Fire-Lite MRP2002E Programming Manual

PN: 53049:A ECN 07-072
Agent Release Control System
MRP-2002 & MRP-2002E
Installation, Operation and Programming Manual
Document #53049 4/16/07 Revision:
A
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Table of Contents
Table of Content s
SECTION 1: Product Description .........................................................................................................................11
1.1: Product Features..........................................................................................................................................11
1.2: Specifications ..............................................................................................................................................13
1.3: Controls and Indicators................................................................................................... .............................14
1.4: Components.................................................................................................................................................15
1.5: Optional Modules and Accessories .............................................................................................................16
SECTION 2: Installation ........................................................................................................................................17
2.1: Backbox Mounting......................................................................................................................................17
2.2: Operating Power..........................................................................................................................................20
2.3: Input Circuits...............................................................................................................................................21
2.4: Output Circuits ............................................................................................................................................23
2.4.1: Outputs/Notification Appliance/Releasing Circuits..........................................................................23
2.4.2: Special Application DC Power Output Connections ........................................................................24
2.4.3: Relays - Programmable.....................................................................................................................24
2.5: Power-limited Wiring Requirements.................................................. .........................................................25
2.6: Installation of Optional Modules.................................................................................................................26
2.6.1: CAC-5X Class A Converter Module ................................................................................................26
2.6.1.1 Installation ............................ ........................................................... ........................................26
2.6.1.2 Wiring NACs and IDCs for Class A .......................................................................................27
2.6.2: 4XTMF Municipal Box Transmitter Option Module........................................................................28
2.6.2.1 4XTMF Transmitter Module Installation ................................................................................29
2.7: ANN-BUS Devices .....................................................................................................................................30
2.7.1: ANN-BUS Wiring.............................................................................................................................30
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules ............................................................ 30
2.7.1.2 Wiring Configuration ........................................................ ......................................................32
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply ................................................33
2.7.2: ANN-BUS Device Addressing.......................................................................................................... 33
2.7.3: ANN-80 Remote LCD Annunciator .................................................................................................34
2.7.4: Specifications....................................................................................................................................34
2.7.5: Installation.........................................................................................................................................34
2.7.5.1 Mounting .................................................... .............................................................................34
2.7.5.2 Opening/Closing Annunciator ................................................................................................34
2.7.5.3 Wiring ANN-80 to FACP .......................................................................................................35
2.7.6: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................37
2.7.6.1 Specifications ..........................................................................................................................37
2.7.6.2 PRN-6 Printer Installation .......................................................................................................37
2.7.6.2.1 Connecting PRN-6 Printer ...................................................................................................38
2.7.6.2.2 Setting Printer Options .........................................................................................................38
2.7.7: ANN-I/O LED Driver Module..........................................................................................................39
2.7.7.1 ANN-I/O Board Layout ..........................................................................................................39
2.7.7.2 Specifications ..........................................................................................................................39
2.7.7.3 ANN-I/O Connection to FACP ............................................ ...................................................40
2.7.7.4 ANN-I/O Module LED Wiring ............................................ ...................................................41
2.7.8: ANN-LED Annunciator Module.......................................................................................................41
2.7.8.1 ANN-LED Board Layout ........................................................................................................42
2.7.8.2 Specifications ..........................................................................................................................42
2.7.8.3 Mounting/Installation ..............................................................................................................42
2.7.8.4 ANN-LED Connection to FACP ............................................................................................43
2.7.9: ANN-RLY Relay Module..................................................................................................................44
2.7.9.1 ANN-RLY Board Layout ........................................................................................................44
