
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72-
1993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120O F
and at a relative humidity of 85% RH (non-condensing) at 30O C/86O F.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27O C/60-80
F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
O
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further-
more, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
FCC Warning
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Technical Publishing Document PRECAULG.PM6 12/31/96
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.

Table of Contents
Section One: General Information.......................................................... 4
Standard Features .............................................................. 4
Section Two: Controls and Indicators.................................................... 5
Section Three: Technical Specifications .................................................. 6
System Power Requirements.............................................. 6
Detection Loop .................................................................... 6
Two-wire Smoke Detector................................................... 6
Main Notification Appliance Circuits .................................... 6
External Device Power........................................................ 6
Battery Charger................................................................... 6
Optional Modules ................................................................ 7
Section Four: Installation Instructions ................................................... 8
PC Board Removal ............................................................. 8
Optional Module Installation ................................................ 8
PC Board Installation .......................................................... 8
Field Wiring ....................................................................... 10
Alarm Initiating Devices..................................................... 11
Notification Appliance Circuits........................................... 12
Regulated DC Output........................................................ 12
AC Power Connections ..................................................... 12
Standby Battery Power ..................................................... 12
Section Five: Periodic Testing and Maintenance ................................ 13
Section Six: Troubleshooting Guide .................................................. 14
Appendix A: Battery Selection Guide.................................................. 16
MP-12/24 Fire Alarm Control Panel Document 15440:G 6/6/96
3

Section One:
General Information
The MP-12/24 fire alarm control panel provides reliable fire signaling protection for small to medium sized
commercial, industrial, and institutional buildings. This control panel functions in accordance with the following National Fire Protection Association (NFPA) standards:
• NFPA 72-1993 Local Fire Alarm Systems
• NFPA 72-1993 Remote Station Fire Alarm Systems (requires an optional Remote Station Output
Module).
The MP-12/24 control panels were tested as fire protective signaling system control units under Underwriters
Laboratories, Inc., Standard for Safety, Number UL864.
Activation of a compatible two-wire detector or any normally open fire alarm initiating device will sound
audible signaling devices, illuminate an indicating LED at the control panel and operate an optional module.
The optional modules can be used to notify a remote station or initiate a supplementary control function.
Standard Features
•
A trouble circuit which monitors the following fault conditions:
Open detector loop(s).
Low battery voltage.
Missing or disconnected battery.
Ground fault.
Low AC voltage (Brown-out condition).
Loss of AC power.
“Off normal” switch position.
Open or shorted Notification Appliance (bell) Circuit.
•
Control switches.
Reset for control and detectors.
Trouble Silence with resound.
Disable to silence alarm.
•
LED indicating lamps.
AC power.
Alarm Annunciator(s).
Trouble.
•
Detection loop.
Compatible with many types of two-wire detectors.
Power limited for limited energy cable.
Supervised Style B (Class B) operation.
•
Supervised Style Y (Class B) audible/visual signaling circuit.
•
Compact size with solid state electronics.
•
Automatic float charger.
•
Piezoelectric transducer for audible trouble signal.
•
Panel will accept one of the following optional modules:
Supplementary alarm contacts, two Form-C.
Supplementary alarm and trouble contacts, Form-C alarm, Form-C trouble.
Remote station output, alarm only.
Remote station output, alarm and trouble.
4
MP12/24 Fire Alarm Control Panel Document 15440:G 6/6/96

Section Two:
Controls and Indicators
RESET - The function of this switch is to reset the control panel and the smoke detectors provided the alarm
condition has been cleared. A trouble condition is indicated while this switch is depressed.
TROUBLE SILENCE - This latching, two-position switch, when pressed, will silence the pulsing audible
trouble signal. The trouble LED will continue to indicate a trouble condition. An intermittent tone will sound
when the trouble is corrected to indicate that this switch should be returned to its outward (normal) position.
DISABLE - This latching, two-position switch, when pressed, will prevent the activation of Notification
Appliances and the operation of the optional modules. The alarm LED(s) will continue to indicate the alarm
conditions. A trouble condition is indicated while this switch is in the off-normal position.
ALARM - Red LED(s) which indicate an alarm condition. The DISABLE switch will not effect the ALARM
LED(s).
TROUBLE - A yellow LED which is illuminated during a fault or abnormal operating condition.
AC - The green LED is on when the control panel is operating from the AC power source. Yellow and green
LEDs both flash to indicate below normal line voltage (brown-out). An extinguished green LED indicates
complete loss of AC power.
AUDIBLE TONE - An audible tone will sound to indicate the following:
• Alarm: A continuous sounding audible tone.
• Trouble: A pulsing audible tone signal having a short on time and long off time.
NORMAL STANDBY OPERATION
• All push button switches must
be in the normal outward
position.
• Green AC power indicator on
steady.
• Red ALARM indicator(s) off.
• Yellow TROUBLE indicator off.
ALARM CONDITION
• A red Alarm indicator will light.
• Alarm Notification appliances
are activated.
• Option module (remote station or supplementary alarm relay) is activated.
• Off-Normal Trouble Silence Switch: Indicated by an intermittent audible tone signal having a long on
time and short off time.
ALARM RESET
After locating and correcting the alarm condition, reset the control panel by pressing the RESET switch.
Return all switches to their normal positions.
Figure 2.1: Controls And Indicators
TROUBLE CONDITIONS
Activation of a trouble signal under normal operation indicates a condition that requires immediate correction. Contact your local service representative. The audible signal may be silenced by depressing the
TROUBLE SILENCE switch. The trouble LED will continue to flash.
MP-12/24 Fire Alarm Control Panel Document 15440:G 6/6/96
5

Section Three:
Technical Specifications
All specifications are typical characteristics measured under nominal conditions at 25° C, unless otherwise specified.
System Power Requirements
MP-12/24 Operating voltage: 120 VAC, 60 Hz (standard).
MP-12/24 Current Draw: 0.5 A (maximum).
MP-12/24E Operating voltage: 220/240 VAC, 50/60 Hz
MP-12/24E Current Draw: 0.250 A (maximum).
Standby battery:
Voltage: (MP-12) 12 VDC; (MP-24) 24 VDC
Capacity: 2.5 to 7.0 AH (dependent on external loading).
Detection Loop
Operation: Style B (Class B).
Voltage: (MP-12) 8.6 to 12.2 VDC, ripple 0.65 Vp-p. (MP-24) 18 to 26.2 VDC, ripple 2.0 Vp-p.
Current required to ensure alarm: 20 mA (minimum)
Short circuit current: 40 mA - 10 mA
Supervision current: 5 mA
ELR: (MP-12) 2.2 K, 0.5 W; (MP-24) 4.7K, 0.5 W
Max resistance per side: 100 ohms.
Max total zone resistance: 200 ohms.
Two-wire Smoke Detectors
Head voltage, standby: MP-12, 11 VDC; MP-24, 23 VDC.
Total standby head current per zone: 2 mA peak
Minimum head current to ensure alarm: 20 mA
Maximum alarm current supplied to initiating devices, per zone: 40 mA - 10 mA.
Main Notification Appliance (bell) Circuits
Activation: By any zone alarm
Disconnect: By DISABLE switch
Operation: Style Y (Class B).
Notification Appliances: Use polarized, UL Listed, Notification Appliances with a minimum rated voltage
range of 9-15 VDC on MP-12 and 18-30 VDC on MP-24. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible devices.
Nominal output voltage: (MP-12) 12 VDC; (MP-24) 24 VDC.
Output is
Output current: Total current to all external Notification Appliances cannot exceed: (MP-12) 1.0 A; (MP-24)
0.75 A.
Special Purpose Power
(full wave rectified DC, unregulated and unfiltered).
External Device Power
Regulated DC output: Resettable power primarily for four-wire smoke detectors and/or other low power
electronic devices. Maximum current available: 100 mA
Note: Size standby battery to include external loading.
Nominal voltage: (MP-12) 12 VDC; (MP-24) 24 VDC.
Battery Charger
Float type, turned off during alarm.
Float voltage setting: (MP-12) 13.8 VDC; (MP-24) 27.6 VDC. Automatic current limiting.
Note: Since battery charger is pulsed on and off, the charger output cannot be read with a voltmeter when
battery is not connected. A typical voltmeter would read approximately 8.5 V on the MP-12 and 16.5 V on the
MP-24.
6
MP12/24 Fire Alarm Control Panel Document 15440:G 6/6/96