Fire-Lite MS-10UD User Manual

Fire Alarm Control Panels
MS-5UD Series
MS-10UD Series
Manual
Document 52626 3/7/2014 Rev:
P/N 52626:C4 ECN 14-167
C4
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifi­cation capability—can provide early warn ing of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice commu­nication, and other various interoperable communication met h­ods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association S tandard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http: // www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States governme nt) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smok e ” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown aw a y from de tectors by air outlets, such as air conditioning vent s.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designe d to ala rm at var­ious levels of smoke density. If such density levels are not cre­ated by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing cham­bers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growt h, neither type of detector i s necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warn­ing of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions
(caused by escaping gas, improper storage of flammable materi­als, etc.).
Heat detectors do not sense particles of combustion and al arm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detec­tors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector shoul d be tested at least once per year by a qualified fire protection specialist . Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a devel­oping fire may damage the alarm system, compromising its abil­ity to report a fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices
are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messaging systems must be desi gned to meet intelligi­bility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under c ertain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have sh own that certain people, even when they he ar a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm sig­nals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compat­ible with the control panel. It is essential to use only equipment l
ist
ed for service with your control panel.
Telephone lines needed to transmit alarm signals from a prem­ises to a central monitoring station may be out of service or tem­porarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of life safety system malfunction is inadequate maintenance. To keep t he entire life safety sys tem in excellent working order , ongoing mai ntenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be fol­lowed. Environments with large amounts of dus t, dirt, or hig h air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthl y or as required by National and/or local fire codes and should be per­formed by authorized professional life safety system installers only . Adequate written reco rds of all inspecti ons should be kept.
Limit-D-1-2013
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to li ght ­ning induced transients. Although no system is completely immune from lightning transients and interf erence, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body . Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, ope rati ng, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and a ssociated equipment. FACP operation and rel iability depend upon proper inst allat ion.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi ­oelectriques depassant les limites applic ables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauth orized use of this document is strictly prohibited.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

Table of Contents

Section 1: Product Description .............................................................................................13
1.1: Product Features ..........................................................................................................................................14
1.2: Specifications...............................................................................................................................................15
1.3: Controls and Indicators................................................................................................................................20
1.4: Digital Alarm Communicator/Transmitter ..................................................................................................21
1.5: Components.................................................................................................................................................21
1.6: Optional Modules and Accessories .............................................................................................................21
1.7: Telephone Requirements and Warnings.......................................................................................................23
1.7.1: Telephone Circuitry...........................................................................................................................23
1.7.2: Digital Communicator.......................................................................................................................23
1.7.3: Telephone Company Rights and Warnings.......................................................................................24
1.7.4: For Canadian Applications................................................................................................................24
Section 2: Installation.............................................................................................................26
2.1: Backbox Mounting ......................................................................................................................................26
2.2: Operating Power..........................................................................................................................................28
2.3: Input Circuits...............................................................................................................................................30
2.4: Output Circuits.............................................................................................................................................32
2.4.1: Notification Appliance Circuits.........................................................................................................32
2.4.2: Special Application DC Power Output Connections.........................................................................33
2.4.3: Relays - Programmable .....................................................................................................................33
2.4.4: Remote Synchronization Output .......................................................................................................34
2.5: Power-limited Wiring Requirements................................................................................ ...........................35
2.6: Digital Communicator.................................................................................................................................36
2.7: Installation of Optional Modules.................................................................................................................37
2.7.1: CAC-5X Class A Converter Module.................................................................................................37
Installation............................................................................................................................................37
Wiring NACs and IDCs for Class A....................................................................................................38
2.7.2: 4XTMF Option Module ....................................................................................................................39
4XTMF Transmitter Module Installation.............................................................................................39
2.7.3: ANN-SEC Option Card.....................................................................................................................40
2.8: ANN-BUS Devices......................................................................................................................................41
Guidelines.............................................................................................................................................41
2.8.1: ANN-BUS Wiring.............................................................................................................................41
Calculating Wiring Distance for ANN-BUS Modules.........................................................................41
Wiring Configuration ................................................ .................................. .........................................44
Powering ANN-BUS Devices from Auxiliary Power Supply .............................................................45
2.8.2: ANN-BUS Device Addressing ..........................................................................................................45
2.8.3: ANN-80(C) Remote Fire Annunciator/Indicator ..............................................................................46
Specifications .......................................................................................................................................46
Installation............................................................................................................................................46
Opening/Closing Annunciator..............................................................................................................46
Mounting ..............................................................................................................................................47
Wiring ANN-80 to FACP................................................................................. ....................................47
2.8.4: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................48
Specifications .......................................................................................................................................49
PRN-6F Printer Installation..................................................................................................................49
2.8.5: ANN-I/O LED Driver Module..........................................................................................................51
ANN-I/O Board Layout........................................................................................................................51
Specifications .......................................................................................................................................51
ANN-I/O Connection to FACP............................................................................................................52
.....
ANN-I/O Module LED Wiring.......................................................................................................
2.8.6: ANN-LED Annunciator Module.......................................................................................................53
Specifications .......................................................................................................................................53
52
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 5
Table of Contents
Mounting/Installation ...........................................................................................................................54
ANN-LED Board Layout and Connection to FACP............................................................................54
2.8.7: ANN-RLY Relay Module..................................................................................................................54
Specifications........................................................................................................................................54
Mounting/Installation ...........................................................................................................................55
ANN-RLY Board Layout and Connection to FACP............................................................................56
2.9: ANN-BUS Audio Panel...............................................................................................................................56
Section 3: Programming........................................................................................................58
3.1: User Programming.......................................................................................................................................58
3.2: Initial Power-up............................................................................................................................................59
3.3: Programming Screens Description ..............................................................................................................59
3.4: Programming and Passwords.......................................................................................................................60
3.5: Master Programming Level .........................................................................................................................61
3.5.1: Input Zones........................................................................................................................................61
3.5.2: NAC (Notification Appliance Circuit) ..............................................................................................66
Enabled.................................................................................................................................................66
NAC Coding.........................................................................................................................................67
Silence...................................................................................................................................................68
Auto Silence..........................................................................................................................................69
Silence Inhibited...................................................................................................................................69
3.5.3: Relays ................................................................................................................................................69
3.5.4: System Setup .....................................................................................................................................69
Timers...................................................................................................................................................70
Banner...................................................................................................................................................72
Time-Date.............................................................................................................................................72
Trouble Reminder.................................................................................................................................74
Canadian Option...................................................................................................................................74
Charger Disable....................................................................................................................................74
3.5.5: Option Modules ................................................................................................................................75
ANN-BUS.............................................................................................................................................75
ANN-RLY Options Screen...................................................................................................................78
ANN-AUDIO Options Screen..............................................................................................................79
ANN-SEC Enable...................................... ................................................................. ..........................79
Onboard DACT ............................................................................................ ........................................79
3.5.6: History ...............................................................................................................................................90
View Events..........................................................................................................................................90
Erase History ........................................................... .................................. ...........................................91
3.5.7: Walktest.............................................................................................................................................91
3.5.8: Clear Program....................................................................................................................................92
Printer/PC .............................................................................................................................................92
3.5.9: Password Change...............................................................................................................................92
3.6: Maintenance Programming Level................................................................................................................93
3.6.1: Input Zones - Enable/Disable ............................................................................................................93
3.6.2: History ...............................................................................................................................................94
3.6.3: Walktest.............................................................................................................................................94
3.6.4: Time-Date..........................................................................................................................................95
Section 4: Operating Instructions.........................................................................................96
4.1: Panel Control Buttons..................................................................................................................................96
4.1.1: Acknowledge/Step.............................................................................................................................96
4.1.2: Alarm Silenced ..................................................................................................................................96
4.1.3: Drill/Hold 2 Sec.................................................................................................................................96
4.1.4: Reset ..................................................................................................................................................96
4.2: LED Indicators.............................................................................................................................................96
4.3: Normal Operation ........................................................................................................................................97
4.4: Trouble Operation........................................................................................................................................97
4.5: Alarm Operation ..........................................................................................................................................99
6 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Table of Contents
4.6: Supervisory Operation.................................................................................................................................99
4.7: Process Monitor Operation........................................................................................................................100
4.8: Hazard/Tornado Condition Operation .......................................................................................................100
4.9: Medical Alert Condition Operation...........................................................................................................101
4.10: Disable/Enable Operation........................................................................................................................101
4.11: Waterflow Circuits Operation..................................................................................................................101
4.12: Detector Functions................................... ................................................................. ... ............................102
4.13: Time Functions: Real-Time Clock...........................................................................................................102
4.14: Coded Operation................................................................................... ...................................................102
4.15: Presignal .......................................................................................... ........................................................102
4.16: Positive Alarm Sequence.........................................................................................................................103
4.17: Special System Timers............................................................... ..............................................................103
4.17.1: Silence Inhibit Timer.....................................................................................................................103
4.17.2: Autosilence Timer ................................................ .................................. .......................................103
4.17.3: Trouble Reminder........................................................................................ ..................................103
4.17.4: Waterflow Retard Timer.............................................................................. ..................................104
4.17.5: Alarm Verification (None or One Minute)....................................................................................104
4.18: Walktest ..................................................................................... ..............................................................104
4.19: Read Status ....................................................... .......................................................................................105
4.19.1: Input Zones.................................................................................... ................................................105
4.19.2: NAC........................................................ .................................. .....................................................106
4.19.3: Relays ............................................................................................................. ...............................106
4.19.4: System Settings .......................... ................................................................. ..................................107
4.19.5: Timers....................................... ................................................................ .....................................107
4.19.6: Daylight Savings ....................................................... ....................................................................107
4.19.7: History................................ .................................. .........................................................................107
4.19.8: Print .......................................................... .....................................................................................107
4.19.9: ANN-BUS ........................................................................................... ..........................................108
4.19.10: Central Station.............................................................................................................................108
4.19.11: Phone Line...................................................................................................................................109
4.19.12: Service Terminal..........................................................................................................................109
Section 5: Central Station Communications......................................................................110
5.1: Transmittal Priorities.................................................................................................................................111
Section 6: Local/Remote Site Upload/Download...............................................................113
6.1: Remote Download .....................................................................................................................................113
6.2: Transferring a Program..............................................................................................................................114
6.2.1: Security Features .............................................................................................................................114
Section 7: Power Supply Calculations................................................................................116
7.1: Overview....................................................................................................................................................116
7.2: Calculating the AC Branch Circuit............................................................................................................116
7.3: Calculating the System Current Draw.......................................................................................................117
7.3.1: Overview .........................................................................................................................................117
7.3.2: How to Use Table 7.3 on page 118 to Calculate System Current Draw .........................................117
7.4: Calculating the Battery Size ......................................................................................................................119
7.4.1: NFPA Battery Requirements...........................................................................................................119
7.4.2: Selecting and Locating Batteries.....................................................................................................119
Appendix A: Ademco Contact ID Format Event Code Descriptions................................120
A.1: Transmission Format Between DACT and Receiver................................................................................120
A.2: Ademco Contact ID Typical Printout .......................................................................................................120
Appendix B: NFPA Standard-Specific Requirements .......................................................125
B.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts....................................130
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 7
Table of Contents
Appendix C: FACP with Keltron..........................................................................................131
Appendix D: Wire Requirements.........................................................................................132
D.1: MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring.......................................................................................132
D.2: MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring................................................................................133
Appendix E: Default Programming .....................................................................................134
Appendix F: Canadian Application.....................................................................................136
F.1: ANN-LED Annunciator Installation for Canadian Applications...............................................................136
Index ......................................................................................................................................138
8 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S559 Standard for Equipment for Fire Signal Receiving Centers and
Systems
This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part I NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384 CHG-120F Battery Charger Manual Document #50888 CHG-75 Battery Charger Manual Document #51315 411UD Manual Document #50759 411UDAC Manual Document #51073 ANN-80 Product Installation Doc. Document #52749 ANN-(R)LED Product Installation Doc. Document #53032 ANN-I/O Product Installation Doc. Document #151416 ANN-RLY Product Installation Doc. Document #53033 ANN-S/PG Product Installation Doc. Document #151417 ACC-25/50 Series Audio Panel Document #51889
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 9
MS-5UD Series Main Circuit Board
S
W
1
Dummy load all unused circuits
with 4.7K, ½ watt End-of-Line
resistors
Style Z (Class A) NAC
Style D (Class A) IDC
Class A Converter Module
3 Programmable Relays
Nonsupervised relay contacts
Contact Ratings
2.0 amps @ 30 VDC (resistive)
0.5 amp @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble, or supervisory activity)
A Fail Safe Trouble relay switches
to the NC position during trouble
conditions and under loss of all
power.
(*Factory default relay
programming)
Alarm*
Trouble*
Supervisory*
Remote
Synchronization
Output (see note 2)
Special Application
Power
24 VDC filtered,
supervised, and power-
limited. 0.040 amp
maximum. Requires
4.7K ohm ELR.
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(C/E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): Refer to “Remote
Synchronization Output” on page 34.
3. 18 Amp Hour max. for MS-5UD-3(E)
26 Amp Hour max. for MS-5UD-7(E)
18 Amp Hour max. for MS-5UD-7C
Class A Converter Module
Remove jumper JP43 to
disable Ground Fault
Detection circuit (only with
approval of AHJ)
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
Relay when 4XTMF
module is installed
Auxiliary
Trouble Input
Kiss-off LED
Secondary Phone
Active LED
Primary Phone
Active LED
Primary
Secondary
ANN-SEC
option card connector
USB port for local programming using a
personal computer and PK-5X Utility
DACT Phone Line Jacks
Nonpower-Limited
Battery (see note 3)
24 VDC, supervised,
nonpower-limited
Basic System Connections
5-Zone Panel
Power Supply Connector
For more specific UL wiring
information, refer to page 35.
Important! Removing Ground Fault Disable
Jumper JP43 voids UL/NFPA Style/Class
indentifications for circuits. Remove jumper
JP43 only with the approval of the local AHJ
(Authority Having Jurisdiction).
Special Application
DC Power Outputs 24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay
EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.5 amp maximum) to
smoke detectors (IDC). Supervision
required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC
filtered, power-limited (0.5 amp maximum).
Supervision required. Nonresettable
Power suitable for powering smoke
detectors.
Configure TB9, Terminals 1 & 2 as
Resettable or Nonresettable Power.
• Resettable Power - jumper JP31 pins 2
& 3
• Nonresettable Power - jumper JP31 pins
1 & 2 (as shown)
4
3
2
1
{
{
Notification Appliance Circuits (see note 1)
Special Application Power
NAC #1, #2, #3, & #4, Style Y (Class B) (Supervised, Power-
Limited) (See Style Z illustra ted near right edge of board.)
4.7Kohm, ½ watt End-of-Line Resistor
PN 71252
NAC #1 NAC #2 NAC #3 NAC #4
Special Application
Power
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power-Limited) (See
Style D illustrated near
right edge of board.)
4.7Kohm, ½ watt End-of-
Line Resistor
PN 71252
Initiating Device Circuits
Push switch down to
upgrade software
ms-5udlayout.wmf
10 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
4
6
6
4
T
B
6
Z
O
N
E
6
Z
O
N
E
7
Z
O
N
E
8
Z
O
N
E
9
Z
O
N
E
1
0
S
W
1
TB4
/
T
B
6
1
/
6
2
/73/85/
1
0
4
/
9
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(C/E) = 3 amps max. per
NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page34.
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(E)
18 Amp Hour max. for MS-10UD-7C
Dummy load all unused circuits
with 4.7K, ½ watt End-of-Line
resistors
Style Z (Class A) NAC
Style D (Class A) IDC
Class A Converter Module
3 Programmable Relays
Nonsupervised relay contacts
Contact Ratings
2.0 amps @ 30 VDC (resistive)
0.5 amp @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble, or supervisory activity)
A Fail Safe Trouble relay switches to
the NC position during trouble
conditions and under loss of all
power.
(*Factory default relay programming)
Alarm*
Trouble*
Supervisory*
Remote
Synchronization
Output (see note 2)
Special Application Power
24 VDC filtered, supervised,
and power-limited. 0.040 amp
maximum. Requires 4.7K
ohm ELR.
Class A Converter Module
Remove jumper JP43 to
disable Ground Fault
Detection circuit (only with
approval of AHJ)
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Cut this jumper to
enable Supervisory
Relay when 4XTMF
module is installed
Auxiliary
Trouble Input
Kiss-off LED
Secondary Phone
Active LED
Primary Phone
Active LED
Primary
Secondary
ANN-SEC
option card connector
USB port for local programming using a
personal computer and PK-5X Utility
DACT Phone Line Jacks
Nonpower-Limited
Battery (see note 3)
24 VDC, supervised,
nonpower-limited
Basic System Connections
10-Zone Panel
Power Supply Connector
For more specific UL wiring
information, refer to page 35.
Important! Removing Ground Fault Disable
Jumper JP43 voids UL/NFPA Style/Class
indentifications for circuits. Remove jumper
JP43 only with the approval of the local AHJ
(Authority Having Jurisdiction).
Special Application
DC Power Outputs 24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay
EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.5 amp maximum) to
smoke detectors (IDC). Supervision
required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC
filtered, power-limited (0.5 amp maximum).
Supervision required. Nonresettable
Power suitable for powering smoke
detectors.
Configure TB9, Terminals 1 & 2 as
Resettable or Nonresettable Power.
• Resettable Power - jumper JP31 pins 2
& 3
• Nonresettable Power - jumper JP31 pins
1 & 2 (as shown)
4
3
2
1
{
{
Notification Appliance Circuits (see note 1)
Special Application Power
NAC #1, #2, #3, & #4, Style Y (Class B) (Supervised, Power-
Limited) (See Style Z illustrated near right edge of board.)
4.7Kohm, ½ watt End-of-Line Resistor
PN 71252
NAC #1 NAC #2 NAC #3 NAC #4
Special Application
Power
IDCs 1 through 5, Style B
(Class B) (Supervised,
Power-Limited) (See
Style D illustrated near
right edge of board.)
4.7Kohm, ½ watt End-of-
Line Resistor
PN 71252
Initiating Device Circuits
Push switch down to
upgrade software
Special Application Power
IDCs 1 through 5, Style B
(Class B) (Supervised, Power-
Limited) (See Style D
illustrated near right edge of
board.)
4.7Kohm, ½ watt End-of-Line
Resistor
PN 71252
Initiating Device Circuits
ms-10udlayout.wmf
MS-10UD Series Main Circuit Board
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 11
-
+-+
JP1
JP3
SW1
JP4
TB3
TB4
TB2
ENABLE
AC DELAY
16 HR DELAY
TENS
ONES
CUT FOR 240VAC
GND FLT DISABLE
AM-1 ENABLE
ADDRESS
ON OFF
AM-1
JP5
JP2
F1
F2
J4
J1 J2
J3
F3
TB1
HOT
OUT
+
BAT
+
OUT
-
BAT
-
EARTH
NEUT
1
5
1
5
A- B- A+ B+
NC NO C
043
9
261578121315
14
10
1104
3
9
261
578
121315
14
10
11
TB1
TBL
J1
J2
7 6 5 1
POWER LIMITED
Sw1
P1
P2
P3
P4
110
11
20
21 30
31
40
1 2 3 4 5
ALARM
TROUBLE
FIRE ALARM ANNUNCIATOR
A
C
K
S
T
E
P
TB1
J1
SW1
JP2
ANN-BUS
1 2 3 4 5 6 7 8
TB6
TB3
TB5
TB4
TB2
Alarm
Silenced
Earth Fault
ZONE 1
ALM
TBL
SUP
1
ZONE 6
ALM
TBL
SUP
6
NAC 1
Fault
Battery
Fault
ZONE 2
ALM
TBL
SUP
2
ZONE 7
ALM
TBL
SUP
7
NAC2
Fault
Charger
Fault
ZONE 3
ALM
TBL
SUP
3
ZONE 8
ALM
TBL
SUP
8
FIRE ALARM ANNUNCIATOR
NAC 4
Fault
ZONE 5
ALM
TBL
SUP5ALM
TBL
SUP
NAC 3
Fault
Disabled
ZONE 4
ALM
TBL
SUP
4
ZONE 9
ALM
TBL
SUP
9
F
ROM AP PHONE PS
TN TO AP
O
UT NC
OUT N
O
INPUT TAMPER GND +12/24
V
P4CN2P5P6
P7P
8
P9P10
P11P1
2
CHG-120 Charger
Doc. #
ANN-BUS - TB3
Battery Connector - J12
510udperi.wmf
ANN-80(C)
LCD Text Annunciator/Indicator
Doc. #
ANN-I/O
LED Driver
Doc. #
ANN-S/PG
Printer Driver
Doc. #
CHG-75 Charger
Doc. # 51315
ANN-(R)LED
LED Display
Doc. #
ANN-RLY
10 Form-C Relay Card
Doc. #
4XTM
Reverse Polarity Module
J4 & J5
IPDACT
Internet Communicator
Doc. #53109
J8 & J9 Telephone Connections
USB
Local PC
12 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014