2.7.9.2 Specifications ..........................................................................................................................44
2.7.9.3 Mounting/Installation ..............................................................................................................44
2.7.9.4 ANN-RLY Connection to FACP ............................................................................................45
SECTION 3: Programming ..................................................................................................................................46
3.1: User Programming.......................................................................................................................................46
4
MRP-2002 & MRP-2002E P/N: 53049:A 4/16/07
Table of Contents
3.2: Initial Power-up................................. ........................................................... ...............................................47
3.3: Programming Screens Description..............................................................................................................47
3.4: Programming and Passwords ......................................................................................................................48
3.5: Master Programming Level............................................................ .............................................................49
3.5.1: FACP CONFIG (Application Templates).........................................................................................50
3.5.2: Input Zones........................................................................................................................................50
3.5.3: Output Circuits................................................. .................................................................................57
3.5.3.1 Enabled ....................................................................................................................................58
3.5.3.2 Type ........................................................................................................................................58
3.5.3.2.1 Release Circuit 1 or Release Circuit 2 .................................................................................58
3.5.3.2.2 Release Stage NAC ........................................ ......................................................................59
3.5.3.3 Silence .....................................................................................................................................59
3.5.3.4 Auto Silence ............................................................................................................................60
3.5.3.5 Silence Inhibited .....................................................................................................................60
3.5.3.6 Coding .....................................................................................................................................61
3.5.3.6.1 Synchronized NAC Operation .............................................................................................62
3.5.4: Cross Input Zones .............................. ...............................................................................................63
3.5.5: On-Board Relays................................... ........................................................... .................................64
3.5.6: System Setup......................................................................................... ............................................64
3.5.6.1 Abort Type ..............................................................................................................................65
3.5.6.2 Timers .....................................................................................................................................66
3.5.6.2.1 Pre-Discharge .......................................................................................................................66
3.5.6.2.2 Discharge Timer ...................................................................................................................67
3.5.6.2.3 Waterflow Delay ..................................................................................................................68
3.5.6.2.4 AC Loss Delay .....................................................................................................................68
3.5.6.3 Banner .....................................................................................................................................68
3.5.6.4 Time-Date ...............................................................................................................................70
3.5.6.4.1 Time .....................................................................................................................................70
3.5.6.4.2 Date ......................................................................................................................................70
3.5.6.4.3 Clock Format ........................................................................................................................71
3.5.6.4.4 Daylight Savings Time .........................................................................................................71
3.5.6.5 Trouble Reminder ...................................................................................................................71
3.5.6.6 Charger Disable .......................................................................................................................72
3.5.7: ANN-BUS............................................. ............................................................................................72
3.5.7.1 ANN-BUS Enabled .................................................................................................................72
3.5.7.2 ANN-BUS Modules ................................................................................................................73
3.5.7.3 Auto-Configure .......................................................................................................................73
3.5.7.4 ANN-S/PG Options .................................................................................................................74
3.5.7.5 ANN-I/O LED Zone Assignments ..........................................................................................75
3.5.7.6 ANN-80 Options .....................................................................................................................76
3.5.7.7 ANN-RLY Options .................................................................................................................77
3.5.8: History........................................................ .......................................................................................78
3.5.8.1 View Events ............................................................................................................................78
3.5.8.2 Erase History ...........................................................................................................................78
3.5.9: Walktest................................................... ............................................................. .............................79
3.5.10: Clear Program ........................................................ ..................................................
