FAAC 6550-080 User Manual

Page 1
Installation/Owner’s Manual
Series 6550
Heavy-Duty Vehicular Swing Gate Operator
Series 6550
Series 6550
Use this manual for circuit board 4405-010 Revision E or higher.
6550-065-A-4-12
Date Installed:
Phone Number:
Leave Manual with Owner
UL 325 Compliant
Circuit Board Serial Number and Revision Letter:
Copyright 2012 DoorKing, Inc. All rights reserved.
TM
Copyright 2009 DoorKing, Inc. All rights reserved.
Page 2
Page 3
SPECIFICATIONS
Use this manual for the Model 6550 operators with circuit board 4405-010 Rev E or higher ONLY.
Class of Operation Model 6550 - UL325 Class I, II, III, IV Type of Gate Vehicular Swing Gates Only Entrapment Protection Primary - Inherent entrapment sensing system (Type A) Secondary - Provision for connection of a non-contact sensor (Type B1)
Model #
6550-080 6550-081 6550-082 6550-083 6550-084
Type
Operator
Primary
Secondary
Primary Primary Primary
Horsepower - Volts
1 HP - 115 VAC 1 HP - 115 VAC 1 HP - 208 VAC 1 HP - 230 VAC 1 HP - 460 VAC
Phase Amp
ø
1
ø
1
ø
1
ø
1
ø
1
9.7
9.7
4.9
4.9
2.5
Max Gate
Weight
2000 Lbs. 2000 Lbs. 2000 Lbs. 2000 Lbs. 2000 Lbs.
Max Gate
Length
25 Ft. 25 Ft. 25 Ft. 25 Ft. 25 Ft.
Cycles Per
Hour
60 60 60 60 60
Speed
90°
12-14 Sec 12-14 Sec 12-14 Sec 12-14 Sec 12-14 Sec
38.5”
38”
35.25”
20.5” 29.5”
DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to this manual. This manual is copyrighted, all rights reserved. No portion of this manual may be copied, reproduced, translated, or reduced to any electronic medium without prior written consent from DoorKing, Inc.
6550-065-A-4-12
1
Page 4
TABLE OF CONTENTS
SPECIFICATIONS 1
ASTM F2200 Standard for Gate Construction
Important Safety Instructions
Instructions regarding intended installation:
Important Notices
UL 325 Entrapment Protection
Glossary
Swing Gate Requirements
Swing Gate Protection
SECTION 1 - INSTALLATION 10
1.1 Underground Conduit Requirements
1.2 Concrete Pad
1.3 Type of Installations
1.4 Securing Operator to Pad
10
10
11-12
12
4
4
4
5
6
7
8
9
1.5 Attach Gate Bracket
1.6 Determining Arm Lengths
1.7 Installation of Warning Signs
13
14
14
SECTION 2 - AC POWER TO OPERATOR(S) 14
2.1 High Voltage Wire Run
2.2 High Voltage Terminal Connection
2.3 Bi-Parting Gates Wiring - Dual Gate Operators
15
15
16
SECTION 3 - ADJUSTMENTS 18
3.1 4405 Circuit Board Descriptions and Adjustments
3.2 DIP-Switch Settings for 4405 Circuit Board
3.3 Limit Sensors
3.4 Inherent Reverse Sensors Adjustment
3.5 Secondary Current Sensor Adjustment
18
18-19
20
21
22
2
6550-065-A-4-12
Page 5
TABLE OF CONTENTS
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION 23
4.1 UL 325 Terminal Description
4.2 Entrapment and Safety Protection Device Locations
4.3 Loop Detector Wiring
23
24
25
SECTION 5 - MAIN TERMINAL WIRING 26
5.1 Terminal Description
5.2 Control Wiring
26
27
SECTION 6 - OPERATING INSTRUCTIONS 28
6.1 AC Power Switch and Reset Button
6.2 Shutdown Conditions
28
29-30
Soft Shutdown Hard Shutdown
6.3 Manual Gate Operation
Emergency Vehicle Access Conditions Manual Release
30-31
SECTION 7 - MAINTENANCE AND TROUBLESHOOTING 32
7.1 Maintenance
7.2 Troubleshooting
7.3 Built-in Diagnostics
7.4 Accessory Items
7.5 Gearbox Shaft Extension Replacement
Model 6550’s Wiring Diagrams
32
33-34
35
35
36
37-39
6550-065-A-4-12
3
Page 6
ASTM F2200 Standard for Gate Construction
Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard Specification for Automated Vehicular Gate Construction. For a copy of this standard, contact ASTM directly at 610-832-9585; service@astm.org; or
www.astm.org.
Important Safety Instructions
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. SAVE THESE INSTRUCTIONS!
Instructions regarding intended installation:
Install the gate operator only if:
1. The operator is appropriate for the construction of the gate and the usage class of the gate.
2. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet (1.83 m) above the ground to prevent a 2 ¼ inch (57.2 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
3. All exposed pinch points are eliminated or guarded.
4. Guarding is supplied for exposed rollers.
The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate
access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures
when opening and closing to reduce the risk of entrapment. Swinging gates should not open into public access areas.
The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not
over-tighten the operator clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.
For gate operators utilizing Type D protection:
1. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
2. A warning placard shall be placed adjacent to the controls.
3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.
4. No other activation device shall be connected.
Controls intended for user activation must be located at least ten feet (10’) away from any moving part of the gate and
where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls should have a security feature to prevent unauthorized use.
The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not
cause the operator to start.
A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
For gate operators utilizing a non-contact sensor:
1. See the instructions on the placement of non-contact sensors for each type of application.
2. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is still moving in the opening direction.
3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the perimeter reachable by a moving gate or barrier.
4
6550-065-A-4-12
Page 7
For gate operators utilizing contact sensors:
1. One or more contact sensors shall be located where the risk of entrapment or obstruction exist, such as at the leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate.
2. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
3. One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
4. A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is not subjected to mechanical damage.
5. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstructions. A wireless contact sensor shall function under the intended end-use conditions.
6. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).
Important Notices
Vehicular gate operator products provide convenience and security. However, gate operators must use high levels of force to move gates and most people underestimate the power of these systems and do not realize the potential hazards associ­ated with an incorrectly designed or installed system. These hazards may include:
Pinch points
Entrapment areas
Reach through hazards
Absence of entrapment protection devices
Improperly located access controls
Absence of vehicle protection devices
Absence of controlled pedestrian access In addition to these potential hazards, automated vehicular gate systems must be installed in accordance with the UL 325
Safety Standard and the ASTM F2200 Construction Standard. Most lay persons are unaware of, or are not familiar with, these standards. If an automated vehicular gate system is not properly designed, installed, used and maintained, serious injuries or death can result. Be sure that the installer has instructed you on the proper operation of the gate and gate operator system. Be sure that the installer has trained you about the basic functions of the required reversing systems associated with your gate operating system and how to test them. These include reversing loops, inherent reversing system, electric edges, photoelectric cells, or other external devices.
This Owner’s Manual is your property. Keep it in a safe place for future reference.
Be sure that all access control devices are installed a minimum distance of 10 feet away from the gate and gate
operator, or in such a way that a person cannot touch the gate or gate operator while using the device. If access control devices are installed in violation of these restrictions, immediately remove the gate operator from service and contact your installing dealer.
Loops and loop detectors, photo-cells or other equivalent devices must be installed to prevent the gate from
closing on vehicular traffic.
The speed limit for vehicular traffic through the gate area is 5 MPH. Install speed bumps and signs to keep
vehicular traffic from speeding through the gate area. Failure to adhere to posted speed limits can result in damage to the gate, gate operator, and to the vehicle.
Be sure that all persons who will use the gate system are familiar with the proper use of the gate and gate
operator and are familiar with the possible hazards associated with the gate system.
Be sure that warning signs are permanently installed on both sides of the gate in an area where they are fully
visible to traffic.
It is your responsibility to periodically check all entrapment protection devices. If any of these devices are
observed to function improperly, remove the operator from service immediately and contact your installing or servicing dealer.
Follow the recommended maintenance schedule.
Do not allow children to play in the area of the operator or to play with any gate-operating device.
To remove the gate operator from service, operate the gate to the full open position and then shut off power to
the operator at the service panel.
6550-065-A-4-12
5
Page 8
UL 325 Entrapment Protection
Class I
A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or a garage or parking area associated therewith.
Class II
A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units) hotel, garages, retail store or other building servicing the general public.
Class III Class IV
A vehicular gate operator (or system) intended for use in a industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
STATE PRISON
This table illustrates the entrapment protection requirements for each of the four UL 325 classes.
UL 325
Classifications
Class I and II
Class III
Class IV
A - Inherent entrapment protection system. B1 - Provision for connection of, or supplied with, a non-contact sensor (photoelectric sensor or the equivalent).
When used as the PRIMARY device, must be monitored. B2 - Provision for connection of, or supplied with, a contact sensor (edge device or the equivalent).
When used as the PRIMARY device, must be monitored.
