Chronometer , Frequencymeter and Tachometer Functions
-Programmable Time Bases for Timer and Chronometer (Second ,
Minute ,Hour )
Operation with Automatic and Manual Reset
-
- Output Module System
- INC,DEC,INC/INC,INC/DEC,UP/DOWN, x1 / x2 / x4
with Phase Shifting Property in Counter Function
Multiplication Coefficient and Decimal Point Position
-
-Different Alarm Alternatives in Frequencymeter and Cycle
Measuring Functions
- Absolute or Offset Operation in Counter Function
- RS-232 (standard) or RS-485 (optional) Serial Communication with
Modbus ASCII or RTU Protocol
Counting
ENGLISH
EZM-XX50 Programmable Timers & Counters
SPECIFICATIONS
INPUT :
Counting Inputs (Ch-A,Ch-B): Switch, Proximity,Capacitive sensor or encoder can be
connected.
Reset Input: Switch, Proximity or Capacitive sensor can be connected.
Pause Input: Switch, Proximity or Capacitive sensor can be connected.
Input Type Selection: It can be selected NPN/PNP with DIP Switch that is located on
the device.
Reset Function: Automatic or Manual.
Count Input Types:
Output Modules : There are two module sockets for plugging the output modules.
- Relay Output Module
- SSR Output Module (Max. 26mA, 22V )
- Digital (Transistor) Output Module (Max.40mA@18V )
SUPPLY VOLTAGE
Supply Voltage :
100-240 V V 50/60 Hz (-15%;+10%) -6VA
24V V 50/60 Hz (-15% ; +10%) -6VA
24V (-15% ; +10%) -6W
Z
Must be determined in order.)
(
DISPLAY
Actual Count Value Display
EZM-4450 : 8 mm Red 6 digit LED Display
EZM-4950 : 13.2 mm Red 6 digit LED Display
EZM-7750 : 10.8 mm Red 6 digit LED Display
EZM-9950 : 13.2 mm Red 6 digit LED Display
Set :
Value Display
EZM-4450 : 8 mm Green 6 digit LED Display
EZM-4950 : 8 mm Green 6 digit LED Display
EZM-7750 : 8 mm Green 6 digit LED Display
EZM-9950 : 8 mm Green 6 digit LED Display
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS Operating
Temperature
Humiditynone condensing
Protection Class
Mounting: Type-1 Enclosure Mounting
Installation: Fixed installation Category II
Over Voltage Category: II
Pollution Degree: II, office or workplace, none conductive pollution
Weight
:
EZM-4450 : 210 gr. ; EZM-4950 : 210 gr.
EZM-7750 : 250 gr. ; EZM-9950 : 340 gr.
:
:
: 0...50°C
: 0-90%RH ()
: IP65 at Front, IP20 at rear.
Z
Phase Shifting
Z
2
Dimensions:
EZM-4450 : (48 x 48mm,Depth:116 mm)
EZM-4950 : (96 x 48mm,Depth:86.5 mm)
EZM-7750 : (72 x72mm, Depth:87.5 mm)
EZM-9950 : (96 x 96mm,Depth:87.5 mm)
DIP SWITCH Adjustment
Function Selection
Counter / Totalizer Counter
Batch Counter
Timer
Frequencymeter / Tachometer
Chronometer
Input Type Selection
NPN
PNP
Electrical Wirings
Sensor
Supply
Max.50mA
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Output
Module-2
Relay, SSR or
Digital
(Transistor)
Panel Cut-Out:
EZM-4450 : (46 x 46mm)
EZM-4950 : (92 x 46mm)
EZM-7750 : (69 x 69mm)
EZM-9950 : (92 x 92mm)
Fuse
Note-1
a
External
(-)
(+)
Note-3
Communication
Module
RS-232(Standard)/
RS-485 (Optional)
Supply
Switch
Fuse
Note-2
3
Sensor
Supply
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Sensor
Supply
Max.50mA
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Sensor
Supply
Max.50mA
Output
Module-1
Relay, SSR or
Digital
(Transistor)
Max.50mA
Output
Module-2
Relay, SSR or
Digital
(Transistor)
Output
Module-2
Relay, SSR or
Digital
(Transistor)
Output
Module-2
Relay, SSR or
Digital
(Transistor)
a
(-) (+)
Note-3
a
(-) (+)
Note-3
Communication
Module
RS-232(Standard)/
RS-485 (Optional)
Fuse
Note-1
a
(-) (+)
Note-3
External
Fuse
Note-2
Fuse
Fuse
Note-1
Communication
Module
RS-232(Standard)/
RS-485 (Optional)
Note-1
External
Fuse
Note-2
Supply
Switch
Communication
Module
RS-232(Standard)/
RS-485 (Optional)
Supply
External
Switch
Fuse
Note-2
Supply
Switch
Note-1 :There is an internal fusible flameproof resistor.