.......................80
3.5.11: Password Change.................................. ..........................................................................................80
3.6: Maintenance Programming Level......................................... ......................................................................81
3.6.1: Input Zones - Enable/Disable............................................................................................................82
3.6.2: History........................................................ .......................................................................................82
3.6.3: Walktest................................................... ............................................................. .............................83
3.6.4: Time-Date..........................................................................................................................................84
SECTION 4: Operating Instructions .................................................................................................................... 85
4.1: Panel Control Buttons .................................................................................................................................85
4.1.1: Acknowledge/Step ................................................. ...........................................................................85
MRP-2002 & MRP-2002E P/N: 53049:A 4/16/07 5
Table of Contents
4.1.2: Alarm Silenced..................................................................................................................................85
4.1.3: Drill/Hold 2 Sec ................................................................................................................................85
4.1.4: Reset..................................................................................................................................................85
4.2: Indicators.....................................................................................................................................................86
4.3: Normal Operation........................................................................................................................................86
4.4: Trouble Operation........................................................................................................................................87
4.5: Alarm Operation..........................................................................................................................................88
4.6: Supervisory Operation.................................................................................................................................89
4.7: Disable/Enable Operation............................................................................................................................90
4.8: Waterflow Circuits Operation......................................................................................................................90
4.9: Detector Functions.......................................................................................................................................90
4.10: Time Functions: Real-Time Clock ............................................................................................................90
4.11: Coded NAC Operation..............................................................................................................................90
4.12: Release Stages...........................................................................................................................................91
4.13: Special System Timers..............................................................................................................................91
4.13.1: Silence Inhibit Timer.......................................................................................................................91
4.13.2: Autosilence Timer...........................................................................................................................91
4.13.3: Trouble Reminder............................................................................................................................91
4.13.4: Pre-Discharge Delay Timer.............................................................................................................91
4.13.5: Discharge Timer ..............................................................................................................................91
4.13.6: Waterflow Delay Timer...................................................................................................................91
4.14: Walktest .....................................................................................................................................................92
4.15: Read Status................................................................................................................................................92
4.15.1: FACP Configuration........................................................................................................................93
4.15.2: Input Zones......................................................................................................................................93
4.15.3: Output Circuits................................................................................................................................94
4.15.4: Cross Input Zones............................................................................................................................95
4.15.5: On-Board Relays.............................................................................................................................95
4.15.6: System Settings...............................................................................................................................96
4.15.7: Timers..............................................................................................................................................96
4.15.8: Daylight Savings.............................................................................................................................97
4.15.9: History.............................................................................................................................................97
4.15.10: ANN-S/PG ................................... .................................................................................................97
4.15.11: ANN-BUS.............................................................. .......................................................................98
SECTION 5: Power Supply Calculations .............................................................................................................99
5.1: Overview .....................................................................................................................................................99
5.2: Calculating the AC Branch Circuit..............................................................................................................99
5.3: Calculating the System Current Draw.........................................................................................................100
5.3.1: Overview...........................................................................................................................................100
5.3.2: How to Use Table 5-3 on page 101 to Calculate System Current Draw...........................................100
5.4: Calculating the Battery Size........................................................................................................................102
5.4.1: NFPA Battery Requirements.............................................................................................................102
5.4.2: Selecting and Locating Batteries.......................................................................................................102
APPENDIX A: Circuit Mapping and Cross-Zoning ..........................................................................................103
A.1: Input-to-Output Circuit Mapping and Cross-Zone Operation ...................................................................103
A.1.1: Mapping Input Zones to Output Circuits for Direct Activation ......................................................104
A.1.2: Mapping Input Zones to Release Circuits for Cross Zone
Activation ........................................................................................................................................105
A.1.3: Complex Examples of Cross Zoning and I/O Mapping for
Release Circuits ..............................................................................................................................107
APPENDIX B: FACP Configuration Templates ................................................................................................108
B.1: Template 1: Cross-Zone System - Zones 1 & 4: All Active ................................ .....................................109
B.2: Template 2: Single Zone System With Horn ............................................................................................111
6
MRP-2002 & MRP-2002E P/N: 53049:A 4/16/07
Table of Contents
APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................113
C.1: NFPA 72 Auxiliary Fire Alarm System ....................................................................................................116
C.2: Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts ...........................................................................................................119
APPENDIX D: FACP with Keltron .....................................................................................................................120
APPENDIX E: Testing & Maintenance ...............................................................................................................121
E.1: Testing ........................................................................................................................................................121
E.1.1: Inspection .......................... ...............................................................................................................121
E.1.2: Alarm Test .......................................................................................................................................121
5.4.3: Detector Testing ................................................................................................................................121
E.2: Maintenance ................................................. ..............................................................................................122
7
MRP-2002 & MRP-2002E P/N: 53049:A 4/16/07
WARNING!
