While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
1.3: Controls and Indicators................................................................................................... .............................14
2.6: Installation of Optional Modules.................................................................................................................26
2.6.1: CAC-5X Class A Converter Module ................................................................................................26
3.1: User Programming.......................................................................................................................................46
3.4: Programming and Passwords ......................................................................................................................48
3.5.3.2 Type ........................................................................................................................................58
3.5.3.2.1 Release Circuit 1 or Release Circuit 2 .................................................................................58
3.5.6: System Setup......................................................................................... ............................................64
3.5.6.1 Abort Type ..............................................................................................................................65
3.5.6.4.1 Time .....................................................................................................................................70
3.5.6.4.2 Date ......................................................................................................................................70
3.5.6.4.3 Clock Format ........................................................................................................................71
3.5.6.4.4 Daylight Savings Time .........................................................................................................71
4.1: Panel Control Buttons .................................................................................................................................85
4.3: Normal Operation........................................................................................................................................86
4.13: Special System Timers..............................................................................................................................91
4.15.6: System Settings...............................................................................................................................96
5.3.2: How to Use Table 5-3 on page 101 to Calculate System Current Draw...........................................100
5.4: Calculating the Battery Size........................................................................................................................102
E.1.2: Alarm Test .......................................................................................................................................121
When used for CO2 releasing applications,
observe proper precautions as stated in
NFPA 12.
DO NOT enter the protected space unless
physical lockout and other safety procedures
are fully completed.
DO NOT use software disable functions in the
panel as lockout.
8MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 12 CO
Extinguishing Systems (High Pressure Only)
2
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
NFPA 2001 Clean Agent Fire Extinguishing Systems
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MRP-2002 & MRP-2002E PN 53049:A 4/16/20079
Main Circuit Board
A
Style D (Cl ass A) IDC
-
A
+
11
-
A
TB4/
TB6
A
+
11
TB1
J2
-
B
22
B
CAC5
REL-4.7K
Releasing Circuit
+
OUT1 OUT2
+ - + -
Class A Converter Module
Ω
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) N A C
NO NC C
+
+
Supervisory*
NO NC CNO NC C NO NC C
-
A
11 2
A
+
-
A
OUT1/3 OUT2/4
11
A
+
TB5/
TB7
OUT OUT
TB2
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
(Supervised, Power-limited, Class 2)
Unused
Output Circuit
TB5
Ω
P/N 71245
4.7K dummy load
J6
J5
J4
4XTMF OPT BD
JP30
JP24
(See Style D illustrated near right edge of board).
Ω
4.7K , ½ watt End-of-Line Resistor PN 71252
Alarm* Troub le*
A Fail Safe Trouble
relay switches to the
NC position during
trouble conditions and
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
3 Programmable Relays
trouble or supervisory activity).
under loss of all power.
(*)Factory default relay programming
TB8
Input Initiating Device Circuit - TB4 & TB6
IDCs 1 through 6, Style B (Class B) (Supervised, Power Limited, Class 2)
J7
or
Open
Devices
Normally
Pressure
Switches
Waterflow
Input IDC
Circuit #6
Waterflow
+
NAC
Output
Circuit #3
Special Application Power
Ω
Output Circuits - TB5 & TB7
4.7K , ½ watt End-of-Line Resistor PN 71252
3.0 amps max. per circuit. (See Style Z illustrated near right edge of board).
AC Output Circuit #2 (Releasing), Style Y (Class B) (Supervised, Nonpower Limited, Class 1)
N
+
In this example, NAC Output Circuit s#1, #3 & #4, Styl e Y (Class B) (Supervised, Power Limited, Class 2)
NAC
Output
Circuit #1
polarized
+
+
or
Open
Tampe r
Normally
Pressure
Switches
Input IDC
Circuit #5
Supervisory
Input IDC
Circuit #1
bell
pull
station
smoke
detector
Output
Circuit #2
+
+
horn
strobe
polarized
polarized
manual
heat
detector
abort
Releasing
TB6
B
-
+ -
B
+
66
Output
Circui t #3
B
-
+ - + -
B
+
33
OUT3 OUT4
TB7
release
5
B
-
5
B
+
B
-
B
+
33
-
B
22
B
+
-
B
+ - + - + - + - + -
11
B
+
switch
B
-
22
B
+
-
B
11
B
+
+ - + -
CAC5 Class A Converter Module
TB4
OUT1 OUT2
TB5
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
FIRE ALARM
ABORT
AC POWER
J3
J2
321
JP31
RST AUX
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
ALARM
TROUBLE
ST
1
DEF
3
ABC
2
1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TU V
7
4
ANN-BUS
A B
- +
- +
GND PWR
TB3
RESET
DRILL
MODE
_/.
