J Type thermocouple Input or,
K Type thermocouple Input or,
2-Wire PT-100 Input or,
2-Wire PT-1000 Input
ON/OFF temperature control
-
2 output for compressor and alarm controls
-
- Selectable heating or cooling function
- Selection of operation with hysteresis
- Adjustable temperature offset
- Process Set value and Alarm Set value low limit and set value
high limit boundaries
- Operation selection of compressor operates continuously,
stops or operates periodically in case of sensor defect
- Compressor protection delays
- Alarm parameters
- Adjustable Alarm Set Value from front panel
Adjustable internal buzzer according to Sensor prob defect and
-
Alarm status
- Password protection for programming section
- Installing parameters using Prokey
- Remote access, data collecting and controlling with Modbus RTU
- Having CE mark according to European Norms
(Must be determined in order.)
ESM-3712-HCN 77x35 DIN Size Temperature Controller
Instruction Manual. ENG ESM-3712-HCN 01 V03 10/19
ENGLISH
1.Preface
ESM-3712HCN series temperature controllers are designed for measuring and controlling
temperature. They can be used in many applications with their On / Off control form, heating
and cooling control form and easy-use properties. Some application fields which they are
used are below:
Application FieldsApplications
Glass Heating
Food Baking Ovens
PlasticIncubators
Petro-Chemistry Storages
Textile, Automative Air Conditioning
Machine Production Industries Etc... Etc...
1.1 Environmental Ratings
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Forbidden Conditions:
Corrosive atmosphere
c
Explosive atmosphere
Home applications (The unit is only for industrial applications)
1.2 General Specifications
Standard
230V ( %15) 50/60HzV ±
Optional Supply Voltage
V
115 V (±%15) 50/60Hz,
V
24 V (±%15) 50/60Hz,
W
24 V (±%15) 50/60Hz,
10
- 30 V Z
NTC, PTC,
J or K Type TC
2-Wire PT-100
2-Wire PT-1000
ESM-3712-HCN
Power Supply
Input
Temperature Sensor
Input
Compressor Output
Alarm Output
Heating or Cooling
Function
ON/OFF Operation
Alarm Control Output
ON/OFF Operation
2
1.3 Installation
A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the
system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent
failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the
unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage
of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
1.4 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts
from the delivery date. This warranty is in force if duty and responsibilities which are determined
in warranty document and instruction manual performs by the customer completely.
1.5 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in
ethyl alcohol or water to clean the external plastic case.
1.6 Manufacturer Company
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA /TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
3
2. General Description
Front Panel
IP65 protection
NEMA 4X
Panel Surface
(maximum thickness 15 mm / 0.59 inch)
Mounting Clamp
2.1 Front View and Dimensions of ESM-3712-HCN Temperature Controller
Maximum 15 mm / 0.59 inch
34,5 mm / 1.36 inch
76 mm / 3 inch
6 mm / 0.24 inch
65 mm / 2.56 inch
2.2 Panel Cut-Out
110 mm / 4.33 inch (min)
50 mm / 1.97 inch (min)
29 mm / 1.14 inch
71 mm / 2.79 inch
4
2.3 Panel Mounting
1
3
2
1-Before mounting the device in your panel,
make sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the
mounting clamps are on the unit, put out them
before inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets
that located left and right sides of device and make
the unit completely immobile within the panel
3
2.4 Removing from the Panel
1-Pull mounting clamps from left and right fixing
sockets.
2-Pull the unit through the front side of the panel
1
2
Before starting to remove the unit from
panel, power off the unit and the related
system.
c
3. Using Prokey
TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE ‘0’.
IF PrC=1 AND BUTTON IS PRESSED MESSAGE WILL BE SHOWN. 10s. LATER
DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET
BUTTON TO TURN BACK TO MAIN OPERATION SCREEN.
DOWNLOADING FROM DEVICE TO PROKEY
1.The device is programmed by using the parameters.
2.Energize the device then put in PROKEY and press button. Message is shown on the
display. When the loading has finished, message is shown.
3.Press any button to turn back to main operation screen.
4.Remove the PROKEY.
