Emko EZM-7750, EZM-4450, EZM-9950 User manual

EZM-4450,EZM-4950,EZM-7750,EZM-9950
Programmable Timers & Counters
EZM-4450,EZM-4950,EZM-7750,EZM-9950 Universal Input Programmable Timer & Counter with Output Module System
6 digits Process (PV) and 6 digits Set (SV) Value Display
-
Operation with 2 Set Values
-
- Reset , Pause and ChA-ChB Counting Inputs
- NPN/PNP input type selection
- Configurable Counter/Totalizer Counter,Batch Counter,Timer,
-Programmable Time Bases for Timer and Chronometer (Second ,
Minute ,Hour )
Operation with Automatic and Manual Reset
-
- Output Module System
- INC,DEC,INC/INC,INC/DEC,UP/DOWN, x1 / x2 / x4
with Phase Shifting Property in Counter Function
Multiplication Coefficient and Decimal Point Position
-
-Different Alarm Alternatives in Frequencymeter and Cycle
Measuring Functions
- Absolute or Offset Operation in Counter Function
- RS-232 (standard) or RS-485 (optional) Serial Communication with
Modbus ASCII or RTU Protocol
Counting
ENGLISH
EZM-XX50 Programmable Timers & Counters
SPECIFICATIONS
INPUT :
Counting Inputs (Ch-A,Ch-B): Switch, Proximity,Capacitive sensor or encoder can be
connected.
Reset Input: Switch, Proximity or Capacitive sensor can be connected. Pause Input: Switch, Proximity or Capacitive sensor can be connected. Input Type Selection: It can be selected NPN/PNP with DIP Switch that is located on
the device.
Reset Function: Automatic or Manual. Count Input Types:
INC,DEC,INC/INC,INC/DEC,UP/DOWN ,x1 / x2 / x4: ( for encoder ) counting
OUTPUT
Output Modules : There are two module sockets for plugging the output modules.
- Relay Output Module
- SSR Output Module (Max. 26mA, 22V )
- Digital (Transistor) Output Module (Max.40mA@18V )
SUPPLY VOLTAGE Supply Voltage :
100-240 V V 50/60 Hz (-15%;+10%) -6VA 24V V 50/60 Hz (-15% ; +10%) -6VA 24V (-15% ; +10%) -6W
Z
Must be determined in order.)
(
DISPLAY Actual Count Value Display
EZM-4450 : 8 mm Red 6 digit LED Display EZM-4950 : 13.2 mm Red 6 digit LED Display EZM-7750 : 10.8 mm Red 6 digit LED Display EZM-9950 : 13.2 mm Red 6 digit LED Display
Set :
Value Display
EZM-4450 : 8 mm Green 6 digit LED Display EZM-4950 : 8 mm Green 6 digit LED Display EZM-7750 : 8 mm Green 6 digit LED Display EZM-9950 : 8 mm Green 6 digit LED Display
LEDs : S1(Set1 value),S2(Set2 value),O1/2(Output Status) LEDs.
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS Operating Temperature Humidity none condensing Protection Class
Mounting: Type-1 Enclosure Mounting Installation: Fixed installation Category II Over Voltage Category: II Pollution Degree: II, office or workplace, none conductive pollution
Weight
:
EZM-4450 : 210 gr. ; EZM-4950 : 210 gr. EZM-7750 : 250 gr. ; EZM-9950 : 340 gr.
:
:
: 0...50°C
: 0-90%RH ( )
: IP65 at Front, IP20 at rear.