Section 1: Product Description

The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone F ACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise specified. The combination control and digital communicator panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s i transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervi­sory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately
o
F (refer to System Sensor i3 Installation and Maintenance Instructions). In addition, the control
45 panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Fire•Lite Device Compatibility Document for a complete listing of compati­ble devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application reset­table and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery level and telephone line integrity. Available accessories include local and remote upload/download soft­ware, remote annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone net­work. Local programming interrogation is also possible using the PS-Tools and the USB port on the FACP. Any personal computer with Windows of 2400 baud and PS-Tools may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.
3
detectors which are conventional smoke detectors that can
®
XP or newer, compatible modem with a speed
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, display alarm informa­tion on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 13
Product Description Product Features
The following versions of the MS-5UD and MS-10UD are available:
FACP Version Description
MS-5UD-3 Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-5UD-7 Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
MS-5UD-7C Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current. Includes built-in ANN-LED Annunciator . This panel is approved for Canadian applications
MS-5UD-3E Five Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-5UD-7E Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
MS-10UD-3 Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-10UD-3E Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps total 24
VDC output current
MS-10UD-7 Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
MS-10UD-7C Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current. Includes built-in ANN-LED Annunciator . This panel is approved for Canadian applications.
MS-10UD-7E Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps total 24
VDC output current
NOTE: Unless otherwise specified, the information in this manual applies to all versions of the panels.

1.1 Product Features

Built-in DACT (Digital Alarm Communicator/Transmitter)
Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD - five programmable IDCsMS-10UD - ten programmable IDCs
Four Style Y (Class B) NAC (Notification Appliance Circu it) ­special application power
Three programmable Form-C relays
Built-in Programmer
Touchtone/Rotary dialing
Programmable Make/Break Ratio
Optional Dress Panel: DP-51050
A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED Annunciator module
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
ANN-BUS for connection to optional:
ANN-80 Remote LCD AnnunciatorANN-I/O LED DriverANN-S/PG Printer Module
14 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Specifications Product Description
ANN-RLY Relay Module
ANN-LED Annunciator Module
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History log with 256 event storage
Control Buttons
ACK (Acknowledge)Alarm SilenceSystem Reset/Lamp TestDrill
LED Indicators
Fire AlarmSupervisoryTroubleAC PowerAlarm SilencePrimary and Secondary Phone Line Active LEDs
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:
Silence Inhibit Auto-Silence Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)Selective Silence (horn-strobe mute)Temporal or Steady SignalSilenceable or Nonsilenceable
Automatic battery charger with charger supervision
Silent or audible walktest capabilities
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program and data
Optional CAC-5X Class A Converter Module for NACs and IDCs
Optional 4XTMF Transmitter Module
Optional ANN-SEC card for a secondary ANN-BUS

1.2 Specifications

NOTE: For wiring specifications, refer to“Wire Requirements” on page 132.
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-5UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-10UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 15
Product Description Specifications
MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
2
Wire size: minimum #14 AWG (2.0 mm
) with 600V insulation
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp Supervised, nonpower-limited Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-5UD-7C, MS -10UD­3(E), and MS-10UD-7C, and 26 Amp Hour battery for MS-5UD-7(E) and MS-10UD-7(E) [two 18 Amp Hour batteries can be housed in FACP cabinet. Larger batteries require a separate battery box such as the BB-26 or BB-55F and the CHG-75 or CHG-120F Battery Charger.] Minimum Battery Size: 7 Amp Hour (12 Amp Hour for MS-5UD-7C & MS-10UD-7C)
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD) Alarm Zones 6 - 10 on TB6 (MS-10UD only) Supervised and power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms (700 ohms per zone for linear heat detection - See Section 2.3, “Input Circuits” for more information.) End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Standby Current: 2 mA Refer to the Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB7
Four NACs Operation: Style Y (Class B) Special Application power Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC) End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Refer to the Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors Power-limited Circuitry Refer to the Fire•Lite Device Compatibility Document for compatible listed devices
16 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Specifications Product Description
Special Application Resettable or N o nre se tt a bl e Pow e r - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA Power-limited Circuitry Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable powerJumper pins 2 & 3 on JP31 for resettable power
Refer to the Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Primary ANN-BUS Power - TB3
Operating voltage: Nominal 24 VDC Maximum Available Current: 500mA Power-limited circuit
Special Application Secondary ANN-BUS Power - ANN-SEC - TB1
Operating voltage: Nominal 24 VDC Maximum Available Current: 500mA Power-limited circuit
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS-5UD-3(E), MS-10UD­3(E) (refer to
“Remote Synchronization Output” on page 34)
24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7K Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an external device for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits. All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 17
Product Description Specifications
TB9
TB5
TB7
TB3
TB2
TB1
Figure 1.1 Current Availability with FACP and FLPS-3 Power Supply
powerdist510.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application Nonresettable or Resettable Power
Special Application Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
Alarm
3.0 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
Remote
Synchronization
Output
0.040 amp max
per circuit
ANN-SEC
Option Card
0.5 amp max
per circuit
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-3 power supply. This applies to the MS-5UD-3, MS-10UD-3, MS-5UD-3E, and MS-10UD-3E.
18 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Specifications Product Description
TB9
TB5
TB7
TB3
TB1
Figure 1.2 Current Availability with FACP and FLPS-7 Power Supply
powerdistmrp.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application Nonresettable or Resettable Power
Special Application Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
Alarm
7.0 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
0.5 amp max
per circuit
ANN-SEC
Option Card
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-7 power supply. This applies to the MS-5UD-7, MS-5UD-7C, MS-10UD-7, MS-10UD-7C, MS-5UD-7E, and MS-10UD-7E.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 19
Product Description Controls and Indicators
SYSTEM ALL NORMAL
10:00A 012105
Figure 1.3 Membrane/Display Panel
9050udkypd.cdr

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED back­light will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
LED Indicators
LEDs are provided to annunciate the following conditions:
Fire Alarm - red LED
Supervisory - yellow LED
AC Power - green LED
System Trouble - yellow LED
Alarm Silence - yellow LED
Primary Phone Line Active (on circuit board) - red LED
Secondary Phone Line Active (on circuit board) - red LED
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process monitor and supervisory conditio ns as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off
Process Monitor - pulse ¼ second on and ¼ second off
20 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Digital Alarm Communicator/Transmitter Product Description

1.4 Digital Alarm Communicator/Transmitter

T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the fol­lowing functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
®
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA-DCS-8SIA-DCS-20
, programmable to rotary

1.5 Components

Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and wir­ing interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied
standard with a modified dress panel and one ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS­10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condi­tion exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 21
Product Description Optional Modules and Accessories
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display and provides remote RESET, SILENCE, ACKNOWLEDGE, and DRILL.
ANN-80C LCD Indicator (Canadian applications)
The ANN-80C is a remote LCD indicator which mimics the information displayed on the FACP LCD display but does not allow remote control of the FACP.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. ANN-LED module is installed in dress panel for Canadian version.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for Cana­dian applications requiring remote annunciation.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. The Canadian version is supplied standard with a modified dress panel.
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the cab­inet.
Battery Box
The BB-26 or BB-55F battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP bat­tery charger must be disabled, through software programming, when using the CHG-75. The char­ger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the F ACP. The FACP battery charger must be disabled, through software programming, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using a BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
22 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Telephone Requirements and Warnings Product Description
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible personal computers (PC), running Windows program files can also be created and stored on the PC and then downloaded later to the control panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “Remote Download” on page 113). Remote interrogation of panel pro­gramming, history logs, detector status, etc., is possible without enabling the remote download option.

1.7 Telephone Requirements and Warnings

1.7.1 Telephone Circuitry

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
®
XP (or newer). FACP

1.7.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-5UD/MS-10UD FCC Registration Number: 1W6AL00B10UD Ringer Equivalence: 0.0B
Important! The DACT must not
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, com­puter modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these
be used to dial a phone number that is call-forwarded.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 23
Product Description Telephone Requirements and Warnings
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to “Digital Communicator” on page 36 for an illustration of the proper installation of this equipment.

1.7.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be pro vid ed except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same tele-
phone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACTA. This equip­ment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.

1.7.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements docu­ment(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility des­ignated by the supplier. Any repairs or alterations made by the user to this equipment, or equip­ment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspections authority, or electrician.
24 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Telephone Requirements and Warnings Product Description
“The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termi­nation of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emis­sions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Road Woodbridge, Ontario L4L7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: 2132A-10UD Ringer Equivalence Number (REN): 0.0B Load Number: 2
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 25

Section 2: Installation

!
mounting studs
mounting slots
mounting tabs
mounting holes
grounding stud: attach solid earth ground wire (refer to Figure 2.4 on page 29)
MS-5UD Board on Chassis
MS-5UD Backbox
Figure 2.1 Chassis Mounting in Backbox
5udbrdinbox.wmr
mounting slots
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Backbox Mounting

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2 on page 27.
Install center top fastener in the wall with the screw head protruding.Place backbox over the top screw, level and secure.Mark and drill the left and right upper and lower mounting holes.
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
Install remaining fasteners and tighten.
26 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Backbox Mounting Installation
9050UDencl.wmf
Figure 2.2 Cabinet Dimensions
Hinge Slot for optional Dress Panel
Semi­Flush mounting hole
Mounting slots for optional Trim Ring
Hinge Slot for optional Dress Panel
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 27
Installation Operating Power
!
Figure 2.3 Backbox and Battery Box
9050UDcab2.wmf
Door = 19.26” (48.92 cm) Backbox = 19.0” (48.26)
Door = 16.821” (42.73 cm) Backbox = 16.65” (42.29 cm)
Depth = 5.207” (13.23 cm)
Depth = 5.257”
(13.353 cm)
Top
Left Side
Right Side
Bottom

2.2 Operating Power

WARNING: RISK OF ELECTRICAL SHOCK AND/OR EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the sec­tion titled “Specifications” on page 15, for power and current requirements for each FACP version. Run a pair of wires (with ground conductor) from the protected premises main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14
2
AWG (2.00 mm
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment
28 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Operating Power Installation
!
Figure 2.4 Operating Power Connections
AC Power
Hot (L1)
Earth
Neutral (L2)
Ground Stud
J12
to batteries
5ud_10udacpower.wmf
+
-
Ground Stud
J12
to batteries
+
-
FLPS-7
Power Supply
FLPS-3
Power Supply
AC Power
AC Hot
AC Neutral
Earth
MS-5UDC-7(C)(E)
MS-10UD-7(C)(E)
MS-5UD-3(E)
MS-10UD-3(E)
may be connected to this circuit. In addition, this circuit must be provided with overcurrent protec­tion and may not contain any power disconnect devices. An Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth
2
Ground wire [minimum 14 AWG (2.00 mm
)] to the grounding stud in the backbox and then run
the wire to TB1. Do not use conduit for the Earth Ground connection since this does not provide
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Conn ect the battery cable to J12 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
WARNING: SULFURIC ACID
BATTERIES CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 29
Installation Input Circuits
Figure 2.5 IDC Connections
Class B Initiating Device Circuits (supervised and power-limited) 4.7 K, ½ watt resistor P/N:71252
UL listed compatible 2-wire smoke detectors
manual pull stations
heat detectors
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
ms-10UDidc.wmf
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
UL listed compatible 4-wire smoke detector

2.3 Input Circuits

The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each cir­cuit is compatible with System Sensor’s i when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient tempera­ture falls below the detector rating of approximately 45 each IDC is 100 ohms (700 ohms per zone for linear heat detection). Do not use 2-wire smoke detectors on input zones used for linear heat detection. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to “CAC-5X Class A Converter Module” on page 37.
3
smoke detectors which generate a maintenance signal
o
F. The maximum loop resistance limit for
3
smoke detectors, any
30 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Input Circuits Installation
Class B Initiating Device Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
In-Line-Resistor
1.2 K, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Supervisory Switch
(tamper)
ms10udcomboIDC.wmf
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distin guish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before the
In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6
Program the FACP Initiating Device Circuit as a Combination circuit as described in “Input
Zones” on page 61. Note that since a Waterflow Supervisory Switch is included in a Combination circuit, the waterflow delay must be taken into consideration. Refer to “Wat erflow Delay” on page 71.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition is cleared) if the Combo Autoresettable Supervisory type code is selected
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 31
Installation Output Circuits
Figure 2.7 NAC Connections
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
Dummy load any unused circuits (P/N: 71245)
Polarized Bell
Polarized Strobe
Polarized Horn Polarized Horn
Polarized Horn-Strobe
Polarized Bell
Notification Appliance Circuit polarity shown in alarm condition
ms-10UDnac.wmf
+ - + -
Ferrite Bead
p/n 50116546-001

2.4 Output Circuits

2.4.1 Notification Appliance Circuits

T otal current drawn from the four Style Y (Class B) Notification Appliance Circuits as well as other DC power outputs cannot exceed 3.0 amps for the MS-5UD-3(E), MS-10UD-3(E) [2.5 amp maxi­mum per NAC] powered by the FLPS-3 power supply or 7.0 amps for the MS-5UD-7(C/E), MS­10UD-7(C/E) [3.0 amps maximum per NAC] powered by the FLPS-7 power supply (refer to “Power Supply Calculations” on pag e 116). Each circuit is super vised , po wer-limited and provides special application power. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing the optional Class A Converter mod­ule. Refer to “CAC-5X Class A Converter Module” on page 37.
For FCC compliance with Class B wiring, a ferrite bead (supplied) is required for NAC 1 and for NAC 2. If using both NAC 1 and NAC 2 with Class B wiring, a single ferrite may be used with wiring as shown in Figure 2.7.
32 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Output Circuits Installation
Figure 2.8 Special Application Auxiliary Power
Special Application 4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from these terminals (power-limited)
Special Application Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be obtained from these terminals (power-limited)
• Jumper JP31 pins 1 & 2 for nonresettable power (as illustrated in figure to right)
• Jumper JP31 pins 2 & 3 for resettable power
­+
­+
ms-10UDtb9.wmf
4 3 2 1
Figure 2.9 Relay Terminals
Note: Relay contacts are shown with
power applied to the panel and no active troubles, alarms or supervisories. The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.
ms10udrelay.wmf

2.4.2 Special Application DC Power Output Connections

Special Application Resettable and Nonresettable 24 VDC power is available on the MS-5UD and MS-10UD control panel.