Note-2 : External fuse is recommended.
100...
1AVT for power supply 240 VV or 24VV
1AZT for power supply 24V Z Note-3 : “L” is ( + ) ,” N” is ( - ) for 24V Z supply voltage
4
DIMENSIONS
EZM-4450
O1
O2
S1
S2
Timer & Counter
TOTALPRESET
SET1 SET2
48 mm / 1.89 inch
Timer & Counter
S1
O1
S2
O2
SET2
SET1
P
96 mm / 3.78 inch
S1
O1
S2
O2
48 mm / 1.89 inch
11.5±1mm/0.45 inch
EZM-4950
TOTAL
RESET
EZM-7750
Maximum 5 mm / 0.2 inch
104.5mm / 4.11 inch
Maximum 15 mm / 0.59 inch
48 mm / 1.89 inch
10.5±1mm/0.41 inch
Maximum 15 mm / 0.59 inch
76mm / 2.99 inch
RESET
P
SET1SET2
Timer & Counter
72 mm / 2.83 inch
S1S1
O1O1
S2S2
O2O2
RESET
P
SET1
Timer & Counter
EZM-9950EZM-9950
96 mm / 3.78 inch
TOTAL
TOTAL
SET2
72 mm / 2.83 inch
11.5±1mm/0.45 inch
Maximum 15 mm / 0.59 inch
96 mm / 3.78 inch
11.5±1mm/0.45 inch
76mm / 2.99 inch
76mm / 2.99 inch
5
PANEL MOUNTING
2
4
4
1-
Before mounting the
device in your panel,
1
makesure that the panel
cut-out is suitable.
2-
Check front panel gasket
Position.
3-
Insert the device through
the cut-out. If the mounting
3
clamp are on the unit, put
out them before inserting
the unit to the panel.
4-5-Insert the unit in the panel
cut-out from the front side.
Insert the mounting
clamps to the holes that
5
5
located top and bottom
sides of device and screw
up the fixing screws until
the u ni t co m pl et e ly
immobile within the panel.
6
Accessing to the Program Parameters
Main Operation
Screen
TOTAL
RESET
SET1
SET2
When PROG button is
pressed for 3 seconds,
password must be
entered for accesing to
the parameters.
Password Screen
TOTAL
RESET
SET1
SET2
The most significant digit of
the parameter(4th digit for
this parameter flashes.)
Password Screen
TOTAL
RESET
SET1
SET2
After
entered the
password,
press Enter
button.
Input Types and
Functions
TOTAL
RESET
SET1
SET2
You can change
the parameter with
INCREMENT
button, save it to
the memory and
pass to the next
parameter with
ENTER button.
Main Operation
SET1
Press PROG
button to exit from
programming
selection without
doing any
changes.
Pulse Time for Ch-A,Ch-B
Reset and Pause Inputs
(1)
Screen
TOTAL
RESET
SET2
TOTAL
RESET
SET1
SET2
You can change
the parameter with
INCREMENT
button, save it to
the memory and
pass to the next
parameter with
ENTER button.
Program Password
TOTAL
SET1
SET2
You can change
the parameter with
INCREMENT
button, save it to
RESET
the memory and
pass to the next
parameter with
ENTER button.