When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12.
DO NOT enter the protected space unless physical lockout and other safety procedures are fully completed.
DO NOT use software disable functions in the panel as lockout.
8 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 12 CO
Extinguishing Systems (High Pressure Only)
2
NFPA 12A Halon 1301 Extinguishing Systems NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module) NFPA 2001 Clean Agent Fire Extinguishing Systems
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems Other: NEC Article 250 Grounding
NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384 411UD Manual Document #50759 411UDAC Manual Document #51073
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 9
Main Circuit Board
A
Style D (Cl ass A) IDC
-
A
+
11
-
A
TB4/
TB6
A
+
11
TB1
J2
-
B
22
B
CAC5
REL-4.7K
Releasing Circuit
+
OUT1 OUT2
+ - + -
Class A Converter Module
Ω
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) N A C
NO NC C
+
+
Supervisory*
NO NC CNO NC C NO NC C
-
A
11 2
A
+
-
A
OUT1/3 OUT2/4
11
A
+
TB5/
TB7
OUT OUT
TB2
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
(Supervised, Power-limited, Class 2)
Unused
Output Circuit
TB5
Ω
P/N 71245
4.7K dummy load
J6
J5
J4
4XTMF OPT BD
JP30
JP24
(See Style D illustrated near right edge of board).
Ω
4.7K , ½ watt End-of-Line Resistor PN 71252
Alarm* Troub le*
A Fail Safe Trouble
relay switches to the
NC position during
trouble conditions and
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
3 Programmable Relays
trouble or supervisory activity).
under loss of all power.
(* )Factory default relay programming
TB8
Input Initiating Device Circuit - TB4 & TB6
IDCs 1 through 6, Style B (Class B) (Supervised, Power Limited, Class 2)
J7
or
Open
Devices
Normally
Pressure
Switches
Waterflow
Input IDC
Circuit #6
Waterflow
+
NAC
Output
Circuit #3
Special Application Power
Ω
Output Circuits - TB5 & TB7
4.7K , ½ watt End-of-Line Resistor PN 71252
3.0 amps max. per circuit. (See Style Z illustrated near right edge of board).
AC Output Circuit #2 (Releasing), Style Y (Class B) (Supervised, Nonpower Limited, Class 1) N
+
In this example, NAC Output Circuit s#1, #3 & #4, Styl e Y (Class B) (Supervised, Power Limited, Class 2)
NAC
Output
Circuit #1
polarized
+
+
or
Open
Tampe r
Normally
Pressure
Switches
Input IDC
Circuit #5
Supervisory
Input IDC
Circuit #1
bell
pull
station
smoke
detector
Output
Circuit #2
+
+
horn
strobe
polarized
polarized
manual
heat
detector
abort
Releasing
TB6
B
-
+ -
B
+
66
Output
Circui t #3
B
-
+ - + -
B
+
33
OUT3 OUT4
TB7
release
5
B
-
5
B
+
B
-
B
+
33
-
B
22
B
+
-
B
+ - + - + - + - + -
11
B
+
switch
B
-
22
B
+
-
B
11
B
+
+ - + -
CAC5 Class A Converter Module
TB4
OUT1 OUT2
TB5
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
FIRE ALARM
ABORT
AC POWER
J3
J2
321
JP31
RST AUX
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
ALARM
TROUBLE
ST
1
DEF
3
ABC
2 1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TU V
7
4
ANN-BUS
A B
- +
- +
GND PWR
TB3
RESET
DRILL
MODE
_/.
#
0
QZ_
*
- +
J12
BATTERY
Battery
nonpower-limited
24 VDC, supervised,
J15
26 Amp Hour maximum
Removing Ground Fault
Power Supply Connector J15
Basic System Connections
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
Important!
(Authority Having Jurisdiction).
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited (Class 2) circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited, Class 2 (0.500 amps
maximum) to smoke detectors (IDC).