2.4.3 Relays - Programmable

The MS-5UD and MS-10UD control panels provide a factory default programmed alarm relay, fail­safe trouble relay and supervisory relay. Each relay can be programmed to activate for other con­ditions (refer to “Relays” on page 69). Each Form-C relay is rated for 2 amps @ 30VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 33
Installation Output Circuits
Remote Power Supply
FACP main circuit board
4.7K ELR
Sync Input
Remote Sync Output
Figure 2.10 Remote Sync Output
10xudsync.wmf

2.4.4 Remote Synchronization Output

Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activat­ing strobes which must be synchronized to avoid random activation and a potential hazard to indi­viduals. Devices connected directly to the control panel’s NAC can be synchronized as described in “Synchronized NAC Operation” on page 68.
Notification appliances connected to remote power sources may require synchronization with the FACP’s devices. For the MS-5UD-3(E), MS-10UD-3(E), this can be accomplished by connecting the Remote Synchronization Output from TB2 of the FACP to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics the signal on NAC 1 (Out 1). This allows the devices connected to the power supply to be synchro­nized with the devices connected to Out 1 on the FACP.
For the MS-5UD-7(C/E), MS-10UD-7(C/E), the Remote Sync Output is not required. Synchroni­zation for remote power supplies is provided directly from NAC1 (Out 1). Note that NAC 1 (Out
1) must be programmed for sync operation when used for this purpose.
The Remote Synchronization Output is power-limited and supervised and requires a 4.7K ELR resistor at the remote power supply end of the wiring.
34 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Power-limited Wiring Requirements Installation
J13
Figure 2.11 Typical UL Power-limited Wiring Requirements
Power-limited Circuits
(Class 2)
Power-limited
Circuits
(Class 2)
Nonpower­limited Circuit
AC Power
CAC-5X
10udULwire2.wmf
4XTMF
CAC-5X
earth
ground
Nonpower­limited Circuit
Power-limited
Circuit
(Class 2)
MS-10UD FACP
Power-limited Circuits (Class 2)

2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim­ited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is illus­trated below.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 35
Installation Digital Communicator
Figure 2.12 DACT Installation
Customer Premises Equipment and Wiring
Telephone
Line
FACP with DACT
Network
Service
Provider’s
Facilities
Network
Demarcation
Point
RJ31X
Jack
Unused
RJ-11 Jack
Unused
J-11 Jack
Telephone
Telephone
Telephone
Answering
System
Fax Machine
Computer
9050ACTAdact.wmf
123
456
778
123
4
568
J8
J9
Figure 2.13 Wiring Phone Jacks
10UDJACK2.wmf
RJ31X
Jack
RJ31X
Jack
(Secondary Lines)
Incoming Telco
phone lines
(Primary Lines) Incoming Telco
phone lines
Ring
Ring
Ring
Tip
Tip
Tip
Green Wire Red Wire
to premise phones
Ring
Tip
Green Wire Red Wire
to premise phones
Note: Shorting bars
inside RJ31X Jack
removed during
male plug insertion
7 foot cable
MCBL-7
(ordered separately)
Primary phone line PH-1
Secondary phone line PH-2
Modular female connectors
Male plug
connectors
Primary phone line active LED
Secondary phone line active LED

2.6 Digital Communicator

T wo independent telephone lines can be connected to the control panel. Telephone line con­trol/command is made possible via double line seizure as well as usage of an RJ31X style intercon­nection. Note that it is critical that the panel's digital communicator be located as the first device
on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
The control panel's digital communicator is built into the main circuit board. Connection and wir­ing of two phone lines is required as shown below.
36 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Installation of Optional Modules Installation
!
Figure 2.14 CAC-5X Module Installation
MS-10UD Main Circuit Board
Metal Standoff
Plastic Standoff
CAC-5X Module
ms-10udcac5mnt.wmf
CAC-5X Module
Metal Standoff
Metal Standoff
Installation in MS-5UD or MS-10UD
Installation in MS-10UD

2.7 Installation of Optional Modules

WARNING: RISK OF ELECTRICAL SHOCK
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING MODULES OR WIRING.

2.7.1 CAC-5X Class A Converter Module

Installation
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module plugs into connector J2 which is located at the top left of the MS-5UD and MS­10UD main circuit board and J7 which is located at the top center of the MS-10UD. Note that two
CAC-5X modules are required to convert all NACs and IDCs on the MS-10UD to Class A circuits.
T o install the CAC-5X in the MS-5UD or MS-10UD, remove the two main circuit board mounting screws referenced in the following illustration and replace with the two supplied male/female standoffs in the locations indicated in the following figure. Carefully align the connector on the CAC-5X with J2 on the FACP main circuit board and press the module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to the standoffs with the screws that were just removed.
To install the second CAC-5X on J7 of the MS-10UD, remove the main circuit board mounting screw referenced in the following illustration and replace with the supplied male/female standoff. Insert the supplied plastic standoff in the location indicated in the following illustration. Carefully align the connector on the CAC-5X with J7 and press the module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to the metal standoff with the screw that was just removed.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 37
Installation Installation of Optional Modules
Figure 2.15 Wiring NACs and IDCs for Class A Operation
CAC-5X Class A Converter Module
MS-5UD Circuit Board
Class B (Style B) IDC - 4.7 K
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Dummy load all unused circuits - 4.7 K ½ watt resistor (P/N: 71245)
Polarized
Bell
Circuit polarities shown in alarm condition
Class A (Style Z) NAC
(supervised and power-limited)
Class A (Style D) IDC
(supervised and power-limited)
Polarized
Strobe
Polarized
Horn
Smoke
Smoke
Pull Station
Pull Station
Heat
Heat
ms10udclassa.wmf
B+ B- B+ B-
A+ A-
A+ A-
A+ A- A+ A- A+ A- A+ A- A+ A-
B+ B- B+ B- B+ B- B+ B- B+ B-
Ferrite Bead
p/n 50116546-001
Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the MS-5UD/MS-10UD and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits using TB4 of the MS-5UD/MS-10UD and TB1 of the CAC-5X. Note that the wiring will be identical when using TB7 NAC and TB6 IDC of the MS-10UD. Make certain to observe polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed and return for the positive side of a device and the B- and A- terminals must comprise the feed and return for the negative side of a device. To configure any of the zones for Class B when the CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-5X module. For FCC compliance with Class A wiring, a ferrite bead (supplied with the CAC-5X board) is required for NAC 1 and for NAC 2. If using NAC 1 and/or NAC 2 with Class A wiring, a ferrite must be used for each NAC with wiring as shown in Figure 2.15.
38 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Installation of Optional Modules Installation
S
W
1
Figure 2.16 4XTMF Option Module Connection to MS-5UD
J4
J5
Standoffs
ms-5board.wmf
Note: This illustration shows the installation of the Option Module on the 5-zone panel. The module is installed in the same location on the 10-zone panel.

2.7.2 4XTMF Option Module

The 4XTMF module can be plugged into connectors J4 and J5 on the main circuit board. The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing the modules.
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the placement of the 4XTMF option module.
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide the required earth ground protection.
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP main circuit board, being careful not to bend any pins.
5. Secure the option module to the standoff on the main circuit board with the supplied screws.
6. For proper 4XTM operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3.
7. When the installation has been completed, connect the wiring to the modules as indicated in the following sections.
8. Test system for proper operation.
4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 39
Installation Installation of Optional Modules
Figure 2.17 4XTMF Transmitter Module
Connect to FACP Connectors J4 & J5
Disconnect Switch shown in disconnect position
TBL Jumper
Remote Alarm - Class 2
(power-limited)*
Remote Trouble - Class 2
(power-limited)* No connection
Municipal Box (nonpower-limited)*
1+ 2­3+ 4­5 6+ 7-
Polarities are shown for module activation
Note: the 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal. For an application of reverse polarity of a supervisory signal, refer to the Appendix titled “FACP with Keltron” on page 131.
* Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7K, ¼ watt resistor) if Municipal Box is not connected.
Disconnect LED
4xtmf.wmf
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to pre­vent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.

2.7.3 ANN-SEC Option Card

The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.
1. Remove the chassis mounting screw to the right of TB3 and replace it with the supplied 0.5” x 4-40 male-female standoff.
2. Install the header into J13 on the main circuit board.
40 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
TB1
J1
ANN-SEC
FACP Circuit Board
connector to J13 on main circuit board
standoff and screw
Figure 2.18 Installing the ANN-SEC Option Card
ann-secinst.wmf
!
3. Secure the ANN-SEC to the circuit board with the supplied screw.

2.8 ANN-BUS Devices

WARNING: RISK OF ELECTRICAL SHOCK
Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.

2.8.1 ANN-BUS Wiring

Guidelines

A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485) terminals on TB3. A secondary communication circuit (EIA-485) for these devices is available at TB1 on the ANN-SEC card.
When using one ANN-BUS circuit, up to eight (8) annunciators can be supported.
When using both ANN-BUS communication circuits, the primary circuit supports up to three (3) annunciators and the secondary circuit supports up to (5) annunciators. Compatible devices include:
– ANN-80 LCD Annunciator – ANN-80C LCD Indicator (Canadian Applications) – ANN-S/PG Serial/Parallel Printer Interface Module – ANN-I/O LED Driver Module – ANN-LED Annunciator Module – ANN-RLY Relay Module (can be mounted in the FACP chassis)
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in the system.
The panel is capable of operating a primary ANN-BUS (TB3) and a secondary ANN-BUS (TB1 on ANN-SEC card) simultaneously.
This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B). The length of the 4-conductor wire run is governed by the power pair loading as described below.
Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 41
wiring distance that can be used with FACP ANN-BUS accessory modules.
Installation ANN-BUS Devices
T o calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is nec­essary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the following table:
ANN-80(C) LCD Annunciator/Indicator 0.040 amps ANN-S/PG Serial/Parallel Printer Interface Module 0.040 amps ANN-I/O LED Driver Module 0.200 amps ANN-LED Annunciator Module 0.068 amps ANN-RLY Relay Module 0.075 amps
1 Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.
After calculating the total worst case current draw, Table 2.1 specifies the maximum distance the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardles s of gauge us ed. The formula used to generate this chart is shown in the note below.
24 VDC Power Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case Current
Draw (amps)
0.100 1,852 ft. 4,688 ft. * 6,000 ft. * 6,000 ft.
0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.
0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.
Model Number
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Worst Case Current Draw
1
0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.
0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.
Table 2.1 Wiring Distances
The following formulas were used to generate the wire distance chart:
6.0 Volts
Maximum Resistance (Ohms) =
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)
(6,000 feet maximum)
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
=
Maximum Resistance (Ohms)
Rpu
*500
42 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
Wire Gauge Ohms per 1,000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum 24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:
Wire Gauge Maximum Wire Length
18 312 feet 16 497 feet 14 787 feet 12 1,250 feet
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
2 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
1 ANN-I/O LED Driver Module
The total worst case current is calculated as follows:
ANN-80 Current Draw = 2 X 0.040 amps = 0.080 amps ANN-S/PG Current Draw = 1 X.0.040 amps = 0.040 amps ANN-I/O Current Draw = 1 X.0.200 amps = 0.200 amps Total Worst Case Current Draw = 0.320 amps
Using this value and referring to the Wiring Distance Table 2.1 on page 42, it can be found that the available options are:
463 feet maximum using 22 Gauge wire1,172 feet maximum using 18 Gauge wire1,866 feet maximum using 16 Gauge wire2,953 feet maximum using 14 Gauge wire
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 43
Installation ANN-BUS Devices
Figure 2.19 FACP wiring to ANN-BUS Device on Primary ANN-BUS
FACP
ANN-80
ANN-BUS and power wiring are supervised and power-limited
TB3
Primary ANN-BUS
ann80to5x.wmf
TB1
J1
- + A B
ANN-SEC
Figure 2.20 FACP wiring to ANN-BUS Device on Secondary ANN-BUS via ANN-SEC
FACP
ANN-80
ANN-BUS and power wiring are supervised and power-limited
Secondary ANN-BUS
ann80to5x2.wmf
Wiring Configuration
Figure 2.19 illustrates the wiring between the F ACP’s Primary ANN-BUS and ANN-BUS devices.
illustrates the wiring between the FACP’s Secondary ANN-BUS, via the ANN-SEC option card, and ANN-BUS devices.
44 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
Figure 2.21 Powering ANN-BUS Devices from FCPS-24FS6/8
ANN-80
MS-5UD/MS-10UD
FCPS-24FS6/8
+24 VDC
-24 VDC
ANN-BUS
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
ANN-BUS and power wiring are supervised and power-limited
TB3
ann80tofcps5x.wmf
Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.21 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN-BUS power requirements.

2.8.2 ANN-BUS Device Addressing

Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the F ACP. A 5-position DIP switch on each device is used to set this address. The address set for these devices must also be programmed at the FACP for the specific device (refer to the programming section titled “ANN-BUS” on page 75).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device addresses do not need to be sequential and can be set to any number between 01 and 08. Note that 00 is not a valid address. The following table shows the DIP switch setting for each address.
NOTE: address (ID Number) DIP switches on some devices may have more than 5 switch positions. Unless otherwise specified in the documentation supplied with each device, switch positions 6 and above must be set to OFF.
Address Switch 5 Switch 4 Switch 3 Switch 2 Switch 1
not valid OFF OFF OFF OFF OFF 01 OFF OFF OFF OFF ON 02 OFF OFF OFF ON OFF 03 OFF OFF OFF ON ON
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 45
Installation ANN-BUS Devices
Key switch shown in ON position
Press in latch and Pull annunciator cover open
Annunciator cover with LCD display
Annunciator backplate
ann-80_iso.wmf
04 OFF OFF ON OFF OFF 05 OFF OFF ON OFF ON 06 OFF OFF ON ON OFF 07 OFF OFF ON ON ON 08 OFF ON OFF OFF OFF

2.8.3 ANN-80(C) Remote Fire Annunciator/Indicator

The ANN-80(C) Annunciator/Indicator is a compact, 80 character, backlit LCD remote fire annun­ciator which mimics the FACP display. It also provides system status indicators for AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. The ANN-80 Annunciator provides buttons for remote Reset, Silence, Acknowledge, and Drill of the FACP. The ANN-80C Indicator does not provide these buttons. Communication between the ANN-80(C) and FACP is accom­plished over a two wire serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, fil­tered, power supply.
Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mATrouble: 39.0 mAAlarm: 40.0 mAAC Fail ( not backlit): 15.0 mA
For use indoors in a dry location
Installation
Ensure that all power (AC and DC) has been removed from the F ACP before installing the annunci­ator.
Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the termi­nal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
46 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
Annunciator mounted on
surface wedge from the
ANN-SB80KIT
Annunciator mounted on
surface backbox from the
ANN-SB80KIT
Annunciator mounted on
stacked surface wedge
and backbox from the
ANN-SB80KIT
ann80kitmount.wmf
wiring channel
wires
TB1
ann-80boxinside.wmf
Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box. Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of installation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit comes with a surface backbox and surface wedge for angled viewing. The two pieces can be used separately or can be stacked together.
The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has been mounted.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 47
Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal block TB1.
2. Remove appropriate amount of wire insulation.
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B). Make certain to connect A to A and B to B.
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals 3 & 4. Make certain to connect A to A and B to B.
Installation ANN-BUS Devices
Figure 2.22 ANN-80 Wiring to FACP
FACP
ANN-80
ANN-BUS and power wiring are supervised and power-limited
4 3 2 1
TB3
Primary ANN-BUS
ann80to5x.wmf
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+). Make certain to observe proper polarity.
6. If appropriate, connect the power wiring going to the next device to terminals 1 (-) & 2 (+). Make certain to observe proper polarity.
7. After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any excess wire pushed back through hole into electrical box.