C - Inherent adjustable clutch or pressure relief device. D - Provision for connection of, or supplied with, an actuating device requiring continuous pressure to maintain
opening or closing motion of the gate.
E - An inherent audio alarm.
6
Horizontal Slide, Vertical Lift, Vertical Pivot Swing and Vertical Barrier (arm)
Primary Protection
A B1, B2 or D A, B1, B2, C or D A or C
A, B1 or B2 A, B1, B2, D or E A, B1, B2, C or D A, B1, B2 or C
A, B1, B2 or D A, B1, B2, D or E A, B1, B2, C, D or E A, B1, B2, C or D
Secondary Protection Primary Protection Secondary Protection
6550-065-A-4-12
Page 9
Glossary
GATE - A moving barrier such as a swinging, sliding, raising, lowering, or the like, barrier, that is a stand-alone passage
barrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles and completes the perimeter of a defined area.
RESIDENTIAL VEHICULAR GATE OPERATOR – CLASS I - A vehicular gate operator (or system) intended for use in a home
of one-to four single family dwelling, or garage or parking area associated therewith.
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR - CLASS II - A vehicular gate operator (or system)
intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotels, garages, retail store, or other building servicing the general public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR - CLASS III - A vehicular gate operator (or system)
intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR - CLASS IV - A vehicular gate operator (or system) intended for use in
a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
VEHICULAR BARRIER (ARM) OPERATOR (OR SYSTEM) - An operator (or system) that controls a cantilever type device (or
system), consisting of a mechanical arm or barrier that moves in a vertical arc, intended for vehicular traffic flow at entrances or exits to areas such as parking garages, lots or toll areas.
VEHICULAR HORIZONTAL SLIDE-GATE OPERATOR (OR SYSTEM) - A vehicular gate operator (or system) that controls a
gate which slides in a horizontal direction that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
VEHICULAR SWING-GATE OPERATOR (OR SYSTEM) - A vehicular gate operator (or system) that controls a gate which
moves in an arc in a horizontal plane that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
SYSTEM - In the context of these requirements, a system refers to a group of interacting devices intended to perform a
common function.
WIRED CONTROL - A control implemented in a form of fixed physical interconnections between the control, the associated
devices, and an operator to perform predetermined functions in response to input signals.
WIRELESS CONTROL - A control implemented in means other than fixed physical interconnections (such as radio waves or
infrared beams) between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
INHERENT ENTRAPMENT PROTECTION SYSTEM - A system, examples being a motor current or speed sensing system,
which provides protection against entrapment upon sensing an object and is incorporated as a permanent and integral part of the operator.
EXTERNAL ENTRAPMENT PROTECTION DEVICE - A device, examples being an edge sensor, a photoelectric sensor, or
similar entrapment protection device, which provides protection against entrapment when activated and is not incorporated as a permanent part of an operator.
ENTRAPMENT - The condition when an object is caught or held in a position that increases the risk of injury.
6550-065-A-4-12
7
Page 10
Swing Gate Requirements
The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate
access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate. (ref. UL325 56.8.4.b)
Closed Gates
Opened Gate
Closed Gate
If distance is greater than 4 inches,
A
entrapment protection for this area is required. ASTM F2200 7.1.1.1
If distance is less than 16 inches,
B
entrapment protection in this area is required. ASTM F2200 7.1.1.2
Not Allowed OK
A
B
Opened Gate
Opened Gate
Closed Gate
With the hinge mounted on the corner of the pilaster, the entrapment area is
eliminated and protection is NOT required for this area.
A
Opened Gate
Gates shall have smooth bottom edges, with vertical bottom edged protrusions not exceeding 0.50 inches. ASTM F2200 4.3
8
6550-065-A-4-12
Page 11
Swing Gate Protection
Reverse Loop
Minimizes the potential of the gate closing when a vehicle is present. Number and placement of loops is dependent on the application.
D
Shadow Loop
Provides a hold open command to the operator(s) only if the gate(s) are at the full open position.
C
Non-contact Sensor
Minimizes the potential of the gate closing on vehicular or other traffic that loops cannot sense. See pages 23-24 for typical layout locations.
C
D
D
Warning Signs
Permanently mounted and easily visible from either side of the gate.
Reverse Loop
Minimizes the potential of the gate closing when a vehicle is present. Number and placement of loops is dependent on the application.
Automatic Exit Loop
(Optional) will provide an open command to the gate operator(s) when a vehicle is exiting the property.
See page 25 for loop information.
Moving Gate Can Cause Serious Injury or Death
KEEP CLEAR! Gate may move at any time without prior warning. Do not let children operate the gate or play in the gate area. This entrance is for vehicles only. Pedestrians must use separate entrance.
Separate Pedestrian
Walkway
Located so pedestrians cannot come in contact with the vehicular gate.
6550-065-A-4-12
9
Page 12
SECTION 1 - INSTALLATION
Prior to beginning the installation of the swing gate operator, we suggest that you become familiar with the instructions, illustrations, and wiring guide-lines in this manual. This will help insure that your installation is performed in an efficient and professional manner compliant with UL 325 safety and ASTM F2200 construction standards. The proper installation of the vehicular swing gate operator is an extremely important and integral part of the
overall access control system.
Check all local building ordinances and building codes prior to installing
this operator. Be sure your installation is in compliance with local codes.
1.1 Underground Conduit Requirements
Primary
Operator
Position
Secondary
Operator
Position
DoorKing’s Primary/Secondary Interconnection Cable (Dual Operator Application Only)
(Secondary Power and Communication wires)
Control and/or P.A.M.S. Wires (Low Voltage wire insulation)
Sweeps
Loop Lead-In Wires (Low Voltage wire insulation)
AC Input Power (High Voltage wire insulation)
Concrete Pad
The conduit requirements are for a typical slide gate operator installation (the secondary operator is shown for those
applications where a secondary operator may be used). The conduit requirements for your application may vary from
this depending on your specific needs.
Use only sweeps for conduit bends. Do not use 90° elbows as this will make wire pulls very difficult
and can cause damage to wire insulation.
DoorKing recommends using 3/4-inch conduit.
Be sure that all conduits are installed in accordance with local codes.
Sweep
YES
Elbow
Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
1.2 Concrete Pad
Conduit Location
6 1/2”
Center Line
12”
CAUTION
NEVER REMOVE HUB after manual release.
NO
3”
Conduit Area
36” Concrete Pad Length
Conduit Area
6 1/2”
24” Concrete Pad Width
10
208/230/460 Step-Down Transformer Plate
13” x 7 1/2”
13” x 6 1/2”
6 1/2”
21 1/4”
to
Center
of
Conduit
Area
38”
29”
to
Center
of
Conduit
Area
4” minimum above ground
Underground depth of the concrete pad is determined by soil conditions and local building codes. Reinforced concrete recommended.
Concrete pad MUST be level.
Note: Bevel the edges of concrete pad to eliminate water puddling under the operator.
24”
Approximate Conduit Position
6550-065-A-4-12
Page 13
1.3 Type of Installations
Standard Installation
1
Recommended for gates up to 25 feet opening 90°.
90°
2”
Alternate Installation
2
Recommended for gates up to 18 feet opening 90°.
17”
36”
24”
Concrete Pad
Concrete Pad Location
38.5”
46” 14”
30”
Operator Installation
12”
35”
44”
90°
2”
6550-065-A-4-12
17”
36”
24”
Concrete Pad
Concrete Pad Location
42” 14”
35”
30”
12”
35”
38”
Operator Installation
Space Gained from Alternate Installation
11
Page 14
Compact Installation
3
Recommended for gates up to 14 feet opening 90°.
90°
12”
2”
24”
Concrete Pad
Concrete Pad Location
36”
34” 14”
29.5”
26”
12”
30”
26”
Operator Installation
1.4 Securing Operator to Pad
Permanently attach the operator to the concrete pad using six (6) 3/8” x 3” sleeve anchors (not supplied).
208/230/460 Step-Down Transformer Plate
Sleeve Anchor (Not supplied)
3/8
12
6550-065-A-4-12
Page 15
1.5 Attach Gate Bracket
Release hub with release tool. DO NOT REMOVE HUB!
A
Bolt crank arm to operator.
B
Slide elbow assembly on crank arm.
C
Bolt control arm to gate bracket.
D
Slide control arm into elbow assembly.
E
KEEP ARM ASSEMBLY LEVEL.
Bolt gate bracket to gate.
F
D
Gate Bracket
Control Arm
F
Gate Bracket
Arm assembly and gate bracket MUST be level for gate to function correctly.
E
D
Elbow
Assembly
38”
CAUTION
DO NOT REMOVE HUB!
Control Arm
B
C
Crank Arm
A
6550-065-A-4-12
13
Page 16
1.6 Determining Arm Lengths
Slide elbow assembly back and fourth, manually opening and closing gate until satisfied with the gate’s 90° open and fully closed positions.
