Fire-Lite MPS-24B-BE-BF User Manual

Power-limited Notification Appliance Power
The +24 VDC regulated, nonresettable power available on TB2 Terminal 3 is power-limited only when used with the minus return on TB2 Terminal 4.
Do not use the minus return on TB2 Terminal 2 with
the +24 VDC power on TB2 Terminal 3. Refer to the illustration below.
+
Four-Wire Smoke Detector/Annunciator Power
+ 24 VDC (20.4-26.4, 200 mV ripple), 200 mA max. Filtered, regulated and resettable*. Power-limited but when used for four-wire detectors, must be supervised by
-
a UL listed Power Supervision Relay.
+
-
Primary Power
120 VAC, 50/60 HZ, 1.8 amps max.
Neutral Hot
Earth Ground
Earth Ground
Connect to chassis with a Grounding Cable Assembly.
Cut R55 to disable Earth Fault Detection
MPS-24B/BE/BF
Technical Supplement
Document 50289 Rev A 5/4/95 ECN 95-219
Notification Appliance power + 24 VDC power-limited, RMS-regulated, non­resettable, 2.0 amps (in alarm) max. Power is supervised by output module.
suitable for powering annunciators!
CAUTION: The +24 VDC provided on TB2 Terminal 3 is power-limited only when used with the minus return on TB2 Terminal 4.
return on TB2 Terminal 2 with the +24 VDC power on TB2 Terminal 3.
Secondary Power
27.6 VDC, 6.5 to 17 AH. Supervised and power-limited. Fast charge =750mA max., trickle charge = 20 mA (typ).
Battery + Battery -
This output is not
Do not use the minus
Cut JP2 to disable the battery charger when employing the Remote Battery Charger.
LED Indicators
Ground Fault (-) Ground Fault (+) Battery Fail AC Power Fail
* Cut JP1 to make Four­Wire Smoke Detector Power on TB2 Terminals 1 and 2 a nonresettable circuit.