NOTE: message is shown when an error occurs while programming. If you want to reload, put
in PROKEY and press button. If you want to quit, remove PROKEY and press button. The
device will turn back to main operation screen.
DOWNLOADING FROM PROKEY TO DEVICE
1.Switch off the device.
2.Put in PROKEY then energize the device.
3.When the device is energized, the parameter values in PROKEY, start downloading to the device
automatically. At first, message is shown on the display, when loading has finished,
message is shown.
4.After 10 seconds device starts to operate with new parameter values.
5.Remove the PROKEY.
NOTE: message is shown when an error occurs while programming. If you want to reload,
switch off the device and put in PROKEY then energize the device. If you want to quit remove
PROKEY and press button. The device will turn back to main operation screen.
5
4. Electrical Wiring Diagram
a
4.1 Supply Voltage Input Connection of the Device
Power Supply Connection
L
N
a
(+)(-)
7
8
EXTERNAL
FUSE
(1A T)
Note-1
Supply
Switch
c
Supply Voltage
V ±
230V ( %15) 50/60Hz ,
V ±
115V ( %15) 50/60Hz,
V ±
24V ( %15) 50/60Hz ,
W ±
24V ( %15) 50/60Hz ,
10..30 V - 1.5 W
Z
Must be determined in order.
Note-1 : External fuse is recommended.
Make sure that the power supply voltage is the same
indicated on the instrument.
c
Switch on the power supply only after that all the electrical
connections have been completed.
Supply voltage range must be determined in order. While
installing the unit, supply voltage range must be controlled
and appropriate supply voltage must be applied to the unit.
There is no power supply switch on the device. So a power
supply switch must be added to the supply voltage input.
c
Power switch must be two poled for seperating phase and
neutral, On/Off condition of power supply switch is very
important in electrical connection.
External fuse that on Vpower supply inputs must be on
phase connection.
External fuse that on Zpower supply inputs must be on (+)
connection.
4.2 Device Label and Connection Diagram
230VV CONNECTION DIAGRAM
16(8)A@250VV
16(8)A@250VV
1HP COMP.
5A@250VV
ALARM
230VV
1HP COMP.
Temperature Sensor
TC, NTC, PTC, PT-100
or PT-1000
Supply Voltage Input
V ±
230V ( %15) 50/60Hz
V ±
115V ( %15) 50/60Hz
V ±
24V ( %15) 50/60Hz
W ±
24V ( %15) 50/60Hz
10...30 V
Z
Must be determined in order.
Process and Alarm
Relay Outputs
5A@250VV
230VV
ALARM
Input
INPUT SCALE
(-50°C, 150°C; -58°F,302°F)
16A T Fuse
5A T Fuse
230VV
6
5.Front Panel Definition and Accessing to the Menus
5
8
11
96710
12
1
2
BUTTON DEFINITIONS
1. Increment Button :
** It is used to increase the value in the Set screen and Programming mode.
**In the main operation screen: After pressing this button for 5 seconds, alarm output will be
Active manually during pressing button. Alarm output will be passive after release the button.
2. Decrement, Silencing Buzzer and Downloading to Prokey Button :
** It is used to decrease the value in the Set screen and Programming mode.
** It is used to silence the buzzer.
** If Prc =0, it is used to download from device to prokey.
3. Set Button :
** In the main operation screen; if this button pressed, set value will be displayed. Value can be
changed using increment and decrement buttons. When Set button pressed again, value is
saved and returns back to main operating screen.
** To access the programming screen; in the main operation screen, press this button for 5
seconds.
** It is used to saving value in the Set screen and programming screen.
4. Alarm Set Button :
** In the main operation screen; if this button is pressed, Alarm set value will be displayed. Value
can be changed using increment and decrement buttons. When Set button is pressed again,
value is saved and returns back to main operating screen.
LED DEFINITIONS
5. Cooling led :
** This led indicates that cooling control is selected and process output relay is active. If any of
compressor protection time active, this led blinks.
