Emerson Lorain BD 800 Data Sheet

Lorain® BD 800
800 Amp Battery Disconnect
Key Features
nSmall footprint and multiple
wiring attachment points allow for ease of installation
nCurrent monitoring is
provided by a 25mV shunt included within each breaker and fuse
nVoltage trip breakers
permit remote shutdown/ disconnect
nSafety features include
a Lock Out-Tag Out (LO/ TO) attachment point and a door latch that is
tool-secured for restricted access
nAlarm options include a
Form C, CBA/FA alarm and a door open alarm
nAn LED indicator provides a
visual display of the status of the breaker/fuse for each
position
nDisconnect assists in
compliance with local codes
Feature-rich design provides flexibility; small footprint allows for relay rack mounting.
586400100 List 1 e/w Fuse
Product Overview
The Lorain® BD 800 provides disconnection and overcurrent protection for +24 VDC or -48VDC battery strings. Disconnects are available in single and dual positions. Over­current protection is provided by a user-specified fuse or breaker rated from 300 to 800 amps per position. A shunt, included with the over-current protection device, measures charge and discharge current and can be monitored by a Lorain Emerson Monitoring Equipment, or any monitoring system using a 25mV shunt input. The disconnect can be wall-mounted or 23" rack mounted as required. Breakers equipped with voltage trip coils can be used to satisfy code requirements for EPO circuits.
The built-in shunt measures charge and discharge current for the batteries. Battery dam­age is prevented and battery life is increased with the use of a built-in PS shunt card and an optional VPS or LVS MCA set up to limit battery recharge current. Voltage trip breakers permit remote operation. An EPO switch may be used to comply with local and national fire codes (NEC).
®
VPS or LVS MCA,
Safety and security features include a cover that can be locked in place during mainte­nance operations to prevent access to the battery breakers or fuses. A door alarm switch provides a set of contacts that will change state whenever the door is opened. Any access or operation of the door can be monitored using this feature. The door latch can also be tool-secured for restricted access.
1011D-LBD800 / 1206
Lorain® BD 800
Application
The Emerson Network Power Battery Disconnect is ideal for a data center, wireless site or central office applications. For additional specification, engineering or installation information, specify model Lorain number 586400100 for disconnect.
Technical Specifications
586400100
Rating (Amps) 300-800 per position Rated Voltage 60VDC Operating Voltage +24VDC/-48VDC Max Size of Overcurrent Device 800 Amps Breaker/Fuse Dimensions (H x W x D) Single: 6U x 21-3/8" x 7-1/4" (265mm x 543mm x 184mm)
Weight Single: Net 40 lbs., Shipping 50 lbs.
Int Rating (kIAC) Fuse/Breaker 100kAIC Fuse/50kAIC / Breaker/10kAIC Disc Compliance UL/cUL Listed to 1801 FA/CBA Alarm Contact Rating 0.5A@125VAC, 1.0A@30VDC, 0.3A@110VDC Door Alarm Contact Rating 1A-125VAC, 2A-24VDC, 0.1A@125VDC (Form C contacts) Operating Temperature 0-40°C Mounting Wall or 23" Relay Rack Mounted
®
BD 800, specification
Dual: 13U x 21-3/8" x 7-1/4" (576mm x 543mm x 184mm)
Dual: Net: 76 lbs., Shipping 90 lbs.
586400100 List 2 e/w Breakers
EmersonNetworkPower.com/EnergySystems (North America) EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2014.
Business-Critical Continuity™, Emerson Network Power™, the Emer son Net work Power l ogo, Emer son™ and Consi der it Solv ed are ser vice mark s and trade -
marks o f Emerson E lectri c Co. Energy Master Power, Ener gy Systems, N orth Am erica, In c. Any other p roduct , brand, or co mpany names o r logos are t he proper ty of the r especti ve owner.
2
, eSure™, NetPerform™, NetReach™, NetSpan™, NetSu re™ and NetXtend™ are trad emarks of E merson Ne twork
While ev ery prec aution has b een taken to e nsure accur acy and completeness herein, Emerson Electric Co. assumes no responsibility, and disc laims all liab ility, for da mages resul ting from u se of this information or for any errors or omissions. Specifications subject to change without notice.
011D-LBD800 / 1206
Loading...