Z
Phase Shifting
Z
2
Dimensions:
EZM-4450 : (48 x 48mm,Depth:116 mm) EZM-4950 : (96 x 48mm,Depth:86.5 mm) EZM-7750 : (72 x72mm, Depth:87.5 mm) EZM-9950 : (96 x 96mm,Depth:87.5 mm)
DIP SWITCH Adjustment
Function Selection
Counter / Totalizer Counter
Batch Counter
Timer
Frequencymeter / Tachometer
Chronometer
Input Type Selection
NPN PNP
Electrical Wirings
Sensor Supply
Max.50mA
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Output
Module-2
Relay, SSR or
Digital
(Transistor)
Panel Cut-Out:
EZM-4450 : (46 x 46mm) EZM-4950 : (92 x 46mm) EZM-7750 : (69 x 69mm) EZM-9950 : (92 x 92mm)
Fuse
Note-1
a
External
(-)
(+)
Note-3
Communication Module RS-232(Standard)/ RS-485 (Optional)
Supply Switch
Fuse
Note-2
3
Sensor Supply
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Sensor Supply
Max.50mA
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Sensor Supply
Max.50mA
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Max.50mA
Output
Module-2
Relay, SSR or
Digital
(Transistor)
Output
Module-2
Relay, SSR or
Digital
(Transistor)
Output
Module-2
Relay, SSR or
Digital
(Transistor)
a
(-) (+)
Note-3
a
(-) (+)
Note-3
Communication Module RS-232(Standard)/ RS-485 (Optional)
Fuse
Note-1
a
(-) (+)
Note-3
External
Fuse
Note-2
Fuse
Fuse
Note-1
Communication Module RS-232(Standard)/ RS-485 (Optional)
Note-1
External
Fuse
Note-2
Supply Switch
Communication Module RS-232(Standard)/ RS-485 (Optional)
Supply
External
Switch
Fuse
Note-2
Supply Switch
Note-1 :There is an internal fusible flameproof resistor.
Note-2 : External fuse is recommended.
100...
1AVT for power supply 240 VV or 24VV 1AZT for power supply 24V Z Note-3 : “L” is ( + ) ,” N” is ( - ) for 24V Z supply voltage
4
DIMENSIONS
EZM-4450
O1
O2
S1
S2
Timer & Counter
TOTALPRESET
SET1 SET2
48 mm / 1.89 inch
Timer & Counter
S1
O1
S2
O2
SET2
SET1
P
96 mm / 3.78 inch
S1
O1
S2
O2
48 mm / 1.89 inch
11.5±1mm/0.45 inch
EZM-4950
TOTAL
RESET
EZM-7750
Maximum 5 mm / 0.2 inch
104.5mm / 4.11 inch
Maximum 15 mm / 0.59 inch
48 mm / 1.89 inch
10.5±1mm/0.41 inch
Maximum 15 mm / 0.59 inch
76mm / 2.99 inch
RESET
P
SET1 SET2
Timer & Counter
72 mm / 2.83 inch
S1S1
O1O1
S2S2
O2O2
RESET
P
SET1
Timer & Counter
EZM-9950EZM-9950
96 mm / 3.78 inch
TOTAL
TOTAL
SET2
72 mm / 2.83 inch
11.5±1mm/0.45 inch
Maximum 15 mm / 0.59 inch
96 mm / 3.78 inch
11.5±1mm/0.45 inch
76mm / 2.99 inch
76mm / 2.99 inch
5
PANEL MOUNTING
2
4
4
1-
Before mounting the
device in your panel,
1
makesure that the panel cut-out is suitable.
2-
Check front panel gasket
Position. 3-
Insert the device through
the cut-out. If the mounting
3
clamp are on the unit, put out them before inserting the unit to the panel.
4-5-Insert the unit in the panel
cut-out from the front side.
Insert the mounting
clamps to the holes that
5
5
located top and bottom sides of device and screw up the fixing screws until the u ni t co m pl et e ly immobile within the panel.
6
Accessing to the Program Parameters
Main Operation
Screen
TOTAL
RESET
SET1
SET2
When PROG button is pressed for 3 seconds, password must be entered for accesing to the parameters.
Password Screen
TOTAL
RESET
SET1
SET2
The most significant digit of the parameter(4th digit for this parameter flashes.)
Password Screen
TOTAL
RESET
SET1
SET2
After entered the password, press Enter button.
Input Types and
Functions
TOTAL
RESET
SET1
SET2
You can change the parameter with INCREMENT button, save it to the memory and pass to the next parameter with ENTER button.
Main Operation
SET1
Press PROG button to exit from programming selection without doing any changes.
Pulse Time for Ch-A,Ch-B
Reset and Pause Inputs
(1)
Screen
TOTAL
RESET
SET2
TOTAL
RESET
SET1
SET2
You can change the parameter with INCREMENT button, save it to the memory and pass to the next parameter with ENTER button.