6.Heating led :
** This led indicates that heating control is selected and process output relay is active.
7.Alarm led :
** It is active in all alarm status.
8.Celcius led :
** Indicates that device is in C mode.
9.Fahrenheit led :
** Indicates that device is in F mode.
10.Alarm Set led :
** It is active when alarm statuses.
11.Set led :
** Indicates that device is in Set value changing mode.
12.Program led :
**Blinks in programming mode .
o
o
4
3
7
6. Changing and Saving Temperature Set Value
Main Operation Screen
O
O
S
P
C
F
A
S
ü
When SET button pressed ‘’S’’ led will
be active and temperature set value will
be displayed.
SET Value Screen
O
O
S
P
C
F
A
S
ü
When SET button pressed
temperature set value can be saved.
Temperature set value parameter (Default=30) MODBUS ADDRESS:40001
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
SET Value Screen
O
O
S
P
C
F
Temperature set value can
be changed with increment
and decrement buttons.
Main Operation Screen
O
O
S
P
C
F
‘’S’’ will be inactive and goes back to
main operation screen.
6.1 Changing and Saving Alarm Set Value
Alarm Set ScreenMain Operation Screen
O
O
SA
P
C
F
O
O
SA
P
C
F
When ALARM SET button pressed ‘’A’’
led will be active and temperature set
value will be displayed.
Alarm set value can be
changed with increment and
decrement buttons.
Main Operation ScreenAlarm Set Screen
O
O
O
SA
P
C
F
A
S
ü
When SET button pressed
Alarm set value can be
saved.
If no operation is performed in Alarm set value changing mode and process set value changing
i
mode for 20 seconds, device turns to main operation screen automatically.
’A’ will be inactive and goes back to
O
C
F
Alarm set Value saved,
main operation screen.
S
P
8
6.2 Programming Mode Parameter List
Temperature Unit Selection Parameter ( Default = 0 ) MODBUS ADDRESS : 40002
Hysteresis Parameter for Compressor Output (Default = 1)
MODBUS ADDRESS:40004
From 1 to 20°C for NTC (-50°C, 100°C), PTC (-50°C, 150°C), J Type TC ( 0°C, 800°C ),
K Type TC ( 0°C, 1000°C), PT-100 Type ( -50°C,400°C ), PT-1000 Type ( -50°C,400°C )
PT-100 Type ( -20°C,100°C ),
From 1 to 36°F for NTC (-58°F, 212°F),PTC (-58°F, 302°F), J Type TC (32°F,1472°F)
K Type TC (32°F,1830°F), PT-100 Type (-58°F,752°F),PT-1000 Type (-58°F,752°F),
PT-100 Type (-4°F,212°F)
From 0.1 to 10.0°C for NTC (-50.0°C,100.0°C), PTC (-50.0°C,150.0°C),
PT-100 (-19.9°C,99.9°C),
From 0.1 to 18.0°F for NTC (-58.0°F,212.0°F), PTC (-58.0°F,302.0°F),
PT-100 (-4.0°F,212.0°F),
In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, tem perature
value oscillates continuously. Temperature
value’s oscillation period or amplitude around
set value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is formed
below or around set value and this zone is
named hysteresis.
Minimum Temperature Set Value Parameter (Default = Minimum Value of Device
Scale ) MODBUS ADDRESS:40005
Temperature set value can not be lower than this value.
This parameter value can be adjusted from minimum value of device scale to maximum
temperature set value parameter
Maximum Temperature Set Value Parameter (Default = Maximum Value of Device
Scale )MODBUS ADDRESS:40006
Temperature set value can not be bigger than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale
From -20 to 20 °C for NTC (-50°C, 100°C), PTC (-50°C, 150°C), J Type TC (0°C,800°C),
KType TC (0°C,1000°C), PT-100 (-50°C, 400°C), PT-1000 (-50°C, 150°C),
PT-100(-20°C, 100°C),
From -36 to 36 °F for NTC (-58°F, 212°F), PTC (-58°F, 302°F), J Type TC (32°F,1472°F),
K Type TC (32°F,1830°F), PT-100 (-58°F, 752°F), PT-1000 (-58°F, 752°F), PT-100 (-4°F, 212°F)
From -10.0 to 10.0°C for NTC (-50.0°C,100.0°C), PTC (-50.0°C,150.0°C),
PT-100 (-19.9°C,99.9°C)
From -18.0 to 18.0°F for NTC (-58.0°F,212.0°F), PTC(-58.0°F,302.0°F),
PT-100 (-4.0°F, 212.0°F)
Operating Type Parameter ( Default = 0) MODBUS ADDRESS:40008
If parameter value is ‘0’ device skips to parameter
Heating
Cooling
Compressor Start Delay at Power On Parameter ( Default = 0)
MODBUS ADDRESS:40009
When power is first applied to the device, compressor is on when this time delay is expired.