Supervise with a power supervision
relay E OLR-1.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited, Class 2 (0.500 amps maximum)
Supervise with a power
supervision relay EOLR-1.. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
10 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Product Features Product Description
SECTION 1 Product Description
The MRP-2002 is a six zone FACP for single and dual hazard agent releasing applications. The FACP provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings requiring agent-based releasing. The FACP is compatible with System Sensor’s i trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45 Sensor for i compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Device Compatibility Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and nonresettable power outputs are also included on the main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control functio n.
3
detectors which are conventional smoke detectors that can transmit a maintenance
o
3
Installation and Maintenance Instructions). In addition, the control panel is
F (refer to System
The MRP-2002E offers the same features as the MRP-2002 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this manual applies to both the 110/120 VAC and 220/240 VAC versions of the panels.
1.1 Product Features
Six programmable Style B (Class B) IDCs (Initiating Device Circuit)
Four programmable Style Y (Class B) output circuits - (special application power)
Three programmable Form-C relays
7.0 amps total 24 VDC output current
Resettable and non-resettable output power
Built-in Programmer
ANN-BUS for connection to optional:
ANN-80 Remote LCD AnnunciatorANN-I/O LED DriverANN-S/PG Printer ModuleANN-RLY Relay ModuleANN-LED Annunciator Module
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History log with 256 event storage
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 11
Product Description Product Features
Control Buttons
ACK (Acknowledge)Alarm SilenceSystem Reset/Lamp TestDrill
Indicators
Fire AlarmSupervisoryTroubleAC PowerAlarm SilenceDischargePre-DischargeAbort
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Outputs Programmable for:
Releasing SolenoidsNACs programmable for:
Silence Inhibit Auto-Silence Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco) Selective Silence (horn-strobe mute) Temporal or Steady Signal Silenceable or Nonsilenceable Release Stage Sounder
Designed for agent releasing standards NFPA 12, 12A and 12B
Disable/Enable control per input zone and output zone
Extensive transient protection
Dual hazard operation
Adjustable pre-discharge, discharge and waterflow delay timers
Cross-zone (double-interlock) capability
Pre-programmed and custom application templates
Programmable Abort operation
Automatic battery charger with charger supervision
Silent or audible walktest capabilities
Optional Dress Panel DP-51050 (red)
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
Optional CAC-5X Class A Converter Module for Outputs and IDCs
Optional 4XTMF Municipal Box Transmitter Module
Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
12 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Specifications Product Description
1.2 Specifications
AC Power
MRP-2002: 120 VAC, 60 Hz, 3.66 amps MRP-2002E: 240 VAC, 50 Hz, 2.085 amps Wire size: minimum #14 AWG (2.0 mm Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp Supervised, nonpower-limited Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed in the F A CP cabinet. Larger batteries require separate battery box such as the BB-26 or BB-55) Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 and TB6
Alarm Zones 1 - 5 on TB 4 Alarm Zone 6 on TB6 Supervised and power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Standby Current: 2 mA Refer to the Device Compatibility Document for listed compatible devices
Notification Appliance and Releasing Circuit(s) - TB5 and TB7
Four Output Circuits Operation: Style Y (Class B) Special Application power Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC) End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Max. Wiring Voltage Drop: 1.5 VDC Refer to the Device Compatibility Document for compatible listed devices
2
) with 600V insulation
1
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Relay Contact Ratings: 2 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive)
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector, unsupervised circuit which can be used to monitor external devices for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits. All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note 1) Power-limited Circuitry Refer to the Device Compatibility Document for compatible listed devices
1. Total current for resettable power, nonresettable power and Output Circuits must not exceed
7.0 amps.