Mark and cut off excess arms. Secure arms to elbow assembly with 6 allen screws. Tighten hub and replace release tool. Install safety covers.
excess
excess
1.7 Installation of Warning Signs
This DoorKing Swing Gate Operator is shipped with two warning signs. The purpose of the warning sign is to alert uninformed persons, and to remind persons familiar with the gate system, that a possible hazard exists so that appropriate action can be taken to avoid the hazard or to reduce exposure to the hazard. See page 9 for suggested mounting positions of signs.
Permanently install the supplied warning signs in locations so
that the signs are visible by persons on both sides of the gate.
Use appropriate hardware such as wood or sheet metal screws
(not supplied) to install the warning signs.
SECTION 2 - WIRING
Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a licensed electrical contractor perform this work.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
14
6550-065-A-4-12
Page 17
2.1 High Voltage Wire Runs
The distance shown in the chart is measured in Feet from the operator to the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. The wire run calculations are based on a power source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
This table illustrates the high voltage wire size and distance requirements for a single operator. Model
Type
6550 1 HP 6550 1 HP 6550 1 HP
Voltage
Required
115
208/230
460
Amps
Required
9.7
4.9
2.5
12 AWG 10 AWG 8 AWG 6 AWG
100 395
1550
Wire Size / Distance in Feet
162 630
2480
270 1055 4140
405 1580 6210
Reduce the wire distance in half for a primary/secondary dual gate operator application
Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
“Optional” 3.3 Amp Heater Installation Note: When installing the heater(s), refer to the “high voltage AC power wire size and distance requirements” table on the instruction sheet with the heater kit (P/N 6550-480) for AC power wire run requirements.
2.2 High Voltage Terminal Connections
Route incoming high voltage power through conduit and
into the operator as shown.
Be sure wiring is installed in accordance with local codes.
Be sure to color code all wiring.
It is recommended that a surge suppressor be installed on
the high voltage power lines to help protect the operator and circuit board from surges and power fluctuations.
Secondary operator in a dual operator application gets AC
power through the 8-wire interconnection cable that connects the 2 operators together. See next page.
High Voltage Conduit
6550-065-A-4-12
115 VAC
208 / 230 / 460 VAC
DANGER
HIGH VOLTAGE!
Neutral
E
AT
y
R
E
onl
P
e
O
s u
O
n
T
a
i
H
c
S
U
hni
P
ec t
115 VAC
HotNeu
208/230/460 VAC
Input
208/230/460 VAC
115 VAC Neu
115 VAC Neu
115 VAC Hot
Output
Chassis Ground
High Voltage AC Input Wire
Use only two legs of the
High Voltage
AC Input Wire
High Voltage
AC Input Wire
incoming 3-phase power.
DO NOT cycle the operator without the OPEN and CLOSE limit sensors in their specific open
and close positions.
an open cycle has started. This could cause damage to the gate and/or operator if the gate opens too far!
The limit sensors or the AC power switch are the ONLY ways to stop the operator once
Chassis
Ground
15
Page 18
2.3 Bi-Parting Gates Wiring - Dual Gate Operators
Connect the Primary/Secondary operators together with DoorKing’s interconnection cable as shown (Different lengths sold separately). High voltage power and low voltage communications are supplied to the secondary operator by DoorKing’s UL approved cable that is run in a single conduit. Two conduits (High voltage and low voltage) will need to be provided to the secondary operator when NOT using DoorKing’s UL listed, wet environment interconnection cable.
1
1
2
2
3
3
4
4
SELF TEST
NC NO
4405
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
Primary Operator 8-Pin Secondary
Chassis Ground
Interface Terminal
Primary Operator Control Board (4405)
All loop detector, safety and access control devices
are wired to the primary operator.
ON
1 2 3 4 5 6 7 8
SW 1,
switches 1
and 2 will
be opposite
each other.
Switch 6
MUST be
ON, see
page 18.
Interconnection Cable Wiring
Secondary OperatorPrimary Operator
(Red) Motor 1 High
(Blue) Motor 2 High (White) Neutral 3 High (Purple) 24VAC 4 Low
(Yellow) Limit 5 Low (Brown) Spare 6 Low (Orange) Limit 7 Low
(Gray) COM 8 Low
1
Motor2Motor3Neutral424VAC5Limit6Spare7Limit8COM
Motor 1 High (Red) Motor 2 High (Blue) Neutral 3 High (White) 24VAC 4 Low (Purple) Limit 5 Low (Yellow) Spare 6 Low (Brown) Limit 7 Low (Orange) COM 8 Low (Gray)
Secondary Operator Terminal
Secondary operator contains
NO control board.
1
Motor2Motor3Neutral424VAC5Limit6Spare7Limit8COM
Operator Chassis Ground
Conduit
E T A
y l
R
n
o
PE
e
O O T
an us i
H
c
S U
hni c
P
e t
conduit to primary
operator only.
Conduit
DoorKing’s UL Listed (Wet Environment)
Primary/Secondary Interconnection Cable
30 feet: P/N 2600-755, 40 feet: P/N 2600-756, 50 feet: P/N 2600-757
Primary Operator
AC power
power the secondary operator’s heater. Refer to the instruction
sheet with the heater kit (P/N 6550-480) for more information.
AC Power
Secondary
Operator
Primary/secondary
interconnection cable
in underground conduit.
power wires through the interconnection cable conduit to
Optional 3.3 Amp Heater Installation Note:
If the optional heaters are to be installed on the
operators, run two (AWG 16-600 volt insulation)
16
6550-065-A-4-12
Page 19
SECTION 3 - ADJUSTMENTS
The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) is complete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then
turned back on for the new setting to take effect.
3.1 4405 Circuit Board Descriptions and Adjustments
ON
1
DIP-Switches
Set the DIP-switches on the circuit board to the desired setting. See switch-settings on next 2 pages.
9410
Single
Channel
EXIT Loop Terminal
See page 25.
9409
SHADOW Output Terminal
Plug-In Loop Detectors (Sold separately)
Dual
Channel
Loop Terminals
REVERSE/SHADOW
Inherent
Reverse Sensors
Adjust reversing sensitivity for the open AND close direction of the PRIMARY (single) and SECONDARY (dual) operators, See page 21.
Secondary Primary
2 3 4 5 6 7 8 1
SW 1
2 3 4
SW 2
ON
Limit
Sensors
Plug P2
P2 P8
EXIT LOOP
Limit LEDs
See page 20
EXIT Loop PortREVERSE Loop Port
Loop LEDs
REVERSE LOOP
Terminal Plug
Power LED
Secondary
Interface
Auto-Close Timer
Auto-close timer (when turned on) SW 1, switch 4.
Time Delay:
Adjust from 1 second (full counter-clockwise) to approximately 23 seconds (full clockwise).
4-Pin Terminal
Not used for 6550.
ON SW 1
1 2 3 4 1
ON SW 2
2 3 45 6 7 8
TIME DELAY
REV SENSE
REV SENSE
PRIMARY
SECONDARY
4405-010
Primary Current Sensor
Uses a sensing coil with a given number of wire turns through it to monitor the current flow of the primary operator motor.
SELF TEST
Factory Set:
1/2 HP Motor - 2 Turns
1 HP Motor - 1 Turn
ON
1 2 3 4 5 6 7 8
SW 1
123
1
2
3
4
5
6
7
8
Input LEDs
9
10
NC
NO
11
12
13
14
15
16
17
18
19
20
How LEDs Function
Illuminated LEDs Indicates that low voltage power is being applied to the circuit board.
Input LEDs should be OFF and will
only illuminate when the input is activated.
Limit LEDs will only illuminate when
the respective limit sensor has been activated.
Loop LEDs will only illuminate when a
reverse, shadow or exit loop is activated (Vehicle passing over a loop).
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
6-Pin UL 325 Removable Terminal
See page 23.
Dry Relay Contact
N.O.
Terminals 10-11 can be set for Normally Open (NO) or Normally Closed (NC) operation by placing the relay shorting bar on the N.O. or N.C. pins respectively. (Standard shadow loop function, NO)
N.C.
Self-Test
Self-test mode is for bench checks ONLY!
Self-Test
Secondary Current Sensor
Uses a sensing coil with a given number of wire turns through it to monitor the current flow of the secondary gate operator motor.
The operator will continually cycle the gate.
Mode
The jumper must be set at normal mode for normal operator function.
Normal
Mode
Factory Set: 1/2 HP Motor - 2 Turns 1 HP Motor - 1 Turn
See page 22.
6550-065-A-4-12
17
Page 20
3.2 DIP-Switch Settings for 4405 Circuit Board
The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
SW 1 (Top 8 Switches)
Switch Function Setting Description
1
2
3
4
5
6
7 and 8
Primary
Operator
Opening
Direction
Secondary
Operator Opening
Direction
Exit Loop Port
Output
Full Open Input
Auto-Close
Timer
Reverses Gate
Not Used
Single Operator
Dual Operators
Circuit
Board
Relay
7-OFF
7-OFF
7-ON 7-ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
8-OFF
8-ON
8-OFF
8-ON
Opens Counter-Clockwise using OFF setting.
Opens Clockwise using ON setting.
Opens Counter-Clockwise using OFF setting.