It can be adjusted from 0 to 20 minutes.
Alarm Set Value Low Limit Parameter ( Default = Minimum Value of Device Scale)
MODBUS ADDRESS:40016
Alarm set value can not be lower than this value.This parameter value can be adjusted
from minimum process set value parameter to alarm set value high limit parameter
value.
Alarm Set Value High Limit Parameter ( Default = Maximum Value of Device Scale)
MODBUS ADDRESS:40017
Alarm set value can not be greather than this value.This parameter value can be
adjusted from alarm set value low limit parameter value to maximum process set value
parameter.
Alarm On Delay Time Parameter( Default = 0 ) MODBUS ADDRESS:40018
It can be adjusted from 0 to 999 minutes.
Alarm Off Delay Time Parameter( Default = 0 ) MODBUS ADDRESS:40019
It can be adjusted from 0 to 99 minutes.When this parameter is 99, if increment button is
pressed, is observed and alarm latching output is selected. To make the alarm latching
output passive,decrement button must be pressed in main operation screen.
Alarm Delay Parameter After Power On
This parameter defines the delay for the alarm is being active after power on.It can be
adjusted from 0 to 99 minutes.
Alarm Set Value Parameter ( Default = 20 ) MODBUS ADDRESS:40021
Alarm output is controlled according to this value.For alarm type selection paramater
=1 or 2,this parameter value is can be adjusted from alarm set value low limit
parameter to alarm set value high limit parameter,for alarm type selection parameter
=3,4,5 or 6 this parameter value is can be adjusted from 0 to alarm set value high limit
parameter.
Alarm Hysteresis Parameter
Alarm hysteresis value.
This parameter is can be adjusted 0 to %50 of the device scale.
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
Slave ID Parameter 26( Default = 1 ) MODBUS ADDRESS=400
Device communication address parameter (1 to 247).
Manual Alarm Output Active Parameters (Default=0) MODBUS ADDRESS=40027
Manual Alarm output passive
Manual Alarm output active
Programming Section Accessing Password 28
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is
selected 0, password will not be asked
, , , , and Parameters are observed if Operation type
i
is selected “Cooling”. If operation type is selected “Heating ” ,skip to the parameter.
( Default = ) MODBUS ADDRESS:40024
( Default = 0 ) MODBUS ADDRESS:400
.
6.3 Modbus Adresses of Device Status Parameters (Read Input Register)
MODBUS ADRES:30001 Temperature Value
MODBUS ADRES:30002 Led Status : 0.bit C Led,6.bit Compressor Led,
7.bit Alarm Led, 13.bit Program Led,
14.bit Set Led
MODBUS ADRES:30003 Device Status : 0.bit Alarm Status
A
2.bit Buzzer Status
3.bit Sensor Break Status
MODBUS ADRES:30004 Output Status 0.Bit Compressor Output,1.bit Alarm Output
MODBUS ADRES:30005 Device Type and Device Version
o
11
6.4 Operation Graphics of Alarm Output and Alarm Types
Power
Alarm
Status
Alarm
Output
Active
Led
Alarm
Output
°C
Time
Time
Time
Time
Power
Alarm
Status
Alarm
Output
Active
Alarm
Output
6.4 Operation Graphics of Alarm Output and Alarm Types
Process High Alarm
Alarm
Output
ON
OFF
Deviation High Alarm
Alarm
Output
ON
OFF
= Alarm Set Value
i
( + )
= Process Set Value
Process
Value
Process
Value
Alarm
Output
( Alarm Latching Output is Selected )
=
°C
Led
Process Low Alarm
ON
OFF
Deviation Low Alarm
Alarm
Output
ON
OFF
( - )
Time
Time
Decrement
Button must
be pressed
to make alarm
output is
passive.