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 13
Product Description Controls and Indicators
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA (see note 1 on previous page) Power-limited Circuitry Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable powerJumper pins 2 & 3 on JP31 for resettable power
Refer to the Device Compatibility Document for compatible listed devices
1.3 Controls and Indicators
LCD Display The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
SYSTEM ALL NORMAL
10:00A 012106
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
RP2001kypd.cdr
Figure 1.1 Membrane/Display Panel
14 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Components Product Description
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
Indicators
Indicators are provided to annunciate the following conditions:
Fire Alarm - red indicator
Supervisory - yellow indicator
AC Power - green indicator
System Trouble - yellow indicator
Alarm Silence - yellow indicator
Discharge - red indicator
Pre-discharge - red indicator
Abort - yellow indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse ½ second on and ½ second off
Supervisory - pulse ½ second on and ½ second off
1.4 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One FLPS-7 power supply is provided standard with each F ACP, mounted to a chassis.
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp Hours). Also available is optional dress panel (DP-51050 [red] and supplied standard with Canadian FACPs, DP-51050LED for mounting ANN-LED annunciator modules) which mounts inside the cabinet and trim-ring (TR-CE [red]).
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 15
Product Description Optional Modules and Accessories
1.5 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required to convert all six Output Circuits and four Initiating Device Circuits.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator that mimics the information displayed on the FACP LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 (red) is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel.
DP-51050LED Dress Panel
A DP-51050LED dress panel is supplied standard with Canadian versions of the FACP. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. It also allows the installation of an optional ANN-LED annunciator module.
TR-CE Trim-ring
A trim-ring TR-CE (red) is available as an option. The trim-ring allows semi-flush mounting of the cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
module provides a connection for a serial or parallel printer.
16 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Backbox Mounting Installation
SECTION 2 Installation
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures or levels of humidity are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Backbox Mounting
The circuit board contains static-sensitive components. Always ground yourself with a pr oper wrist strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to th e circui t board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
grounding stud: attach solid earth ground wire (refer to Figure 2.4 on page 20)
Mark and predrill hole in the wall for the center top keyhole mounting bolt us ing the
dimensions illustrated in Figure 2.2 on page 18
Install center top fastener in the wall with the screw head protrudingPlace backbox over the top screw, level and secureMark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” on-center stud mounting
Install remaining fasteners and tighten
Main CircuitBoard on Chassis
mounting holes
mounting slots
mounting studs
mounting slots
mounting tabs
Backbox
5UDBRDINBOX.CDR
Figure 2.1 Chassis Mounting in Backbox
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 17
Installation Backbox Mounting
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to
Hinge Slot for optional Dress Panel
avoid covering venting holes on top of box.
Mounting slots for optional Trim Ring
Semi-Flush mounting hole
Hinge Slot for optional Dress Panel
9050UDencl.cdr
Figure 2.2 Cabinet Dimensions
18 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Backbox Mounting Installation
Figure 2.3 Backbox
9050udcab.cdr
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 19
Installation Operating Power
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equ ipm ent may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The pri mary power source for the panel is 120 VAC, 60 Hz, 3.66 amps for the MRP-2002 or 240 VAC, 50 HZ, 2.085 amps for the MRP-2002E. Run a pair of wires (with ground conductor) from the protected premises main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14 AWG (2.00 mm insulation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm grounding stud in the backbox. Do not use conduit for the Earth Ground connection since this does
not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V
2
)] to the
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
!
water for 15 minutes and seek immediate medical attention.
