Emko ESM-3711-CN User manual

ENGLISH
ESM-3711-CN 77 x 35 DIN Size
Digital , ON / OFF Cooling Controller
- 4 Digits Display
- NTC Input or PTC Input (Must be determined in order.)
- Adjustable temperature offset
- Set value boundaries
- Operation selection of compressor operates continuously, stops or operates periodically in case of sensor defect
- Defrost time easily changeable from front panel
- Manual defrost capability from front panel
- Defrost parameters
- Alarm parameters
- Adjustable internal buzzer according to the defrost, sensor defect and alarm status
- Defrost time and/or manual defrost and/or temperature set value protection
- Password protection for programming section
- Installing parameters using Prokey
- Remote access, data collecting and controlling with Modbus RTU
- Having CE mark according to European Norms
ESM-3711-CN 77x35 DIN Size Cooling Controller
Instruction Manual. ENG ESM-3711-CN 01 V05 07/14
1.Preface
ESM-3711-CN series cooling controllers are designed for controlling cooling process. They can be used in many applications with their easy-use, On / Off control form and defrost properties. Some application and application fields which they are used are below:
1.1 Environmental Ratings
Application Fields
Food Machine production industries etc...
Applications
Refrigerators Air Conditioning Storages Freezers etc...
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m. Forbidden Conditions: Corrosive atmosphere
c
Explosive atmosphere Home applications (The unit is only for industrial applications)
1.2 General Specifications
Standard
230V ( %15) 50/60HzV ±
Optional Supply Voltage
V
115 V (±%15) 50/60Hz,
V
24 V (±%15) 50/60Hz, 10
- 30 V Z
NTC, PTC
ESM-3711-CN
Power Supply Input
Sensor Input
Compressor Output
Cooling Function ON/OFF Operation
ENGLISH
2
1.3 Installation
A visual inspection of this product for possible damage occurred during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product. If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and separate the electrical connection of the device from the system. The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse as required. Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure. Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented. Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in malfunction, electric shock or fire. Do not use the unit in combustible or explosive gaseous atmospheres. During putting equipment in hole on the metal panel while mechanical installation some metal burrs can cause injury on hands, you must be careful. Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the montage. It is your responsibility if this equipment is used in a manner not specified in this instruction manual.
1.4 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.
1.5 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case.
1.6 Manufacturer Company
Manufacturer Company Name :
Emko Elektronik A.S .DOSAB Karanfil Sk.No:6 16369 BURSA/TURKEY Phone : +90 224 261 19 00 Fax : +90 224 261 19 12
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş. Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY Phone +90 224 261 1900 Fax +90 224 261 1912
ENGLISH
3
2. General Description
Front Panel IP65 protection NEMA 4X
Panel Surface (maximum thickness 15 mm / 0.59 inch)
Mounting Clamp
2.1 Front View and Dimensions of ESM-3711-CN Cooling Controller
O
C
ESM-3711CN
O
S
P
F
Maximum 15 mm / 0.59 inch
ü
34,5 mm / 1.36 inch
76 mm / 3 inch
2.2 Panel Cut-Out
29 mm / 1.14 inch
6 mm / 0.24 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
65 mm / 2.56 inch
ENGLISH
50 mm / 1.97 inch (min)
4
2.3 Panel Mounting
1
3
3
2
1-Before mounting the device in your panel, make sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the mounting clamps are on the unit, put out them before inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets that located left and right sides of device and make the unit completely immobile within the panel
2.4 Removing from the Panel
1-Pull mounting clamps from left and right fixing sockets.
2-Pull the unit through the front side of the panel
1
2
Before starting to remove the unit from panel, power off the unit and the related system.
c
3. Using Prokey
TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE ‘0’. IF PrC=1 AND BUTTON IS PRESSED MESSAGE WILL BE SHOWN. 10s. LATER DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET BUTTON TO TURN BACK TO MAIN OPERATION SCREEN.
DOWNLOADING FROM DEVICE TO PROKEY
1.The device is programmed by using the parameters.
