J Type thermocouple Input or,
K Type thermocouple Input or,
2-Wire PT-100 Input or,
2-Wire PT-1000 Input
- Adjustable temperature offset
ON/OFF temperature control
-
- Selectable heating or cooling function
- Selection of operation with hysteresis
- Adjustable temperature offset
- Set value low limit and set value high limit boundaries
- Operation selection of compressor operates continuously,
stops or operates periodically in case of sensor defect
- Compressor protection delays
- Adjustable internal buzzer according to sensor defect status.
- Password protection for programming section
- Installing parameters using Prokey
ESM-3710-N 77x35 DIN Size Temperature Controller
- Remote access, data collecting and controlling with Modbus RTU
- Having CE mark according to European Norms
(Must be determined in order.)
Instruction Manual. ENG ESM-3710-N 01 V07 11/18
ENGLISH
1.Preface
ESM-3710N series temperature controllers are designed for measuring and controlling
temperature. They can be used in many applications with their On / Off control form, heating
and cooling control form and easy-use properties. Some application fields which they are
used are below:
Application FieldsApplications
Glass Heating
Food Baking Ovens
PlasticIncubators
Petro-Chemistry Storages
Textile, Automative Air Conditioning
Machine Production Industries Etc... Etc...
1.1 Environmental Ratings
Operating Temperature : -20 to 70 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Forbidden Conditions:
Corrosive atmosphere
c
Explosive atmosphere
Home applications (The unit is only for industrial applications)
1.2 General Specifications
Standard
230V ( %15) 50/60HzV ±
Optional Supply Voltage
V
115 V (±%15) 50/60Hz,
V
24 V (±%15) 50/60Hz,
W
24 V (±%15) 50/60Hz,
10
- 30 V Z
NTC, PTC,
J or K Type TC
2-Wire PT-100
2-Wire PT-1000
ESM-3710-N
Power Supply
Input
Temperature Sensor
Input
Standard
Output-1
(Relay Output)
Optional
Output-1
(SSR Drive Output)
Control Output
Alarm Output
Control Output
Alarm Output
Heating or Cooling
Function
ON/OFF Operation
2
1.3 Installation
A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the
system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent
failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the
unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage
of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
1.4 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts
from the delivery date. This warranty is in force if duty and responsibilities which are determined
in warranty document and instruction manual performs by the customer completely.
1.5 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in
ethyl alcohol or water to clean the external plastic case.
1.6 Manufacturer Company
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA /TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
3
2. General Description
Front Panel
IP65 protection
NEMA 4X
Panel Surface
(maximum thickness 15 mm / 0.59 inch)
Mounting Clamp
2.1 Front View and Dimensions of ESM-3710-N Temperature Controller
Maximum 15 mm / 0.59 inch
O
C
ESM3710-N
O
S
P
F
SET
P
ü
34,5 mm / 1.36 inch
76 mm / 3 inch
2.2 Panel Cut-Out
29 mm / 1.14 inch
6 mm / 0.24 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
65 mm / 2.56 inch
50 mm / 1.97 inch (min)
4
2.3 Panel Mounting
1
3
2
1-Before mounting the device in your panel,
make sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the
mounting clamps are on the unit, put out them
before inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets
that located left and right sides of device and make
the unit completely immobile within the panel
3
2.4 Removing from the Panel
1-Pull mounting clamps from left and right fixing
sockets.
2-Pull the unit through the front side of the panel
1
2
Before starting to remove the unit from
panel, power off the unit and the related
system.
c
3. Using Prokey
TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE ‘0’.
IF PrC=1 AND BUTTON IS PRESSED MESSAGE WILL BE SHOWN. 10s. LATER
DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET
BUTTON TO TURN BACK TO MAIN OPERATION SCREEN.
DOWNLOADING FROM DEVICE TO PROKEY
1.The device is programmed by using the parameters.
2.Energize the device then put in PROKEY and press button. Message is shown on the
display. When the loading has finished, message is shown.