Time
Time
Process
Value
Process
Value
Deviation Band Alarm
Alarm
Output
ON
OFF
( - )
( + )
Deviation Range Alarm
Alarm
Output
ON
OFF
Process
Value
( - ) ( + )
Process
Value
12
6.5 Operation Graphics of ESM-3712-HCN ControllerTemperature
1-If Operating Type Parameter Value = 1 (Cooling),
Switch On Delay After Power On Parameter Value ³ 1 ,
Compressor Stop/Start Time Delay Parameter Value ³ 1 and
Compressor Start/Start Time Delay Parameter Value ³ 1;
Power
°C
SET
Output
Led
Output
2-If Operating Type Parameter Value = 0 (Heating),
i
Hst
Temperature
Value
SET
ON
OFF
to set value by opening or closing the last control element. ON/OFF controlled
system, temperature value oscillates continuously. Temperature value’s oscillation
period or amplitude around set value changes according to controlled system. For
reducing oscillation period of temperature value, a threshold zone is formed below or
around set value and this zone is named hysteresis. Action of control output is
described with figures above.
HSt
Temperature Control Output
HStHSt
In ON/OFF control algorithm, temperature value is tried to keep equal
Time
Time
Time
Time
Time
Time
6.6 Failure Messages in ESM-3712-HCN Temperature Controller
Screen BlinkingSensor failure . Sensor connection is wrong or there is no sensor
connection. If buzzer function selection parameter is 2, internal buzzer starts to
operate.
13
6.7 Entering To The Programming Mode, Changing and Saving Parameter
Main Operation Screen
O
O
S
P
C
F
A
S
ü
Password Entering Screen
O
O
S
C
F
P
A
S
ü
When SET button is pressed for 5
seconds, “PR” led starts to blink. If
programming mode entering
password is different from 0,
programming mode entering screen
will be observed.
Note1: If programming
mode accessing
password is 0,
Temperature Unit screen
is observed instead of
programming screen
Password Entering Screen
O
O
S
P
C
F
A
S
ü
Enter programming mode accessing
password with increment and
decrement buttons.
Note2: If programming mode accessing password is 0, only three parameters are accessible, and the
parameter values can be changed.
Programming Screen
O
O
S
P
C
F
A
S
ü
Press SET button for accessing to the
paramete r v alue. Press increment
button for accessing to the ne xt
parameter, press decrement button for
accessing to the previous parameter.
Hysteresis Value for
Compressor Output
O
O
S
P
C
F
A
S
ü
Press set button for saving the
parameter.
If no operation is performed in programming mode for 20 seconds, device turns to main
i
operation screen automatically..
Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter
Press SET button for
accessing to the
password entering
screen.
Password Entering Screen
O
O
S
P
C
F
A
S
ü
Press SET/OK button for
entering the password.
Hysteresis Value for
Compressor Output
O
O
S
P
C
F
A
S
ü
Change the value with increment
and decrement buttons.
Hysteresis Parameter for
Compressor Output
O
O
S
P
C
F
A
S
ü
14
7. Specifications
Device Type: Temperature Controller
Housing&Mounting: 76mm x 34.5mm x 71mm plastic housing for panel
Protection Class: NEMA 4X (Ip65 at front, Ip20 at rear).
Weight: Approximately 0.20 Kg.