Opens Clockwise using ON setting.
The output wired to terminal #4 becomes the output from the exit loop detector plugged into the EXIT Loop port.
Normal Setting. Terminal #4 is a normal full open input. Auto-close timer is OFF. Manual input required to close gate.
Normal Setting. Auto-close timer is ON. Adjustable from 1-23 seconds. Normal Setting. Input to terminal #6 and reverse loop will stop and reverse gate to
the full open position during the close cycle ONLY. Do Not use this setting for the 6550.
Normal Setting. Switch must be OFF for single operator. Switch must be ON when primary/secondary (dual) gates are used.
Normal Setting. Relay activates when gate is at open limit. (Shadow loop setting when used) Relay activates when gate is not closed. Relay activates when gate is opening and open. Relay activates during opening and closing cycle.
See next page for ALL 12 switch definitions and typical settings.
SW 2 (Bottom 4 Switches)
Switch Function Setting Description
Primary and secondary operators start at the same time (Normal setting for single
OFF
1
2
3 4
18
Gate Overlap
Magnetic lock
gate operator). The secondary operator will start 1.5 sec. before primary operator during open
ON
cycle and the primary operator will start 1.5 sec. before the secondary operator during the close cycle (Normal setting for bi-parting gate operators).
Normal Setting. Magnetic lock is not used.
OFF
Magnetic lock is used and connected to terminals 9 and 12. See page 27 for wiring.
ON
Normal Setting. Switch 3 MUST be turned OFF for Model 6550 operator.
OFF
Normal Setting. Switch 4 MUST be turned OFF for Model 6550 operator.
OFF
6550-065-A-4-12
Page 21
3.2 Continued
Switch Definitions
ON
1 2 3 4 5 6 7 8
SW 1 (Top 8 Switches)
Typical Settings
Switch 1 Must OPEN the primary operator’s gate upon initial AC power up and open command. If the FIRST open command
begins to close the gate, turn AC power off and reverse this switch.
Switch 2 Must OPEN the secondary operator’s gate upon initial AC power up and open command. If the FIRST open command
begins to close the gate, turn AC power off and reverse this switch. This switch will be set the opposite of switch 1 (e.g. If switch 1 is OFF, then switch 2 will be ON).
Switch 3 Determines that a device wired to terminal #4 is a normal full open command OR terminal #4 becomes the output
from the exit loop detector that is plugged into the EXIT Loop port in the circuit board (Used for specialized functions).
Switch 4 Turns the auto-close timer on or off. Maximum time that the close timer can be set for is approximately 23 seconds. Switch 5 OFF setting is Standard Reverse for a CLOSING gate. An input to terminal #6 (e.g.: photo beam gets obstructed)
AND/OR reverse loops will stop and reverse the gate back to the full open position. If the auto-close timer is ON, when gate reaches the open position, timer will not close the gate. Another input command is needed to reset and close the gate. DO Not use the ON setting for the 6550 operator.
Switch 6 Sets up the circuit board for a single gate operator or primary / secondary (dual) gate operators. Switches 7-8 These work in conjunction with each other and determine when the relay on the board will be activated. This relay
can be used as a switch for various functions such as illuminating a warning light when the gate is moving, or turning on a green light when the gate is full open. This relay is not available for these uses if it is being used for the shadow loop function.
ON
1 2 3 4
Switch 1 When the gate overlap is OFF, the gate operator(s) will start the open and close cycles at the same time. This is the
normal setting for a single gate operator. Turning the gate overlap ON when using dual gate operators will cause the secondary operator to start the open cycle 1.5 seconds before the primary operator. The primary operator will start the close cycle 1.5 seconds before the secondary opera­tor.
Switch 2 If a magnetic lock is not used with the gate operator, leave this switch in the OFF position. Turn this switch ON if a
magnetic lock is used and connected to terminals 9 and 12. This applies magnetic lock power and logic to these terminals (NC).
Switch 3 MUST be turned OFF for the Model 6550. Switch 4 MUST be turned OFF for the Model 6550.
6550-065-A-4-12
SW 2 (Bottom 4 Switches)
Typical Settings
19
Page 22
3.3 Limit Sensors
The hub must not slip during operation. Tighten bolt to stop any slipping.
CAUTION
DO NOT REMOVE HUB!
Important Limit Sensor Adjustment Note:
It is very important NOT to cycle the gate operator before the limit sensors are in the correct position or it could cause damage to the gate and operator.
HUB
Magnetic Sensor Activator
Magnetic Close
Loosen set screw to adjust the limit
CLOSE
Limit Sensor
sensor.
OPEN
Magnetic Open Limit Sensor
Note: If P2 plug is not connected
P2
to the circuit board and AC power is turned on, alarm will sound and operator will NOT function.
P2 P8
Limit
Sensors
EXIT LOOP
Primary
Sensors
Close
Limit
Plug
Open
Close
Secondary Limit Sensors
Not Used
Open
PRIMARY Operator DIP Switch OPENING Direction
1
2 3 4 5 6 7 8
ON
Switch 1 “OFF”
SW 1
Operator Opens Counter-clockwise
1
2 3 4 5 6 7 8
ON
Switch 1 “ON”
SW 1
Operator Opens Clockwise
SECONDARY Operator DIP Switch OPENING Direction
ON
1
2 3 4 5 6 7 8
Switch 2 “OFF”
ON
1
2 3 4 5 6 7 8
Switch 2 “ON”
ONLY turn ON AC power. Manually release the gate
operator hub with the release tool (See page 31). Physically move the gate to the desired open position. Loosen the set screw on the OPEN limit sensor and slowly slide it under the magnetic sensor activator until the OPEN limit Sensor LED lights up on the circuit board. Tighten the set screw and repeat this process for the close gate position. Secure the hub with the release tool and cycle the
Release Tool
operator a few times and readjust if necessary.
CLOSE SENSOR
Limit Sensor LEDs
P2 P8
EXIT LOOP
REVERSE LOOP
OPEN SENSOR
TIME DELAY
REV SENSE SECONDARY
ON SW 1
1 2 3 4 1
ON SW 2
2 3 45 6 7 8
REV SENSE PRIMARY
4405-010
Magnetic sensor activator must be directly above the limit sensor to activate it.
1
1
2
2
3
3
4
SELF TEST
4
5
5
6
6
7
7
8
8
9
9
10
10
NC
NO
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
SW 1
Operator Opens Counter-clockwise
20
SW 1
Operator Opens Clockwise
Dual Gate Operators Note: SW 1, switch 2 will be set the opposite of SW 1, switch 1 (e.g. If switch 1 is OFF, then switch 2 will be ON).
6550-065-A-4-12
Page 23
3.4 Inherent Reverse Sensors Adjustment
This vehicular gate operator is equipped with an inherent adjustable reversing sensor (Type A) used as the primary entrapment protection system according to UL 325 standards. The gate will reverse direction after “physically” encountering an obstruction in either the opening or closing gate cycle. If the Auto-Close Timer (DIP-switch SW 1, switch 4) is ON and the gate physically encounters an obstruction during the CLOSING cycle, it will reverse to the open position and HOLD the gate at this position (Soft shutdown condition). Another input command is needed before the gate will reset and close again. For the reverse sensors to function correctly, THE HUB MUST NOT SLIP when the gate encounters an obstruction. The gate must be properly installed and work freely in both directions. A good set of roller bearing hinges is essential for proper swing gate operation. For the reverse system to function correctly, the gate must be properly installed and work freely in both directions and the limit sensors must be properly adjusted BEFORE adjusting the reverse sensors. The ideal adjustment will allow the operator to move the gate through its entire travel cycle without reversing, but will reverse upon contact with an obstruction with no more than 40 Lbs of force. This force can be measured with a gate scale, P/N 2600-225.
CAUTION: Keep pedestrians and vehicles clear of the gate while adjusting and testing sensors!
Note: “Push to Operate” button will use the Auto-Close timer if turned ON (SW 1, switch 4 ON).
Press the “Push to Operate” button to OPEN the gate.
1
PUSH TO OPERATE
technician use only
Note: The LED will turn on briefly when AC power is turned on.
While gate is opening, slowly rotate the primary reverse sensor clockwise until the LED
2
lights up and the gate reverses direction. Rotate the primary reverse sensor back counter-clockwise approximately 1/8 turn to decrease the sensitivity (LED will turn off).
Note: The LED will light up during the first seconds of gate travel. Wait until it turns off before adjusting the reverse sensor.
Press the “Push to Operate” button and CLOSE the gate.
3
Make sure the gate closes completely. If it reverses and opens (LED will turn on), rotate the primary reverse sensor counter-clockwise a little more to decrease the reverse sensitivity (LED will turn off). Cycle the gate a few times to be sure that it cycles completely in both directions, adjusting the primary sensor as necessary.
PUSH TO OPERATE
technician use only
Dual Operators:
Adjust reverse sensors for each operator when dual operators have been installed.
Note: If the minimum or maximum reverse sensor sensitivity adjustment is reached and the Secondary Operator will not reverse properly, the Secondary Operator Current Sensor’s wire turns will have to be altered. See 3.5 Secondary Current Sensor Adjustment on the next page.