120 VAC Power
Hot (L1)
Ground
Neutral (L2)
Ground Wire
J12
+-
Batteries
rp2001powr.cdr
Figure 2.4 Operating Power Connections
20 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Input Circuits Installation
2.3 Input Circuits
The MRP-2002 has six programmable IDCs (Initiating Device Circuits). Each circuit is compatible with System Sensor ’s i
3
smoke detectors which generate a maintenance signal when the detector
becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating of approximately 45
o
F. The maximum loop resistance limit for each IDC is 100 ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. Refer to the Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
UL listed Power Supervision Relay
UL listed compatible 4-wire smoke detector
manual pull stations
heat detectors
Dummy load all unused circuits - 4.7 K resistor (P/N: 71245)
Ω, ½ watt
abort switch
manual release
3
smoke detectors, any
Input IDC Waterflow Circuit Normally Open Waterflow Devices or Pressure Switches
Figure 2.5 IDC Connections
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 21
ms-10UDidc.cdr
Installation Input Circuits
Combination Waterflow/Su pervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch (tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch (waterflow)
Dummy load all unused circuits - 4.7 KΩ, ½ watt resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6
ms10udcomboIDC.cdr
Program the FACP Initiating Devi ce Circui t as a Combination circuit as described in
"Input Zones" on page 50. Note that since a Waterflow Supervisory Swit ch is inclu ded in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to "Waterflow Delay" on page 68.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition is cleared) if the Combo Autoresettable Supervisory type code is selected
22 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Output Circuits Installation
2.4 Output Circuits
2.4.1 Outputs/Notification Appliance/Releasing Circuits
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and provides special application power. Refer to the Device Compatibility Document for a listing of compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Ferrite Beads P/N 29150
Polarized Bell
Polarized Strobe
Polarized Horn
+ - + -
Polarized Bell
Polarized Strobe
Polarized Horn
Releasing Solenoid
Notification Appliance Circuits polarity shown in alarm condition
Ferrite Bead P/N 29150
Note: Short Circuit Supervision must be enabled when using the REL-4.7K for Canadian Applications. Refer to the section titled "Release Circuit 1 or Release Circuit 2" on page 58 for information on enabling short circuit supervision.
Dummy load any unused circuits (P/N: 71245)
+ - + -
rp2001nac.cdr
Ferrite Bead (P/N 29150)
Large gauge wire should be looped through bead at least once as illustrated. Smaller gauge wire can be looped more often.
Ferrite Bead in open position
Ferrite Bead in closed position
Figure 2.7 NAC/Output Connections
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 23
Installation Output Circuits
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the MRP-2002 control panel.
Special Application 4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from these terminals (power-limited)
Special Application Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be obtained from these terminals (power-limited)
Jumper JP31 pins 1 & 2 for nonresettable power (as illustrated in figure to right)
-
4
+
3
-
2
+
1
ms-10UDtb9.cdr
Jumper JP31 pins 2 & 3 for resettable power
Figure 2.8 Special Application Auxiliary Power
2.4.3 Relays - Programmable
The MRP-2002 control panel provides a factory default programmed alarm relay, fail-safe trouble relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer to "On-Board Relays" on page 64). Each Form-C relay is rated for 2 amps @ 30VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Note: Relay contacts are shown with power applied to the panel and no active troubles, alarms or supervisories. The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.
ms10udrelay.cdr
Figure 2.9 Relay Terminals
24 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Power-limited Wiring Requirements Installation
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower­limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is illustrated below.
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent to a releasing circuit (nonpower-limited without supervision kit REL-4.7K)
Nonpower-limited Circuits*
Power-limited Circuits (Class 2)
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
earth
ground
CAC-5X
Power-limited Circuits (Class 2)
Power-limited
Circuits
(Class 2)
CAC-5X
4XTMF
Nonpower­limited Circuit
Nonpower­limited Circuit
Power-limited Circuit (Class 2)
Agent Releasing FACP
Figure 2.10 Typical UL Power-limited Wiring Requirements
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 25
RP2001ULwire.cdr
Installation Inst allation of Optional Modules
2.6 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.6.1 CAC-5X Class A Converter Module
2.6.1.1 Installation
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). Two CAC-5X Modules are required to convert all Output Circuits and/or Initiating Device Circuits to Class A. The modules plug into connector J2 which is located at the top left of the main circuit board and J7 which is located at the top center of the main circuit board.
To install the CAC-5X, remove the two main circuit board mounting screws referenced in the following illustration and replace with the two supplied male/female standoffs in the locations indicated in the following figure. Carefully align the connector on the CAC-5X with J2 on the FACP main circuit board and press the module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to the standoffs with the screws that were just removed.