2.8.4 ANN-S/PG Serial/Parallel Printer Interface Installation

The following table shows the ANN-80 connections to the MS-5UD/MS-10UD.
MS-5UD/MS-10UD (TB3) ANN-80 (TB1)
Terminal 4 GND (-) Terminal 1 (-) Terminal 3 PWR (+) Terminal 2 (+) Terminal 2 A (ANN-BUS) Terminal 3 (A) Terminal 1 B (ANN-BUS) Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via FACP programming. Refer to the programming section titled “ANN-BUS” on page 75 in this manual for detailed programming information. Select the LCD option for programming.
The ANN-S/PG Serial/Parallel Printer Interface module allows the ancillary connection of a serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. Proceed with the installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
48 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
Figure 2.23 ANN-S/PG Connection to FACP
ANN-S/PG Module
Cable
Connectors
for connection
to printer
Parallel
Serial
ANN-BUS and power wiring are supervised and power-limited
TB3
Primary ANN-BUS
Primary ANN-BUS
annspfto5x.wmf
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.23.
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module.
4. Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual (refer to“ANN-BUS” on page 75). Note that the Auto-configure feature allows the programmer to quickly bring all instal led ANN-BUS modules online (refer to“Auto-Configure” on page 76).
5. Connect a printer to the ANN-S/PG Parallel and/or Serial connectors (refer to Figure 2.23 on page 49).
Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32
o
F to 120oF (0oC to 49oC)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
PRN-6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes within the control panel and time-stamps the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section con­tains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configu­ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as a standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may be used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 f or further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable. One end of the cable will plug into the DB-25 connector on the PRN-6F printer and the other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the same time.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 49
Installation ANN-BUS Devices
Setting Printer Options
Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer menu controls. Set the printer options (under the menu area) as shown in the following table:
Option Setting Option Setting
Font HS Draft CPI 10CPI LPI 6 LPI Skip 0.5 ESC Character ESC Emulate Epson FX-850 Bidirectional Copy ON I/O CG-TAB Graphic Buffer 40K Country E-US ASCII Serial Auto CR OFF Baud 9600 or 2400 Color Option Not Installed Format 7 Bit, Even, 1 Stop Formien Protocol XON/XOFF Lines 6LPI=60 Character Set Standard Standard Exec 10.5 SI.Zero On
Auto LF On PAPER BIN 1 12/72” BIN 2 12/72” SINGLE 12/72” PUSH TRA 12/72” PULL TRA 12/72” PAP ROLL 12/72”
Table 2.2 PRN-6F Setup Options
50 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
Figure 2.24 ANN-I/O Board Layout
ANN-BUS (ID#) Address DIP switch
ANN-BUS Connector
Terminals not used (future)
anniobrd.wmf

2.8.5 ANN-I/O LED Driver Module

The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The following sections describe hardware installation. Refer to the section titled“ANN­BUS” on page 75 for programming information.
ANN-I/O Board Layout
Figure 2.24 illustrates the ANN-I/ O bo ard showing locations of screw terminals for connection to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID number.
Specifications
Max. ANN-BUS Voltage: 28 VDC
Max. Current:
Alarm: 200 mAStandby: 35 mAEach LED: 10 mA
Operating Temperature: 32
For indoor use in a dry location only
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 51
o
F to 120oF (0oC to 49oC)
Installation ANN-BUS Devices
Figure 2.25 ANN-I/O Connection to FACP
ANN-I/O Module
ANN-BUS and power wiring are supervised and power-limited
TB3
Primary ANN-BUS
ann-ioto5x.wmf
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.25. After the ANN-I/O is connected to the panel, it must be added to the system via FACP programming.
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10 LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so that there is approximately 10 mA of current for each LED. No series resistors are required. LED outputs are mapped to output circuits. Refer to the section titled “ANN-I/O LED Zone Assign­ments” on page 77 of this manual.
52 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
Figure 2.26 ANN-I/O Board Layout
ann-ioleds.wmf
The LEDs are wired as illustrated in Figure 2.26. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).

2.8.6 ANN-LED Annunciator Module

The ANN-LED annunciator module provides LED annunciation of general system faults and input zones when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones.
Canadian Applications: The ANN-LED is supplied standard with the MS-5UD-7C and MS-10UD­7C models. It is mounted to the dress panel included with these models.
Specifications
Max. ANN-BUS Voltage: 24 VDC
Max. Current:
Alarm: 68 mAStandby: 28 mA
Operating Temperature: 32
o
F to 120o F (0o C to 49o C)
For indoor use in a dry location only
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 53
Installation ANN-BUS Devices
Figure 2.27 ANN-LED Board Layout and Connection to FACP
FACP
ANN-LED
Primary ANN-BUS
+24 VDC
-24 VDC
ANN-BUS (ID#) Address DIP switch
TB3
annledto5x.wmf
Mounting/Installation
Install the ANN-LED Module as described in the documentation supplied with the annunciator.
ANN-LED Board Layout and Connection to FACP
Figure 2.27 illustrates the ANN-LED board wiring connections to the FACP.

2.8.7 ANN-RLY Relay Module

The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat­ible FACP.
Specifications
Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mAStandby: 15 mA
Relay Contact Ratings:
2 amps @ 30 VDC (resistive)0.5 amps @ 30 VAC (resistive)
Operating Temperature: 32
For indoor use in a dry location only
o
F to 120o F (0o C to 49o C)
54 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Devices Installation
mounting holes
mounting hooks through
mounting slots
grounding wire
ANN-RLY
ANN-MBRLY
mounting bracket
mounting holes
mounting holes
FACP Backbox Installation
using ANN-MBRLY mounting bracket
FACP Chassis Installation
mounting holes
mounting holes
ANN-RLY on ANN­MBRLY mounting bracket
ROME Series Installation
using ANN-MBRLY mounting bracket
Figure 2.28 ANN-RLY Mounting Options
ann-rlyinchassis.wmf
ann_mbriyincab3.wmf
rome-relay-plate3.wmf
Mounting/Installation
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis or inside the ROME Series enclosure. Refer to the ANN-RLY Installation Document #53033 for instructions on chassis mounting or to the ROME Series Installation Document #53530 for mounting in the sep­arate backbox.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 55
Installation ANN-BUS Audio Panel
Figure 2.29 ANN-RLY Board Layout and Connection to FACP
FACP
ANN-RLY
Primary ANN-BUS
+24 VDC
-24 VDC
ANN-BUS (ID#) Address DIP switch
TB3
ann-rlyto5x.wmf
!
ANN-RLY Board Layout and Connection to FACP
Figure 2.29 illustrates the ANN-RLY board wiring connections to the FACP.

2.9 ANN-BUS Audio Panel

WARNING: RISK OF ELECTRICAL SHOCK
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY WIRING.
The FACP must be enabled to communicate with the ACC-25/50ZS/T Audio Panel over the ANN­BUS (refer to “ANN-BUS Enabled” on page 75). This is accomplished by programming the Audio Panel ANN-BUS address into the FACP (refer to“BUS Modules” on page 75). For details on set­ting the ANN-BUS address and programming the audio panel, refer to the ACC-25/50ZS/T Series Audio Panel manual (document #51889).
The ACC-25/50ZS/T Series audio panel connects to the FACP via the ANN-BUS communication circuit. The five input zones on the MS-5UD correspond to the first five ACC-25/50ZS/T Series audio zones and the ten input zones on the MS-10UD correspond to the first ten ACC-25/50ZS/T Series audio zones. The programmer can select which of the five audio messages at the audio panel will play when an FACP input zone goes into alarm (refer to“ACC Message” on page 64). The
56 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
ANN-BUS Audio Panel Installation
A (+)
B (-)
FACP
ACC-ZPMK
on ACC-25/50ZST
-
+
Figure 2.30 FACP Connection to ACC-25/50ZS/T Audio Panel
Primary ANN-BUS
acczpmto5x.wmf
message will play over the corresponding audio panel output circuit. For example, if FACP Input Zone 3 goes into alarm, the programmed message will play over the ACC-25/50ZS/T output circuit
3. If two or more input zones are active at the same time, the highest priority message will turn on.
One of the F ACP input zones can be programmed as an All-Call Zone. If t his zone goes into alarm, all ACC-25/50ZS/T Series audio zones will activate (refer to“ANN-AUDIO Options Screen” on page 79).
A fault at the ACC-25/50ZS/T Series panel will cause the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault.
The only connection between the MS-5UD/10UD and the ACC-25/50ZS/T audio panel is a pair of communication wires connected between the A/B terminals on TB3 of the FACP and TB1 termi­nals 2 & 3 of the ACC-ZPMK module on the ACC-25/50ZS/T.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 57

Section 3: Programming

!
SYSTEM ALL NORMAL 10:00A 070707
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below:
Program feature or
option
Trouble Call Limit N Refer to “Trouble Call Limit (Dialer Runaway Prevention)” on
Permitted in UL
864? (Y/N)
Possible settings
page 89.
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period
Settings permitted in
UL 864
Trouble Call Limit = 0
for unlimited Central
Station trouble calls
Remote Download Y Refer to“Remote Download” on page 113.
Combo Y Refer to Table 3.1 on page 62. One Waterflow and one
Combo
w/AutoResettable
Superv
Y Refer to Table 3.1 on page 62. One Waterflow and one
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Remote Download Proprietary Yes for Proprietary system
intended to protect only
contiguous properties
Supervisory device
Supervisory device

3.1 User Programming

The MS-5UD/MS-10UD FACP is completely field programmable using the panel keypad and requires no special software skills.
CAUTION: FIRE PROTECTION ENABLED
WHILE PROGRAMMING THE FACP, THE FIRE PROTECTION CAPABILITIES OF THE CONTROL PANEL ARE INACTIVITY.
Site-specific programming may be accomplished in the following ways:
Manual programming or editing, using the FACP keypad
Remote Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based computer and modem. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming CD ROM can be ordered for this purpose
Local Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based computer and USB connection. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming CD ROM can be ordered for this purpose
ENABLED. PROGRAMMING MODE TIMES-OUT AFTER 10 MINUTES OF
The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below:
58 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Initial Power-up Programming
1=READ STATUS MODE 2=PROGRAMMING MODE 3=FUTURE USE 4=REMOTE DOWNLOAD
TROUBLE PULL STATION
ZONE 1 OPEN FAULT 09:03A 090909
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or super­visory event exists at the panel, the event must be cleared before entering Programming mode. To access any of the programming or read status features, the Enter or Mode key must be pressed, which will cause the LCD to display the following:
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta­tus Mode which allows the user to view the programmed features and status of the control panel The Read Status feature is not password protected. Refer to “Read Status” on page 105 for a detailed description of this feature.
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options.
Pressing 4 will select Remote Download which allows the user to enable the remote programming option. Refer to “Remote Download” on page 113.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Ten minutes of inactivity will also cause the panel to exit Pro­gramming Mode Note that the data which is entered during Programming mode is not saved until
the programmer exits this mode by r epeatedly pr ess ing the ‘ESC’ key. If the Reset key is pressed or power is lost before exiting Programming mode, all data just entered will be lost.
User Programming Levels
There are two user programming levels:
User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change.

3.2 Initial Power-up

The following sections describe the initial programming procedures for a new system. The same procedures are used to modify programming in an existing system.
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an example of a possible trouble message that may be displayed.

3.3 Programming Screens Description

Three options are available when the Enter key is pressed: Read Status, Programming, and Remote Download Mode. The Read Status and Programming options have multiple functions or features which may be chosen. T o view all of the choices, it is neces sary that the programmer scroll through
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 59
Programming Programming and Passwords
1=READ STATUS MODE 2=PROGRAMMING MODE 3=FUTURE USE 4=REMOTE DOWNLOAD
PROGRAMMING
ENTER PASSWORD

PROGRAMMING 1=INPUT ZONES 2=NACS 3=RELAYS
PROGRAMMING 1=INPUT ZONES 2=HISTORY 3=WALKTEST
a number of additional subscreens. These selections are displayed on multiple screens to make them more readable for the programmer. Refer to “Master Programming Level” on page 61, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the pro­grammer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the pro­grammer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is follo wed to view all option choices.

3.4 Programming and Passwords

There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored in non­volatile memory . The factory set passwords can be changed by the user as described in “Password Change” on page 92. If an invalid password is entered, the blinking cursor will return to the first password character position. T o exit Programming or Read Stat us mode at any time, press the ESC (Escape) key repeatedly . Note that Programming mode must be exited using the ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved.
T o access user Programming mode, press the Enter or Mode key. The LCD will display the follow- ing:
To enter the user Programming mode, press 2. The display will read as follows:
Entering the Master
If the Maintenance
level password (default 00000) will cause the following screen to appear:
level password (default 11111) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key.
60 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
PROGRAMMING 1=INPUT ZONES 2=NACS 3=RELAYS
Programming Screen #1
PROGRAMMING 1=SYSTEM SETUP 2=OPTION MODULES 3=HISTORY
PROGRAMMING 1=WALKTEST 2=CLEAR PROGRAM 3=PASSWORD CHANGE
Programming Screen #2
Programming Screen #3
PROGRAMMING 1=INPUT ZONES 2=NACS 3=RELAYS
Programming Screen #1
INPUT ZONES 1=ZONE 1 2=ZONE 2 3=ZONE 3
Input Zone Screen #1
PULL STATION

ZONE 1 PRESS TO EDIT
Edit Input Zone Screen #1

3.5 Master Programming Level

When the Master Program Level password is entered, the control panel will enter user Program­ming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the sys­tem Trouble LED flashes until Programming mode is exited. The following display will appear:
The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the dis­play, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen.

3.5.1 Input Zones

The Input Zones option allows the user to initially program or change the programming for the five input zones (circuits) on the MS-5UD or the ten input zones (circuits) on the MS-10UD. Pressing 1, while viewing Programming Screen #1, will select the Input Zones option and display a screen similar to the following:
Pressing the down arrow key will display additional screens for Input Zones 4 through 5 in the MS­5UD or Input Zones 4 through 10 in the MS-10UD. To program a specific zone, press the number key corresponding to the desired zone while viewing one of the Input Zone screens. To program Input Zone 1, press the 1 key while viewing Input Zone Screen #1. The following screens will be displayed:
To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to view the Edit Zone screens.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 61
Programming Master Programming Level
INPUT ZONE 1 1=ENABLED YES 2=TYPE PULL STATION 3=VERIFICATION NO
Edit Input Zone Screen #2
INPUT ZONE 1 1=PAS/PRE-SIG DELAY NO DELAY
Edit Input Zone Screen #3
Edit Input Zone Screen #5
INPUT ZONE 1 1=ADJECTIVE/NOUN 2=DESCRIPTION