Primary
Max
Safety Note: The LED will
remain ON after a cycling gate gets obstructed during normal operation to indicate that the reverse sensor has been tripped. Always check the gate area for possible obstructions before putting operator back in service.
Secondary Primary
Min
LED
Sensitivity
Test the operator reversing sensitivity:
Place an immobile object along the gate path, allowing the gate to strike it while in the open and close cycles. The gate must reverse direction after striking the object. If it does not, increase the reverse sensitivity and repeat this testing until the correct sensitivity has been achieved in BOTH directions. The operator will assume a soft shutdown (Hold the auto-close timer) after striking and reversing the gate which will require pressing the “Push to Operate” button to cycle the operator again.
6550-065-A-4-12
21
Page 24
3.5 Secondary Current Sensor Adjustment (Dual Gates ONLY)
The PRIMARY gate operator’s “secondary reversing sensor” uses a secondary current sensing device (Located only in the primary operator) to detect any obstructions “physically” encountered in the SECONDARY gate path when using dual gates.
The secondary current sensor uses a sensing coil with a given number of turns through it to monitor the current flow into the secondary operator. Each time the wire passes through the coil, it is considered a turn. The number of turns through the sensing coil is dependant on the operating voltage of the operator and the weight of the gate. In general, light weight gates may require additional turns of wire through the secondary current sensor, while heavier gates may require less turns. CAUTION – HIGH VOLTAGE: Be sure power is turned OFF before changing the number of wire turns to the secondary current sensor. When you are setting the secondary reverse sensor (section 3.4 on the previous page) and reach the MAXIMUM sensitivity position on the reverse sensor without activating the secondary operator reversing function, add an additional turn of wire through the secondary current sensor. If you set the secondary reverse sensor to the MINIMUM sensitivity position and the gate will not cycle completely, reduce the number of turns through the secondary current sensor.
Sample Turns
Primary Operator
Typical Number of Turns for
Secondary Current Sensor
Secondary Operator Model Turns
1
1 HP - Single Phase 1
1 Turn
Secondary Current Sensor located only in primary operator.
E T A
y
R
e onl s
OPE
u
O
T
an ci i
SH
U
chn
P
e
t
To AC power terminal. See wiring schematics in back of manual.
2
1
2 Turns
To AC power terminal. See wiring schematics in back of manual.
Secondary
Operator
Reverse
Shadow
Primary Operator
AC Power
22
Primary/secondary interconnection cable
in underground conduit.
Reverse
6550-065-A-4-12
Page 25
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION
Secondary Entrapment Protection Device:
In addition to the inherent reversing sensor system, the Model 6550 has a 6-pin UL 325 terminal for the connection of photo sensors-Type B1 secondary entrapment protection device required by UL 325 standards. Entrapment protection devices must be installed to reduce the risk of injury. Install these devices where the risk of entrapment or a hazard exists while the gate is moving. Specific installations will vary.
4.1 UL 325 Terminal Description
ON SW 1
REV SENSE SECONDARY
TIME DELAY
1 2 3 4 1
2 3 45 6 7 8
REV SENSE PRIMARY
4405-010
1
1
2
2
3
3
ON SW 2
SELF TEST
4
4
5
5
6
6
7
7
8
8
9
9
10
10
NC
NO
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
Note: The 6-pin terminal can be unplugged from circuit board for easy wire connections.
All inputs are normally open (NO).
6-Pin UL 325 Terminal
Secondary Entrapment Protection
Device Connection
OPEN Entrapment Sensor
1
CLOSE Entrapment Sensor
2
Not Used
3
Not Used
4
Low Voltage Common
5
Low Voltage Common
6
ATE
ly
R
n
E
o
P
O
se
u
O
n
T
a
H
ci
i
S
n
U
h c
P
e t
(3) Three 115 VAC Convenience Outlets
P2 P8
EXIT LOOP
REVERSE LOOP
Wall
OPEN Entrapment Sensor (Photo Sensor): Obstructed opening-direction
1
photo beam will STOP the gate during the opening-direction only. Gate will resume the open cycle when the obstructed photo beam has been cleared.
Entrapment Protection Device Note:
Specific gate installations may require more entrapment protection devices than are shown here. Install them where necessary to protect against ANY potential entrapment or hazard area.
Wall
CLOSE Entrapment Sensor (Photo Sensor): Obstructed closing-direction
2
photo beam will STOP the gate during the closing-direction only. Gate will resume the close cycle when the obstructed photo beam has been cleared. Note: The closing-direction photo sensor typically should REVERSE the gate when the photo beam gets obstructed. See the next page for “Reverse” closing-direction option.
Potential
Hazard Area
Opening Gate
Closing-Direction Photo Beam
Potential
Hazard Area
Potential
Entrapment
Potential
Pinch Point
Hazard Area
Opening-Direction
Photo Beam
Potential Pinch Point Hazard Area
Area
Low Voltage Common: Common terminals for all the secondary
5 & 6
entrapment protection device inputs.
6550-065-A-4-12
Closing Gate
Potential Entrapment Zone Hazard Area
23
Page 26
4.2 Entrapment and Safety Protection Device Locations
Typical UL Photo Sensor mounting height and distance away from gate.
Closing-Direction Photo Sensors
5”
or less
Gate Frame (Closed)
21”
Typical
Non-Secure Side
Outside Property
Secure Side
Inside Property
Photo Sensors Sample Setup
This diagram is for illustration purposes. The actual placement of the protection devices is dependent on the specific installation requirements.
Wall
6-Pin UL 325 Terminal Wiring
OPEN Entrapment Sensor
CLOSE Entrapment Sensor
Not Used
Not Used
Low Voltage Common Low Voltage Common
IF the closing-direction photo sensor is wired to the UL 325
terminal #2, a closing-direction photo beam that gets obstructed will STOP the gate then resume closing the gate when the obstructed photo beam has been cleared (Typically not used).
1 2
3 4
5 6
Normally Open
Common
“Reverse” Closing-Direction Option
IF the closing-direction photo sensor is wired to the #6 main terminal, a closing-direction photo beam that gets obstructed will REVERSE the gate back to the open position (Typical).
Opening-Direction Photo Sensors
UL sensor mounted just above top of operator
Gate Frame (Closed)
If this space is less than 16 inches, secondary entrapment protection is required in this area.
1
2
3
4
5
6
7
8
9
10
NC NO
11
12
13
14
15
16
17
4405-010
18
19
20
SW 1, switch 5 MUST be OFF.
Closing-Direction Photo Beam
Closed Gate
1 2 3 4 5 6 7 8
ON
SW 1
Wall
Common
Normally Open
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 54321
Opened Gate
Opening-Direction
Photo Beam
Photo Sensor Power Note: Photo sensors can be powered by the built-in convenience outlets located on the operator (See previous page).
24
6550-065-A-4-12
Page 27
4.3 Loop Detector Wiring
To help protect the operator from accidentally closing on vehicles in the gate’s path, DoorKing highly recommends that loops and loop detectors be installed. Loops are laid underneath, cut into asphalt or concrete driveways or buried beneath gravel and earth driveways. A loop detection system will sense a vehicle like a metal detector and send a signal to the gate operator preventing the gate from automatically opening or closing on a vehicle when it is in the gate’s path. DoorKing recommends that a licensed installer perform this work.
Reverse
Shadow
Loop detector wiring is shown for DoorKing
plug-in loop detectors. If other loop detectors are used, refer to the installation instructions supplied with those detectors for wiring instructions.
If other detectors are used, use a separate power
supply to power these detectors.
Loop layout shown is for a typical swing gate
application with two-way traffic, or one-way exit only traffic.
DoorKing offers a free “Loop and
Loop-Detectors Information Manual” PDF located at
DoorKing’s web site for more information. www.dkaccess.com
Automatic Exit Loop
Automatically opens the gate for exiting vehicles without having to use a transmitter or keypad. The exit loop can be placed a minimum of 4 feet away from the reverse loop or far enough away from the gate so the gate has started opening or even completely opened by the time you drive up to it (Free exit).
Automatic exit loop lead in wires are twisted approx. 6 twists per foot.
LOOP 1
Shadow Loop will ONLY HOLD the
main gates in the Full Open Position when a vehicle is on the shadow loop. However, it WILL NOT stop or reverse the main gates once they start to close.
Shadow loop lead in wires are twisted approx. 6 twists per foot.
LOOP 2
DoorKing Plug-In
Single Channel
Loop Detector
Reverse Loops are placed on
each side of the gate to prevent the gate from closing on a vehicle in the gate’s path. They will stop or reverse the cycling of the gate while a vehicle is in or near the gate’s pathway.
Reverse loop lead in wires are twisted approx. 6 twists per foot and are wired in series.
LOOP 1
Shadow Loop
Output
Com
N.O.
DoorKing Plug-In
Loop Detector
9410
Dual Channel
9409
4 Ft. min. to avoid gate
movement interference.