#
0
QZ_
*
- +
J12
BATTERY
Battery
nonpower-limited
24 VDC, supervised,
J15
26 Amp Hour maximum
Removing Ground Fault
Power Supply Connector J15
Basic System Connections
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
Important!
(Authority Having Jurisdiction).
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited (Class 2) circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited, Class 2 (0.500 amps
maximum) to smoke detectors (IDC).
Supervise with a power supervision
relay E OLR-1.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited, Class 2 (0.500 amps maximum)
Supervise with a power
supervision relay EOLR-1.. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
10MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Product FeaturesProduct Description
SECTION 1Product Description
The MRP-2002 is a six zone FACP for single and dual hazard agent releasing applications. The
FACP provides reliable fire detection, signaling and protection for commercial, industrial and
institutional buildings requiring agent-based releasing. The FACP is compatible with System
Sensor’s i
trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when
the ambient temperature falls below the detector rating of approximately 45
Sensor for i
compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke
detectors, pull stations, waterflow devices, tamper switches and other normally-open contact
devices. Refer to Device Compatibility Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids.
Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory)
and 24 VDC special application resettable and nonresettable power outputs are also included on the
main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicator, display alarm information on
the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate
an optional module used to notify a remote station or initiate an auxiliary control functio n.
3
detectors which are conventional smoke detectors that can transmit a maintenance
o
3
Installation and Maintenance Instructions). In addition, the control panel is
F (refer to System
The MRP-2002E offers the same features as the MRP-2002 but allows connection to 220/240 VAC.
Unless otherwise specified, the information in this manual applies to both the 110/120 VAC and
220/240 VAC versions of the panels.
1.1 Product Features
•Six programmable Style B (Class B) IDCs (Initiating Device Circuit)
•Four programmable Style Y (Class B) output circuits - (special application power)
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 26 Amp Hour battery (two 18 Amp Hour batteries can be housed
in the F A CP cabinet. Larger batteries require separate battery box such as the BB-26 or BB-55)
Minimum Battery Size: 7 Amp Hour
Initiating Device Circuits - TB4 and TB6
Alarm Zones 1 - 5 on TB 4
Alarm Zone 6 on TB6
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to the Device Compatibility Document for listed compatible devices
Notification Appliance and Releasing Circuit(s) - TB5 and TB7
Four Output Circuits
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Max. Wiring Voltage Drop: 1.5 VDC
Refer to the Device Compatibility Document for compatible listed devices
The Auxiliary Trouble Input is an open collector, unsupervised circuit which can be used to
monitor external devices for trouble conditions. It can be connected to the trouble bus of a
peripheral, such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to the Device Compatibility Document for compatible listed devices
1. Total current for resettable power, nonresettable power and Output Circuits must not exceed
7.0 amps.
MRP-2002 & MRP-2002E PN 53049:A 4/16/200713
Product DescriptionControls and Indicators
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1 on previous page)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to the Device Compatibility Document for compatible listed devices
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
SYSTEM ALL NORMAL
10:00A 012106
Function keys:
•Acknowledge/Step
•Alarm Silence
•Drill
•System Reset (lamp test)
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
•1st Event key
•Clear key
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
RP2001kypd.cdr
Figure 1.1 Membrane/Display Panel
14MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
ComponentsProduct Description
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory
conditions.
Indicators
Indicators are provided to annunciate the following conditions:
•Fire Alarm - red indicator
•Supervisory - yellow indicator
•AC Power - green indicator
•System Trouble - yellow indicator
•Alarm Silence - yellow indicator
•Discharge - red indicator
•Pre-discharge - red indicator
•Abort - yellow indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
•Alarm - on steady
•Trouble - pulse 1 second on and 1 second off
•Maintenance - pulse ½ second on and ½ second off
•Supervisory - pulse ½ second on and ½ second off
1.4 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring
interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One FLPS-7 power supply is provided standard with each F ACP, mounted to a chassis.