Program Password
TOTAL
SET1
SET2
You can change the parameter with INCREMENT button, save it to
RESET
the memory and pass to the next parameter with ENTER button.
Input Types and
Functions
TOTAL
SET1
SET2
Continue to press ENTER button for scanning all parameters.
Multiplication
Coefficient
TOTAL
RESET
SET1
SET2
You can change the parameter with INCREMENT button, save it to the memory and pass to the next parameter with ENTER button.
RESET
(1)
7
Parameter Definitions
:Input Types and Functions
Upcount on rising edge of Ch-A input
0 : . (INC)
count on rising edge of Ch-A input
1 : Down . (DEC)
Upcount on rising edge of Ch-A input count on rising edge of Ch-B input
2 : ,Down .(INC/DEC)
Upcount on rising edge of Ch-A input,Upcount on rising edge of
3 :
Ch-B input
4 :
when Ch-B is at 1
5 : x1 .(For Incremental Encoder ) 6 : x2 .(For Incremental Encoder ) 7 : x4 .(For Incremental Encoder )
. (INC/INC)
Upcount on rising edge of Ch-A input when Ch-B is at 0 Downcount on rising edge of Ch-A
Phase Shifting Phase Shifting Phase Shifting
.(UP/DOWN)
: Selection of Input Type Function for Chronometer
0 : Period measurement in Ch-A input
Pulse time measurement in Ch-A input
1 : .
Sum of the time difference between Ch-A and Ch-B inputs rising edges
2 : .
.
: Selection of Measuring Method
0 : Frequency or cycle is calculated by measuring cycle time of the signals in Ch-A input
1 :
Frequency or cycle is calculated by counting the pulses in Ch-A input during the time
is set in measurement period.
.
: Pulse Time of Ch-A, Ch-B, Reset and Pause Input
It is used to protect against the electrical contact debounce or the signal that is less than the determined pulse time. It can be adjusted from to millisecond.
: Selection of Time Unit and Scale
Hour / Minute It can be adjusted from . 0 to 99.59. Minute It can be adjusted from / Second . 0 to 99.59.
Second / milisecond. 0 to 99.99.It can be adjusted from
Hour / Minute It can be adjusted from . 0 to 23.59.
Hour. 0 to 999.99.It can be adjusted from Minute. 0 to 999.99.It can be adjusted from Second. 0 to 999.99.It can be adjusted from
: Output Functions
0:
Manual Reset-1:
Device continues to count till manual reset is applied. When count value reaches the Set value, output position is changed.
Out-1 Out-1 Out-2
Reset
Set2 Set1
0
= = =
=
8
1:
Manual Reset-2:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
2:
Manual Reset-3:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
3:
Automatic Reset-1:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
4:
Automatic Reset-2:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
Out-1 Out-1 Out-2
Out-1 Out-2
Out-1 Out-1
Out-2
Out-1 Out-1 Out-2
Out-1
Out-2
Reset
Reset
Set2
Set1
Reset
Out-1 Out-1 Out-2
Reset
Set2
Set1
0
Set2
Set1
0
0
Set2
Set1
0
= =
= =
= = =
= =
= = =
= =
= = =
5:
Automatic Reset-3:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
Out-1 Out-1 Out-2
Reset
Set2
Set1
0
= = =
9
6:
Automatic Reset-4:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
Out-1 Out-1 Out-2
Reset
Set2
Set1
0
= = =
Out-1 Out-2
Reset
Set2
Set1
0
7:
Automatic Reset-5:
Count value is added to total value when manual reset is active in COUNTER/TOTALIZER COUNTER functions.
: Input Signal Reset Time (Time Out)
Actual count value is reset if no signal is applied to Ch-A input for a time which is
bigger than the value is set in this parameter.
It can be adjusted from to seconds.
: Measurement Period
Number of pulses in Ch-A input is counted during this time.
It can be adjusted from to seconds .
: Output-1 Function
Output is latched
0 : . (Latching).
Non-latched with hysteresis output is selected.
1 :
Output-1 is an alarm output.
2 :
: Output-2 Function
0 : . (Latching).
Output is latched
1 :
Non-latched with hysteresis output is selected.
: Alarm Functions for Output-1
If Output-1 function parameter is selected alarm output, then
Output-1 becomes active according to this parameter.
