANN-BUS for connection to optional:
ANN-80 Remote LCD AnnunciatorANN-I/O LED DriverANN-S/PG Printer Module
14 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Specifications Product Description
ANN-RLY Relay Module
ANN-LED Annunciator Module
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History log with 256 event storage
Control Buttons
ACK (Acknowledge)Alarm SilenceSystem Reset/Lamp TestDrill
LED Indicators
Fire AlarmSupervisoryTroubleAC PowerAlarm SilencePrimary and Secondary Phone Line Active LEDs
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:
Silence Inhibit Auto-Silence Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)Selective Silence (horn-strobe mute)Temporal or Steady SignalSilenceable or Nonsilenceable
Automatic battery charger with charger supervision
Silent or audible walktest capabilities
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program and data
Optional CAC-5X Class A Converter Module for NACs and IDCs
Optional 4XTMF Transmitter Module
Optional ANN-SEC card for a secondary ANN-BUS

1.2 Specifications

NOTE: For wiring specifications, refer to“Wire Requirements” on page 132.
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-5UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-10UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 15
Product Description Specifications
MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
2
Wire size: minimum #14 AWG (2.0 mm
) with 600V insulation
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp Supervised, nonpower-limited Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-5UD-7C, MS -10UD­3(E), and MS-10UD-7C, and 26 Amp Hour battery for MS-5UD-7(E) and MS-10UD-7(E) [two 18 Amp Hour batteries can be housed in FACP cabinet. Larger batteries require a separate battery box such as the BB-26 or BB-55F and the CHG-75 or CHG-120F Battery Charger.] Minimum Battery Size: 7 Amp Hour (12 Amp Hour for MS-5UD-7C & MS-10UD-7C)
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD) Alarm Zones 6 - 10 on TB6 (MS-10UD only) Supervised and power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms (700 ohms per zone for linear heat detection - See Section 2.3, “Input Circuits” for more information.) End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Standby Current: 2 mA Refer to the Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB7
Four NACs Operation: Style Y (Class B) Special Application power Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC) End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Refer to the Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors Power-limited Circuitry Refer to the Fire•Lite Device Compatibility Document for compatible listed devices
16 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Specifications Product Description
Special Application Resettable or N o nre se tt a bl e Pow e r - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA Power-limited Circuitry Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable powerJumper pins 2 & 3 on JP31 for resettable power
Refer to the Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Primary ANN-BUS Power - TB3
Operating voltage: Nominal 24 VDC Maximum Available Current: 500mA Power-limited circuit
Special Application Secondary ANN-BUS Power - ANN-SEC - TB1
Operating voltage: Nominal 24 VDC Maximum Available Current: 500mA Power-limited circuit
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS-5UD-3(E), MS-10UD­3(E) (refer to
“Remote Synchronization Output” on page 34)
24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7K Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an external device for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits. All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 17
Product Description Specifications
TB9
TB5
TB7
TB3
TB2
TB1
Figure 1.1 Current Availability with FACP and FLPS-3 Power Supply
powerdist510.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application Nonresettable or Resettable Power
Special Application Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
Alarm
3.0 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
Remote
Synchronization
Output
0.040 amp max
per circuit
ANN-SEC
Option Card
0.5 amp max
per circuit
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-3 power supply. This applies to the MS-5UD-3, MS-10UD-3, MS-5UD-3E, and MS-10UD-3E.
18 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Specifications Product Description
TB9
TB5
TB7
TB3
TB1
Figure 1.2 Current Availability with FACP and FLPS-7 Power Supply
powerdistmrp.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application Nonresettable or Resettable Power
Special Application Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
Alarm
7.0 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
0.5 amp max
per circuit
ANN-SEC
Option Card
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-7 power supply. This applies to the MS-5UD-7, MS-5UD-7C, MS-10UD-7, MS-10UD-7C, MS-5UD-7E, and MS-10UD-7E.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 19
Product Description Controls and Indicators
SYSTEM ALL NORMAL
10:00A 012105
Figure 1.3 Membrane/Display Panel
9050udkypd.cdr

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED back­light will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
LED Indicators
LEDs are provided to annunciate the following conditions:
Fire Alarm - red LED
Supervisory - yellow LED
AC Power - green LED
System Trouble - yellow LED
Alarm Silence - yellow LED
Primary Phone Line Active (on circuit board) - red LED
Secondary Phone Line Active (on circuit board) - red LED
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process monitor and supervisory conditio ns as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off
Process Monitor - pulse ¼ second on and ¼ second off
20 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Digital Alarm Communicator/Transmitter Product Description

1.4 Digital Alarm Communicator/Transmitter

T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the fol­lowing functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
®
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA-DCS-8SIA-DCS-20
, programmable to rotary

1.5 Components

Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and wir­ing interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied
standard with a modified dress panel and one ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS­10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condi­tion exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 21
Product Description Optional Modules and Accessories
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display and provides remote RESET, SILENCE, ACKNOWLEDGE, and DRILL.
ANN-80C LCD Indicator (Canadian applications)
The ANN-80C is a remote LCD indicator which mimics the information displayed on the FACP LCD display but does not allow remote control of the FACP.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. ANN-LED module is installed in dress panel for Canadian version.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for Cana­dian applications requiring remote annunciation.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. The Canadian version is supplied standard with a modified dress panel.
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the cab­inet.
Battery Box
The BB-26 or BB-55F battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP bat­tery charger must be disabled, through software programming, when using the CHG-75. The char­ger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the F ACP. The FACP battery charger must be disabled, through software programming, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using a BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
22 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Telephone Requirements and Warnings Product Description
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible personal computers (PC), running Windows program files can also be created and stored on the PC and then downloaded later to the control panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote Download” on page 113). Remote interrogation of panel pro­gramming, history logs, detector status, etc., is possible without enabling the remote download option.