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available is optional dress panel (DP-51050
[red] and supplied standard with Canadian FACPs, DP-51050LED for mounting ANN-LED
annunciator modules) which mounts inside the cabinet and trim-ring (TR-CE [red]).
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.
MRP-2002 & MRP-2002E PN 53049:A 4/16/200715
Product DescriptionOptional Modules and Accessories
1.5 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect
to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required
to convert all six Output Circuits and four Initiating Device Circuits.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator that mimics the information displayed on the FACP
LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and
Supervisory.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 (red) is available as an option. The dress panel restricts access to the
system wiring while allowing access to the membrane switch panel.
DP-51050LED Dress Panel
A DP-51050LED dress panel is supplied standard with Canadian versions of the FACP. The dress
panel restricts access to the system wiring while allowing access to the membrane switch panel. It
also allows the installation of an optional ANN-LED annunciator module.
TR-CE Trim-ring
A trim-ring TR-CE (red) is available as an option. The trim-ring allows semi-flush mounting of the
cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour.
The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
module provides a connection for a serial or parallel printer.
16MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Backbox MountingInstallation
SECTION 2Installation
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the
installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots
at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures or levels of humidity are not encountered. The area
should be readily accessible with sufficient room to easily install and maintain the panel. Locate
the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the
left. Determine the number of conductors required for the devices to be installed. Sufficient
knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the
conductors into the box. All wiring should be in accordance with the National and/or Local codes
for fire alarm systems.
2.1 Backbox Mounting
The circuit board contains static-sensitive components. Always ground yourself with a pr oper wrist
strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to th e circui t board and to facilitate backbox mounting, the chassis with main
circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top
flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis
assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
grounding stud:
attach solid earth
ground wire (refer to
Figure 2.4 on page 20)
Mark and predrill hole in the wall for the center top keyhole mounting bolt us ing the
dimensions illustrated in Figure 2.2 on page 18
Install center top fastener in the wall with the screw head protruding
Place backbox over the top screw, level and secure
Mark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” on-center stud mounting
Install remaining fasteners and tighten
Main CircuitBoard on Chassis
mounting holes
mounting slots
mounting studs
mounting slots
mounting tabs
Backbox
5UDBRDINBOX.CDR
Figure 2.1 Chassis Mounting in Backbox
MRP-2002 & MRP-2002E PN 53049:A 4/16/200717
InstallationBackbox Mounting
Semi-Flush Mounting
Do not recess box more
than 3.875” into wall to
Hinge Slot for
optional Dress Panel
avoid covering venting
holes on top of box.
Mounting
slots for
optional
Trim Ring
Semi-Flush
mounting hole
Hinge Slot for optional
Dress Panel
9050UDencl.cdr
Figure 2.2 Cabinet Dimensions
18MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Backbox MountingInstallation
Figure 2.3 Backbox
9050udcab.cdr
MRP-2002 & MRP-2002E PN 53049:A 4/16/200719
InstallationOperating Power
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equ ipm ent may be damaged by
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The pri mary power source for the
panel is 120 VAC, 60 Hz, 3.66 amps for the MRP-2002 or 240 VAC, 50 HZ, 2.085 amps for the
MRP-2002E. Run a pair of wires (with ground conductor) from the protected premises main
breaker box to the AC terminal block TB1 on the main power supply. As per the National
Electrical Code, use 14 AWG (2.00 mm
insulation. No other equipment may be connected to this circuit. In addition, this circuit must be
provided with overcurrent protection and may not contain any power disconnect devices. A
separate Earth Ground connection must be made to ensure proper panel operation and lightning and
transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
grounding stud in the backbox. Do not use conduit for the Earth Ground connection since this does
not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit
board using the plug-in connector and cable provided. The battery charger is current-limited and
capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V
2
)] to the
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
!
water for 15 minutes and seek immediate medical attention.