Reverse
4 Ft. min. to avoid reverse
loop interference.
Exit Loop Port
Shadow Loop Note: Circuit board relay MUST be used and set to N.O.
NO
NC
Reverse Loop Port
Automatic Exit
Jumper Note: SW 1, switch 5 OFF.
Relay Note:
SW 1, switches 7 and 8 must be OFF.
4405
Relay Relay
10
11
12
13
14
15
16
17
18
19
20
ON
1 2 3 4 5 6 7 8
1
2
SW 1
3
4
5
6
7
8
9
Jumper
6550-065-A-4-12
25
Page 28
SECTION 5 - MAIN TERMINAL WIRING
5.1 Terminal Description
4405 Main Terminal
Low Voltage Common
Full Open
24 VAC - 250 ma max.
Full Open
Full Open
Standard Reverse
Gate Tracker Data
Gate Tracker Busy
24 VDC Mag Lock Power
Dry Relay Contact
Dry Relay Contact
Low Voltage Common
Low Voltage Common
Entrapment Alarm
Alarm Reset
Secondary Current Sensor
Motor
Motor
Circuit Board Power
Circuit Board Power
DANGER
HIGH VOLTAGE!
4405
SELF TEST
NC NO
20
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
ON
1
NO
2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW 1
ON
SW 1
ON
SW 1
ON
SW 1
lf SW 1, switch 3 is ON, functions as a
normal full open input (Normal setting).
4
When gate is closed, input will open gate.
When gate is open and auto close timer SW 1,
switch 4 is turned ON, input will re-set and hold timer.
When gate is open and auto close timer SW 1,
5
switch 4 is turned OFF, input will close gate.
When gate is closing, input will reverse gate.
6
10
14
lf SW 1, switch 3 is OFF, input to
terminal #4 becomes the output from the EXIT loop detector plugged into the EXIT loop port. (Used for specialized functions).
This input ONLY functions when gate is
fully opened or in the closing cycle.
When gate is closing: SW 1, switch 5 is
OFF, an input to terminal #6 (e.g.: photo beam gets obstructed) will stop and reverse and the gate to the full open position. Note: If the auto-close timer is ON, when gate reaches the open position, timer will not close the gate. Another input command is needed to reset and close the gate (Normal Setting).
Do Not use SW 1, switch 5 ON, for the 6550.
24-volt DC magnetic lock power is
9
11
15
provided constantly except when the gate is opening or open (Normally Closed function). 1 Amp Max.
Operation of the circuit board dry relay contact is dependent on setting of SW 1, switches 7 and 8. Relay contacts can be set for Normally Open (NO) or Normally Closed (NC) operation.
Contact rating is 1 amp maximum at 24-volts DC.
NC
DoorKing’s Remote alarm reset station can be connected. See next page for wiring. It MUST be mounted in the line-of-sight of the gate operator. (DKS P/N 1404-080)
For dual operator applications ONLY. Allows the secondary
reversing sensor to monitor
16
26
the current flow into the secondary operator. See page 22 for more information.
6550-065-A-4-12
Page 29
5.2 Control Wiring
3-Wire Radio
Receiver
Important: Controls must be installed
a minimum of 10-feet from the gate or
installed in such a way that the person using the control cannot come in contact with the gate or gate operator.
Com
1
1
Radio
2
Open
2
3
3
Safety
4
Open
4
Access
Device
5
Open
NC NO
5
6
6
7
7
8
8
9
9
10
10
11
11
Com
12
12
#6 Normally Open
#9 Normally Close
Com
Relay
24 Volt
3-Pin
123
Remote Terminal
Power is limited to 250 mamps.
White
Brown
Orange
#4 Normally Open
#5 Normally Open
“REVERSE” Closing-Direction Photo Sensors
ON
1 2 3 4 5 6 7 8
SW 1
SW 1, switch 5: After photo sensor beam gets obstructed:
OFF- Reverses gate.
See page 24 for more information.
TE A
y l
R
n
E
o
e
OP
us
O T
ian
H
ic
S
n
U
h
P
ec
t
(3) Three 115 VAC Convenience Outlets
ON
#4 - Safety
Opening
1 2 3 4 5 6 7 8
Device
SW 1
SW 1, Switch 3 Must be ON.
#5 - Access Control
Devices
Telephone
Entry
Stand-Alone
Key Switch
4405-010
20
6550-065-A-4-12
13
Com
13
14
14
15
15
16
16
17
17
18
18
19
19
Alarm
Alarm Reset
Blue
Red
White
24 Volt
1 amp max.
Com
Remote Alarm Reset Station
(DKS P/N 1404-080) MUST be mounted in the line-of-sight of the gate operator.
Magnetic Lock
Power (24-Volt DC) and logic output. Power is shut off .5 sec. prior to gate starting and remains off while gate is opening and in the open position.
SW 2, switch 2 ON.
1
2 3 4
ON
SW 2
Stand-Alone
Keypad
Stand-Alone Card Reader
Note: All stand-alone and telephone entry devices must use a separate power source.
20
Quad Box
Shown
Gate Tracker - DoorKing Access Control System (Model 1833, 1835, 1837 or 1838) tracker
system can be connected. This system can keep track of gate operator cycle count, shorted inputs, loop detector problems, any forced entry attempts, if the gate has struck anything during the open or close cycle, power interruptions, etc. For more detailed information refer to the Tracker Installation and Wiring Manual, DoorKing P/N 2351-010.
Terminal #2 (Full open) required only if the tracker board will activate the gate operator. Refer to the manual 2351-065 for detailed information.
27
Page 30
SECTION 6 - OPERATING INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving and power has been shut-off.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. SAVE THESE INSTRUCTIONS.
6.1 AC Power Switch and Reset Button
Unlock the power switch cover and open to access the MAIN POWER and the operator RESET button.
Reset Button - Used to turn off the
RESET
AC
POWER
entrapment alarm and to reset the operator after a hard shutdown has occurred.
Alarm Siren
AC Power Switch - Powers the operator
ON (toggle up) or OFF (toggle down).
OFF
28
6550-065-A-4-12
Page 31
6.2 Shutdown Conditions
Under various entrapment conditions the operator will assume either a soft or hard (alarm) shutdown. To determine what type of reset action is required, you will need to understand how the different entrapment conditions affect the gate operator.
Soft Shutdown
This occurs in various situations where the inherent or secondary entrapment protection devices have been activated. In a soft shutdown condition, the operator will not respond to any input that was present when the entrapment protection device sensed an obstruction. If the gate stops at the open position, the operator will not respond to the automatic close timer.
Example 1 - A time clock keys the gate open in the morning and an entrapment protection device senses
an obstruction prior to the gate reaching the full open position. If the entrapment is sensed by the inherent system, the gate will reverse and run back to the closed position. The time clock input is still present, but the gate will not re-open.
NOTE: In some systems, the time clock input comes from the telephone entry system relay. This same relay may also provide open commands for a card reader, MicroPLUS transmitters and the visitor telephone entry. If so, these devices will also be disabled in a soft shutdown condition.
Example 2 - If the gate is closing and an entrapment protection device is activated, the gate will either stop
or reverse and run back to the open position, depending upon if the secondary or inherent device was activated. The automatic close timer will not close the gate.
Example 3 - Vehicle arrives at open loop and gate runs towards the open position. The inherent entrapment
protection is activated. The gate reverses and runs back to the closed position. If the vehicle is still present at the open loop a soft shutdown condition does not occur. The loop input provides an immediate reset of the operator and the gate will again run to the open position.
Resetting a Soft Shutdown
In some conditions, a soft shutdown will reset as soon as the entrapment condition clears. For example, if a non-contact sensor (photo sensor) is sensing an obstruction, the operator will stop the gate and assume a soft shutdown condition. When the photocell clears, the operator will return to normal operation.
When the operator is in a soft shutdown, activation of any "intended input" will reset the operator. An "intended input" includes any command, any standard safety input and any loop input. Activating any of these inputs will reset the gate. At that point the gate will return to normal operation. If the gate is open, the automatic close timer will then time out and close the gate.
Hard Shutdown (Alarm Activated)
A hard shutdown condition occurs when the inherent entrapment protection system has sensed TWO consecutive obstructions before the gate reaches the full open or closed position.
Example - The gate is closing and the inherent entrapment protection system senses an obstruction and
causes the gate to reverse direction. As the gate begins to run in the open direction, a second obstruction is sensed prior to the gate reaching the full open position. Once the second obstruction has been sensed, the operator will stop, the audio alarm will be activated and all standard inputs are shut down (including open commands, safety commands, loop inputs, etc.).
The audio alarm will sound for five minutes, or until the operator’s reset button is pushed. After (5) five minutes the alarm will “chirp every 5 sec.” and the hard shutdown condition will remain in affect until the reset button is pushed.
After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard
shutdown condition and the reset switch must be activated to reset the operator and silence the alarm.