3.Press any button to turn back to main operation screen.
4.Remove the PROKEY.
NOTE: message is shown when an error occurs while programming. If you want to reload, put
in PROKEY and press button. If you want to quit, remove PROKEY and press button. The
device will turn back to main operation screen.
DOWNLOADING FROM PROKEY TO DEVICE
1.Switch off the device.
2.Put in PROKEY then energize the device.
3.When the device is energized, the parameter values in PROKEY, start downloading to the device
automatically. At first, message is shown on the display, when loading has finished,
message is shown.
4.After 10 seconds device starts to operate with new parameter values.
5.Remove the PROKEY.
NOTE: message is shown when an error occurs while programming. If you want to reload,
switch off the device and put in PROKEY then energize the device. If you want to quit remove
PROKEY and press button. The device will turn back to main operation screen.
5
4. Electrical Wiring Diagram
N
a
L
3
214 56 7
(-)
P/N : ESM-3710-N
Electrical Wiring Diagram for 30(15)A @ 240 V V Relay Output Devices:
P/N : ESM-3710-N
(+)
For SSR Output
N
a
L
3 4
215 67 8
4.1 Supply Voltage Input Connection of the Device
Power Supply Connection
L
N
a
(+)(-)
4
5
EXTERNAL
FUSE
(1A T)
Note-1
Supply
Switch
c
Supply Voltage
V ±
230V ( %15) 50/60Hz ,
V ±
115V ( %15) 50/60Hz,
V ±
24V ( %15) 50/60Hz ,
W ±
24V ( %15) 50/60Hz ,
10..30 V - 1.5 W
Z
Must be determined in order.
Note-1 : External fuse is recommended.
Make sure that the power supply voltage is the same
indicated on the instrument.
c
Switch on the power supply only after that all the electrical
connections have been completed.
Supply voltage range must be determined in order. While
installing the unit, supply voltage range must be controlled
and appropriate supply voltage must be applied to the unit.
There is no power supply switch on the device. So a power
supply switch must be added to the supply voltage input.
c
Power switch must be two poled for seperating phase and
neutral, On/Off condition of power supply switch is very
important in electrical connection.
External fuse that on Vpower supply inputs must be on
phase connection.
External fuse that on Zpower supply inputs must be on (+)
connection.
Temperature Sensor
TC,NTC,PTC,PT-100
or PT-1000
Supply Voltage Input
V ±
230V ( %15) 50/60Hz
V ±
115V ( %15) 50/60Hz
V ±
24V ( %15) 50/60Hz
10...30 V
Z
Must be determined in order.
Relay or SSR Output
Temperature Sensor
NTC
Supply Voltage Input
V ±
230V ( %15) 50/60Hz
V ±
115V ( %15) 50/60Hz
V ±
24V ( %15) 50/60Hz
10...30 V
Z
Must be determined in order.
Relay Output
30(15)A@240 V V
Input
Input
6
Supply Voltage InputConnection for 30(15)A @ 240 V V Relay Output Devices:
L
N
EXTERNAL
FUSE
(1A T)
a
(+)(-)
5
6
Note-1
Supply
Switch
V ±
230V ( %15) 50/60Hz ,
V ±
115V ( %15) 50/60Hz,
V ±
24V ( %15) 50/60Hz ,
W ±
24V ( %15) 50/60Hz ,
10..30 V - 1.5 W
Z
Must be determined in order.