INPUT ZONE 1 1=FREEZE SUPV. NO
2=ACC MSG# 2
Edit Input Zone Screen #4
INPUT ZONE 1=ENABLED 2=TYPE 3=VERIFICATION
Edit Input Zone Screen #2
ZONE TYPE 1=PULL STATION 2=WATERFLOW 3=WATERFLOW NS
Zone Type Screen #1
The following examples show the editing of Input Zone 1:
Enable/Disable Zone
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the zone will be disabled by the control panel, preventing the circuit from reporting alarms and troubles to the panel. The control panel LCD will display the zone which has been disabled and FACP will turn on the Trouble LED.
Type
To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone Screen #2. This will cause the control panel to display the following Zone Type Screen:
62 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Pressing the down arrow key will display additional zone types as indicated in the following table. Some of the following Zone Types are not available for Canadian applications. Refer to “Canadian
Option” on page 74 for additional details.
Zone Type Action When Activated
Pull-Station Fire Alarm Waterflow Fire Alarm Delayed (uses waterflow delay) Waterflow Nonsilenceable Fire Alarm (uses waterflow delay) Combo Fire/Supervisory (uses waterflow delay) Combo AutoResettable Fire/Supervisory AR, nonlatching (uses waterflow delay) 2-Wire Detector Fire Alarm Normally Open Contact Fire Alarm Fire Fire Alarm Tamper Supervisory Supervisory Supervisory, latching Supervisory AutoResettable Supervisory, nonlatching Medic-Alert Supervisory, latching Hazard-Alert Supervisory, latching Tornado-Alert Supervisory, latching
Table 3.1 Zone Types
Master Programming Level Programming
INPUT ZONE 1=ENABLED 2=TYPE 3=VERIFICATION
Edit Input Zone Screen #2
INPUT ZONE # 1=PAS/PRE-SIG DELAY NO DELAY
Edit Input Zone Screen #3
PAS/PRE-SIG DELAY 1=NO DELAY 2=PRE-SIGNAL DELAY 3=PAS DELAY
PAS/Pre-Signal Delay Screen
Proc-Mon Piezo Procmon-AR Piezo, nonlatching AC-Loss-Mon Trouble Ack-Switch Acts like panel Acknowledge Key Sil-Switch Acts like panel Alarm Silence Key Drill-Switch Acts like panel Drill Key Reset-Switch Acts like panel Reset Key PAS-Bypass Positive Alarm Sequence Disable Drill-Switch AutoResettable Acts like panel Drill Key, nonlatching
Table 3.1 Zone Types
While viewing any Zone Type screen, select the type of zone being programmed by pressing the corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and indicate the selection next to the Type option.
NOTE: Almost any Input Zone type can activate an ACC-25/50ZST audio zone and output an
assigned message with the exception of ACKNOWLEDGE, SILENCE, RESET and PAS BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all of the corresponding ACC-25/50ZST audio zones to go active and will output Message 1.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen #2 so that the display reads Verificatio n On. Each time the 3 key is pressed, the display wil l togg le between Verification On and Verification Off. For a detailed description, refer to “Alarm Verifica- tion (None or One Minute)” on page 104.
Note that verification can only be enabled for a zone that is programmed as a smoke detector type. Zones programmed for any other type will not allow the Verification feature to be enabled. Do not
use the verification feature if a mix of smoke detectors and normally open contact devices are con­nected to the same zone.
PAS/Pre-Signal Delay
Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen:
Pre-signal
The Pre-signal option programs the zone to delay panel activation for a preprogrammed time delay of up to three minutes while allowing for visual verification by a person. Note that the alarm relay and communicator will respond to the initial alarm immediately. To enable the Pre-signal feature, press 2 while viewing PAS/Pre-Signal Screen. Refer to “Presignal” on page 102.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 63
PAS
The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation (includ­ing alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3 minutes. T o enable the PAS feature, press 3 while viewing the P AS/Pre-Si gnal Screen. This option is available only for circuits programmed as smoke detector circuits. Refer to “Positive Alarm
Programming Master Programming Level
INPUT ZONE # 1=FREEZE SUPV. NO 2=ACC MSG #
Edit Input Zone Screen #4
ACC MSG NUMBER 1=NO MSG-ACTIVE 2=NO MSG-INACTIVE 3=MESSAGE 1
ACC Message Screen #1
ACC MSG NUMBER 1=MESSAGE 2 2=MESSAGE 3 3=MESSAGE 4
ACC Message Screen #2
ACC MSG NUMBER 1=MESSAGE 5
ACC Message Screen #3
INPUT ZONE # 1=ADJECTIVE/NOUN 2=DESCRIPTION

Edit Input Zone Screen #5
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Adjective/Noun Screen

1=NORTH 2=SOUTH 3=EAST
Adjective Screen #1

1=WEST 2=FRONT 3=CENTER
Adjective Screen #3

1=REAR 2=UPPER 3=LOWER
Adjective Screen #5

1=MAIN 2=FIRST 3=2ND
Adjective Screen #7

1=3RD 2=4TH 3=5TH
Adjective Screen #2

1=FLOOR4 2=FLOOR5 3=ROOM
Adjective Screen #6

1=FLOOR1 2=FLOOR2 3=FLOOR3
Adjective Screen #4
Sequence” on page 103.
Freeze Supervision
Pressing 1 for Freeze Supv. while viewing Edit Input Zone Screen #4 programs the FACP to super- vise the devices connected to the selected zone for freeze conditions. Each press of the 1 key will toggle the display between Freeze Supv. Yes and No. The factory default setting is No Freeze Supervision.
ACC Message
Pressing 2 for ACC MSG # while viewing Edit Input Zone Screen #4 will cause the following screens to be displayed:
Using these screens, the programmer can assign an audio message to each input zone. The NO MSG-ACTIVE option is the factory default selection which means that no message has been pro­grammed for the input zone but its corresponding ACC-25/50ZST audio zone will turn on when this input zone goes active (if an input zone with a programmed audio message goes active, the message will also be played over this zone). The NO MSG-INACTIVE option will not turn on the corresponding ACC-25/50ZST audio zone when this input goes active. If MESSAGE 1 through 5 is the programmed option, the selected message will play when the FACP is connected to an ACC­25/50ZST Audio Panel via the ANN-BUS and the corresponding FACP input zone goes into alarm.
Adjective/Noun
The Adjective/Noun selection allows the programmer to enter specific descriptors about the detec­tor currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #4 will cause the following screen to be displayed:
Pressing 1 while viewing the Adjective/Noun Screen will cause the following screen(s) to be dis­played. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the detector currently being programmed. When an adjective has been selected, it will appear at the top of the display as indicated by the asterisks.
64 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Adjective/Noun Screen

1=BASEMENT 2=BOILER RM 3=CLASSROOM
Noun Screen #1

1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
Noun Screen #3

1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #5

1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #7

1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #2

1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #6

1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #4

1=ZONE
Noun Screen #8
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Adjective/Noun Screen
INPUT ZONE # 1=ADJECTIVE/NOUN 2=DESCRIPTION
Edit Input Zone Screen #4
ZONE # DESCRIPTION
PRESS ENTER IF DONE

Adjective/Noun Screen
Pressing 2 while viewing the Adjective/Noun Screen will cause the following screen(s) to be dis­played. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the detec­tor currently being programmed. When a noun has been selected, it will appear at the top of the display as indicated by the asterisks.
Pressing 3 or 4 while viewing the Adjective/Noun Screen will display screens similar to the previ­ous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns which have been programmed into the control panel by the user utilizing the PK-CD programming kit. These descriptors are selected as described in the previous sections.
Description
The Description selection allows the programmer to enter additional information about the zone currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Input Zone Screen #4 will cause the following screen to be displayed:
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A, and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Input Zone Screen #4, dis­playing the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Description, Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 65
Programming Master Programming Level
PROGRAMMING 1=INPUT ZONES 2=NACS 3=RELAYS
Programming Screen #1
NACS 1=NAC 1 3=NAC 3 2=NAC 2 4=NAC 4
NAC Selection Screen
NAC # 1=ENABLED YES 2=CODING STEADY
NAC Screen #1
NAC Screen #2
NAC # 1=SILENCE YES 2=AUTO SILENCE NO 3=SIL INHIBITED NO
NAC # 1=ENABLED 2=CODING STEADY
NAC Screen #1
If the zero key is then pressed a second time with no intervening key actions, the entire field is replaced with the field entered for the previous device programmed
, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one. If the last character is a letter, it changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last character are also numbers, they are also incremented (overflow)
The above increment function may be repeated with each press of the zero key
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the dis­play ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field.
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305.
4. Press the Enter key to store the information.

3.5.2 NAC (Notification Appliance Circuit)

The options for the NACs on the control panel main circuit board can be configured by pressing 2 while viewing Programming Screen #2. The following screens will be displayed:
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2 for NAC 2, 3 for NAC 3, or 4 for NAC 4.
To program an NAC circuit, press the number corresponding to the NAC to be programmed. The following screens will be displayed for each selection:
Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is enabled.
66 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA
Coding Screen #1
CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MIN
Coding Screen #2
CODING 1=SYNC SYSTEM SENSR 2=SYNC WHEELOCK 3=SYNC GENTEX
Coding Screen #3
CODING 1=SYNC FARADAY 2=SYNC AMSECO
Coding Screen #4
NAC Coding
The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #1 will cause the following displays to appear:
The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selections are:
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
T emporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
Two Stage 3 Minutes or 5 Minutes - refer to “Two Stage Operation” on page 68 for a description of this feature
Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to “Synchronized NAC Operation” on page 68 for additional information
Selection of one of the above options will cause the control panel to store the information in mem­ory and return the display to NAC Screen #1, which will display the new coding choice.
Two Stage Operation
Two Stage operation consists of the following:
1st stage output - 20 ppm (pulse-per-minute) coding
2nd stage output - Temporal coding as described above
Acknowledge button functions as the automatic alarm signal cancel button
If Two Stage operation is programmed as the Coding option, the following sequence of events will occur during an alarm.
1. The on-board NACs will activate with a 1st stage output upon activation of any alarm.
2. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not
been pressed,
all NACs presently in 1st stage activation will go to 2nd stage activation.
3. If an Acknowledge switch has been pressed, the Alarm LED will turn from flashing to steady. Any NACs currently in 1st stage activation will remain in 1st stage. Pressing the Acknowl­edge switch does not affect NACs already in 2nd stage activation.
4. If another alarm point is activated and the countdown timer is counting, the alarm point will have no effect on the NACs.
5. If another alarm point is activated and the countdown timer has stopped counting due to the Acknowledge switch being pressed, the countdown timer will restart and the NACs will respond as outlined in step 1. NACs already in 2nd stage activation will not be affected.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 67
Programming Master Programming Level
NAC # 1=SILENCE YES 2=AUTO SILENCE NO 3=SIL INHIBITED NO
NAC Screen #2
SILENCEABLE 1=SILENCEABLE 2=NON SILENCEABLE 3=SYNC MUTE
Silenceable Screen
Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is pa rticularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices.
Maximum Number of Strobes for Synchronization
The maximum current draw for a Notification Appliance Circuit cannot exceed 2.5 amps for mod­els with the FLPS-3 power supply or 3.0 amps for models with the FLPS-7 power supply (refer to the AC Power section under“Specifications” on page 15). Refer to the manufacturer’s documenta­tion supplied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.
T o ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following is a list of the strobes that have been tested with this FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum current is not exceeded:
Strobe Manufacturer
System Sensor 35 46 Wheelock 24 50 Gentex 22 39 Faraday 22 33 Amseco 19 34
FACP with FLPS-3 Power Supply:
Maximum Number of Strobes
FACP with FLPS-7 Power Supply:
Maximum Number of Strobes
Silence
Pressing 1 while viewing NAC Screen #2 will cause the following screen to be displayed:
Pressing 1 while viewing the Silenceable Screen will program the selected NAC as a silenceable circuit. This will allow the NAC to be silenced by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 2 while viewing the Silenceable Screen will program the selected NAC as a nonsilence­able circuit. This will prevent the selected main circuit board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 3 while viewing the Silenceable Screen will program the selected NAC as a synchronized mute circuit. Refer to “Synchronized NAC Operation” on page 68 for a description of synchroni­zation.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is pro­grammed for Sync Mute, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.
68 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
PROGRAM NAC # 1=SILENCEABLE YES 2=AUTO SILENCE NO 3=SIL INHIBITED NO
NAC Screen #2
AUTO SILENCE 1=NO 2=5 MINUTES 3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE 1=30 MINUTES
Auto Silence Screen #2
AUTO SILENCE 1=15 MINUTES 2=20 MINUTES 3=25 MINUTES
Auto Silence Screen #3
PROGRAMMING 1=INPUT ZONES 2=NACS 3=RELAYS
Programming Screen #1
RELAYS 1=RELAY 1 ALARM 2=RELAY 2 TROUBLE 3=RELAY 3 SUPERV
Relays Selection Screen
RELAY TYPE 1=ALARM 2=TROUBLE 3=SUPERVISORY
Relay Screen #1
RELAY TYPE 1=PROCESS MONITOR 2=AC LOSS 3=HAZARD
Relay Screen #3
RELAY TYPE 1=COMM FAIL 2=MEDICAL 3=SILENCEABLE ALARM
Relay Screen #2
Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the time delay before Auto Silence activation, press 2 while viewing NAC Screen #2. The following screens will be displayed:
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the number corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the disp lay will return to NAC Screen #1.
Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for a period of one minute. Resetting the FACP will also be prevented for one minute while the NAC programmed for silence inhibit is activated. Pressing 3 while viewing NAC Screen #2 will cause a screen to be displayed with the options 1=No Silence Inhibit and 2=1 Min. Silence Inhibit. Pressing 1 will disable the Silence Inhibit feature while pressing 2 will enable a 1 minute Silence Inhibit for the selected Output.

3.5.3 Relays

Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three main circuit board Form-C relays. The following screen will be displayed:
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following screens will appear for each relay to be programmed:
While viewing the selected screen, press the number corresponding to the desired relay type to pro­gram the main circuit board relay. The choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
NOTE: A relay programmed with the Silenceable Alarm type will deactivate when the FACP Alarm Silenced LED is illuminated.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 69

3.5.4 System Setup

System Setup allows the programmer to configure the following control panel features:
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and Waterflow time delay
Programming Master Programming Level
PROGRAMMING 1=SYSTEM SETUP 2=OPTION MODULES 3=HISTORY
Programming Screen #2
SYSTEM SETUP 1=TIMERS 2=BANNER 3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP 1=TROUBLE REMIND NO 2=CANADIAN OPTION OFF 3=CHARGR DISABLE NO
System Setup Screen #2
SYSTEM SETUP 1=TIMERS 2=BANNER 3=TIME-DATE
System Setup Screen #1
TIMERS 1=PAS DELAY 120 2=PRE SIGNAL 120 3=WATERFLW DELAY 0
Timer Screen #1
TIMERS 1=AC LOSS DELAY 2
Timer Screen #2
TIMERS 1=PAS DELAY 120 2=PRE SIGNAL 120 3=WATERFLW DELAY 0
Timer Screen #1
PAS DELAY
RANGE 000-180 SECONDS
PAS Delay Screen
Banner: This option allows the user to change the top two lines of the LCD display from the factory default readout, which is blank, to a user defined readout when the control panel is in Normal condition
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time feature into the FACP memory
Trouble Rem inder: This feature, when enabled, provides an audible reminder that an alarm or trouble still exists on the FACP after the control panel has been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If the Trouble Reminder feature is not
enabled and a trouble condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the central station if connected
Canadian Option: This option allows the automatic programming of the FACP to Canadian specifications (refer to “Canadian Option” on page 74).
Important! For Canadian Applications, this option must be set to ON prior to any other panel programming.
Charger Disable: This option allows the programmer to disable the onboard battery charger in the event an external battery charger is being used
Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following screens to be displayed:
Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing System Setup Screen #1. The following screen will be displayed:
PAS (Positive Alarm Sequence) Delay
The factory default setting for P AS is 000 for no delay . To select a PAS delay of 001 to 180 seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following dis­play will appear:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indi­cate the new delay time.
70 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
PRESIGNAL DELAY
RANGE 000-180 SECONDS
Pre-signal Delay Screen
TIMER 1=PAS DELAY 120 2=PRE SIGNAL 120 3=WATERFLW DELAY 0
Timer Screen #1
WATERFLOW DELAY
RANGE 00-90 SECONDS
Waterflow Delay Screen
TIMER
1=AC LOSS DELAY 2
Timer Screen #2
AC LOSS DELAY
RANGE 00-24 HOURS
AC Loss Delay Screen #1
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds. Upon entering the third di git, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indi­cate the new delay time.
Note that the FACP can have both PAS and Pre-signal timers programmed with values but a zone can only use either the PAS or Pre-signal feature, but not both.
Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built­in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing Tim er Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length of the desired delay . Press 1 while viewing Timer Screen #2 to disp lay the fo llowing:
A flashing cursor will appear in the lower left corner of the display. The factory default setting is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When the sec­ond digit is entered, the display will return to AC Loss Delay Screen #1.
NOTE: Upon the loss of AC power at the control panel, relays programmed for AC Loss will transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC Loss Delay setting.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 71
Programming Master Programming Level
SYSTEM SETUP 1=TIMERS 2=BANNER 3=TIME-DATE
System Setup Screen #1
SELECT BANNER 1=FACTORY BANNER 2=USER BANNER
Select Banner Screen
FACTORY BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER-LINE 1
PRESS ENTER IF OK
User Defined Banner Screen
SYSTEM SETUP 1=TIMERS 2=BANNER 3=TIME-DATE
System Setup Screen #1
TIME AND DATE 1=TIME 10:00 AM 2=DATE 07072007 3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE 1=DAYLIGHT SAVINGS
Time-Date Screen #2
Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed:
Pressing 1 while viewing the Select Banner Screen will display the following screen:
This screen allows the user to select the factory default Banner which will be displayed when the system is in Normal Mode of operation. Press the Enter key to accept this as the default display. Press the Escape key to cancel and return to the Select Banner Screen.
Pressing 2 wile viewing the Select Banner Screen will display the following screen:
This screen allows the programmer to enter a custom banner. A flashing cursor will appear in the bottom left corner of the display. A maximum of 20 characters (including spaces) can be entered into the screen. After entering up to 20 characters in the screen, press Enter to store the entry. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A, and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times to place a blank in the desired position. When all charac­ters have been entered, press the Enter key to store the information. The display will return to the Select Banner Screen.
Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The following screen will be displayed:
72 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
ENTER TIME AS 12HRS
10:00 AM 1=AM 2=PM
Time Screen
ENTER DATE -- MONTH DAY YEAR 07-07-2007
Date Screen
TIME AND DATE 1=DAYLIGHT SAVINGS
Time & Date Screen #2
DAYLIGHT SAVINGS 1=ENABLED YES 2=START MONTH MAR 3=START WEEK WK 2
Daylight Savings Screen #1
Daylight Savings Screen #2
DAYLIGHT SAVINGS 1=END MONTH NOV 2=END WEEK WK 1
Time
T o change the time, press 1 while viewing the Time-Date Screen. The following screen will be dis­played:
A flashing cursor is located toward the top left of the display. Below the cursor is the current time. To change the time, enter the two-digit hours followed by the two-digit minutes. The cursor will move one position to the right each time a digit is entered. After the last minutes digit is entered, the cursor will again move one position to the right. At this point enter 1 for AM or 2 for PM. The display will then return to the Time-Date Screen which will show the new time entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again.
Date
To change the date, press 2 while viewing the Time-Date Screen. The following screen will be dis­played:
A flashing cursor is located toward the top left of the display. Below the cursor is the current date. To change the date, enter the two-digit month followed by the two-digit day and then the two-digit year (07 for 2007, 08 for 2008, etc.). The cursor will move one position to the right each time a digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen which will show the new date entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and beginning again.
Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
NOTE: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display purposes only).
Daylight Savings Time
Pressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 73
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected. Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows the
programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April, and 3 will select May.
Programming Master Programming Level
SYSTEM SETUP 1=TROUBLE REMIND NO 2=CANADIAN OPTION OFF 3=CHARGR DISABLE NO
System Setup Screen #2
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will begin. In the first sub­screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third week, while in the second sub-screen, pressing 1 will select the fourth week, and 2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1 will select September, 2 will select October, and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will end. In the first sub­screen, pressing 1 will select the first week, 2 will select the second week, and 3 will select the third week, while in the second sub-screen, pressing 4 will select the fourth week, and 5 will select the last week of the selected month.
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 70, for a detailed description of this feature. Pressing 1 while viewing System Setup Screen #2 will cause the display to toggle to Tr ouble Rem Yes, which enables this feature. Each press of the 1 key will cause the display to toggle between Trouble Rem Yes and Trouble Rem No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more than 24 hours will cause the FACP to resound the trouble sounder.
Canadian Option
Pressing 2 while viewing System Setup Screen #2 will configure the FACP to comply with Cana­dian requirements. The display will change to Canadian Opt. On. Each press of the 2 key will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory default setting is Canadian Opt. Off.
For Canadian applications, remote annunciation must be done using the secondary ANN-BUS. The Canadian Options configures the FACP with the following as required by Canada:
The following zone type codes are not available:
non-latching supervisorynon-latching drillprocess monitor (latching or non-latching)hazardtornadomedical alertcombo autoresettable
The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals will be turned off after 20 minutes of activation
The installer must write in the Date of Final Assembly on the Master Marking and Warranty label, located on the FACP backbox door
Charger Disable
74 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable the onboard battery charger. If an external battery charger is being used, the onboard battery char­ger must be disabled. Each press of the 3 key will toggle between Chrgr Disable No and Chrgr
Disable Yes.
Master Programming Level Programming
PROGRAMMING 1=SYSTEM SETUP 2=OPTION MODULES 3=HISTORY
Programming Screen #2
OPTION MODULES 1=ANN-BUS 2=ON BOARD DACT
ANN-BUS 1=BUS ENABLED NO 2=BUS MODULES 3=AUTO CONFIGURE
ANN-BUS Screen #1
ANN-BUS 1=ANN-S/PG OPTIONS 2=ANN-80 OPTIONS 3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS 1=ANN-AUDIO OPTIONS 2=ANN-SEC ENABLE NO
ANN-BUS Screen #3
ANN-BUS MODULES 1=ADDR. 1 NONE 2=ADDR. 2 NONE 3=ADDR. 3 NONE
On Board DACT Screen #1
ANN-BUS MODULE TYPE 1=NOT INSTALLED 2=ANN-80 3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE 1=ANN-S/PG 2=ANN-RLY 3=ANN-LED
Module Type Screen #2
ANN-BUS MODULE TYPE 1=ANN-AUDIO MODULE
Module Type Screen #3