2.Energize the device then put in PROKEY and press button. Message is shown on the display. When the loading has finished, message is shown.
3.Press any button to turn back to main operation screen.
4.Remove the PROKEY. NOTE: message is shown when an error occurs while programming. If you want to reload, put
in PROKEY and press button. If you want to quit, remove PROKEY and press button. The device will turn back to main operation screen.
DOWNLOADING FROM PROKEY TO DEVICE
1.Switch off the device.
2.Put in PROKEY then energize the device.
3.When the device is energized, the parameter values in PROKEY, start downloading to the device automatically. At first, message is shown on the display, when loading has finished, message is shown.
4.After 10 seconds device starts to operate with new parameter values.
5.Remove the PROKEY.
NOTE: message is shown when an error occurs while programming. If you want to reload, switch off the device and put in PROKEY then energize the device. If you want to quit remove PROKEY and press button. The device will turn back to main operation screen.
ENGLISH
5
4. Electrical Wiring Diagram
21 3 54 6 87 9 10
a
L N
V ± V ±
Z
Temperature Sensor
Input (NTC or PTC)
Relay Output
Supply Voltage Input
230V ( %15) 50/60Hz , 115V ( %15) 50/60Hz ,
10...30 V - 1.5 W
4.1 Supply Voltage Input Connection of the Device
Power Supply Connection
a
L
N
5
6
EXTERNAL
FUSE
(1A T)
Note-1
Supply Switch
c
Supply Voltage
V ±
230V ( %15) 50/60Hz ,
V ±
115V ( %15) 50/60Hz ,
10...30 V - 1.5 W
Z
Must be determined in order.
Note-1 : External fuse is recommended.
Make sure that the power supply voltage is the same indicated on the instrument.
c
Switch on the power supply only after that all the electrical connections have been completed. Supply voltage range must be determined in order. While installing the unit, supply voltage range must be controlled and appropriate supply voltage must be applied to the unit.
There is no power supply switch on the device. So a power supply switch must be added to the supply voltage input.
c
Power switch must be two poled for seperating phase and neutral, On/Off condition of power supply switch is very important in electrical connection.
External fuse that on Vpower supply inputs must be on phase connection. External fuse that on Zpower supply inputs must be on (+) connection.
4.2 Device Label and Connection Diagram
230VV CONNECTION DIAGRAM
16(8)A
@250VV1HP
16A T Sigorta
L N
Must be determined in order.
.
COMP
2341
a
5
6
N
L
230 VV ± 15% 50/60Hz - 1.5VA
ENGLISH
RS-485
or
7
8 9
PROKEY
10
NTC
6
5.Front Panel Definition and Accessing to the Menus
5 6 7 8
1
2
BUTTON DEFINITIONS
1. Increment Button :
** It is used to increase the value in the Set screen, Defrost screen and Programming mode.
2. Decrement, Silencing Buzzer and Downloading to Prokey Button :
** It is used to decrease the value in the Set screen, Defrost screen and Programming mode. ** It is used to silence the buzzer. ** If Prc =0, it is used to download from device to prokey.
3. Defrost Button :
** In the main operation screen; if this button pressed, defrost time value will be displayed. **In the main operation screen; if this button pressed for 3 seconds, manual defrost starts.
4. Set Button :
** In the main operation screen; if this button pressed, set value will be displayed. Value can be changed using increment and decrement buttons. When Set button pressed again, value is saved and returns back to main operating screen. ** To access the programming screen; in the main operation screen, press this button for 5 seconds. ** It is used to saving value in the Set screen, Defrost screen and programming screen.
LED DEFINITIONS
5. Compressor output led :
** This led indicates that compressor output is active. If any of compressor protection time active, this led blinks.
6.Defrost led :
** This led indicates that defrost output is active. ** Blinks once in a second while Defrost delay time. ** Blinks (5 Hz) while entering Defrost time value.