c
Supply Voltage
4.2 Device Label and Connection Diagram
230VV CONNECTION DIAGRAM
P/N : ESM-3710-N - 5.18.0.1/00.00/2.3.0.0
16(8)A @
230 VV ± 15%
250VV1HP
50/60Hz - 1.5VA
OUTPUT
NONCC
LINE
LOAD
7
NTC
INPUT SCALE
(-50 ,100 ; -58 ,212 ) °C °C °F °F
RS-485
PROKEY
or
L
N
30(15)A @ 240 V V Connection Diagram for Relay Output Devices:
P/N:ESM-3710-N-5.18.0.3/00.00/2.3.0.0
30(15)A @ 240VV
230 VV ± 15%
OUTPUT
50/60Hz - 1.5VA
7 8
NTC
INPUT SCALE
(-50 ,100 ; -58 ,212 ) °C °C °F °F
RS-485
PROKEY
or
L
N
5.Front Panel Definition and Accessing to the Menus
5 6 7 7
1
2
BUTTON DEFINITIONS
1. Increment Button :
** It is used to increase the value in the Set screen and Programming mode.
2. Decrement, Silencing Buzzer and Downloading to Prokey Button :
** It is used to decrease the value in the Set screen and Programming mode.
** It is used to silence the buzzer.
** If Prc =0, it is used to download from device to prokey.
6
16A Fuse
30A Fuse
@250VV1HP
1
1
8
O
O
C
16(8)A
OUTPUT
C
2
30(15)A@240VV
OUTPUT
2
F
LOAD
9
S
3
3
LOAD
10
NCNO
P
ESM3710-N
SET
P
ü
a
4
5
L
N
a
54
6
L
N
3
3
4
RS-485
or
PROKEY
6
7
NTC
RS-485
or
PROKEY
7
8
NTC
7
3. Set Button :
** In the main operation screen; if this button pressed, set value will be displayed. Value can be
changed using increment and decrement buttons. When Enter button pressed, value is saved
and returns back to main operating screen.
** To access the programming screen; in the main operation screen, press this button for 5
seconds.
4. Enter Button :
** It is used to saving value in the Set screen and programming screen.
LED DEFINITIONS
5. Cooling led :
** This led indicates that cooling control is selected and process output relay is active. If any
of compressor protection time active, this led blinks.
6.Heating led :
** This led indicates that heating control is selected and process output relay is active.
7.Celcius led :
** Indicates that device is in C mode.
8.Fahrenheit led :
** Indicates that device is in F mode.
9.Set led :
** Indicates that device is in Set value changing mode.
10.Program led :
**Blinks in programming mode .
6. Changing and Saving Temperature Set Value
Main Operation Screen
When SET button pressed ‘’S’’ led will
be active and temperature set value will
Temperature set value parameter (Default=50) MODBUS ADDRESS:40001
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
be displayed.
When ENTER button pressed
temperature set value can be saved.
6.1 Programming Mode Parameter List
o
o
O
ESM3710-N
O
S
P
C
F
SET
P
ü
O
ESM3710-N
O
S
P
C
F
SET
P
ü
ü
SET Value Screen
O
ESM3710-N
O
S
P
C
F
SET
P
ü
Temperature set value can
be changed with increment
and decrement buttons.
Main Operation Screen
O
‘’S’’ will be inactive and goes back to
main operation screen.
ESM3710-N
O
S
P
C
F
SET
P
ü
ü
Temperature Unit Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40002
from -20 to 20 °C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C) or J Type TC (0°C,800°C)
or J Type TC (0°C,1000°C) or PT-100(-50°C, 400°C)or PT-1000 (-50°C, 150°C) or
PT-100 (-20°C, 100°C), from -36 to 36 °F for NTC(-58°F, 212°F) or PTC (-58°F, 302°F) or J
Type TC (32°F,1472°F) or or K Type TC (32°F,1830°F) or PT-100(-58°F, 752°F) or
PT-1000(-58°F, 752°F) or PT-100(-4°F, 212°F), from -10.0 to 10.0°C for NTC
(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C) or PT-100 (-19.9°C,99.9°C), from -18.0 to
18.0°F for NTC (-58.0°F,212.0°F) or PTC (-58.0°F,302.0°F) or PT-100 (-4.0°F,212.0°F),
In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude around
set value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is formed
below or around set value and this zone is
named hysteresis.
Minimum Temperature Set Value Parameter (Default = Minimum Value of Device
Scale ) MODBUS ADDRESS:40005
Temperature set value can not be lower than this value.