High Alarm
Output-1
ON
OFF
Set1Set1-Hys1
Count Value
= =
= =
10
Low Alarm
-1Output
ON
OFF
Set1 Set1+Hys1
Count Value
Deviation High Alarm
-1Output
ON
OFF
Set2
Deviation Low Alarm
-1Output ON
OFF
Deviation Band Alarm
-1Output
ON OFF
- Hys1
: Hysteresis for Output-1
- Hys1
Set2-Set1
Set2-Set1
Set1+Set2
Set1+Set2
Set2
+ Hys1
Count Value
Set2
Count Value
+ Hys1
Count Value
: Hysteresis for Output-2 : Output-1 Operation Form
Output - 1 Normally De-energised. Output - 1 Normally Energised.
: Output-2 Operation Form
Output - 2 Normally De-energised. Output - 2 Normally Energised.
Output-1 Pulse Time
It determines how long Output-1 will be active.
from
0000.00 to 0099.99 seconds.
It can be adjusted
11
: Output-2 Pulse Time
It determines how long Output-2 will be active. 0000.00 to
0099.99 seconds.
It can be adjusted from
: Start of the Controlling
Control is started when the unit is energised.
Control is started when count value reaches to SET1 value Control is started when count value reaches to SET2 value
.
.
: Direction of Counting
Upcount. ( 0 --> Preset ) Downcount. ( Preset --> 0 )
: Point position for the Display
No point.
Between first and second digits.
Between second and third digits. Between third and fourth digits.
Between fourth and fifth digits.
: Saving Count Value
Count value is saved to memory when power is disconnected and restored on power up.
Count value is not saved to memory when power is disconnected.
: SET1 Operation Form Selection
Absolute operation.SET1 can be adjusted from to .
Operation with offset. SET1 can be defined ± Offset according to SET2 value.( SET1 = SET1 + SET2 )
: Communication Accessing Address
Device address for serial communication bus. to .
It can be adjusted from
: Modbus Protocol Type Selection
Modbus ASCII protocol is selected. Modbus RTU protocol is selected.
: Communication Parity Selection
No Parity . Odd Parity.
Even Parity.
12
: Communication Baud Rate
1200 Baud Rate
2400 Baud Rate
4800 Baud Rate
9600 Baud Rate 19200 Baud Rate
:Communication Stop Bit Selection
1 Stop Bit.
2 Stop Bits.
:Reset and Set Protection (For Accessing from Front Panel)
No Reset and Set protection. Only Reset button protection is active.
SET1 and SET2 can not be changed. Full Protection. Reset protection is active, also SET1
and SET2 can not be changed. SET1 can not be changed.
SET2 can not be changed.
: Frequency / Cycle Coefficient
It can be adjusted from to .Count value is multiplied with this
parameter.
: Multiplication Coefficient
It can be adjusted from to .
: Program Password
It is used for accessing to the program parameters. It can be adjusted from to .
If it is ; there is no password protection while entering to the program parameters.
When programming button is pressed, will appear on the display.
If this parameter is different from “ 0” and user wants to access to the program parameters; 1-
If user does not enter the value correctly ; operation screen will appear
without entering to operator parameters.
2-
When in top display and in bottom display,if user presses ENTER
button without entering password (for observing the parameters):
13
Failure Messages in EZM-XX50 Timer & Counter
Position of the DIP Switch is wrong. (DIP Switch
1-
S2
SET1
2- If the password is not 0, user can access to the parameters
without entering the password and by pressing ENTER button.
determines the operation function of the device and it is under the top cover.)
TOTAL
RESET
SET2
Main Operation
Screen
S2
SET1
SET2
W hen PRO G
button is pressed, password entering screen will appear.
Main Operation
Screen
S2
SET1
SET2
O1
O2
S1
S2
TOTAL
SET1
SET2
O1
O2
S1
S2
TOTAL
SET1
SET2
RESET
RESET
Input Types and
Functions
SET1
SET2
By pressing ENTER button, user can see all parameters except for program password.
TOTAL
RESET
Press PROG button to exit
from
programming
mode.