3.5.5 Option Modules

Options available for the FACP include annunciators, printer connection for acquiring hardcopy printouts of panel data and onboard DACT.
Pressing 2 while viewing Programming Screen #2 will display the following screen:
ANN-BUS
Pressing 1 while viewing the Option Modules screen will cause the control panel to display the fol­lowing screens.
A variety of ANN-BUS option modules can be installed in the FACP. These devices communicate with the FACP over the ANN-BUS terminals on the control panel.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads ANN-
BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANN-BUS Enabled Yes and ANN-BUS Enabled No.
BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select ANN­BUS addresses for the module(s). The following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen with technical information about the selected module.
In the technical information screen, pressing 1 for Type will display the following screens:
Press the number corresponding to the module type, if any, that is installed with the selected address. This will enable the module.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 75
Programming Master Programming Level
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS PLEASE WAIT
Auto-Configure Screen
PROGRAMMING 1=ANN-S/PG OPTIONS 2=ANN-80 OPTIONS 3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-S/PG OPTIONS 1=PORT PARALLEL 2=PRINTER SUPV NO 3=OFFLINE TIMER 60
Printer Options Screen #1
ANN-S/PG OPTIONS 1=BAUD RATE N/A 2=DATA BITS N/A 3=PARITY N/A
Printer Options Screen #2
ANN-S/PG OPTIONS 1=STOP BITS N/A
Printer Options Screen #3
Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically program the device type and address into the system. Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to be displayed:
ANN-S/PG Options Screen
The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing the ANN-BUS Screen #2 will display the following screens:
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the dis­play to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print Options screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer supervision is reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port option has been selected.
Pressing 1 for Baud Rate while viewing Printer Options screen #2 will cause a screen to appear which allow the user to select a Baud Rate of 19200, 9600, or 2400.
Pressing 2 for Data Bits while viewing Printer Options screen #2 will cause screens to appear which allow the user to select 5, 6, 7, or 8 Data Bits.
Pressing 3 for Parity while viewing Printer Options screen #2 will cause a screen to appear which allows the user to select between No Parity, Even Parity, or Odd Parity.
Pressing 1 for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear which allows the user to select between 0.5, 1.0, or 2.0 Stop Bits.
ANN-I/O LED Zone Assignments
76 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
The information displayed by LEDs on every ANN-I/O module is not programmable and will therefore be as indicated in the following table.
LED Zone (any address)
1 AC Fault 2 General Alarm 3 General Supervisory
Master Programming Level Programming
ANN-80 OPTIONS 1=PIEZO ENABLE 2=LOCK ENABLE 3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80 OPTIONS 1=SIL BTN ENABLE 2=RST BTN ENABLE 3=DRL BTN ENABLE
ANN-80 Options Screen #2
4 General Trouble 5 Alarm Silenced 6 Earth Fault 7 Battery Fault 8 Charger Fault
9 Disable 10 Maintenance 11 Zone 1 Alarm 12 Zone 2 Alarm 13 Zone 3 Alarm 14 Zone 4 Alarm 15 Zone 5 Alarm 16 Zone 6 Alarm 17 Zone 7 Alarm 18 Zone 8 Alarm 19 Zone 9 Alarm 20 Zone 10 Alarm 21 Zone 1 Trouble 22 Zone 2 Trouble 23 Zone 3 Trouble 24 Zone 4 Trouble 25 Zone 5 Trouble 26 Zone 6 Trouble 27 Zone 7 Trouble 28 Zone 8 Trouble 29 Zone 9 Trouble 30 Zone 10 Trouble 31 Zone 1 Supervisory 32 Zone 2 Supervisory 33 Zone 3 Supervisory 34 Zone 4 Supervisory 35 Zone 5 Supervisory 36 Zone 6 Supervisory 37 Zone 7 Supervisory 38 Zone 8 Supervisory 39 Zone 9 Supervisory 40 Zone 10 Supervisory
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 77
ANN-80 Options Screen
Pressing 2 while viewing ANN-BUS screen #2 will display the following screen:
The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not the ANN-80 annunciator must be unlocked by its key before any annunciator key presses will function. Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select whether the Ack/Step button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Ack Btn Enable Ye s (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button never functions).
Programming Master Programming Level
PROGRAMMING 1=ANN-S/PG OPTIONS 2=ANN-80 OPTIONS 3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-RLY OPTIONS 1=RELAY 1 IN ZONE 1 2=RELAY 2 IN ZONE 2 3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil Btn Enable Yes (Silence but ton functions normally) and Sil Btn Enable No (Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never func­tions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the Drill button on any installed ANN-80 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never func­tions).
ANN-RLY Options Screen
Pressing 3 for ANN-RLY Options while viewing ANN-BUS Screen #2 will cause the following screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various func­tions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display the remaining relays for this module.
T o program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, press the number key corresponding to the relay to be programmed. Following is a list of the avail­able programming options for each relay:
General Alarm
General Trouble
General Supervisory
•AC Loss
Waterflow Delay
Input Zone 1
Input Zone 2
Input Zone 3
Input Zone 4
Input Zone 5
Input Zone 6
Input Zone 7
Input Zone 8
Input Zone 9
Input Zone 10
Silenceable Alarm
Not Assigned
78 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
PROGRAMMING 1=ANN-AUDIO OPTIONS
ANN-BUS Screen #3
ANN-AUDIO OPTIONS 1=ALL CALL ZONE 1
ANN-AUDIO Options Screen
ANN-AUDIO ALL CALL 1=NO ALL CALL ZONE 2=INPUT ZONE 1 3=INPUT ZONE 2
All-Call Options Screen #1
ANN-AUDIO ALL CALL 1=INPUT ZONE 3 2=INPUT ZONE 4 3=INPUT ZONE 5
All-Call Options Screen #2
ANN-AUDIO ALL CALL 1=INPUT ZONE 9 2=INPUT ZONE 10
All-Call Options Screen #4
(MS-10UD Only)
ANN-AUDIO ALL CALL 1=INPUT ZONE 6 2=INPUT ZONE 7 3=INPUT ZONE 8
All-Call Options Screen #3
(MS-10UD Only)
OPTION MODULES 1=ANN-BUS 2=ON BOARD DACT
Option Module Screen
ANN-BUS 1=ANN-AUDIO OPTIONS 2=ANN-SEC ENABLE NO
ANN-BUS Screen #3
ON BOARD DACT 1=PRIM PHONE TCH TNE 2=SCND PHONE TCH TNE 3=CENTRAL STATION
ON BOARD DACT 1=SERVICE TERMINAL 2=SUPERV PHONE LINE
Onboard DACT Screen 1
Onboard DACT Screen 2
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 (EURO) 3=ROTARY 60/40 (U.S.)
Primary Phone Type Screen
ANN-AUDIO Options Screen
Pressing 1 for ANN-AUDIO Options while viewing ANN-BUS Screen #3 will cause the following screen to be displayed:
This screen shows the Input Zone that has been assigned to be the All-Call Zone. In this example, Zone 1 is the All-Call Zone. The All-Call Zone can be changed by pressing the 1 key while view­ing the ANN-AUDIO Options Screen. The following screens will be displayed.
These screens allow the programmer to select which Input Zone will be assigned as the All-Call Zone.
ANN-SEC Enable
The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card at J13. To enable the Secondary ANN-BUS, press 2 while viewing ANN-BUS Screen #3 so that the display reads ANN-SEC ENABLE YES. Each press of the 2 key will cause the disp l a y to toggle between ANN-SEC ENABLE YES and ANN-SEC ENABLE NO. The factory default setting is ANN- SEC ENABLE NO.
Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a cen­tral station. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed:
Primary Phone
Press 1 while viewing Onboard DACT Screen to program the type of primary phone line being connected to the DACT. The following screen will be displayed:
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 79
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3 to select Rotary dialing with a make/break ratio of 60/40.
Programming Master Programming Level
ON BOARD DACT 1=PRIM PHONE 2=SCND PHONE 3=CENTRAL STATION
Onboard DACT Screen #1
PHONE LINE 1=TOUCHTONE 2=ROTARY 67/33 (EURO) 3=ROTARY 60/40 (U.S.)
Secondary Phone Type Screen
ON BOARD DACT 1=PRIM PHONE 2=SCND PHONE 3=CENTRAL STATION
Onboard DACT Screen #1
CENTRAL STATION 1=REPORTING NO 2=REPORT STYLE FIRST AVAILABLE
Central Station Screen #1
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=CALL LIMIT 0
Central Station Screen #2
REPORT STYLE 1=BACKUP ONLY 2=BOTH 3=FIRST AVAILABLE
Backup Reporting Screen
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=CALL LIMIT
Central Station Screen #2
CENTRAL STATION # 1=TEST TIME INT 24 2=ACCOUNT CODE 0000 3=24HR T TIME 0000
Primary/Secondary Screen #1
CENTRAL STATION 1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION 1=COMM FORMAT ADEMCO CONTACT ID 2=EVENT CODES
Primary/Secondary Screen #3
Secondary Phone
Press 2 while viewing Onboard DACT Screen 1 to program the type of secondary phone line being connected to the DACT. The following screen will be displayed:
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33, or 3 to select Rotary dialing with a make/break ratio of 60/40.
Central Station
Central Station programming configures the control panel DACT for contacting the central station. Pressing 3 while viewing Onboard DACT Screen 1 will cause the following screens to be dis­played:
Reporting
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing Cen­tral Station Screen #1 so the display reads Reporting Yes. Each press of the 1 key will toggle the display between Reporting Yes and Reporting No.
Report Style
The DACT can be programmed to transmit reports to primary and/or secondary central station phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the follow­ing screen:
Press 1 to have all reports transmitted to the central station secondary phone number as a backup only if the primary phone line fails, 2 to transmit all reports to both the primary and seco ndary phone numbers all of the time, or 3 to send reports to the first available phone number.
Central Station Primary and Secondary Phone Numbers
Pressing 1 for Primary or 2 for Secondary, while viewing Central Station Screen #2, will display the following screens.
Note that the following information must be entered for both the Primary and Secondary Central Station Phone Numbers.
80 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 3=24HR TST TIME
Primary/Secondary Screen #1
TEST TIME INTERVAL 1=24 HOURS 2=12 HOURS 3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL 1=6 HOURS
Test Time Interval Screen #2
ACCOUNT CODE
RANGE 0000-FFFF
Account Codes Screen
CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 3=24HR T TIME
Primary/Secondary Screen #1
24 HOUR TEST TIME ENTR USING 24HR TIME RANGE 0000-2359
24 Hour Test Time Screen
CENTRAL STATION 1=PHONE NUMBER
Primary/Secondary Screen #2
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
Test Time Interval
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be dis­played:
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24 hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be dis­played:
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will have a flashing cursor in the lower left corner. Program the supplied 4-digit account code using 0 - 9 and A - F keys. Enter the first digit, then press the right arrow key to move the cursor to the right, one position. Repeat the process until all digits are entered.
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be dis­played:
Use the 24 Hour Test Time screen to program the tim e that the DACT will transmit the 24 Hour Test to the Central Station. A flashing cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time (0000 = midnight and 2359 = 11:59PM).
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be dis­played:
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 81
The Phone Number screen is used to enter the Central Station phone number that the DACT will be contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = look for secondary dial tone for up to 2 seconds (then dial anyway).
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then press the right arrow key to move the cursor to the right one position. Enter the second digit and repeat the process until all digits are entered. Press the Enter key to store the phone number in memory.
Programming Master Programming Level
CENTRAL STATION 1=COMM FORMAT 2=EVENT CODES
Primary/Secondary Screen #3
COMM FORMAT 1=ADEMCO CONTACT ID 2=SIA-DCS-8 3=SIA-DCS-20
EVENT CODES 1=ZONE 1 ALARM 2=ZONE 2 ALARM 3=ZONE 3 ALARM
Event Code Screen
ZONE 3 ACTIVE 115
Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial 9 before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9 fol­lowed by D for a three second pause, or E for a five second pause then the phone number followed by an F to indicate the end of the number.
Communication Format
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be dis­played:
The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen. The following table describes each format:
Screen Selection Communication Format Description
ADEMCO CONTACT ID Contact ID, DTMF, 1400/2300 ACK SIA-DCS-8 Security Industry Association, 8 messages per call SIA-DCS-20 Security Industry Association, 20 messages per call
Table 3.2 Communication Formats
Event Codes
Pressing 2 while viewing Primary/Secondary Screen #3 will cause the following screen to be dis­played:
Pressing the down arrow key allows viewing of all Events associated with the selected Communi­cation Format. Pressing the number corresponding to the event displayed in each screen will dis­play its default active and restoral event codes which can be customized by the programmer.
For example, if Ademco Contact ID is the selected format, pressing 3 for Zone 3 Alarm will display the following screen which allows the Event Code to be changed from the default value.
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10 and the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that Table 3.4 on page 84, Table 3.5 on page 85, Table 3.6 on page 86 and Table 3.7 on page 87 list the default set­tings for Zone 1 through Zone 10. These can be changed to any of the Types listed in Table 3.3.
82 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