This parameter value can be adjusted from minimum value of device scale to maximum
temperature set value parameter
Maximum Temperature Set Value Parameter (Default = Maximum Value of Device
Scale ) MODBUS ADDRESS:40006
Temperature set value can not be bigger than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale
from -20 to 20 °C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C) or J Type TC (0°C,800°C) or
J Type TC (0°C,1000°C) or PT-100(-50°C, 400°C)or PT-1000 (-50°C, 150°C) or
PT-100 (-20°C, 100°C), from -36 to 36 °F for NTC(-58°F, 212°F) or PTC (-58°F, 302°F) or J
Type TC (32°F,1472°F) or or K Type TC (32°F,1830°F) or PT-100(-58°F, 752°F) or
PT-1000(-58°F, 752°F) or PT-100(-4°F, 212°F), from -10.0 to 10.0°C for NTC
(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C) or PT-100 (-19.9°C,99.9°C), from -18.0 to
18.0°F for NTC (-58.0°F,212.0°F) or PTC (-58.0°F,302.0°F) or PT-100 (-4.0°F,212.0°F),
Operating Type Parameter ( Default = 0) MODBUS ADDRESS:40008
If parameter value is ‘0’ device skips to parameter
Temperature
Set
Control
Output
ON
OFF
HSt
HSt
Time
Time
Heating
Cooling
Compressor Start Delay at Power On Parameter ( Default = 0)
MODBUS ADDRESS:40009
When power is first applied to the device, compressor is on when this time delay is expired.
It can be adjusted from 0 to 20 minutes.
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to and Time periods in
case of sensor defect.
Compressor is active during this time period in case of probe defect (Default = 0)
MODBUS ADRES:40013
If probe defect parameter is 2, then this parameter is observed. It can be adjusted
from 0 to 99 minutes.
Compressor is inactive during this time period in case of probe defect
( Default = 0 )MODBUS ADRES:40014
If probe defect parameter is 2, then this parameter is observed. It can be adjusted
from 0 to 99 minutes.
Buzzer is inactive.
Buzzer is active during sensor failures.
Buzzer is active during this time
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is
selected 0, password will not be asked
, , , , and Parameters are observed if Operation type
i
is selected “Cooling”. If operation type is selected “Heating ” ,skip to the parameter
( Default = ) MODBUS ADDRESS:40016
6.2 Modbus Adresses of Device Status Parameters (Read Input Register)
MODBUS ADDRESS:30001 Temperature Value
MODBUS ADDRESS:30002 Reserved
MODBUS ADDRESS:30003 Led Status : 0.bit C Led,
A
6.bit Compressor Led,
A
13.bit Program Led, 14.bit Set Led
MODBUS ADDRESS:30004 Device Status : 1.bit Buzzer Status
A
2.bit Sensor Lost Status
MODBUS ADDRESS:30005 Output Status
MODBUS ADDRESS:30006 Device Type and Device Version
o
10
6.3 Operation Graphics of ESM-3710-N ControllerTemperature
1-If Operating Type Parameter Value = 1 (Cooling),
Switch On Delay After Power On Parameter Value ³ 1 ,
Compressor Stop/Start Time Delay Parameter Value ³ 1 and
Compressor Start/Start Time Delay Parameter Value ³ 1;
Power
°C
SET
Output
Led
Output
2-If Operating Type Parameter Value = 0 (Heating),
i
Hst
Temperature
Value
SET
ON
OFF
to set value by opening or closing the last control element. ON/OFF controlled
system, temperature value oscillates continuously. Temperature value’s oscillation
period or amplitude around set value changes according to controlled system. For
reducing oscillation period of temperature value, a threshold zone is formed below or
around set value and this zone is named hysteresis. Action of control output is
described with figures above.