Password Screen
TOTAL
RESET
TOTAL
RESET
3- If Actual Value is flashing and counting is stopped;
It appears if any of the count value is bigger than the maximum count value.(Total count value for
RESET
Counter/”Totalizer Counter” Function - Batch count value for Batch Counter FUNCTION ) To remove this warning and reset the count value press RESET button.
4- If actual value is flashing and counting is not
performed; It appears if any of the count value is less than the
RESET
minimum count value. (Total count value for Counter/Totalizer Counter” Function - Batch count value for Batch Counter FUNCTION )To remove this warning and reset the count value press RESET button.
SET1
SET2
Press ENTER Button without entering the password.
Input Types and
Functions
TOTAL
SET1
SET2
TOTAL
Multiplication Coefficient
TOTAL
SET1
SET2
Continue to
Press ENTER
button for scanning the parameters.
RESET
14
Installation
Before beginning installation of this product, please read the
c
In package ,
-One piece unit
-Two pieces mounting clamp
-One piece instruction manual A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product. If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and the electrical connection of the device from the system. The unit is normally supplied without a power switch or a fuse. Use power switch and fuse as required. Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure. Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented. Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in malfunction, electric shock or fire. Do not use the unit in combustible or explosive gaseous atmospheres. During the equipment is putted in hole on the metal panel while mechanical installation some metal burrs can cause injury on hands, you must be careful. Montage of the product on a system must be done with it’s mounting clamp. Do not do the montage of the device with in appropriate mounting clamp. Be sure that device will not fall while doing the montage. It is your responsibility if this equipment is used in a manner not specified in this instruction manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case.
instruction manual and warnings below carefully.
Garanti
Warranty
Maintenance
15
Diğer Bilgiler
Other Informations
Manufacturer Information
Emko Elektronik Sanayi ve Ticaret A.Ş. Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY Phone : +90 224 261 1900 Fax : +90 224 261 1912
Repair and maintenance service information
Emko Elektronik Sanayi ve Ticaret A.Ş. Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY Phone : +90 224 261 1900 Fax : +90 224 261 1912
:
:
Order Information
Supply Voltage
Customer Maximum
Serial Communication Module Codes
None
Output-1
None
Module-1
None Relay Output Module SSR Driver Output Module
(Maximum 26mA, 22VZ)
Digital(Transistor)Output Module
(Maximum 40mA@18VZ)
Module-2
None Relay Output Module SSR Driver Output Module
(Maximum 26mA, 22VZ)
Digital(Transistor)Output Module
(Maximum 40mA@18VZ)
Module Codes
Module Codes
16
Note-1 : EMO-4xx is used in EZM-4450 and EZM-4950 EMO-7xx is used in EZM-7750 EMO-9xx is used in EZM-9950
Note-2 :
EMO-400 Relay Output Module’s rating is 3A@250V on resistive load. EMO-700 and EMO-900 is 3A@250V on resistive load.
Function
Counter / Totalizer Counter Batch Counter Timer Frequencymeter / Tachometer Chronometer
Input Type
All order information of EZM-xx50 series are given on the table at
above.User may form appropriate device configuration from information and codes that at the table and convert it to the ordering codes. Firstly, supply voltage then other specifications must be determined. Please fill the order code blanks according to your needs. Please contact us, if your needs are out of the standards.
This symbol is used for safety warnings. User must pay attention to these warnings.
c
This symbol is used to determine the dangerous situations as a result of an electric shock. User must pay attention to these warnings definitely.
a
This symbol is used to determine the important notes about functions and usage of the device
i
17
Your Technology Partner
Thank you very much for your preference to use Emko Elektronik products, please visit our web page to download detailed user manual.