Environmental Ratings: Standard, indoor at an altitude of less than 2000 meters
Storage / Operating Temperature : -40 C to +80 C / -30 C to +80 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
:10 - 30
Temperature Sensor Input : NTC, PTC, TC, RTD
NTC input type : NTC (10 kW @25 °C )
PTC input type : PTC (1000 W @25 °C )
Thermocouple input type : J, K (IEC584.1) (ITS 90)
Thermoresistance input type : PT-100, PT-1000 (IEC751) (ITS 90)
Accuracy : ± 1 % of full scale for thermoresistance
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Form : ON / OFF
Relay Outputs : 16(8) A@250 V V for Resistive load (Compressor output)
(Electrical life : 100.000 switching at full load)
: for Resistive load 5 A@250 V V (Alarm output)
Display : 14 mm Red 4 digits LED Display
LED : S (Green), P (Green), A(Green), C (Yellow), F(Yellow),
NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with 1.5 m cable
3
for cooling application)
NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with 1.5 m cable
4
for cooling application)
Customer
9
All order information of ESM-3712-HCN Temperature Controller are given on the table at above. User
may form appropriate device configuration from information and codes that at the table and convert it to
the ordering codes.Firstly, supply voltage then other specifications must be determined. Please fill the
order code blanks according to your needs.
Please contact us, if your needs are out of the standards.
Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0,3 or 4) must be declared in ordering information.
A BC D E FG HI /
020 0
-19.9°C/-4°F ; 99.9°C/212°F
-19.9°C/-4°F ; 99.9°C/212°F
U
V W Z/
00
/
/
Scale(°C)
0°C/32°F ; 800°C/1472°F
0°C/32°F ; 999°C/1830°F
-50°C/-58°F ; 400°C/752°F
-50°C/-58°F ; 400°C/752°F
-50°C/-58°F ; 150°C/302°F
-50°C/-58°F ; 100°C/212°F
Your Technology Partner
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
www.emkoelektronik.com.tr
16
ESM-3712-HCN Digitaler EIN/AUS-
Temperaturregler DIN-Größe
77 x 35 (ALARM+SET)
– 4-stelliges Display
– NTC-Eingang oder PTC-Eingang (muss in der Bestellung
angegeben werden.)
– Auswählbare Heiz- oder Kühlfunktion
– Auswahl des Betriebs mit Hysterese
– Einstellbarer Temperatur-Offset
– Prozesssollwert Unter- und Obergrenzen
– Auswahl des Kompressorbetriebs: durchgängiger Betrieb, Stopp
oder intermittierender Betrieb bei einem Sensordefekt
– Kompressorschutzverzögerungen
– Alarmparameter
– Von der Vorderseite aus einstellbarer Alarmsollwert
Einstellbarer interner Summer abhängig vom Sensordefekt-Statusund Alarmstatus
– Passwortschutz für den Programmierabschnitt
– Installationsparameter unter Verwendung von Prokey
– Fernzugriff, Datenerfassung und Regelung mit Modbus RTU
– Mit CE-Zeichen gemäß europäischen Normen
EIN/AUS-Temperaturregelung2 Ausgänge für Kompressor- undAlarmsteuerelemente
ESM-3712-HCN Temperaturregler DIN-Größe 77x35
Bedienungshandbuch. DE ESM-3712-HCN 01 V0310/19
DEUTCH
1. Vorwort
Temperaturregler der Baureihe ESM-3712-HCN sind auf die Temperaturmessung und regelung ausgelegt. Mit ihrer Ein/Aus-Regelungsfunktion, Heiz- und Kühlfunktionen und
benutzerfreundlichen Eigenschaften können sie in zahlreichen Anwendungen eingesetzt
werden. Nachfolgend sind einige Anwendungsbereiche aufgelistet, für die sie geeignet sind
Explosive Atmosphäre
Anwendungen im Wohnbereich (Das Gerät ist nur für industrielle
Anwendungen vorgesehen)
1.2 Allgemeine Spezifikationen
Standard
230V ( %15) 50/60HzV ±
Optionale
Versorgungsspannung
115 V (±%15) 50/60Hz,
V
24 V (±%15) 50/60Hz,
V
W
24 V (±%15) 50/60Hz,
- 30 V Z
10
NTC, PTC,
J oder K Typ TC
2-Wire PT-100
2-Wire PT-1000
ESM-3712-HCN
Stromversorgung
Eingang
NTC-, PTCSensoreingang
Kompressorausgang
Alarm Output
Heiz- oder Kühlfunktion
EIN/AUS-Betrieb
Alarmsteuerausgang
EIN/AUS-Betrieb
2
1.3 Installation
Vor der Installation dieses Produkts wird eine Sichtprüfung auf etwaige beim Transport
verursachte Schäden empfohlen. Sie müssen sicherstellen, dass dieses Produkt von
qualifizierten Elektrikern und Mechanikern installiert wird.