7.Alarm led :
** It is active when low alarm and high alarm statuses.
8.Celcius led :
** Indicates that device is in C mode.
9.Fahrenheit led :
** Indicates that device is in F mode.
10.Set led :
** Indicates that device is in Set value changing mode.
11.Program led :
**Blinks in programming mode .
o
o
10
11
9
O
O
C
F
ESM-3711CN
S
P
ü
3
4
ENGLISH
7
6. Changing and Saving Temperature Set Value
Main Operation Screen
O
ESM-3711CN
O
S
P
C
F
SET Value Screen
O
O
C
F
ESM-3711CN
S
P
ü
When SET button pressed ‘’S’’ led will
be active and temperature set value will
be displayed.
O
O
C
F
ESM-3711CN
S
P
Temperature set value can be changed with increment
and decrement buttons.
Main Operation Screen
O
C
ü
When SET button pressed
temperature set value can be saved.
Temperature set value parameter (Default=50) MODBUS ADDRESS:40001
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
‘’S’’ will be inactive and goes back to
main operation screen.
ü
ESM-3711CN
O
S
P
F
ü
6.1 Changing and Saving Defrost Time Set Value
Main Operating Screen
O
ESM-3711CN
O
S
P
C
F
ü
When defrost button is pressed, defrost
time set value is shown and defrost output led starts to fast blink (5 Hz).
Defrost Time Value Screen
O
ESM-3711CN
O
S
P
C
F
ü
Press set button for saving the defrost
time set value
Defrost Time Value Screen
O
ESM-3711CN
O
S
P
C
F
ü
Change the defrost time set
value with increment and
decrement buttons.
Main Operating Screen
O
ESM-3711CN
O
S
P
C
F
ü
Defrost time set value is saved, defrost
output led stop the fast blink (5 Hz), main
operation screen is shown.
ENGLISH
If no operation is performed in defrost time set value changing mode and temperature set
i
value changing mode for 20 seconds, device turns to main operation screen automatically.
8
6.2 Programming Mode Parameter List
Temperature Unit Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40002
°C selected. °F selected.
Decimal Seperator Enabling Parameter ( Default = 0 ) MODBUS ADDRESS:40003
Disable. Enable.
Hysteresis Parameter for Compressor Output ( Default = 1 ) MODBUS ADDRESS:40004
from 1 to 20°C for NTC (-50°C, 100°C) or PTC (-50°C, 150°C), from 1 to 36°F for NTC (-58°F, 212°F) or PTC (-58°F, 302°F), from 0.1 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC (-50.0°C,150.0°C), from 0.1 to 18.0°F for NTC (-58.0°F,212.0°F) or PTC (-58.0°F,302.0°F),
In ON/OFF control algorithm, temperature value is tried to keep equal to set value by opening or closing the last control element. ON/OFF controlled system, temperature value oscillates continuously. Temperature value’s oscillation period or amplitude around set value changes according to controlled system. For reducing oscillation period of temperature value, a threshold zone is formed below or around set value and this zone is named hysteresis.
Minimum Temperature Set Value Parameter (Default = Minimum Value of Device Scale ) MODBUS ADDRESS:40005
Temperature set value can not be lower than this value. This parameter value can be adjusted from minimum value of device scale to maximum temperature set value parameter
Maximum Temperature Set Value Parameter (Default = Maximum Value of Device Scale )MODBUS ADDRESS:40006
Temperature set value can not be greater than this value. This parameter value can be adjusted from minimum temperature set value parameter to maximum value of the device scale
Sensor Offset Parameter ( Default = 0 ) MODBUS ADDRESS:40007
from -20 to 20 °C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C), from -36 to 36 °F for NTC(-58°F, 212°F) or PTC(-58°F, 302°F), from -10.0 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C), from -18.0 to 18.0°F for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F),
Operating Type Parameter ( Default = 1) MODBUS ADDRESS:40008
If parameter value is ‘0’ device skips to parameter
Heating
Cooling
Defrost Time Parameter ( Default =1 0) MODBUS ADDRESS:40009
It can be adjusted from 0 to 999 minutes. If it is selected 0 automatic or manual defrost is not performed.
Defrost Repeat Cycle Parameter ( Default = 1) MODBUS ADDRESS:40010
It can be adjusted from 1 to 99 hours.
Defrost at Power On Parameter ( Default = 0) MODBUS ADDRESS:40011
System does not go through a defrost cycle at start up
System goes through a defrost cycle at start up
Temperature
Set
Control
Output
ON
OFF
HSt
HSt
Time
Time
ENGLISH
9
Defrost Delay at Power On Parameter ( Default = 0) MODBUS ADDRESS:40012
It can be adjusted from 0 to 99 minutes. This parameter can be observed if defrost at power on parameter is 1.
Display Status During Defrost Parameter ( Default = 3 ) MODBUS ADDRESS:40013
The temperature is displayed during defrost. Temperature value at the start of a defrost is displayed during defrost.
Set value is displayed during defrost.
Is displayed to indicate a defrost is in progress.
Compressor Start Delay at Power On Parameter ( Default = 0) MODBUS ADDRESS:40014
When power is first applied to the device, compressor is on when this time delay is expired. It can be adjusted from 0 to 20 minutes.
Compressor Stop-Start Delay Parameter ( Default = 0) MODBUS ADRES:40015
When compressor is inactive, this time delay must be expired for activation of the compressor. It can be adjusted from 0 to 20 minutes.
Compressor Start-Start Delay Parameter ( Default = 0) MODBUS ADRES:40016
This time delay must be expired between two activation of the compressor. It can be adjusted from 0 to 20 minutes.
Sensor Defect Parameter ( Default = 0 ) MODBUS ADRES:40017
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to and Time periods in case of sensor defect.
Compressor is active during this time period in case of probe defect (Default = 0) MODBUS ADRES:40018
If probe defect parameter is 2, then this parameter is observed. It can be adjusted from 0 to 99 minutes.
Compressor is inactive during this time period in case of probe defect ( Default = 0 )MODBUS ADRES:40019
If probe defect parameter is 2, then this parameter is observed. It can be adjusted from 0 to 99 minutes.
Temperature Alarm Function Selection Parameter ( Default = 0 )
MODBUS ADRES:40020
Alarm function is inactive.
Absolute alarm is selected. If temperature lower than and higher than , then alarm is on. Relative alarm is selected. Alarm operates according to the set value. If temperature is below ( Set - ) or above ( Set + ), alarm occurs.
Temperature Minimum Alarm Parameter (Default =Minimum Value of Device Scale) MODBUS ADRES:40021
For temperature alarm function selection parameter = 1(Absolute alarm), this parameter value is can be adjust from minimum value of device scale to temperature alarm maximum parameter value , for temperature alarm function selection parameter = 2(Relative alarm), this parameter value is can be adjusted 0 to %50 of the device scale
Temperature Alarm Maximum Parameter ( Default = Maximum Value of Device Scale)
MODBUS ADRES:40022
For temperature alarm function selection parameter = 1(Absolute alarm), this parameter value is can be adjust from temperature alarm minimum parameter value to maximum value of device scale, for temperature alarm function selection parameter = 2(Relative alarm), this parameter value is can be adjusted 0 to %50 of the device scale
10
ENGLISH
Temperature Alarm On Delay Time Parameter(Default = 0)MODBUS ADDRESS:40023
Temperature alarm on delay time can be defined with this parameter. It can be adjusted from 0 to 99 minutes.
Temperature Alarm Delay After Power On Parameter
MODBUS ADRES:40024
When power is first applied to the device, this time delay must be expired for activation of temperature alarm. It can be adjusted from 0 to 99 minutes.
Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40025
Buzzer is inactive.
Buzzer is active during defrost operation.
Buzzer is active if an alarm occurs. Buzzer is active during sensor failures. Buzzer is active during defrost operation, alarm or sensor failures.
Buzzer is active during this time
If buzzer function selection parameter value =0, this parameter can not be observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
When this parameter is 1, if decrement button is pressed, is observed. In this condition buzzer is active till buzzer silence button is pressed.
Button Protection Parameter ( Default = 4 ) MODBUS ADDRESS:40027
There is no protection. Defrost time can not be changed and manual defrost is not available.
Temperature Set value can not be changed. Defrost time set value and temperature set value can not be changed. Manual defrost is not available. Defrost time value can not be changed, manual defrost is available..
Communication Mode Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40028
PROKEY communication selected.
Rs485 communication selected.
Slave ID Parameter ( Default = 1 ) MODBUS ADDRESS=40029
Device communication address parameter (1 to 247).
ON/OFF Parameter ( Default = 0 ) MODBUS ADDRESS:40030
When device energized; if (increment button) pressed for 10 seconds, device stops controlling and screen will be displayed. If (increment button) pressed again for 10 seconds, device continues controlling and display changes back to main operating screen.
ON/OFF function with button is not available.
ON/OFF function with button is available.
Programming Section Accessing Password
It is used for accessing to the programming section. It can be adjusted from 0 to 999. If it is selected 0, password will not be asked
parameters will be accessible.
( Default = ) MODBUS ADDRESS:40026
. If password selected ‘12’, only , and
( Default = 0 )
( Default = 0 ) MODBUS ADDRESS:40031
ENGLISH
11
6.3 Modbus Adresses of Device Status Parameters (Read Input Register)
MODBUS ADDRESS:30001 Temperature Value MODBUS ADDRESS:30002 Reserved MODBUS ADDRESS:30003 Led Status : 0.bit C Led, 5.bit Defrost Led,
A
6.bit Compressor Led, 7.bit Alarm Led
A
13.bit Program Led, 14.bit Set Led
MODBUS ADDRESS:30004 Device Status : 0.bit Alarm Status
A
1.bit Buzzer Status
A
2.bit Sensor Lost Status
A
7.bit Defrost Status
MODBUS ADDRESS:30005 Output Status MODBUS ADDRESS:30006 Device Type and Device Version
o
ENGLISH
12
6.4 Operation Graphics of ESM-3711-CN Cooling Controller
1-If defrost time parameter 1 , Defrosting repeat cycle 1 , Defrost at Power On Parameter = 1 and Defrost Delay at Power On Parameter 1;
Power
Defrost
Led
Output
2- If is 1 ,
Compressor Start Delay at Power On Parameter
1 and
Compressor Stop-Start Delay Parameter is
Compressor Start-Start Delay Parameter is 1 then ;
Power
Defrost time
starts with button.
Time
Time
ENGLISH
Time
Time
Time
Time
Time
Output
Led
Output
Time
Time
13
6.5 Entering To The Programming Mode, Changing and Saving Parameter
Main Operation Screen
O
ESM-3711CN
O
S
P
C
F
O
O
S
C
F
P
ESM-3711CN
ü
When SET button is pressed for 5
seconds, “PR” led starts to blink. If
programming mode entering password is different from 0,
programming mode entering screen
will be observed.
O
O
S
P
C
F
Note1: If programming
mode accessing password is 0, Temperature Unit Selection parameter is observed instead of programming screen
ESM-3711CN
Programming Mode
Entering Screen
Press SET button for
accessing to the
password entering
screen.
O
O
C
ü
Password Entering Screen
Enter programming mode accessing password
with increment and decrement buttons.
Note2: If programming mode accessing password is 0, only three parameters are accessible, and the parameter values can be changed.
Programming Screen
ESM-3711CN
O
O
S
P
C
F
Password Entering Screen
Press SET/OK button for
entering the password.
O
O
C
ü
Press SET button for accessing to the parameter value. Press increment button for accessing to the next parameter, press decrement button for accessing to the previous parameter.
ESM-3711CN
O
O
S
P
C
F
Hysteresis Value for Compressor Output
Change the value with increment
and decrement buttons.
O
O
C
ü
Hysteresis Value for Compressor Output
Press set button for saving the
parameter.
If no operation is performed in programming mode for 20 seconds, device turns to main
i
operation screen automatically..
Press increment button for accessing to the next parameter, press decrement button for accessing to the previous parameter
Hysteresis Parameter
for Compressor
ü
ESM-3711CN
S
P
F
ENGLISH
ü
ESM-3711CN
S
P
F
ü
ESM-3711CN
S
P
F
ü
14
7. Failure Messages in ESM-3711-CN Cooling Controller
1. Screen Blinking Sensor failure . Sensor connection is wrong or there is no sensor connection. If buzzer function selection parameter is 3 or 4, internal buzzer starts to operate.
2- Blinking the Screen Value If temperature higher than the alarm parameters limit, value on the screen starts to blink.
Example-1 : If alarm function selection parameter In programming section is 1(Absolute alarm) and minimum alarm parameter is 20 ; When temperature is less than 20°C, value on the screen starts to blink. Also if buzzer function selection parameter is 2 or 4 , then internal buzzer is on.
Example-2 : If alarm function selection parameter in programming section is 1 (Absolute Alarm) and maximum alarm parameter is 50 When temperature is above 50 °C, value on the screen starts to blink. Also buzzer function selection parameter is 2 or 4, then internal buzzer is on.
8. Manual Defrost Operation with Defrost Button
ESM-3711CN
O
O
S
P
C
F
ü
While defrost time parameter value 1, button protection parameter value = 0 or 2 and defrost output is inactive,
3 sn.
in main operation screen if defrost button is pressed for 3 seconds defrost operation starts and defrost led becomes
active.If defrost button pressed for 3 seconds while defrost continues,defrost is finished and defrost led becomes inactive.
9. Specifications
Device Type : Cooling Controller Housing&Mounting : 76mm x 34.5mm x 71mm plastic housing for panel
Mounting. Panel cut-out is 71x29mm.
Protection Class : NEMA 4X (Ip65 at front, Ip20 at rear). Weight : Approximately 0.20 Kg. Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
Storage / Operating Temperature: -40 C to +80 C / -30 C to +80 C Storage / Operating Humidity : 90 % max. (None condensing) Installation : Fixed installation Overvoltage Category : II. Pollution Degree : II, office or workplace, none conductive pollution Operating Conditions : Continuous Supply Voltage and Power : : 115
: 24 ,10-30
Temperature Sensor Input : NTC or PTC NTC input type : NTC (10 kW @25 °C ) PTC input type : PTC (1000 W @25 °C ) Accuracy : ± 1 % of full scale for thermoresistance Sensor Break Protection : Upscale Sampling Cycle : 3 samples per second Control Form : ON / OFF Relay Outputs : 16(8) A@250 V V for Resistive load (Compressor
output) (Electrical life : 100.000 switching at full load)
Display : 14 mm Red 4 digits LED Display LED : S (Green), P (Green), C (Yellow), F(Yellow), Alarm (Red),
Defrost (Red), Compressor Output (Red) Internal Buzzer : 83dB Approvals :
o o o o
V ±
230V ( %15) 50/60Hz - 1.5VA
V ±
V ( %15) 50/60Hz - 1.5VA
V ±
V ( %15) 50/60Hz - 1.5VA VZ 1.5W
o o
,
15
ENGLISH
10.Ordering Information
00 00
U
V W Z/
/
ESM-3711-CN
(77x35 DIN Size)
Supply VoltageA
3
24V ( %15) 50/60Hz - 1.5VAV ±
4
115V ( %15) 50/60Hz - 1.5VAV ±
5
230V ( %15) 50/60Hz - 1.5VAV ±
8
10 - 30 V Z
Input Type
BC
PTC (Note-1)
12
NTC (Note-1)
18
E
Compressor Output
Relay Output ( 16(8) A@250 V V at resistive load, 1 NO )
1
Temp. Sensor which is given with ESM-3711-CN
V
None
0
1
PTC-M6L40.K1.5 (PTC Air Probe with 1.5 mt silicon cable)
PTCS-M6L30.K1.5.1/8” (PTC Liquid Probe with1.5 mt silicon cable)
2
NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with
3
1.5 m cable for cooling application)
NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with
4
1.5 m cable for cooling application)
Customer
All order information of ESM-3711-CN Cooling Controller are given on the table at left. User may form appropriate device configuration from information and codes that at the table and convert it to the ordering codes. Firstly, supply voltage then other specifications must be determined. Please fill the order code blanks according to your needs. Please contact us, if your needs are out of the standards.
Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is selected as NTC, sensor type (V = 0,3 or 4) must be declared in ordering information.
9
A BC D E FG HI /
0 1 0 0
/
Scale(°C)
-50°C/-58°F ; 150°C/302°F
-50°C/-58°F ; 100°C/212°F
11.Optional Accessories
1.RS-485 Module 2.PROKEY Programming Module
ENGLISH
RS-485 Communication Interface
c
Your Technology Partner
The device is programmed(Upload or
V Ş Vac, Z Ş Vdc
Ş Vdc or Vac can be appliedW
Thank you very much for your preference to use Emko Elektronik products, please visit our web page to download detailed user manual.
Download) by using the parameters.
www.emkoelektronik.com.tr
16
ESM-3711-CN 77 x 35 DIN Maß
Digitaler , EIN / AUS Kühlregler
- 4-stellige Anzeige
- NTC Eingang oder PTC Eingang (Muss vorher festgelegt werden)
- Einstellbare Temperaturabweichung
- Begrenzte einstellbare Werte
- Bei Sensorschaden Wahl zwischen Dauerbetrieb, Stopp oder periodischem Betrieb des Kompressors.
- Verzögerter Überstromschutz des Kompressors
- Von der Vorderseite aus einstellbare Abtauzeit
- Manuellles Abtauen von der Vorderseite aus
- Parameter für den Abtauvorgang
- Parameter für den Alarm
- Eingebauter einstellbarer Summer gesteuert vom Kühlfachsensor Schadens- und Alarmstatus
- Schutz der eingestellten Werte für manuell eingestellte Abtauzeit und/oder eingestellte Temperaturwerte
- Passwortschutz für den Programmierbereich
- Parameter werden mit Prokey installiert
- Fernregelung,Datenkontrolle und Regelung mit Modbus RTU
- Mit EU Kennzeichnung gebaut nach den europäischen Normen
ESM-3711-CN 77x35 DIN Maß Kühlregler
Bedienungsanleitung: DE ESM-3711-CN 02 V02 09/12
DEUTSCH
1.Vorwort:
Die Kühlregler der Serie ESM-3711-CN sind für die Regelung von Kühlprozessen gedacht. Durch ihren einfachen Gebrauch sind sie vielfältig einsetzbar, auch wegen ihrer EIN/AUS-
Regelung und ihrer Abtaufunktion. Einige Anwendungen sind in der Liste unten aufgeführt:
Einsatzbereiche: Lebensmittel Maschinen, Produktion, Industrie
usw....
1.1 Umweltfreundlichkeit
Anwendungen:
Kühlschränke Klimaanlagen Lagerung Kühlräume usw...