120 VAC Power
Hot (L1)
Ground
Neutral (L2)
Ground Wire
J12
+-
Batteries
rp2001powr.cdr
Figure 2.4 Operating Power Connections
20MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Input CircuitsInstallation
2.3 Input Circuits
The MRP-2002 has six programmable IDCs (Initiating Device Circuits). Each circuit is compatible
with System Sensor ’s i
3
smoke detectors which generate a maintenance signal when the detector
becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the
detector rating of approximately 45
o
F. The maximum loop resistance limit for each IDC is 100
ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is
supervised for opens, shorts and ground faults. All conditions are visually and audibly
annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
Refer to the Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A
Converter module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
UL listed Power Supervision Relay
UL listed compatible 4-wire smoke detector
manual pull stations
heat detectors
Dummy load all unused
circuits - 4.7 K
resistor (P/N: 71245)
Ω, ½ watt
abort
switch
manual
release
3
smoke detectors, any
Input IDC
Waterflow Circuit
Normally Open
Waterflow
Devices or
Pressure Switches
Figure 2.5 IDC Connections
MRP-2002 & MRP-2002E PN 53049:A 4/16/200721
ms-10UDidc.cdr
InstallationInput Circuits
Combination Waterflow/Su pervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch
(tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6
ms10udcomboIDC.cdr
Program the FACP Initiating Devi ce Circui t as a Combination circuit as described in
"Input Zones" on page 50. Note that since a Waterflow Supervisory Swit ch is inclu ded in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to
"Waterflow Delay" on page 68.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition
is cleared) if the Combo Autoresettable Supervisory type code is selected
Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and
provides special application power. Refer to the Device Compatibility Document for a listing of
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter
module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Ferrite Beads
P/N 29150
Polarized Bell
Polarized Strobe
Polarized Horn
+ - + -
Polarized Bell
Polarized Strobe
Polarized Horn
Releasing Solenoid
Notification Appliance Circuits
polarity shown in alarm condition
Ferrite Bead
P/N 29150
Note: Short Circuit Supervision must be enabled when using the
REL-4.7K for Canadian Applications. Refer to the section titled
"Release Circuit 1 or Release Circuit 2" on page 58 for information
on enabling short circuit supervision.
Dummy load any unused
circuits (P/N: 71245)
+ - + -
rp2001nac.cdr
Ferrite Bead (P/N 29150)
Large gauge wire
should be looped
through bead at least
once as illustrated.
Smaller gauge wire can
be looped more often.
Ferrite Bead in open position
Ferrite Bead in closed position
Figure 2.7 NAC/Output Connections
MRP-2002 & MRP-2002E PN 53049:A 4/16/200723
InstallationOutput Circuits
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the MRP-2002
control panel.
Special Application
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors
can be obtained from these terminals (power-limited)
Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be
obtained from these terminals (power-limited)
•Jumper JP31 pins 1 & 2 for nonresettable power (as
illustrated in figure to right)
-
4
+
3
-
2
+
1
ms-10UDtb9.cdr
•Jumper JP31 pins 2 & 3 for resettable power
Figure 2.8 Special Application Auxiliary Power
2.4.3 Relays - Programmable
The MRP-2002 control panel provides a factory default programmed alarm relay, fail-safe trouble
relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer
to "On-Board Relays" on page 64). Each Form-C relay is rated for 2 amps @ 30VDC (resistive)
and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or
total power failure.
ms10udrelay.cdr
Figure 2.9 Relay Terminals
24MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Power-limited Wiring RequirementsInstallation
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpowerlimited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
*Note: In certain applications, an NAC (power-limited circuit) could be adjacent
to a releasing circuit (nonpower-limited without supervision kit REL-4.7K)
Nonpower-limited Circuits*
Power-limited Circuits (Class 2)
AC Power
120 VAC
Hot (L1)
Ground
Neutral (L2)
earth
ground
CAC-5X
Power-limited Circuits (Class 2)
Power-limited
Circuits
(Class 2)
CAC-5X
4XTMF
Nonpowerlimited
Circuit
Nonpowerlimited
Circuit
Power-limited
Circuit (Class 2)
Agent Releasing FACP
Figure 2.10 Typical UL Power-limited Wiring Requirements
MRP-2002 & MRP-2002E PN 53049:A 4/16/200725
RP2001ULwire.cdr
InstallationInst allation of Optional Modules
2.6 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.6.1 CAC-5X Class A Converter Module
2.6.1.1 Installation
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). Two CAC-5X Modules are required to convert all Output Circuits and/or Initiating
Device Circuits to Class A. The modules plug into connector J2 which is located at the top left
of the main circuit board and J7 which is located at the top center of the main circuit board.