Continued on the next page
6550-065-A-4-12
29
Page 32
Resetting a Hard Shutdown
When the operator is in a hard shutdown condition (audio alarm activated or audio alarm “chirps” every 5 seconds), the only way to reset the gate operator and return it to normal operation is to activate the alarm reset input (auxiliary terminals 2 and 3). An alarm-reset switch can be mounted external of the gate operator provided that it is installed in the line of sight of the gate and gate operator.
Before resetting a hard shutdown, determine why the shutdown occurred. Inspect the gate for any
obstructions along its path that could have activated the inherent entrapment sensing system. Inspect the gate and gate hardware.
NOTE: DoorKing operators have a built-in alarm reset push button mounted on the operator above the power ON-OFF toggle switch. Activating this button will return the gate operator to normal operation, but will not activate
the gate operator.
Once the gate has been reset, an open or close command is needed to start the gate operator. Most activating commands will cause the gate operator to cycle to the open position. This includes activation of a key switch or open command and activation of the automatic exit loop. Activation of a close command will run the gate to the closed position.
6.3 Manual Gate Operation
This operator is equipped with a manual release system that will allow the gate to be pushed open in the event of a power outage or equipment failure. NEVER remove the hub from the operator after manually releasing it.
Emergency Vehicle Access Conditions
The automatic vehicular gate system must be designed to allow access to emergency vehicles under different operating conditions.
Convenience Open
2340-010 Circuit Board
This gate operator CAN NOT be manually forced open in the event of a power failure without FIRST manually releasing the gate! (See next page)
Never attempt to manually push open any gate with an operator attached to it until you have verified that power to the operator has been shut-off.
1. During normal powered operation, emergency vehicles access the gate by use of the Emergency Vehicle
Access Device installed on your gate system. The type of device that is used in your community is dependent
on your city codes. These devices may include (but are not limited to) Fire Department lock boxes, Click-2­Enter radio receivers, strobe light sensors, siren sensors, etc.
2. In the event of a power failure, the emergency vehicle access device may not be functional because the gate operator is un-powered. If the gate operator is equipped with a Convenience Open System, this system will automatically open the gate when primary (AC) power is removed. NOTE: DC convenience open systems are optional and your gate system may or may not be equipped with one. Check with your installer to determine if your gate system is equipped with a convenience open system. The 6550 is NOT equipped with the DC convenience open system.
3. In the event of a primary (AC) power failure and a back-up system (DC) power failure (low charged or dead batteries for example), the system must have a release system to allow the gate to be Manually
Operated (See next page).
30
6550-065-A-4-12
Page 33
Manual Release
Be sure that power is removed or shut-off prior to placing the gate operator in manual operation.
Unlock the cover and
A
rotate sliding door.
Never attempt to manually push open any gate with an operator attached to it until you have verified that power to the operator has been shut-off.
Remove release tool and
B
place where shown.
6550-065-A-4-12
CAUTION
DO NOT REMOVE HUB!
Release hub.
C
Gate can now be manually operated.
31
Page 34
SECTION 7 - MAINTENANCE AND TROUBLESHOOTING
Inspection and service of this gate operator by a qualified technician should be performed anytime a malfunction is observed or suspected. High cycle usage may require more frequent service checks.
7.1 Maintenance
When servicing the gate operator, always check any secondary (external) reversing devices (loops, photo eyes, etc.) for proper operation. If external reversing devices cannot be made operable, do not place this operator in service until the malfunction can be identified and corrected.
Always check the inherent reversing system when performing any maintenance. If the inherent reversing system cannot be made operable, remove this operator from service until the cause of the malfunction is identified and corrected. Keeping this operator in service when the inherent reversing system is malfunctioning creates a hazard for persons which can result in serious injury or death should they become entrapped in the gate.
When servicing this gate operator, always turn power OFF!!
If gearbox requires oil, use only Mobil SYNTHETIC SHC-629 Oil. Do not completely fill gearbox with oil. Gearbox should be half full only. Do not exceed this level.
Operator
Component
Alarm
Arms
Drive Belt
Fire Dept.
Gate
Primary Reverse System
Loop(s)
Release
Secondary Reverse Device
Complete System
Maintenance
Activate the primary (inherent) reverse system by blocking the gate with a solid object. When the gate reverses, block the gate in the opposite direction prior to the limit being reached. The entrapment alarm should activate. Press the reset button to silence the alarm.
Check set screws and nuts. Check bushings for wear.
Check for alignment, tightness and wear.
Check emergency vehicle access device for proper operation.
Inspect for damage. Check gate hinges for wear and grease if necessary.
Check that the gate reverses on contact with an object in both the opening and closing cycles. Adjust the reversing sensor if necessary.
Check vehicular reverse and shadow loops for proper operation.
Check manual release for proper operation.
Check secondary (external) reverse device(s) stop or reverse the gate when activated.
Complete check of gate and gate operating system.
Monthly Interval
6312
✓ ✓
✓ ✓
✓ ✓
32
6550-065-A-4-12
Page 35
7.2 Troubleshooting
Have a good VOM meter to check voltages and continuity. A Meg-Ohm meter capable of checking up to 500 meg-ohms of resistance is necessary to properly check the integrity of the ground loops. When a malfunction occurs, isolate the problem to one of three areas: 1) the operator, 2) the loop system, 3) the keying devices. Use caution when checking high voltage areas:
terminals 17 through 20, the motor capacitor and the motor.
1. Check the input indicator LEDs. They should only come ON when a keying device (card reader, push button, etc.) is
activated. If any of the input LEDs are ON continuously, this will cause the gate operator to hold open. Disconnect the keying devices one at a time until the LED goes OFF.
2. Check any external secondary entrapment protection devices. Any short or malfunction in these devices can cause the gate operator to stop or to hold open.
3.
A malfunction in a loop or loop detector can cause the gate operator to hold open, or to not detect a vehicle when it is present over the loop. The LEDs next to the loop detector ports on the operator circuit board will light only when the loop has detected an object above it. If the LEDs stays on after the object has gone, then the loop detector has malfunc­tioned. Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction persists, the problem is not with the loop system. For more information on trouble shooting loops and loop detectors, refer to your loop detector instruction sheet and to the DoorKing Loop and Loop Detector Information Manual.
4. Check to be sure that there are no shorted or open control wires from the keying devices to the gate operator. If a keying device fails to open the gate, momentarily jumper across terminals 1 and 2 (or 1 and 5) on the gate operator circuit board. If the gate operator starts, this indicates that a problem exist with the keying device and is not with the gate operator.
5. Check the high voltage supply. A voltage drop on the supply line (usually caused by using too small supply voltage wires) will cause the operator to malfunction. Refer to the wire size chart in section 2.1 page 15.
Symptom Possible Solution(s)
Operator will not run. Power LED is OFF.
Operator will not run. Power LED is ON.
Secondary operator motor will not run.
Check that power to the operator is turned ON.
Transformer may be overheated. Turn power off and allow board to cool for several minutes then
retest. Check for low 115 VAC power and low voltage shorts.
Check for 115 VAC at terminals 19 and 20. If voltage measures OK, check the terminal strip or
replace the circuit board.
Push test button or momentarily jumper terminal 1 to terminal 2 (or 1 to 5). If the input LED does
not come ON, check the terminal strip or replace the circuit board. If LED does come ON, proceed to next steps.
Check Motor:
Remove circuit board. With power ON, momentarily jumper terminal 19 to terminal 18 with a
14 AWG insulated jumper wire. CAUTION – HIGH VOLTAGE. The motor should run.
With power ON, momentarily jumper terminal 19 to terminal 17 with a 14 AWG insulated
jumper wire. CAUTION – HIGH VOLTAGE. The motor should run in the opposite direction of the above step.
If the motor runs in both steps above, replace the control board. If the motor does not run,
or runs in only one direction, problem can be a bad motor, motor capacitor, wire connections from the control board to the motor or a bad control board.
Check that SW-1, switch 6 is ON.
Remove circuit board. Momentarily jumper terminal 19 to the primary/secondary connection
terminal block terminal 1, then to terminal 2 with a 14 AWG insulated jumper wire. CAUTION – HIGH VOLTAGE. The secondary motor should run one way, then the other way as power is applied to each terminal.
If the secondary motor runs in both directions, replace the control board. If secondary motor does
not run, or runs in only one direction, problem can be in the wiring from the primary to secondary operator, bad secondary motor or motor capacitor.
6550-065-A-4-12
33
Page 36
Symptom Possible Solution(s)
Gate will not reverse when an obstruction is encountered.
Gate opens a short distance, then stops and reverses.
Gate opens but will not close.
Gate closes but will not open.
Check ERD setting.
Make sure operator hub does not slip when gate encounters an obstruction.
Check the reversing sensitivity.
Disconnect the gate from the gate operator and check that the gate swings freely without any
binding.
Replace the circuit board.
Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.
Check the secondary safety devices. Any activated will hold the gate open and indicates a problem
with the safety device.
Check the loop detectors. Any activated can hold the gate open and indicates a problem with the
loop detector or ground loop.
Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns
to normal operation.
If automatic close is desired, be sure SW-1, switch 4 is ON.
Check motor as described on previous page.