HSt
Temperature Control Output
HStHSt
In ON/OFF control algorithm, temperature value is tried to keep equal
Time
Time
Time
Time
Time
Time
6.4 Failure Messages in ESM-3710-N Temperature Controller
Screen Blinking
Sensor failure . Sensor connection is wrong or there is no sensor connection. If buzzer function
selection parameter is 1, internal buzzer starts to operate.
11
6.5 Entering To The Programming Mode, Changing and Saving Parameter
Main Operation Screen
ESM3710-N
O
O
S
P
C
F
SET
P
O
O
S
C
F
ü
P
ESM3710-N
SET
P
ü
When SET button is pressed for 5
seconds, “P” led starts to blink. If
programming mode entering
password is different from 0,
programming mode entering screen
will be observed.
O
O
S
P
C
F
Note1: If programming
mode accessing
password is 0,
Temperature Unit screen
is observed instead of
programming screen
ESM3710-N
SET
P
Programming Mode
Entering Screen
Press OK button for
accessing to the
password entering
screen.
O
O
C
ü
Password Entering Screen
Enter programming mode accessing password
with increment and decrement buttons.
Note2: If programming mode accessing password is 0, only three parameters
are accessible, and the parameter values can be changed.
Programming Screen
ESM3710-N
O
O
S
P
C
F
SET
P
Password Entering Screen
Press OK button for entering
the password.
O
O
C
ü
Press SET button for accessing to the parameter
value. Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter.
ESM3710-N
O
O
S
P
C
F
SET
P
Hysteresis Value for
Compressor Output
Change the value with increment
and decrement buttons.
O
O
C
ü
Hysteresis Value for
Compressor Output
Press OK button for saving the
parameter.
If no operation is performed in programming mode for 20 seconds, device turns to main
i
operation screen automatically..
Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter
Hysteresis Parameter for
Compressor Output
ESM3710-N
S
P
F
SET
P
ü
ESM3710-N
S
P
F
SET
P
ü
ESM3710-N
S
P
F
SET
P
ü
12
7. Specifications
Device Type: Temperature Controller
Housing & Mounting: 76mm x 34.5mm x 71mm plastic housing for panel
Protection Class: NEMA 4X (Ip65 at front, Ip20 at rear).
Weight: Approximately 0.20 Kg.
Environmental Ratings: Standard, indoor at an altitude of less than 2000 meters
Storage / Operating Temperature : -30 C to +80 C / -20 C to +70 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
:10 - 30
Temperature Sensor Input : NTC, PTC, TC, RTD
NTC input type : NTC (10 kW @25 °C )
PTC input type : PTC (1000 W @25 °C )
Thermocouple input type : J, K (IEC584.1) (ITS 90)
Thermoresistance input type : PT-100, PT-1000 (IEC751) (ITS 90)
Accuracy : ± 1 % of full scale for thermoresistance
Cold Junction Compensation : Automatically ± 0.1°C / ± 1°C
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Form : ON / OFF
Relay Output : 16(8) A@250 V V for Resistive load (Output)
(Electrical life : 100.000 switching at full load)
Optional SSR Drive Output : Maximum 20mA, Maximum 17V
Display : 14 mm Red 4 digits LED Display
LED : S (Green), P (Green), C (Yellow), F(Yellow),
NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with 1.5 m cable for cooling application)
3
NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with 1.5 m cable for cooling application)
4
Customer
All order information of ESM-3710-N Temperature Controller are given on the table at above. User may
form appropriate device configuration from information and codes that at the table and convert it to the
ordering codes.Firstly, supply voltage then other specifications must be determined. Please fill the order
code blanks according to your needs.
Please contact us, if your needs are out of the standards.
Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0,3 or 4) must be declared in ordering information.
c
c
9
Because of limited mechanical life of relay output contact, SSRoutput is recommended which
the device use PID control algoritm. The device with ON/OFF control algoritm, hysteresis
parameter must be set a suitable value for your system, to avoid too much relay switching.
Before commissioning the device, parameters must be set in accordance with desired use.
Incomplete or incorrect configuration can cause dangerous stiuations.