Falls bei einem Ausfall oder Defekt dieser Einheit die Gefahr eines ernsthaften Unfalls
besteht, schalten Sie das System aus und trennen den Stromanschluss des Geräts vom
System. Die Einheit wird normalerweise ohne Netzschalter und Sicherung ausgeliefert.
Verwenden Sie bei Bedarf einen Netzschalter und eine Sicherung.
Achten Sie darauf, die Auslegungsspannung für die Stromversorgung zu verwenden, um
das Gerät vor Schäden zu schützen und Ausfälle zu vermeiden.
Schalten Sie den Strom erst ein, wenn die gesamte Verdrahtung abgeschlossen ist, sodass
ein Stromschlag und Probleme mit dem Gerät vermieden werden können.
Versuchen Sie auf keinen Fall, dieses Gerät zu zerlegen, zu ändern oder zu reparieren. Eine
Manipulation des Geräts führt zu Fehlfunktion, Stromschlag oder Brand.
Setzen Sie das Gerät nicht in feuergefährlichen oder explosiven gasförmigen Atmosphären
ein.
Wenn Sie die Ausrüstung bei der mechanischen Installation in die Öffnung in der
Metallplatte einsetzen, können Metallgrate Verletzungen an den Händen verursachen. Sie
müssen vorsichtig sein.
Die Montage des Produkts an einem System muss unter Verwendung der zugehörigen
Befestigungsklammern erfolgen. Führen Sie die Montage des Geräts nicht mit ungeeigneten
Befestigungsklammern durch. Achten Sie darauf, dass das Gerät während der Montage
nicht zu Boden fällt.
Sie sind dafür verantwortlich, dass dieses Gerät nicht auf eine Weise verwendet wird, die
nicht in diesem Anweisungshandbuch angegeben ist.
1.4 Garantie
EMKO Elektronik garantiert, dass die Ausrüstung frei von Material- und
Herstellungsschäden ist. Diese Garantie gilt für einen Zeitraum von zwei Jahren. Der
Garantiezeitraum beginnt mit dem Lieferdatum. Diese Garantie gilt, solange der Kunde alle
im Garantiedokument und im Betriebshandbuch angegebenen Verpflichtungen und
Verantwortlichkeiten einhält.
1.5 Wartung
Reparaturen dürfen ausschließlich von geschultem und spezialisiertem Personal
durchgeführt werden. Trennen Sie die Stromversorgung zu dem Gerät, bevor Sie auf interne
Bauteile zugreifen.
Reinigen Sie das Gehäuse nicht mit auf Kohlenwasserstoff basierenden Lösungsmitteln
(Benzin, Trichloräthylen usw.). Durch den Einsatz dieser Lösungsmittel kann die
mechanische Zuverlässigkeit des Geräts beeinträchtigt werden. Verwenden Sie ein mit
Ethylalkohol oder Wasser befeuchtetes Tuch, um das äußere Kunststoffgehäuse zu
reinigen.
1.6 Herstellerunternehmen
Herstellerinformationen
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Informationen zum Reparatur- und Wartungsservice:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
3
2. Allgemeine Beschreibung
Frontplatte
IP65 Schutz
NEMA 4X
Schaltschrankoberfläche
(max. Dicke 15 mm / 0,59")
Montageklammer
2.1 Vorderansicht und Abmessungen des Temperaturreglers ESM-3712-HCN
Maximum 15 mm / 0.59 inch
34,5 mm / 1.36 inch
76 mm / 3 inch
6 mm / 0.24 inch
65 mm / 2.56 inch
2.2 Einbauausschnitt
110 mm / 4.33 inch (min)
50 mm / 1.97 inch (min)
29 mm / 1.14 inch
71 mm / 2.79 inch
4
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.