www.emkoelektronik.com.tr
1818
EZM-4450,EZM-4950,EZM-7750,EZM-9950
P
rogrammierbare Timer & Zähler
EZM-4450,EZM-4950,EZM-7750,EZM-9950 Timer & Zähler mit Universaleingang und programmierbarem Ausgangs-Modulsystem
- Anzeige für 6-stelligem Zählwert (PV) und 6-stelligem Vorwahlwert (SV)
- 2 Vorwahlwerte - Rücksetz-, Pause- und ChA-ChB Zähleingang
- NPN/PNP Eingang wählbar
- Konfigurierbarer Zähler/Summenzähler, Chargenzähler, Timer, Chronometer, Frequenzmesser/Tachometer
- Programmierbare Zeitbasis für Timer und Chronometer (Sekunde, Minute, Stunde)
- Automatisches oder manuelles Rücksetzen
- Modulares Ausgangssystem
- INC,DEC,INC/INC,INC/DEC,UP/DOWN, x1 / x2 / x4 Zählauswahl mit Phasenverschiebung (für Drehgeber)
- Multiplikationsfaktor und wählbare Dezimalpunktposition
- Verschiedene Alarmmöglichkeiten bei Frequenzmessung und Zyklus Messfunktionen
- Gesamtmengen- und Teilmengenerfassung bei Zählerfunktion
- RS-232 oder RS-485 serielle Schnittstelle mit Modbus ASCII oder RTU Protokoll.
DEUTCH
EZM-XX50 Programmierbare Timer & Zähler
SPEZIFIKATION: EINGÄNGE: Zähleingänge (Ch-A,Ch-B): Schalter, Näherungsschalter,Kapazitivsensor oder Drehgeber Rücksetzeingang: Schalter, Näherungsschalter, Kapazitivsensor oder Drehgeber Pauseeingang: Schalter, Näherungsschalter, Kapazitivsensor oder Drehgeber Sensortyp: NPN oder PNP Rücksetzfunktion: automatisch oder manuell Zähleingänge und maximale Frequenzen:
INC,DEC,INC/INC,INC/DEC,UP/DOWN x1 / x2 / x4: Phasen-verschiebung (Drehgeber)
AUSGÄNGE Ausgabemodule: 2 Ausgänge wahlweise Relais, SSR oder Transistor
- Relais 3 A @ 250 VV
- SSR max. 20mA @ 18 VZ
- Transistor max. 40mA @18 VZ
VERSORGUNG Versorgungsspannung :
V
100-240 V 50/60 Hz (-15%;+10%) 6VA 24 VV 50/60 Hz (-15% ; +10%) 6VA 24 VZ (-15% ; +10%) 6W
(Bei Bestellung angeben)
ANZEIGE Anzeige für den aktuellen Wert:
EZM-4450: 8 mm rote 6-stellige LED-Anzeige EZM-4950: 13.2 mm rote 6-stellige LED-Anzeige EZM-7750: 10.8 mm rote 6-stellige LED-Anzeige EZM-9950: 13.2 mm rote 6-stellige LED-Anzeige
Anzeige für Set-Wert:
EZM-4450: 8 mm grüne 6-stellige LED-Anzeige EZM-4950: 8 mm grüne 6-stellige LED-Anzeige EZM-7750: 8 mm grüne 6-stellige LED-Anzeige EZM-9950: 8 mm grüne 6-stellige LED-Anzeige
LED-Anzeigen : Vorwahlwert 1/2; Ausgang 1/2
Betriebstemperatur: 0...50°C Feuchtigkeit: 0-90%RH (ohne Kondensation) Schutzklasse: Frontseite IP65, Rückseite IP20 Gewicht:
EZM-4450: 210 g EZM-4950: 210 g EZM-7750: 250 g EZM-9950: 340 g
Abmessungen:
EZM-4450: (48 x 48 mm, Tiefe: 116 mm) EZM-4950: (96 x 48 mm, Tiefe: 86.5 mm) EZM-7750: (72 x 48 mm, Tiefe: 87.5 mm) EZM-9950: (96 x 48 mm, Tiefe: 87.5 mm)
Schalttafelausschnitte:
EZM-4450: (46 x 46 mm) EZM-4950: (92 x 46 mm) EZM-7750: (69 x69 mm) EZM-9950: (92 x 92mm)
2
DIP-Schaler Funktionswahl
Funktionswahl des Gerätes
Zähler / Gesamtzähler
Chargen-Zähler
Timer
Frequenzmesser / Tachometer
Chronometer
Eingangswahl
NPN PNP
Elektrische Anschlüsse
Hilfsausgang
Ausgang-1Ausgang-1
Hilfsausgang
Ausgang-2
Schnittstelle
Sicherung
Modbus
Versorgungsspannung
Ausgang-
1
Ausgang-2
Modbus
Schnittstelle
Sicherung
Versorgungsspannung
3