T o install the second CAC-5X on J7, remove the main circuit board mounting screw referenced in the following illustration and replace with the supplied male/female standoff. Insert the supplied plastic standoff in the location indicated in the following illustration. Carefully align the connector on the CAC-5X with J7 and press the module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to the metal standoff with the screw that was just removed.
Installation on J2 Connector
CAC-5X Module
Metal Standoff
Installation on J7 Connector
CAC-5X Module
Metal Standoff
Main Circuit Board
Figure 2.11 CAC-5X Module Installation
Plastic Standoff
Metal Standoff
rp2001cac5mnt.cdr
26 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Installation of Optional Modules Installation
2.6.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuit board and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits using TB4 of the FACP main circuit board and TB1 of the CAC-5X. Note that the wiring will be identical when using TB7 NAC and TB6 IDC of the FACP. Make certain to observe polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed and return for the positive side of a device and the B- and A- terminals must comprise the feed and return for the negative side of a device. To configure any of the zones for Class B when the CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-5X module.
Class B (Style B) IDC - 4.7 KΩ
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Class A (Style Z) NAC
(supervised and power-limited)
Polarized
Bell
Polarized
Strobe
Polarized
Horn
Ferrite Bead P/N 29150
Circuit polarities shown in alarm condition
B+ B- B+ B-
A+ A-
A+ A-
Smoke
Pull Station
Heat
B+ B- B+ B- B+ B- B+ B- B+ B-
Smoke
Pull Station
Heat
A+ A- A+ A- A+ A- A+ A- A+ A-
Class A (Style D) IDC
(supervised and power-limited)
Dummy load all unused circuits - 4.7 K ½ watt resistor (P/N: 71245)
FACP Main
Circuit Board
Ω
CAC-5X Class A Converter Module
Large gauge wire should be looped through bead at least once as illustrated. Smaller gauge wire can be looped more often.
Ferrite Bead in open position
2550ferr.cdr
Ferrite Bead in closed position
ms10udclassa.cdr
Figure 2.12 Wiring NACs and IDCs for Class A Operation
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 27
Installation Inst allation of Optional Modules
2.6.2 4XTMF Municipal Box Transmitter Option Module
The 4XTMF module can be plugged into connectors J4 and J5 on the main circuit board. The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the placement of the 4XTMF option module
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in the following sections
7. Test system for proper operation
Figure 2.13 4XTMF Option Module Connection
Standoffs
J4 J5
rp2001bord.cdr
28 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Installation of Optional Modules Installation
2.6.2.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFP A 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble indicator will turn on to indicate the Disconnect condition.
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal. For an application using reverse polarity of a supervisory signal, refer to the Appendix titled "FACP with Keltron" on page 120.
TBL Jumper
Disconnect Switch shown in disconnect position
TB1
TBL
J1
J2
Connect to FACP Connectors J4 & J5
Polarities are shown for module activation
1+ 2­3+ 4­5 6+ 7-
}Remote Alarm (power-limited)* }Remote Trouble (power-limited)*
No connection
}Municipal Box (nonpower-limited)*
* Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Box is not connected.
4xtmf.cdr
Disconnect LED
Figure 2.14 4XTMF Transmitter Module
MRP-2002 & MRP-2002E PN 53049:A 4/16/2007 29
Installation ANN-BUS Devices
2.7 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit. Compatible devices include:
ANN-80 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-LED Annunciator Module (annunciates alarms, troubles and supervisories)
ANN-RLED Annunciator Module (annunciates alarms only)
ANN-RLY Relay Module
2.7.1 ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B).
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
T o calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the following table:
Model Number Worst Case Current Draw
ANN-80 LCD Annunciator 0.040 amps
ANN-S/PG Serial/Parallel Printer Interface Module 0.040 amps
ANN-I/O LED Driver Module 0.200 amps
ANN-(R)LED Annunciator Module 0.068 amps
ANN-RLY Relay Module 0.075 amps
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.
30 MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Loading...
+ 102 hidden pages