To install the CAC-5X, remove the two main circuit board mounting screws referenced in the
following illustration and replace with the two supplied male/female standoffs in the locations
indicated in the following figure. Carefully align the connector on the CAC-5X with J2 on the
FACP main circuit board and press the module securely into place. Make certain the pins are
properly aligned to prevent bending or breaking of any connector pins. Secure the CAC-5X to
the standoffs with the screws that were just removed.
T o install the second CAC-5X on J7, remove the main circuit board mounting screw referenced
in the following illustration and replace with the supplied male/female standoff. Insert the
supplied plastic standoff in the location indicated in the following illustration. Carefully align
the connector on the CAC-5X with J7 and press the module securely into place. Make certain
the pins are properly aligned to prevent bending or breaking of any connector pins. Secure the
CAC-5X to the metal standoff with the screw that was just removed.
Installation on J2 Connector
CAC-5X Module
Metal
Standoff
Installation on J7 Connector
CAC-5X Module
Metal
Standoff
Main Circuit Board
Figure 2.11 CAC-5X Module Installation
Plastic
Standoff
Metal
Standoff
rp2001cac5mnt.cdr
26MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Installation of Optional ModulesInstallation
2.6.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuit
board and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits
using TB4 of the FACP main circuit board and TB1 of the CAC-5X. Note that the wiring will
be identical when using TB7 NAC and TB6 IDC of the FACP. Make certain to observe polarity
when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed
and return for the positive side of a device and the B- and A- terminals must comprise the feed
and return for the negative side of a device. To configure any of the zones for Class B when the
CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and install the
End-of-Line Resistor after the last device on the circuit. Do not wire to the corresponding A+
and A- terminals on the CAC-5X module.
Class B (Style B) IDC - 4.7 KΩ
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Class A (Style Z) NAC
(supervised and power-limited)
Polarized
Bell
Polarized
Strobe
Polarized
Horn
Ferrite Bead
P/N 29150
Circuit polarities
shown in alarm
condition
B+ B-B+ B-
A+ A-
A+ A-
Smoke
Pull Station
Heat
B+ B- B+ B- B+ B- B+ B- B+ B-
Smoke
Pull Station
Heat
A+ A- A+ A- A+ A- A+ A- A+ A-
Class A (Style D) IDC
(supervised and power-limited)
Dummy load all unused
circuits - 4.7 K
½ watt resistor
(P/N: 71245)
FACP Main
Circuit Board
Ω
CAC-5X Class A Converter Module
Large gauge wire should be looped through
bead at least once as illustrated. Smaller
gauge wire can be looped more often.
Ferrite Bead in open position
2550ferr.cdr
Ferrite Bead in closed position
ms10udclassa.cdr
Figure 2.12 Wiring NACs and IDCs for Class A Operation
MRP-2002 & MRP-2002E PN 53049:A 4/16/200727
InstallationInst allation of Optional Modules
2.6.2 4XTMF Municipal Box Transmitter Option Module
The 4XTMF module can be plugged into connectors J4 and J5 on the main circuit board.
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP30 on the main circuit board to allow the control panel to supervise the
placement of the 4XTMF option module
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide
the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP
main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in
the following sections
7. Test system for proper operation
Figure 2.13 4XTMF Option Module Connection
Standoffs
J4
J5
rp2001bord.cdr
28MRP-2002 & MRP-2002E PN 53049:A 4/16/2007
Installation of Optional ModulesInstallation
2.6.2.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in
addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. A disable switch
allows disabling of the transmitter output during testing to prevent accidental calling of the
monitoring service.
Local Energy Municipal Box Service (NFP A 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the FACP. In addition, the System Trouble indicator will turn on
to indicate the Disconnect condition.
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application using reverse polarity of a supervisory signal,
refer to the Appendix titled "FACP with Keltron" on page 120.
* Wiring from these terminals can
exit the protected premises.
Dummy load terminals 6 and 7
(4.7kΩ, ¼ watt resistor) if
Municipal Box is not connected.
4xtmf.cdr
Disconnect LED
Figure 2.14 4XTMF Transmitter Module
MRP-2002 & MRP-2002E PN 53049:A 4/16/200729
InstallationANN-BUS Devices
2.7 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit.
Compatible devices include:
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
2.7.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the
maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
T o calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is
necessary to calculate the total worst case current draw for all modules on a single 4-conductor
bus. The total worst case current draw is calculated by adding the individual worst case
currents for each module. The individual worst case values are shown in the following table: