Other Applications:Low-Pressure Actuator: 400 psig / 27.6 barHigh-Pressure Actuator: 400 psig / 27.6 bar
Maximum Pressures over Set Pressure to Avoid
Internal Parts Damage
(1)
Low-Pressure Actuator: 20 psig / 1.4 bar
High-Pressure Actuator: 120 psig / 8.3 bar
/
1. The pressure/temperature limits in this Installation Guide or any applicable limitation should not be exceeded.
2. Maximum Outlet and Emergency Casing Pressures for constructions with Fluorocarbon (FKM) diaphragm are limited to 230 psig / 15.8 bar or the body rating limit, whichever is lower.
3. NPS 2 / DN 50 body size spring range is limited up to 45 psig / 3.1 bar only.
4. Maximum setpoint is limited to 150 psig / 10.3 bar for constructions with Fluorocarbon (FKM) diaphragm.
5. Fluorocarbon (FKM) is limited to 200°F / 93°C hot water.
6. Ethylene Propylene (EPDM) is limited to 20 to 250°F / -7 to 121°C when used with Low Pressure Actuator.
www.sherregulators.com
D103246XUS2
Page 2
Type MR105
Installation
WARNING
!
Only qualied personnel should install
or service a regulator. Regulators should
be installed, operated and maintained
in accordance with international and
applicable codes and regulations and
Emerson Process Management Regulator
Technologies, Inc. instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping uid or bursting of
pressure-containing parts may result if this
regulator is overpressured or is installed
where service conditions could exceed the
limits given in the Specications section or
where conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping uid.
To avoid such injury and damage, install
the regulator in a safe location.
Clean out all pipelines before installation of the regulator
and check to be sure the regulator has not been damaged
or has collected foreign material during shipping. For
NPT bodies, apply pipe compound to the external pipe
threads. For anged bodies, use suitable line gaskets and
approved piping and bolting practices.
Vertical installation with the actuator oriented up or down
is recommended. The unit will operate in horizontal
installation with actuator on the side, however, this could
result in premature wear of parts. Make sure that ow will
be in the same direction as that indicated by the body
arrow. Orientation of the two vents should always be down.
Vents may be rotated after regulator installation so that the
vent screens are down.
A control line must be installed to allow outlet pressure to
register on the actuator’s diaphragm. It should be installed
four to eight pipe diameters downstream of the regulator
and in an area of pipe that is free of turbulence.
Note
It is important that the regulator be installed
so that the vent hole in the spring case
is unobstructed at all times. For outdoor
installations, the regulator should be
located away from vehicular trafc and
positioned so that water, ice and other
foreign materials cannot enter the spring
case through the vent. Avoid placing the
regulator beneath eaves or downspouts and
be sure it is above the probable snow level.
Overpressure Protection
The recommended pressure limitations are stamped
on the regulator nameplate. Some type of overpressure
protection is needed if the actual inlet pressure exceeds the
maximum operating outlet pressure rating. Overpressure
protection should also be provided if the regulator inlet
pressure is greater than the safe working pressure of the
downstream equipment.
Regulator operation below the maximum pressure
limitations does not preclude the possibility of damage
from external sources or debris in the line. The
regulator should be inspected for damage after any
overpressure condition.
Startup
The regulator is set at the factory for the setpoint specied
on the order or at the midpoint of the spring range. The
allowable spring range is stamped on the nameplate. If a
pressure setting other than specied is desired, be sure to
change the pressure setting by following the Adjustment
section. With proper installation completed and relief
valves properly adjusted, slowly open the upstream and
downstream shutoff valves (if applicable).
Adjustment
To change the outlet pressure, loosen the locknut and
turn the adjusting screw clockwise to increase pressure or
counterclockwise to decrease pressure. Monitor the outlet
pressure with a test gauge during the adjustment. Tighten the
locknut to maintain the desired setting.
Taking Out of Service (Shutdown)
WARNING
!
To avoid personal injury resulting from
sudden release of pressure, isolate
the regulator from all pressure before
attempting disassembly.
16 Valve Plug
17 Cage O-ring
18 Travel Indicator Scale
19 Travel Indicator Protector
20 Valve Plug O-ring
21 Lower Indicator Fitting O-ring
22 Flange Nut
23 E-Ring
24 Drive Screw
25 Flow Arrow
26 Vent
27 Plug
28 Spring Seat
29 Hex Nut
30 Pipe Plug
33 NACE Tag (not shown)
34 Seal Wire (not shown)
35 Indicator Fitting
36 Back O-ring
37 Indicator Fitting O-ring
38 Pipe Plug
40 Actuator Stem
43 Nameplate
44 Lube Fitting
45 Wiper Ring
46 Bearing
47 Valve Stem O-ring
48 Jam Nut
49 Spring Washer
51 Lower Diaphragm Head O-ring
52 Lower Spring Guide
53 Lower Diaphragm Head
54 Lower Spring Seat
55 Diaphragm Plate
56 Diaphragm
57 Cap Screw or Stud Bolt
58 Hex Nut
60 Bonnet O-ring
61 Bonnet
62 Lower Diaphragm Casing
63 Upper Diaphragm Casing
64 Spring Case Spacer O-ring
64 Upper Diaphragm Casing O-ring
65 Cap Screw
66 Spring Case Spacer
67 Cap Screw
68 Control Spring
69 Upper Spring Seat
70 Spring Case
71 Seal Washer (not shown)
72 Jam Nut
73 Adjusting Screw
75 Restrictor (not shown)
76 Pipe Bushing
81 Pipe Nipple (not shown)
82 Drain Valve (not shown)
84 Internal Stiffener Plate
85 Bleed Valve (not shown)
87 Upper Casing Welding Assembly (not shown)
69
52
64
66
65
63
56
58
62
51
61
40
17
16
3
43
24
V
X
Z
Y
AA
28
6
21
37
35
8
18
GE38435
23
10
5
W
22
19
Figure 1. Type MR105 Assembly Drawings
25
68
76
26
55
53
65
84
13
12
11
4
9
29
67
57
73
72
70
43
44
30
26
38
1
2
24
3
Page 4
Type MR105
GE38435
36
DETAIL W
15
20
14
DETAIL Y
47
46
45
DETAIL Z
7
46
60
47
DETAIL X
21
27
NO TRAVEL INDICATOR
48
49
DETAIL V
54
64
63
58
56
57
62
53
Figure 1. Type MR105 Assembly Drawings (continued)
Industrial Regulators
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Shanghai 201206, China
Tel: +86 21 2892 9000
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Middle East and Africa
Dubai, United Arab Emirates
Tel: +011 971 4811 8100
Natural Gas Technologies
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Singapore 128461, Singapore
Tel: +65 6770 8337
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Chartres 28008, France
Tel: +33 2 37 33 47 00
Middle East and Africa
TESCOM
Emerson Process Management
Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
+1 800 447 1250
Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287
Asia-Pacic
Shanghai 201206, China
Tel: +86 21 2892 9499
Dubai, United Arab Emirates
Tel: +011 971 4811 8100
For further information visit www.fisherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,
a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties
or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications
of such products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use
and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.