Input Types and
Functions
TOTAL
SET1
SET2
Continue to press
ENTER button for
scanning all
parameters.
Multiplication
Coefficient
TOTAL
RESET
SET1
SET2
You can change
the parameter with
INCREMENT
button, save it to
the memory and
pass to the next
parameter with
ENTER button.
RESET
(1)
7
Parameter Definitions
:Input Types and Functions
Upcount on rising edge of Ch-A input
0 :. (INC)
count on rising edge of Ch-A input
1 : Down. (DEC)
Upcount on rising edge of Ch-A inputcount on rising edge of Ch-B input
2 : ,Down.(INC/DEC)
Upcount on rising edge of Ch-A input,Upcount on rising edge of
Upcount on rising edge of Ch-A input when Ch-B is at 0 Downcount on rising edge of Ch-A
Phase Shifting
Phase Shifting
Phase Shifting
.(UP/DOWN)
: Selection of Input Type Function for Chronometer
0 : Period measurement in Ch-A input
Pulse time measurement in Ch-A input
1 :.
Sum of the time difference between Ch-A and Ch-B inputs rising edges
2 :.
.
: Selection of Measuring Method
0 : Frequency or cycle is calculated by measuring cycle time of the signals in Ch-A input
1 :
Frequency or cycle is calculated by counting the pulses in Ch-A input during the time
is set in measurement period.
.
: Pulse Time of Ch-A, Ch-B, Reset and Pause Input
It is used to protect against the electrical contact debounce or the signal that is less than
the determined pulse time.
It can be adjusted from to millisecond.
: Selection of Time Unit and Scale
Hour / Minute It can be adjusted from .0 to 99.59.
MinuteIt can be adjusted from / Second .0 to 99.59.
Second / milisecond.0 to 99.99.It can be adjusted from
Hour / Minute It can be adjusted from .0 to 23.59.
Hour.0 to 999.99.It can be adjusted from
Minute.0 to 999.99.It can be adjusted from
Second.0 to 999.99.It can be adjusted from
: Output Functions
0:
Manual Reset-1:
Device continues to count till manual reset
is applied. When count value reaches the
Set value, output position is changed.
Out-1
Out-1
Out-2
Reset
Set2
Set1
0
=
=
=
=
8
1:
Manual Reset-2:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
2:
Manual Reset-3:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
3:
Automatic Reset-1:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
4:
Automatic Reset-2:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
Out-1
Out-1
Out-2
Out-1
Out-2
Out-1
Out-1
Out-2
Out-1
Out-1
Out-2
Out-1
Out-2
Reset
Reset
Set2
Set1
Reset
Out-1
Out-1
Out-2
Reset
Set2
Set1
0
Set2
Set1
0
0
Set2
Set1
0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
5:
Automatic Reset-3:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
Out-1
Out-1
Out-2
Reset
Set2
Set1
0
=
=
=
9
6:
Automatic Reset-4:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
Out-1
Out-1
Out-2
Reset
Set2
Set1
0
=
=
=
Out-1
Out-2
Reset
Set2
Set1
0
7:
Automatic Reset-5:
Count value is added to total value
when manual reset is active in
COUNTER/TOTALIZER COUNTER
functions.
: Input Signal Reset Time (Time Out)
Actual count value is reset if no signal is applied to Ch-A input for a time which is
bigger thanthe valueis set in this parameter.
It can be adjusted from to seconds.
: Measurement Period
Number of pulses in Ch-A input is counted during this time.
It can be adjusted from to seconds .
: Output-1 Function
Output is latched
0 : . (Latching).
Non-latched with hysteresis output is selected.
1 :
Output-1 is an alarm output.
2 :
: Output-2 Function
0 : . (Latching).
Output is latched
1 :
Non-latched with hysteresis output is selected.
: Alarm Functions for Output-1
If Output-1 function parameter is selected alarm output, then
Output-1 becomes active according tothis parameter.