1.7 Telephone Requirements and Warnings

1.7.1 Telephone Circuitry

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
®
XP (or newer). FACP

1.7.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-5UD/MS-10UD FCC Registration Number: 1W6AL00B10UD Ringer Equivalence: 0.0B
Important! The DACT must not
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, com­puter modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these
be used to dial a phone number that is call-forwarded.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 23
Product Description Telephone Requirements and Warnings
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to “Digital Communicator” on page 36 for an illustration of the proper installation of this equipment.

1.7.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be pro vid ed except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same tele-
phone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equip­ment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.

1.7.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements docu­ment(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility des­ignated by the supplier. Any repairs or alterations made by the user to this equipment, or equip­ment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspections authority, or electrician.
24 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Telephone Requirements and Warnings Product Description
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termi­nation of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emis­sions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Road Woodbridge, Ontario L4L7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: 2132A-10UD Ringer Equivalence Number (REN): 0.0B Load Number: 2
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 25

Section 2: Installation

!
mounting studs
mounting slots
mounting tabs
mounting holes
grounding stud: attach solid earth ground wire (refer to Figure 2.4 on page 29)
MS-5UD Board on Chassis
MS-5UD Backbox
Figure 2.1 Chassis Mounting in Backbox
5udbrdinbox.wmr
mounting slots
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Backbox Mounting

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2 on page 27.
Install center top fastener in the wall with the screw head protruding.Place backbox over the top screw, level and secure.Mark and drill the left and right upper and lower mounting holes.
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
Install remaining fasteners and tighten.
26 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Backbox Mounting Installation
9050UDencl.wmf
Figure 2.2 Cabinet Dimensions
Hinge Slot for optional Dress Panel
Semi­Flush mounting hole
Mounting slots for optional Trim Ring
Hinge Slot for optional Dress Panel
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 27
Installation Operating Power
!
Figure 2.3 Backbox and Battery Box
9050UDcab2.wmf
Door = 19.26” (48.92 cm) Backbox = 19.0” (48.26)
Door = 16.821” (42.73 cm) Backbox = 16.65” (42.29 cm)
Depth = 5.207” (13.23 cm)
Depth = 5.257”
(13.353 cm)
Top
Left Side
Right Side
Bottom

2.2 Operating Power

WARNING: RISK OF ELECTRICAL SHOCK AND/OR EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the sec­tion titled “Specifications” on page 15, for power and current requirements for each FACP version. Run a pair of wires (with ground conductor) from the protected premises main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14
2
AWG (2.00 mm
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment
28 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Operating Power Installation
!
Figure 2.4 Operating Power Connections
AC Power
Hot (L1)
Earth
Neutral (L2)
Ground Stud
J12
to batteries
5ud_10udacpower.wmf
+
-
Ground Stud
J12
to batteries
+
-
FLPS-7
Power Supply
FLPS-3
Power Supply
AC Power
AC Hot
AC Neutral
Earth
MS-5UDC-7(C)(E)
MS-10UD-7(C)(E)
MS-5UD-3(E)
MS-10UD-3(E)
may be connected to this circuit. In addition, this circuit must be provided with overcurrent protec­tion and may not contain any power disconnect devices. An Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth
2
Ground wire [minimum 14 AWG (2.00 mm
)] to the grounding stud in the backbox and then run
the wire to TB1. Do not use conduit for the Earth Ground connection since this does not provide
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Conn ect the battery cable to J12 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
WARNING: SULFURIC ACID
BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 29
Installation Input Circuits
Figure 2.5 IDC Connections
Class B Initiating Device Circuits (supervised and power-limited) 4.7 K, ½ watt resistor P/N:71252
UL listed compatible 2-wire smoke detectors
manual pull stations
heat detectors
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
ms-10UDidc.wmf
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
UL listed compatible 4-wire smoke detector

2.3 Input Circuits

The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each cir­cuit is compatible with System Sensor’s i when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient tempera­ture falls below the detector rating of approximately 45 each IDC is 100 ohms (700 ohms per zone for linear heat detection). Do not use 2-wire smoke detectors on input zones used for linear heat detection. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to “CAC-5X Class A Converter Module” on page 37.
3
smoke detectors which generate a maintenance signal
o
F. The maximum loop resistance limit for
3
smoke detectors, any
30 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Loading...
+ 114 hidden pages