A BC D EFG HI /
010 0
/
Scale(°C)
0°C/32°F ;
0°C/32°F ;
-50°C/-58°F ;
-19.9°C/-4°F ;
-50°C/-58°F ;
-19.9°C/-4°F ;
-50°C/-58°F ;
-50°C/-58°F ;
14
9.Optional Accessories
Because of limited mechanical life of relay output contact,
SSRoutput is recommended which the device use PID control algoritm.
The device with ON/OFF control algoritm, hysteresis parameter must be set a suitable value
c
for your system, to avoid too much relay switching.
Before commissioning the device, parameters must be set in accordance with desired use.
Incomplete or incorrect configuration can cause dangerous stiuations.
c
1.RS-485 Module2.PROKEY Programming Module
c
V Ş Vac,
RS-485 Communication Interface
Z Ş Vdc
Ş Vdc or Vac
W
can be applied
The device is programmed(Upload or
Download) by using the parameters.
Your Technology Partner
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
www.emkoelektronik.com.tr
15
16
ESM-3710-N Digitaler
EIN/AUS-Temperaturregler
DIN-Größe 77 x 35
– 4-stelliges Display
– NTC-Eingang oder
PTC-Eingang oderThermoelement-Eingang Typ J oderThermoelement-Eingang Typ K oder2-adriger PT-100-Eingang oder2-adriger PT-1000-Eingang(Muss in der Bestellung angegeben werden.)
– Einstellbarer Temperatur-Offset EIN/AUS-Temperaturregelung
Auswählbare
Heiz- oder Kühlfunktion
– Auswahl des Betriebs mit Hysterese
– Einstellbarer Temperatur-Offset
– Sollwertunter- und -obergrenzen
– Auswahl des Kompressorbetriebs: durchgängiger Betrieb, Stop
ESM-3710-N Temperaturregler DIN Größe 77x35
oder intermittierender Betrieb bei einem Sensordefekt
– Kompressorschutzverzögerungen
– Einstellbarer interner Summer abhängig vom Sensordefekt-Status.
– Passwortschutz für den Programmierabschnitt
– Installationsparameter unter Verwendung von Prokey
– Fernzugriff, Datenerfassung und Regelung mit Modbus RTU
– Mit CE-Zeichen gemäß europäischen Normen
Bedienungshandbuch. GERESM-3710-N 01 V07 11/18
DEUTSCH
1. Vorwort
Temperaturregler der Baureihe ESM-3710-N sind auf die Temperaturmessung und -regelung
ausgelegt. Mit ihrer Ein/Aus-Regelungsfunktion, Heiz- und Kühlfunktionen und
benutzerfreundlichen Eigenschaften können sie in zahlreichen Anwendungen eingesetzt
werden. Nachfolgend sind einige Anwendungsbereiche aufgelistet, für die sie geeignet sind:
Explosive Atmosphäre
Anwendungen im Wohnbereich (Das Gerät ist nur für industrielle
Anwendungen vorgesehen)
1.2 Allgemeine Spezifikationen
Standard
230V ( %15) 50/60HzV ±
Optionale
Versorgungsspannung
V
115 V (±%15) 50/60Hz,
V
24 V (±%15) 50/60Hz,
W
24 V (±%15) 50/60Hz,
- 30 V Z
10
NTC, PTC,
J order K Typ TC
2-adriges PT-100
2-adriges PT-1000
ESM-3710-N
Stromversorgung
Eingang
Temperatursensor
Eingang
Standard
Ausgang-1
(Relaisausgang)
Optional
Ausgang-1
(SSR-Antriebsausgang)
Steuerausgang
Alarmausgang
Steuerausgang
Alarmausgang
Hei- oder Kühlfunktion
EIN/AUS-Betrieb
2
1.3 Installation
Vor der Installation dieses Produkts wird eine Sichtprüfung auf etwaige beim Transport
verursachte Schäden empfohlen. Sie müssen sicherstellen, dass dieses Produkt von
qualifizierten Elektrikern und Mechanikern installiert wird.