High Alarm
Output-1
ON
OFF
Set1Set1-Hys1
Count Value
=
=
=
=
10
Low Alarm
-1Output
ON
OFF
Set1Set1+Hys1
Count Value
Deviation High Alarm
-1Output
ON
OFF
Set2
Deviation Low Alarm
-1Output
ON
OFF
Deviation Band Alarm
-1Output
ON
OFF
- Hys1
: Hysteresis for Output-1
- Hys1
Set2-Set1
Set2-Set1
Set1+Set2
Set1+Set2
Set2
+ Hys1
Count Value
Set2
Count Value
+ Hys1
Count Value
: Hysteresis for Output-2
: Output-1 Operation Form
Between second and third digits.
Between third and fourth digits.
Between fourth and fifth digits.
: Saving Count Value
Count value is saved to memory when power is disconnected and restored on
power up.
Count value is not saved to memory when power is disconnected.
: SET1 Operation Form Selection
Absolute operation.SET1 can be adjusted from to .
Operation with offset. SET1 can be defined ± Offset
according to SET2 value.( SET1 = SET1 + SET2 )
: Communication Accessing Address
Device address for serial communication bus.
to .
It can be adjusted from
: Modbus Protocol Type Selection
Modbus ASCII protocol is selected.
Modbus RTU protocol is selected.
: Communication Parity Selection
No Parity .
Odd Parity.
Even Parity.
12
: Communication Baud Rate
1200 Baud Rate
2400 Baud Rate
4800 Baud Rate
9600 Baud Rate
19200 Baud Rate
:Communication Stop Bit Selection
1 Stop Bit.
2 Stop Bits.
:Reset and Set Protection (For Accessing from Front Panel)
No Reset and Set protection.
Only Reset button protection is active.
SET1 and SET2 can not be changed.
Full Protection. Reset protection is active, also SET1
and SET2 can not be changed.
SET1 can not be changed.
SET2 can not be changed.
: Frequency / Cycle Coefficient
It can be adjusted from to .Count value is multiplied with this
parameter.
: Multiplication Coefficient
It can be adjusted from to .
: Program Password
It is used for accessing to the program parameters.
It can be adjusted from to .
If it is ; there is no password protection while
entering to the program parameters.
When programming button is pressed, will appear on the display.
If this parameter is different from “ 0” and user wants to access to the
program parameters;
1-
If user does not enter the value correctly ; operation screen will appear
without entering to operator parameters.
2-
When in top display and in bottom display,if user presses ENTER
button without entering password (for observing the parameters):
13
Failure Messages in EZM-XX50 Timer & Counter
Position of the DIP Switch is wrong. (DIP Switch
1-
S2
SET1
2- If the password is not 0, user can access to the parameters
without entering the password and by pressing ENTER button.
determines the operation function of the device
and it is under the top cover.)
TOTAL
RESET
SET2
Main Operation
Screen
S2
SET1
SET2
W hen PRO G
button is pressed,
password entering
screen will appear.
Main Operation
Screen
S2
SET1
SET2
O1
O2
S1
S2
TOTAL
SET1
SET2
O1
O2
S1
S2
TOTAL
SET1
SET2
RESET
RESET
Input Types and
Functions
SET1
SET2
By pressing ENTER
button, user can
see all parameters
except for program
password.
TOTAL
RESET
Press PROG
button to exit
from
programming
mode.
Password Screen
TOTAL
RESET
TOTAL
RESET
3- If Actual Value is flashing and counting is stopped;
It appears if any of the count value is bigger than
the maximum count value.(Total count value for
RESET
Counter/”Totalizer Counter”
Function - Batch count value for Batch Counter
FUNCTION )
To remove this warning and reset the count value
press RESET button.
4- If actual value is flashing and counting is not
performed;
It appears if any of the count value is less than the
RESET
minimum count value.
(Total count value for Counter/“Totalizer Counter”
Function - Batch count value for Batch Counter
FUNCTION )To remove this warning and reset the
count value press RESET button.
SET1
SET2
Press ENTER
Button without
entering the
password.