NOTE: The third character in the SIA-DCS Format (x in the table below) represents the zone number.
Master Programming Level Programming
Zone Alarm Type Ademco Contact ID SIA-DCS Format
Active Active Restoral
Pull-Station 115 FAx FHx Waterflow 113 SAx SHx Waterflow Nonsilenceable 113 SAx SHx Combo 113 SAx SHx Combo AutoResettable Supervisory 113 SAx SHx 2-Wire Detector 111 FAx FHx Normally Open Contact 110 UAx UHx Fire 110 FAx FHx Tamper 144 TAx THx Supervisory 200 FSx FVx Supervisory AutoResettable 200 FSx FVx Medic-Alert 100 MAx MHx Hazard-Alert 150 PAx PHx Tornado-Alert 150 PAx PHx Proc-Mon 200 IAx IRx Procmon-AR 200 IAx IRx AC-Loss-Mon 301 ATx ARx Drill-Switch 604 FIx FKx Drill-Switch AutoResettable 604 FIx FKx
Table 3.3 Zone Alarm Type Event Codes
The following tables list all of the Events and their default Event Codes for the Ademco Contact ID and SIA-DCS Communication Formats.
NOTE: A detector freeze condition will be reported as a Supervisory Event Code.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 83
Programming Master Programming Level
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.4 is automatically programmed for the Primary Central Station phone number Event Codes when Ademco Contact ID Format is selected. To disable event report­ing, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Primary # Zone 1 - 10 Alarm 115 001 - 010 Primary # Zone 1 - 10 Disabled 570 001 - 010 Primary # Drill 604 000 Primary # AC Fault 301 000 Primary # Zone 1 - 10 Fault 380 001 - 010 Primary # Zone 1 - 10 Dirty 380 001 - 010 Primary # Earth Fault 310 000 Primary # Low Battery Fault 302 000 Primary # No Battery Fault 311 000 Primary # Telco Primary Line Fault 351 001 Primary # Telco Secondar y Line Fault 352 002 Primary # NAC #1 Fault 321 001 Primary # NAC #2 Fault 322 002 Primary # NAC #3 Fault 326 003 Primary # NAC #4 Fault 327 004 Primary # NAC #1 Disable 521 001 Primary # NAC #2 Disable 522 002 Primary # NAC #3 Disable 526 003 Primary # NAC #4 Disable 527 004 Primary # Charger Fault 300 000 Primary # Comm Trouble Primary # 354 001 Primary # Comm Trouble Secondary # Primary # Printer Fault Primary # ANN-Bus Fault
Primary # Option Card Fault 333 000 Primary # CS CALC Fault 304 000 Primary # System Off Normal 308 000 Primary # System Test Message 602 000 Primary # System Abnormal Test Message 608 000 Primary # Upload/Download Request 411 000 Primary # Upload Successful 416 000 Primary # Download Successful 412 000 Primary # Upload/Download Failed 413 000 Primary # Voice EVAC Fault 330 000 Primary # Power Supply Sync Fault 300 000
Event Code Settings
Active
354 336 330
Zone Code
002 000 000
Table 3.4 Ademco Contact ID Primary # Event Codes
84 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Secondary Central Sta­tion phone number Event Codes when Ademco Contact ID Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to dis­able it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Secondary # Zone 1 - 10 Alarm 115 Secondary # Zone 1 - 10 Disabled 570 Secondary # Drill 604 Secondary # AC Fault 301 Secondary # Zone 1 - 10 Fault 380 Secondary # Zone 1 - 10 Dirty 380 Secondary # Earth Fault 310 Secondary # Low Battery Fault 302 Secondary # No Battery Fault 311 Secondary # Telco Primary Line Fault 351 Secondary # Telco Secondary Line Fault 352 Secondary # NAC #1 Fault 321 Secondary # NAC #2 Fault 322 Secondary # NAC #3 Fault 326 Secondary # NAC #4 Fault 327 Secondary # NAC #1 Disable 521 Secondary # NAC #2 Disable 522 Secondary # NAC #3 Disable 526 Secondary # NAC #4 Disable 527 Secondary # Charger Fault 300 Secondary # Comm Trouble Primary # 354 Secondary # Comm Trouble Secondary # 354 Secondary # Printer Fault 336 Secondary # ANN-BUS Fault 330 Secondary # Option Card Fault 333 Secondary # CS CALC Fault 304 Secondary # System Off Normal 308 Secondary # System Test Message 602 Secondary # System Abnormal Test Message 608 Secondary # Upload/Download Request 411 Secondary # Upload Successful 416 Secondary # Download Successful 412 Secondary # Upload/Download Failed 413 Secondary # Voice EVAC Fault 330 Secondary # Power Supply Sync fault 300
Event Code Settings
Active
Table 3.5 Ademco Contact ID Secondary # Event Codes
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 85
Programming Master Programming Level
SIA-DCS Format - Primary Central Station Phone Number
The information shown in Table 3.6 is automatically programmed for the Primary Central Station phone number Event Codes when SIA-DCS Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Primary # Zone 1 Alarm FA1 FH1 Primary # Zone 2 Alarm FA2 FH2 Primary # Zone 3 Alarm FA3 FH3 Primary # Zone 4 Alarm FA4 FH4 Primary # Zone 5 Alarm FA5 FH5 Primary # Zone 6 Alarm FA6 FH6 Primary # Zone 7 Alarm FA7 FH7 Primary # Zone 8 Alarm FA8 FH8 Primary # Zone 9 Alarm FA9 FH9 Primary # Zone 10 Alarm FA10 FH10 Primary # Zone 1 Disabled FB1 FU1 Primary # Zone 2 Disabled FB2 FU2 Primary # Zone 3 Disabled FB3 FU3 Primary # Zone 4 Disabled FB4 FU4 Primary # Zone 5 Disabled FB5 FU5 Primary # Zone 6 Disabled FB6 FU6 Primary # Zone 7 Disabled FB7 FU7 Primary # Zone 8 Disabled FB8 FU8 Primary # Zone 9 Disabled FB9 FU9 Primary # Zone 10 Disabled FB10 FU10 Primary # Drill FI FK Primary # AC Fault AT AR Primary # Zone 1 Fault FT1 FJ1 Primary # Zone 2 Fault FT2 FJ2 Primary # Zone 3 Fault FT3 FJ3 Primary # Zone 4 Fault FT4 FJ4 Primary # Zone 5 Fault FT5 FJ5 Primary # Zone 6 Fault FT6 FJ6 Primary # Zone 7 Fault FT7 FJ7 Primary # Zone 8 Fault FT8 FJ8 Primary # Zone 9 Fault FT9 FJ9 Primary # Zone 10 Fault FT10 FJ10 Primary # Zone 1 Dirty FT1 FJ1 Primary # Zone 2 Dirty FT2 FJ2 Primary # Zone 3 Dirty FT3 FJ3 Primary # Zone 4 Dirty FT4 FJ4 Primary # Zone 5 Dirty FT5 FJ5 Primary # Zone 6 Dirty FT6 FJ6 Primary # Zone 7 Dirty FT7 FJ7 Primary # Zone 8 Dirty FT8 FJ8 Primary # Zone 9 Dirty FT9 FJ9 Primary # Zone 10 Dirty FT10 FJ10 Primary # Earth Fault ET38 ER38
Event Code Settings
Active Restoral
Table 3.6 SIA-DCS Primary # Event Codes
86 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
Primary # Low Battery Fault YT0 YR0 Primary # No Battery Fault YT0 YR0 Primary # Telco Primary Line Fault LT1 LR1 Primary # Telco Secondary Line Fault LT2 LR2 Primary # NAC #1 Fault ET32 ER32 Primary # NAC #2 Fault ET33 ER33 Primary # NAC #3 Fault ET34 ER34 Primary # NAC #4 Fault ET35 ER35 Primary # NAC #1 Disable ET101 ER101 Primary # NAC #2 Disable ET102 ER102 Primary # NAC #3 Disable ET103 ER103 Primary # NAC #4 Disable ET104 ER104 Primary # Charger Fault YP YQ Primary # Comm Trouble Primary # YC1 YK1 Primary # Comm Trouble Secondary # YC2 YK2 Primary # Printer Fault VT VR Primary # ANN-Bus Fault ET61 ER61 Primary # Option Card Fault ET ER Primary # CS CALC Fault YF 000 Future 000 000 Primary # System Off Normal LB LX Primary # System Test Message RP 000 Primary # System Abnormal Test Message RP99 000 Primary # Power Supply Sync Fault OU OV Primary # Upload/Download Request RB 000 Primary # Upload Successful RS 000 Primary # Download Successful RS 000 Primary # Upload/Download Failed RU 000 Primary # Voice EVAC Fault ET ER Primary # Power Supply Sync Fault OU OV
Table 3.6 SIA-DCS Primary # Event Codes (Continued)
SIA-DCS Format - Secondary Central Station Phone Number
The information shown in Table 3.7 is automatically programmed for the Secondary Central Sta­tion phone number Event Codes when SIA-DCS Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the selection).
Event Description
Secondary # Zone 1 Alarm FA1 FH1 Secondary # Zone 2 Alarm FA2 FH2 Secondary # Zone 3 Alarm FA3 FH3 Secondary # Zone 4 Alarm FA4 FH4 Secondary # Zone 5 Alarm FA5 FH5 Secondary # Zone 6 Alarm FA6 FH6 Secondary # Zone 7 Alarm FA7 FH7 Secondary # Zone 8 Alarm FA8 FH8 Secondary # Zone 9 Alarm FA9 FH9 Secondary # Zone 10 Alarm FA10 FH10 Secondary # Zone 1 Disabled FB1 FU1
Event Code Settings
Active Restoral
Table 3.7 SIA-DCS Secondary # Event Codes
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 87
Programming Master Programming Level
Secondary # Zone 2 Disabled FB2 FU2 Secondary # Zone 3 Disabled FB3 FU3 Secondary # Zone 4 Disabled FB4 FU4 Secondary # Zone 5 Disabled FB5 FU5 Secondary # Zone 6 Disabled FB6 FU6 Secondary # Zone 7 Disabled FB7 FU7 Secondary # Zone 8 Disabled FB8 FU8 Secondary # Zone 9 Disabled FB9 FU9 Secondary # Zone 10 Disabled FB10 FU10 Secondary # Drill FI FK Secondary # AC Fault AT AR Secondary # Zone 1 Fault FT1 FJ1 Secondary # Zone 2 Fault FT2 FJ2 Secondary # Zone 3 Fault FT3 FJ3 Secondary # Zone 4 Fault FT4 FJ4 Secondary # Zone 5 Fault FT5 FJ5 Secondary # Zone 6 Fault FT6 FJ6 Secondary # Zone 7 Fault FT7 FJ7 Secondary # Zone 8 Fault FT8 FJ8 Secondary # Zone 9 Fault FT9 FJ9 Secondary # Zone 10 Fault FT10 FJ10 Secondary # Zone 1 Dirty FT1 FJ1 Secondary # Zone 2 Dirty FT2 FJ2 Secondary # Zone 3 Dirty FT3 FJ3 Secondary # Zone 4 Dirty FT4 FJ4 Secondary # Zone 5 Dirty FT5 FJ5 Secondary # Zone 6 Dirty FT6 FJ6 Secondary # Zone 7 Dirty FT7 FJ7 Secondary # Zone 8 Dirty FT8 FJ8 Secondary # Zone 9 Dirty FT9 FJ9 Secondary # Zone 10 Dirty FT10 FJ10 Secondary # Earth Fault ET38 ER38 Secondary # Low Battery Fault YT0 YR0 Secondary # No Battery Fault YT0 YR0 Secondary # Telco Primary Line Fault LT1 LR1 Secondary # Telco Secondar y Line Fault LT2 LR2 Secondary # NAC #1 Fault ET32 ER32 Secondary # NAC #2 Fault ET33 ER33 Secondary # NAC #3 Fault ET34 ER34 Secondary # NAC #4 Fault ET35 ER35 Secondary # NAC #1 Disable ET101 ER101 Secondary # NAC #2 Disable ET102 ER102 Secondary # NAC #3 Disable ET103 ER103 Secondary # NAC #4 Disable ET104 ER104 Secondary # Charger Fault YP YQ Secondary # Comm Trouble Primary # YC1 YK1 Secondary # Comm Trouble Secondary # YC2 YK2 Secondary # Printer Fault VT VR Secondary # ANN-Bus Fault ET61 ER61 Secondary # Option Card Fault ET ER Secondary # CS CALC Fault YF 000
Table 3.7 SIA-DCS Secondary # Event Codes (Continued)
88 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
CENTRAL STATION 1=PRIMARY 2=SECONDARY 3=CALL LIMIT
Central Station Screen #2
TROUBLE CALL LIMIT
RANGE 00-99 TROUBLES
Backup Reporting Screen
DACT 1=SERVICE TERMINAL 2=SUPERV PHONE LINE
Onboard DACT Screen #2
SERVICE TERMINAL 1=RING COUNT 0
Service Terminal Screen
SERVICE TERMINAL 1=RING COUNT
Service Terminal Screen #2
Secondary # System Off Normal LB LX Secondary # System Test Message RP 000 Secondary # System Abnormal Test Message RP99 000 Secondary # Power Supply Sync Fault OU OV
Secondary # Upload/Download Request RB 000 Secondary # Upload Successful RS 000 Secondary # Download Successful RS 000 Secondary # Upload/Download Failed RU 000 Secondary # Voice EVAC Fault ET ER Secondary # Power Supply Sync Fault OU OV
Table 3.7 SIA-DCS Secondary # Event Codes (Continued)
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a pro­grammed amount between 0 and 99, for each unique trouble within a 24 hour period. All call limit counters reset (clear) at each midnight. Separate limit counters keep track of each unique type of trouble. Note that the number of phone line (communication) faults called to the Central Station are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose call limit has been reached. Local DACT annunciation will still track the particular trouble and restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #2. The following screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
NOTE: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the Central Station an unlimited amount of times. This is the factory default setting.
Service Terminal
The FACP can be programmed remotely from a PC using a modem and telephone line. Informa­tion can also be retrieved from the FACP using the same method. The Upload/Download option allows an operator to set the necessary parameters to allow the uploading and downloading of data between the FACP and PC. The Service Terminal selection provides the means for entering these parameters.
Pressing 1 while viewing Onboard DACT Screen #2 will cause the following screens to appear:
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 89
Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an incoming call from a service terminal. The factory default is 0 which means the control panel will not answer an incoming call. This entry may be programmed for 1 to 25 rings.
Programming Master Programming Level
RING COUNT
RANGE 00-25 RINGS
Ring Count Screen
DACT 1=SERVICE TERMINAL 2=SUPERV PHONE LINE
Onboard DACT Screen #2
SUPERVISE PHONE LINE 1=PHONE LINE 2 YES
PROGRAMMING 1=SYSTEM SETUP 2=OPTION MODULES 3=HISTORY
Programming Screen #2
HISTORY 1=VIEW EVENTS 2=ERASE HISTORY
History Screen
HISTORY 1=VIEW EVENTS 2=ERASE HISTORY
History Screen
HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS
View Events Screen
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The following screen will be displayed:
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring count which can be a value between 00 and 25. After the second digit is entered, the display will return to the Service Terminal screen.
Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2 by the DACT when using an alternate means of secondary transmission path. The factory default set­ting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the following screen to be displayed:
Each press of the 1 key while viewing this screen will toggle the option between Supervise Phone Line 2 Yes and No.

3.5.6 History

The History option allows an authorized user to view or erase events which have occurred in the control panel. Pressing 3 while viewing Programming Screen #2 will display the History options as shown in the following display:
View Events
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illustrated in the following:
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms, or 3 to view other events. Use the up and down arrow keys to scroll through all of the displayed events.
90 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Master Programming Level Programming
ERASE HISTORY PROCEED? 1=YES 2=NO
Erase History Screen
PROGRAMMING 1=WALKTEST 2=CLEAR PROGRAM 3=PASSWORD CHANGE
Programming Screen #3
WALKTEST 1=SILENT 2=AUDIBLE 3=VIEW RESULT
Walktest Screen
UNIT IN WALKTEST
Walktest Active Screen
ALARM ZONE 1 <ADJ> <NOUN> Z01 1000A 010805
WALKTEST RESULTS
Erase History
The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history file to track future events. Pressing 2 while viewing the His­tory Screen will display the following screen:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. After the History file has been erased, the display will return to the History Screen.