Betriebstemperatur : 0 bis 50 °C
Max.Feuchtigkeit: : 90% r.L. (kein Kondenswasser)
Höhe: : Bis zu 2000 m. Unzulässig: Korrosive Umgebung
c
Explosive Atmosphäre Verwendung im Heimbereich (Gerät ist für industrielle Anwendung gedacht)
1.2 Allgemeine Daten
Standard
230V ( %15) 50/60HzV ±
Wahlweise auch:
115 V (±%15) 50/60Hz,
V
10 - 30 V Z
NTC,PTC
ESM-3711-CN
Anschluss Stromversorgung
Sensoreingang
Kompressorausgang
Kühlfunkion EIN/AUS-Regelung
DEUTSCH
2
1.3 Installation
Vor Montage das Gerät visuell prüfen, ob das Gerät während der Beförderung beschädigt wurde. Die Montage und Inbetriebnahme muss durch geschultes Personal ausgeführt werden. Dies steht unter der Verantwortung des Käufers. Falls aufgrund eines Fehlers oder einer Störung des Geräts eine Gefahr bestehen sollte, Spannungsversorgung abschalten und alle elektrischen Verbindungen zum Geräts entfernen. Standardmäßig wird das Gerät ohne Netzschalter und ohne Sicherung ausgeliefert. Bei Bedarf müssen diese vom Anwender selbst angebracht werden. Es muss eine zum Gerät passende Versorgungsspannung verwendet werden, um Fehlfunktionen und Schäden zu vermeiden. Um einen elektrischen Schock und ähnliche Unfälle zu vermeiden, darf das Gerät vor Abschluss der Verkabelung nicht mit Spannung versorgt werden. An dem Gerät keine Veränderungen vornehmen, und das Gerät nicht reparieren. Eingriffe am Gerät können fehlerhafte Funktion, Beschädigung des Geräts oder angeschlossener Geräte, elektrischen Schocks und Feuer auslösen. Das Gerät darf unter keinen Umständen in der Nähe von brennbaren und explosiven Gasen verwendet werden. Die Schalttafelausschnitte können scharfe Kanten aufweisen, welche bei der Montage des Geräts Schnittverletzungen verursachen können. Bitte treffen Sie die erforderlichen Vorsichtsmaßnahmen. Es ist wichtig, dass das Gerät mit den mitgelieferten Befestigungsteilen montiertwird. Das Gerät nicht mit ungeeigneten montieren. Achten Siedarauf, dass das Gerät während der Montage nicht herunterfällt. Es unterliegt Ihrer Verantwortung, wenn das Gerät nicht wie in dieser Anleitung beschrieben, verwendet wird.
1.4 Garantie
2 Jahre Garantieschutz gegen Material- und Verarbeitungsfehler. Diese Garantie wird mit dem Vorbehalt gewährleistet, dass der Kunde den in Garantieschein und Bedienungsanleitung erwähnten Pflichten nachkommt.
1.5 Instandhaltung
Das Gerät muss durch geschultes Personal gewartet werden. Vor dem Zugriff auf Innenteile, alle stromführenden Leitungen trennen. Gerät nicht mit auf Kohlenwasserstoff basierenden Lösungsmitteln (wie Benzin, Trichlorethylen etc.) reinigen. Das Reinigen mit diesen Lösungen kann die mechanische Sicherheit des Geräts vermindern. Verwenden Sie ein mit Ethylalkohol oder Wasser benetztes Tuch um das Plastikgehäuse außen zu reinigen.
DEUTSCH
1.6 Sonstige Angaben
Information des Herstellers:
Emko Elektronik Sanayi ve Ticaret A.Ş. Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA Tel : +90 224 261 1900 Fax : +90 224 261 1912
Information über Reparatur und Wartungsdienst
Emko Elektronik Sanayi ve Ticaret A.Ş. Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA Tel : +90 224 261 1900 Fax : +90 224 261 1912
3
3
2. Allgemeine Beschreibung:
Vorderseite Schutzklasse IP65
NEMA 4X
Frontplatte (maximale Dicke 15 mm / 0.59 Zoll)
Halteklammern
2.1 Vorderansicht und Abmessungen des ESM-3711-CN Kühlreglers
Maximal 15 mm / 0.59 Zoll
O
O
S
P
C
F
ü
34,5 mm / 1.36 Zoll
76 mm / 3 Zoll
2.2 Ausschnitt in der Schalttafel
29 mm / 1.14 Zoll
71 mm / 2.79 Zoll
6 mm / 0.24 Zoll
110 mm / 4.33 Zoll (min)
65 mm / 2.56 Zoll
DEUTSCH
50 mm / 1.97 Zoll (min)
4