Input Types and
Functions
TOTAL
SET1
SET2
TOTAL
Multiplication
Coefficient
TOTAL
SET1
SET2
Continue to
Press ENTER
button for
scanning the
parameters.
RESET
14
Installation
Before beginning installation of this product, please read the
c
In package ,
-One piece unit
-Two pieces mounting clamp
-One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off
the system and the electrical connection of the device from the system.
The unit is normally supplied without a power switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres. During the
equipment is putted in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s mounting clamp. Do not do the
montage of the device with in appropriate mounting clamp. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material
and workmanship. This warranty is provided for a period of two years. The warranty
period starts from the delivery date.
This warranty is in force if duty and responsibilities which are determined in warranty
document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
instruction manual and warnings below carefully.
Garanti
Warranty
Maintenance
15
Diğer Bilgiler
Other Informations
Manufacturer Information
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and maintenance service information
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
:
:
Order Information
Supply Voltage
Customer Maximum
Serial Communication Module Codes
None
Output-1
None
Module-1
None
Relay Output Module
SSR Driver Output Module
(Maximum 26mA, 22VZ)
Digital(Transistor)Output Module
(Maximum 40mA@18VZ)
Module-2
None
Relay Output Module
SSR Driver Output Module
(Maximum 26mA, 22VZ)
Digital(Transistor)Output Module
(Maximum 40mA@18VZ)
Module Codes
Module Codes
16
Note-1 :
EMO-4xx is used in EZM-4450 and EZM-4950
EMO-7xx is used in EZM-7750
EMO-9xx is used in EZM-9950
Note-2 :
EMO-400 Relay Output Module’s rating is 3A@250V on resistive load.
EMO-700 and EMO-900 is 3A@250V on resistive load.
All order information of EZM-xx50 series are given on the table at
above.User may form appropriate device configuration from
information and codes that at the table and convert it to the ordering
codes.
Firstly, supply voltage then other specifications must be determined.
Please fill the order code blanks according to your needs.
Please contact us, if your needs are out of the standards.
This symbol is used for safety warnings. User must pay
attention to these warnings.
c
This symbol is used to determine the dangerous
situations as a result of an electric shock. User must
pay attention to these warnings definitely.
a
This symbol is used to determine the important notes
about functions and usage of the device
i
17
Your Technology Partner
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
www.emkoelektronik.com.tr
1818
EZM-4450,EZM-4950,EZM-7750,EZM-9950
P
rogrammierbare Timer & Zähler
EZM-4450,EZM-4950,EZM-7750,EZM-9950
Timer & Zähler mit Universaleingang und programmierbarem
Ausgangs-Modulsystem
- Anzeige für 6-stelligem Zählwert (PV) und 6-stelligem
Vorwahlwert (SV)
- 2 Vorwahlwerte - Rücksetz-, Pause- und ChA-ChB Zähleingang
EZM-4450: 210 g
EZM-4950: 210 g
EZM-7750: 250 g
EZM-9950: 340 g
Abmessungen:
EZM-4450: (48 x 48 mm, Tiefe: 116 mm)
EZM-4950: (96 x 48 mm, Tiefe: 86.5 mm)
EZM-7750: (72 x 48 mm, Tiefe: 87.5 mm)
EZM-9950: (96 x 48 mm, Tiefe: 87.5 mm)
Schalttafelausschnitte:
EZM-4450: (46 x 46 mm)
EZM-4950: (92 x 46 mm)
EZM-7750: (69 x69 mm)
EZM-9950: (92 x 92mm)
2
DIP-Schaler Funktionswahl
Funktionswahl des Gerätes
Zähler / Gesamtzähler
Chargen-Zähler
Timer
Frequenzmesser / Tachometer
Chronometer
Eingangswahl
NPN
PNP
Elektrische Anschlüsse
Hilfsausgang
Ausgang-1Ausgang-1
Hilfsausgang
Ausgang-2
Schnittstelle
Sicherung
Modbus
Versorgungsspannung
Ausgang-
1
Ausgang-2
Modbus
Schnittstelle
Sicherung
Versorgungsspannung
3