Operator may be in a “soft shutdown.” Check input LEDs. If any are ON, momentarily disconnect,
then re-connect the wire going to the respective terminal. Operator should open.
Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back
ON. Activate a keying device. Operator should run in the open direction. If operator runs in the close direction, turn power OFF and change direction switch SW-1, switches 1 and/or 2. Go to above section if operator now opens but will not close.
Be sure that the respective LED on the control board lights when the keying device connected to the
respective terminal is activated. If LED does not light, momentarily place a jumper wire from terminal 1 to the input terminal being checked. If LED lights and gate opens, problem is with the keying device. If LED does not light, replace control board.
Check motor as described on previous page.
Gate starts to close, then reverses to open.
Gate closes and then re-opens.
Alarm sounds for 5 minutes and then beeps once every 5 seconds. Operator will not run.
34
Check that the reverse sensitivity is properly adjusted.
Disconnect the gate from the operator and check that the gate operates freely without any binding.
Check the loop detector LEDs and input LEDs. Any that flash ON will cause the gate to reverse.
If a shadow loop is used, check for proper wiring. A mis-wired shadow loop detector will cause the
gate to reverse.
Replace the circuit board.
Check for any input or loop detector LEDs that are ON.
Check that the operator is running in the proper direction (see “gate closes but will not open” above).
Operator is in a “hard shutdown” condition. Reset switch must be activated to return operator to
normal operation.
6550-065-A-4-12
Page 37
7.3 Built-in Diagnostics
This gate operator is designed with built-in diagnostics that will alert you to potential or existing problems that the microproces­sor has detected. Specific fault conditions are checked and the operator will signal that a fault exist through the built-in alarm.
Constant tone is heard when power is applied: This indicates that the limit switch wire harness is not connected to the circuit
board. In this condition, the operator will not run and the tone will continue until the fault is corrected. Check to be sure that the limit switch plug is properly inserted into P2.
Constant tone is heard: This indicates that the operator is in a hard shutdown condition. The tone will continue to sound for
five minutes, and then will beep once every five seconds. The operator-reset button must be pressed or power must be removed and then reapplied to return the operator to normal operation.
Short tone is heard every five seconds: This indicates that the operator has been in a hard shutdown condition in excess of five
minutes. This will continue until the operator-reset button is pressed or until power is removed from the operator.
Operator runs for 1 second and stops, two short tones are heard: This indicates that there may be a fault with the current
sensor circuit. Check that the black current sensor wire has been passed through the hole in the current sensor donut with the correct number of loops (1 HP motor - 1 loop).
7.4 Accessory Items
The following accessory items are available for the model 6550 swing gate operator.
Contact Sensors - For use as a secondary entrapment protection device. Miller Edge, Inc., MGO20, MGR20, MGS20 Photo Cell - Non-contact (photo-cells) sensors for use as a secondary entrapment protection device.
MMTC, Inc. Model IR55 P/N 8080-010 MMTC, Inc. Model 60-278 P/N 8080-011 Carlo Gavazzi Type PMP12 P/N 8080-030 Carlo Gavazzi Type PMT P/N 8080-031
Loop Detector - Detectors plug directly into ports on circuit board simplifying wiring.
P/N 9410-010 - Single channel detector P/N 9409-010 – Two-channel detector
Magnetic Lock - Magnetic Gate Lock Kit provides an excellent means to secure swing gates and is a fail-safe device allowing
emergency vehicle access upon power outage. P/N 1216-080 and P/N 1216-081
Remote Reset - Provides a remote station to reset an operator in a hard shutdown condition. Must be mounted in line-of-site of
the gate and operator. Includes visual and audible signals. P/N 1404-080.
Control Station - Interior station mounts into single-gang electrical box. Provides open and hold open manual operation of the
gate. P/N 1200-017.
Heater and Fan Assembly - Use for cold weather climates where temperatures routinely drop below 40°F (4°C). P/N 6550-480 Interconnect Cable - Interconnect wire cable contains all the necessary wires to interconnect primary / secondary operators.
Cable length 30 feet. P/N 2600-755 Cable length 40 feet. P/N 2600-756 Cable length 50 feet. P/N 2600-757
Time Clock - 7 day and 365 day time clocks can be used to automatically open gate at pre-set time and days. Compact clock fits
inside the operator. P/N 2600-791 - 7 day clock P/N 2600-795 - 365 day clock
Torsion Rods - Torsion rod assembly is used on uphill swing gates for counter balance.
P/N 1203-084
Hinges - Heavy-duty ball bearing hinges provide easy swing gate operation.
P/N 1200-009, P/N 1200-019, P/N 1200-039.
Surge Devices - High and low voltage surge suppressors help prevent circuit board failure caused by lightning strikes and
power surges. P/N 1876-010 - High Voltage P/N 1878-010 - Low Voltage
Gate Scale - Use to test torque required to move gate. P/N 2600-225 Speed Bumps - Prefabricated six-foot speed bump reduces traffic speed through gate system. P/N 1610-150
6550-065-A-4-12
35
Page 38
7.5 Gearbox Shaft Extension Replacement
Crank Arm
2
Set Screws
Limit Sensor Assemblies
Loosen set screws on plastic limit assemblies to remove them. Be CAREFUL not to damage limit sensor wires after the assemblies have been removed. Note: Close Limit Sensor assembly must be reinstalled on TOP of Open Limit Sensor assembly.
Brass Bushing
CLOSE
OPEN
1
Key
Key
Hub Assembly
bottom of hub to remove the complete hub assembly.
Remove the TWO allen screws on
Limit Sensors Collar
Key
Gearbox Shaft Extension with 4 Keys
Key
Stainless Steel Washer Snap Ring
3
1
2
4
Gearbox Collar
Remove the FOUR allen screws to remove the gearbox collar.
Gearbox
36
6550-065-A-4-12
Page 39
Model 6550 1 HP 115 VAC
Magnetic
Close
Sensor
Yellow
EXIT LOOP
REVERSE LOOP
Magnetic Open Sensor
Orange
Orange
Yellow
ON
REV SENSE SECONDARY
TIME DELAY
1 2 3 4 1
2 3 4 5 6 7 8
REV SENSE PRIMARY
ON
P2
Current Sensor
4405
Remote Terminal
1
2
NC
10
NO
1 Loop
20
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
19
SELF TEST
10
11
12
13
14
15
16
17
18
19
20
White
Brown
Orange
Red Blue White
1 HP
Single-Phase
1
2
3
4
5
6
7
8
9
Alarm
6550-065-A-4-12
Ground
Neutral
Red
Power
Yellow
PUSH TO OPERATE
technician use only
Reset
AC Power
NEU HOT
115 VAC
Power
Brown
Chassis
Ground
Red
Black
1 Loop
Secondary
Current
Sensor
Red
Blue
White
Purple
Yellow
Orange
Gray
Secondary Interface Terminal
37
Page 40
Model 6550 1 HP 208 / 230 / 460 VAC
Magnetic
Close
Sensor
Yellow
EXIT LOOP
REVERSE LOOP
Magnetic Open Sensor
Orange
Orange
Yellow
ON
REV SENSE SECONDARY
TIME DELAY
1 2 3 4 1
2 3 4 5 6 7 8
REV SENSE PRIMARY
ON
P2
Current Sensor
4405
PUSH TO OPERATE
technician use only
Remote Terminal
1
2
NC
10
NO
1 Loop
20
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
19
Power
Brown
SELF TEST
10
11
12
13
14
15
16
17
18
19
20
White
Brown
Orange
Red Blue White
1 HP
Single-Phase
1
2
3
4
5
6
7
8
9
Brown
Red
Black
38
Red
Alarm
Ground
Neutral
Yellow
Reset
Power
Blue
NEU NEU HOT HOT HOT
208 / 230 / 460 VAC
AC Power
Chassis Ground
Secondary
Step-Down
Transformer
1 Loop
Current
Sensor
Blue
Black
Brown
White
Black/White
Red
Blue
White
Purple
Yellow
Secondary Interface Terminal
Blue Black
Brown
White Black/White
Blue Black
Brown
White Black/White
Blue Black
Brown White Black/White
To Blue
To White
To White
To Blue
To White
To Blue
208
VAC
230
VAC
460
VAC
Gray
Orange
White
Blue
6550-065-A-4-12
Page 41
Model 6550 1 HP Secondary Operator
1 HP
Single-Phase
Red
Blue
White
Magnetic
Close
Sensor
Red
Yellow
Blue
White
Magnetic Open Sensor
Orange Orange
Yellow
Gray
6550-065-A-4-12
39
Page 42
Series 6550
Installation/Owner’s Manual
Heavy-Duty Vehicular Swing Gate Operator
Series 6550
Series 6550
Use this manual for circuit board 4405-010 Revision E or higher.
6550-065-A-4-12
www.doorking.com
DoorKing, Inc.
120 Glasgow Avenue
Inglewood, California 90301
Phone: 310-645-0023
Copyright 2009 DoorKing, Inc. All rights reserved.
Fax: 310-641-1586
U.S.A.
Loading...