3.5.7 Walktest

Walktest allows an individual to test the fire alarm system without the necessity to reset the control panel after each device activation. Refer to the sections titled “Walktest” on page 94 and“Walktest” on page 104 for additional information regarding the Walktest feature. Pressing 1 while viewing the Programming Screen #3 will cause the following Walktest options to be displayed:
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the follow­ing screen will be displayed:
The user can now perform a one-person walktest by activating devices throughout the system. As each device is activated, the screen will display the information about the activated device as shown below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the walk­test screen from an actual alarm screen.
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing the Walktest Screen. The following screen will be displayed:
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 91
Use the up and down arrow keys to view all of the walktest results which will be displayed as illus­trated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC and DC) is removed from the FACP, the Walktest log information will be lost. This information is also overwritten when subsequent walktests are performed.
Programming Master Programming Level
PROGRAMMING 1=WALKTEST 2=CLEAR PROGRAM 3=PASSWORD CHANGE
Programming Screen #3
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES 2=NO
OPTION MODULES 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC NO
Option Module Screen
PRINTER-PC 1=PRINTER NO SU NO 2=PRINTER SU YES 3=PC NO
Printer-PC Screen
PRINTER BAUD RATE 1=2400 BAUD 2=4800 BAUD 3=9600 BAUD
Printer Baud Rate Screen
PROGRAMMING 1=WALKTEST 2=CLEAR PROGRAM 3=PASSWORD CHANGE
Programming Screen #3
PASSWORD CHANGE 1=MASTER 2=MAINTENANCE 3=REMOTE DOWNLOAD
Password Change Screen

3.5.8 Clear Program

Pressing 2 while viewing Programming Screen #3, will select the Clear Program option. The con­trol panel will provide a warning to the user by prompting with the following display:
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will pre­vent programming from being cleared.
Printer/PC
A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option Mod­ule Screen will cause the following screen to appear:
Pressing 1 while viewing the Printer-PC Screen will program the control panel for an unsupervised (NO SU) printer. The display will change to the Printer Baud Rate Screen as shown below.
Pressing 2 while viewing the Printer-PC Screen will program the control panel for a supervised (SU) printer. Printer supervision, when enabled, will typically detect the removal of the printer cable and will detect when the printer power has been turned off. Depending upon the brand of printer, other errors such as paper empty or printer off-line may be detected.
The following screen will appear, which allows the programmer to select the baud rate for the printer communication:
Pressing the number key corresponding to the desired baud rate (2 for 4800 Baud for example) will program the control panel for the selected baud rate and return the display to the Option Module Screen which will indicate Printer/PC PR4800 for a supervised printer installed at 4800 baud rate.
Pressing 3 while viewing the Printer-PC Screen will program the control panel for a PC connection. The display will return to the Option Module Screen which will indicate Printer/PC PC for per­sonal computer installed.

3.5.9 Password Change

The factory set passwords, which have been programmed into the control panel, can be changed by selecting the Password Change option. Pressing 3 while viewing Programming Screen #3 will cause the following screen to be displayed:
92 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Press 1 to change the Master Programming Level password, 2 to change the Maintenance Level password, or 3 to change the Remote Download password. Note that the passwords will not
played on annunciators.
be dis-
Maintenance Programming Level Programming
ENTER NEW FIVE DIGIT PASSWORD
Enter Password Screen
VERIFY NEW PASSWORD
Password Change Screen
1=READ STATUS 2=PROGRAMMING 3=REMOTE DOWNLOAD
PROGRAMMING ENTER PASSWORD
PROGRAMMING 1=INPUT ZONES 2=HISTORY 3=WALKTEST
PROGRAMMING 1=TIME-DATE
PROGRAMMING 1=INPUT ZONES 2=HISTORY 3=WALKTEST
Maintenance Screen #1
POINT PROGRAM 1=ZONE 1 2=ZONE 2 3=ZONE 3
Zone Select Screen
The following screen will appear when one of the change options is selected:
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as 10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
The new five digit password must be re-entered to accept the change. The display will then return to the initial Password Change Screen.

3.6 Maintenance Programming Level

T o access Maintenance Programming mode, pre ss the Enter key. The LCD will display the follow­ing:
To enter the Maintenance Programming mode, press 2. The display will read as follows:
When the Maintenance
level password (default 11111) is entered, the following screen will appear:
Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key, as shown in the following screen.

3.6.1 Input Zones - Enable/Disable

The Zone Setup option allows the user to enable or disable desired zones. Pressing 1 for Zone Setup, while viewing Maintenance Screen #1 will cause the following screens to be displayed:
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 93
Programming Maintenance Programming Level
ZONE 1 1=ENABLED YES
Enable/Disable Select Screen
HISTORY 1=VIEW EVENTS 2=ERASE HISTORY
History Screen
HISTORY 1=VIEW ALL 2=VIEW ALARMS 3=VIEW OTHER EVENTS
ERASE HISTORY
PROCEED?
1=YES 2=NO
Erase History Screen
PROGRAMMING 1=INPUT ZONES 2=HISTORY 3=WALKTEST
Maintenance Screen #1
WALKTEST 1=SILENT 2=AUDIBLE 3=VIEW RESULT
Walktest Screen
Pressing the down arrow key will display additional Zones (Zones 4 - 5 for MS-5UD and Zones 4 ­10 for MS-10UD). Select the number corresponding to the desired zone. A screen will appear which will allow enabling or disabling of the selected zone, as illustrated in the following example:
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.

3.6.2 History

Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
The History feature allows the operator to view control panel events which have been stored in a history file in memory and erase the contents of the history file
Pressing 1 while viewing the History screen will cause the following screen to be displayed:
To view all the events which have occurred in the control panel since the history file was last erased, press 1 while viewing the Events screen. To view only alarms/active events which have occurred, press 2 while viewing the Events screen. To view events other than alarms, press 3. The most recent event will be displayed on the screen. T o view all of the selected events, press the up or down arrow keys to scroll through the list of events. If no events have occurred, the display will read NO EVENTS IN HISTORY.
Pressing 2 while viewing the History Screen will cause the following screen to be displayed:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. The display will then return to the History Screen. Pressing 2 will cause the display to return to the His­tory Screen without erasing the History file.

3.6.3 Walktest

94 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
T o perform a walktest, press 3 while viewing Maintenance Screen #1. The following screen will be displayed:
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The dis­play will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.
Maintenance Programming Level Programming
PROGRAMMING 1=TIME-DATE
Maintenance Screen #2
TIME AND DATE 1=TIME 01:00 AM 2=DATE 10-09-2013 3=CLOCK FORMAT 12HRS
Time and Date Screen
ENTER TIME AS 12HRS
:
01:00 AM
1=AM 2=PM
Time Screen
ENTER DATE --
MONTH DAY YEAR
10-15-2013
Date Screen
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the walktest.

3.6.4 Time-Date

T o program the time and date into the control panel, press 1 while viewing Maintenance Screen #2. The following display will appear:
To change the time, press 1 to display the following screen:
A flashing cursor will appear on the left side of the display. Enter the four digit number corre­sponding to the time (0000 - 1259). When the fourth digit is entered, the cursor will move one position to the right. Press 1 for AM or 2 for PM to complete entering the time. The display will return to the Time and Date Screen displaying the new time.
T o change the date, press 2 while viewing the Time and Date Screen. The following screen will be displayed:
A flashing cursor will appear on the left side of the display. Enter the two digit month, two digit day and four digit year. The cursor will move one position to the right after each entry. When the fourth digit of the year has been entered, the display will return to the Time and Date Screen which will show the new date.
To change between 12 hour and 24 hour format, press 3 while viewing the Time and Date screen. Each press of the 3 key will toggle the display between 12 HR and 24 HR format.
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 95

Section 4: Operating Instructions

4.1 Panel Control Buttons

4.1.1 Acknowledge/Step

The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to steady and also changes the status field on the LCD display from capital letters to small letters (TROUBL to Troubl). When the piezo is silenced, an acknowledge message is sent to the printer and the history file. Acknowledge also sends a silence piezo command to the optional annunciators connected to the FACP. The Acknowledge key will have no effect on the Notification Appliance Circuits.
When more than one event exists, the first press of the Acknowledge/Step key functions as described in the preceding paragraph. Subsequent pressing of the key steps through each active event.

4.1.2 Alarm Silenced

The Alarm Silenced key performs the same functions as Acknowledge/Step except it will not step through each event when multiple events are present at the panel. If an alarm exists, the Alarm Silenced key turns off all silenceable NACs (Notification Appliance Circuits) and causes the Alarm Silenced LED to turn on. It also sends an ‘alarm silenced’ message to the printer, history file and optional annunciators. A subsequent new alarm will resound the system NACs. The Alarm Silenced LED is turned off by pressing the Reset key, the Drill key or subsequent activ ation of the NACs.
Note that if Silence Inhibit has been enabled, NACs cannot be silenced for one minute following initiation of an alarm.

4.1.3 Drill/Hold 2 Sec

When the Drill key is held for a minimum of two seconds (time required to prevent accidental acti­vations), the FACP turns on all NAC outputs and turns off the Alarm Silenced LED if it was previ­ously on. The EV AC IN SYSTEM message is shown on the LCD display . The same message is sent to the printer and history file. The Alarm Silence key can be used to turn off all silenceable NAC outputs following activation by the Drill key.

4.1.4 Reset

Pressing and releasing the Reset key turns off all NACs, temporarily turns off resettable power to 4­wire detectors, causes a RESET IN SYSTEM message to be displayed on the LCD and sends the same message to the printer and history file. It also performs a lamp test by turning on all LEDs, piezo sounder and LCD display segments after the Reset key is released. Any alarm or trouble that exists after a reset will resound the system.
Note that if Silence Inhibit has been enabled, the FACP canno t be reset for one minute following initiation of an alarm.

4.2 LED Indicators

The five LED indicators, which are located on the front panel, operate as follows:
AC Power
This is a green LED which illuminates if AC power is applied to the FACP. A loss of AC power will turn off this LED
96 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Normal Operation Operating Instructions
SYSTEM ALL NORMAL 10:00A 070707
Fire Alarm
This red LED flashes when one or more alarms occur. It illuminates steady when the Acknowl­edge/Step or Alarm Silence key is pressed. The Fire Alarm LED turns off when the Reset key is
pressed. The LED will remain off if all alarms have been cleared.
Supervisory
This is a yellow LED that flashes when one or more supervisory conditions occur, such as a sprin­kler valve tamper condition. It illuminates steady when the Acknowledge/Step or Alarm Silence key is pressed. It turns off when the Reset key is pressed and remains off if all supervisory alarms have been cleared.
Trouble
This is a yellow LED that flashes when one or more trouble conditions occur. It stays on steady when the Acknowledge/Step or Alarm Silence key is pressed. The LED turns off when all trouble conditions are cleared. This LED will also illuminate if the microprocessor watchdog circuit is activated.
Alarm Silenced
This is a yellow LED that turns on after the Alarm Silence key is pressed while an alarm condition exists. It turns off when the Drill or Reset key is pressed.

4.3 Normal Operation

With no alarms or troubles in the system, the display message is System All Normal along with the current time and date as shown below. To set the time and date, refer to the appropriate section in this manual.
The FACP performs the following functions at regular intervals in Normal mode:
Monitors AC input voltage and battery voltageMonitors and reports status option cards and control panelRefreshes LCD display and updates timeScans control panel keypad for key pressesTests memoryUpdates and reads all communications busses (EIA-485, etc.)
3
i
smoke detectors will be polled for maintenance and freeze conditions on initial entry into Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions
NOTE: To ensure that the system is functioning properly, the FACP will perform a freeze check five minutes after the panel is reset, followed by a maintenance check. If there is no freeze or maintenance condition, the panel will continue to monitor for freeze conditions every hour and maintenance conditions every four hours.

4.4 Trouble Operation

With no alarms in the system, the detection of a trouble will cause the following:
The piezo to pulse 1 second On and 1 second Off
The system Trouble LED to flash one second On and one second Off
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 97
Operating Instructions Trouble Operation
TROUBL PULL STATION <ADJ> <NOUN> ZONE 10 OPEN FAULT 10:00A 100913
The trouble relay to activate
TROUBL with device type, adjective/noun, address and trouble description will appear on th e LCD display
The same message, along with the time and date, is sent to the optional printer and the history buffer.
Communicate the trouble conditions to the Central Station
Terminate upload or download communications
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn off the AC Power LED, etc.
Input Zone
For Input Zones, the following is a typical message that could appear on the LCD display for a device trouble:
The information displayed in the above example provides the following information:
First line in display: – The type of event; in this example OPEN indicating a circuit trouble – Device type identifier; in this example, PULL STATION indicates a manual device. Other
device type identifiers which can be displayed include SMOKE for Smoke Detector, HEAT for Heat Detector, etc.
Second line in display: – <ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
– <NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
Third line in display indicates Zone and the fault condition. Other possible troubles include:
OPEN - indicating an open circuitDIRTY - maintenance alert indicating that an i
3
detector is near but below the allowed alarm
limit and is in need of maintenance before the performance is compromised
Fourth line in display: – Time; the current time in this example is 10:00A which represents 10:00 AM – Date; the current month, day and year in this example is 10 for October, 09 for the 9th day of
the month and 13 for the year 2013
Pressing the Acknowledge/Step or Alarm Si lenc e key will cause the pulsing piezo to silence and the system Trouble LED to change from flashing to on steady. This block acknowledgment occurs regardless of the number of troubles, alarms and supervisory events active in the system. When the Acknowledge/Step key is pressed and at least one new alarm or trouble exists in the system, the ‘acknowledge’ message is sent to the printer and history file. If the trouble clears, either before or after the Acknowledge/Step key is pressed, the ‘clear trouble’ message is sent to the printer and his­tory file.
If all troubles clear and there are no supervisory o r fi re conditions active in the system, the system returns to normal mode operation and the System All Normal message is shown on the LCD display and sent to the history and printer files. The auto-restore feature will restore cleared troubles even if the troubles were never acknowledged. Note that pressing the Alarm Silence key when only trou­bles exist in the system will have the same effect as pressing the Acknowledge/Step key except the Alarm Silenced LED will light.
98 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Alarm Operation Operating Instructions
ALARM PULL STATION
<ADJ> <NOUN>
ZONE 10
10:00A 100913

4.5 Alarm Operation

Alarm operation is similar to trouble operation with the following differences:
The piezo sounder produces a steady output as opposed to a pulsed output
The Fire Alarm LED flashes 1 second On and 1 second Off
The LCD displays Alarm along with the device name, type, adjective/noun, associated zones and time/date
Communicate the alarm to the Central Station
Alarms latch and are not allowed to clear automatically
Timers for Silence Inhibit, Autosilence and Trouble Reminder are started
Alarms activate the alarm relay
Silenced alarms are resounded
The trouble relay is not activated
Store event in history buffer
Terminate upload or download communications
A typical alarm display would be as illustrated below:
Note that the device type, which in this example is PULL STATION, can be any other programma- ble alarm type.
The information displayed in the above example provides the following information:
First line in display: – The type of event; in this example ALARM indicating an alarm condition – Device type identifier; in this example, PULL STATION indicates a manual pull box. Other
device type identifiers which can be displayed include SMOKE for Smoke Detector, HEAT for Heat Detector, etc.
Second line in display: – <ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
– <NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
Third line in display: Zone 10 indicates the zone programmed to th is device which, in this example, is Input Zone 10.
Fourth line in display: – Time; the current time in this example is 10:00A which represents 10:00 AM – Date; the current month, day and year in this example is 10 for October, 09 for the 9th day of
the month and 13 for the year 2013

4.6 Supervisory Operation

Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type, adjective/noun, associated zones and time/date
MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014 99
Operating Instructions Process Monitor Operation
FREEZE SUPERVISORY <ADJ> <NOUN> ZONE 05 FROZEN SUPRV 10:00A 100913
Communicate the supervisory condition to the Central Station
The supervisory relay is activated
The alarm relay is not
Silenced alarms are not
activated
resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
A typical Supervisory event would be displayed as illustrated in the following:
In the preceding example:
FROZEN SUPRV - indicates zone detector is below approximately 45
o
F
Note that, like alarms, supervisory signals latch, except when programmed for supervisory autore­settable. Supervisory activations do not cause silenced alarms to resound, as do other alarm condi­tions. Open circuits in supervisory wiring are processed by the control panel the same way as other trouble conditions. Refer to “Alarm Operation” on page 99, for a description of the information displayed on the control panel LCD.

4.7 Process Monitor Operation

Process Monitor operation will initiate the following events:
The piezo sounder pulses ¼ second On and ¼ second Off
The LCD displays a process monitor message along with the device name, type, adjective/noun, associated zones and time/date
Communicate the process monitor condition to the Central Station (if the default event code has been changed from 000 to a reportable event code)
Relays programmed for process monitoring will be activated
The alarm relay is not
Silenced alarms are not
activated
resounded
Timers are not started
Store event in history buffer
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Note that, like supervisories, process monitor signals latch, except when programmed for process monitor autoresettable.

4.8 Hazard/Tornado Condition Operation

Hazard/Tornado operation is intended for Manual activation. Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses ¼ second On, ¼ second Off
The LCD displays a hazard message along with the device name, type, adjective/noun, associated zones and time/date
Communicate the hazard condition to the Central Station (if the default event code has been changed from 000 to a reportable event code)
Relays programmed for hazard will be activated
100 MS-5UD & MS-10UD Series Manual — P/N 52626:C4 3/7/2014
Loading...