Falls bei einem Ausfall oder Defekt dieser Einheit die Gefahr eines ernsthaften Unfalls
besteht, schalten Sie das System aus und trennen den Stromanschluss des Geräts vom
System.
Die Einheit wird normalerweise ohne Netzschalter und Sicherung ausgeliefert. Verwenden
Sie bei Bedarf einen Netzschalter und eine Sicherung.
Achten Sie darauf, die Auslegungsspannung für die Stromversorgung zu verwenden, um
das Gerät vor Schäden zu schützen und Ausfälle zu vermeiden.
Schalten Sie den Strom erst ein, wenn die gesamte Verdrahtung abgeschlossen ist, sodass
ein Stromschlag und Probleme mit dem Gerät vermieden werden können.
Versuchen Sie auf keinen Fall, dieses Gerät zu zerlegen, zu ändern oder zu reparieren. Eine
Manipulation des Geräts führt zu Fehlfunktion, Stromschlag oder Brand.
Setzen Sie das Gerät nicht in feuergefährlichen oder explosiven gasförmigen Atmosphären
ein.
Wenn Sie die Ausrüstung bei der mechanischen Installation in die Öffnung in der
Metallplatte einsetzen, können Metallgrate Verletzungen an den Händen verursachen. Sie
müssen vorsichtig sein.
Die Montage des Produkts an einem System muss unter Verwendung der zugehörigen
Befestigungsklammern erfolgen. Führen Sie die Montage des Geräts nicht mit ungeeigneten
Befestigungsklammern durch. Achten Sie darauf, dass das Gerät während der Montage
nicht zu Boden fällt.
Sie sind dafür verantwortlich, dass dieses Gerät nicht auf eine Weise verwendet wird, die
nicht in diesem Anweisungshandbuch angegeben ist.
1.4 Garantie
EMKO Elektronik garantiert, dass die Ausrüstung frei von Material- und
Herstellungsschäden ist. Diese Garantie gilt für einen Zeitraum von zwei Jahren. Der
Garantiezeitraum beginnt mit dem Lieferdatum. Diese Garantie gilt, solange der Kunde alle
im Garantiedokument und im Betriebshandbuch angegebenen Verpflichtungen und
Verantwortlichkeiten einhält.
1.5 Wartung
Reparaturen dürfen ausschließlich von geschultem und spezialisiertem Personal
durchgeführt werden. Trennen Sie die Stromversorgung zu dem Gerät, bevor Sie auf interne
Bauteile zugreifen.
Reinigen Sie das Gehäuse nicht mit auf Kohlenwasserstoff basierenden Lösungsmitteln
(Benzin, Trichloräthylen usw.). Durch den Einsatz dieser Lösungsmittel kann die
mechanische Zuverlässigkeit des Geräts beeinträchtigt werden. Verwenden Sie ein mit
Ethylalkohol oder Wasser befeuchtetes Tuch, um das äußere Kunststoffgehäuse zu
reinigen.
1.6 Herstellerunternehmen
Herstellerinformationen
Informationen zum Reparatur- und Wartungsservice:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Telefon: +90 224 261 1900
Fax : +90 224 261 1912
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA /TURKEY
Telefon: +90 224 261 1900
Fax : +90 224 261 1912
3
2. Allgemeine Beschreibung
Frontplatte
IP65-Schutz
NEMA 4X
Schaltschrankoberfläche
(max. Dicke 15 mm / 0,59")
Montageklammer
2.1 Vorderansicht und Abmessungen des Temperaturreglers ESM-3710-N
Maximum 15 mm / 0.59 inch
O
C
ESM3710-N
O
S
P
F
SET
P
ü
34,5 mm / 1.36 inch
76 mm / 3 inch
2.2 Einbauausschnitt
29 mm / 1.14 inch
6 mm / 0.24 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
65 mm / 2.56 inch
50 mm / 1.97 inch (min)
4