Step 2: Consider Housing Rotation
Step 3: Set Switches and Jumpers
Step 4: Connect Wiring and Power Up
Step 5: Verify Configuration
Step 6: Trim the Transmitter
Safety Instrumented Systems
Product Certifications
Start
End
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
Rosemount 3051S Series Pressure
Transmitter with HART® Protocol
Rosemount 3051SF Series Flowmeter
Transmitter with HART
Beijing Rosemount Far East Instrument
Co., Limited
No. 6 North Street, Hepingli, Dong Cheng District
Beijing 100013, China
T (86) (10) 6428 2233
F (86) (10) 6422 8586
This installation guide provides basic guidelines for Rosemount 3051S
transmitters (reference manual document number 00809-0100-4801). It
also provides the basic electronics guidelines for the 3051SFA
(reference manual document number 00809-0100-4809), 3051SFC
(reference manual document number 00809-0100-4810), and 3051SFP
(reference manual document number 00809-0100-4686). It does not
provide instructions for diagnostics, maintenance, service, or
troubleshooting. This document is also available electronically on
www.rosemount.com.
2
Page 3
Quick Installation Guide
WARNING
00825-0100-4801, Rev HA
February 2008
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in
accordance with the appropriate local, national, and international
standards, codes, and practices. Please review the approvals section of
the 3051S reference manual for any restrictions associated with a safe
installation.
• Before connecting a HART communicator in an explosive
atmosphere, ensure the instruments in the loop are installed in
accordance with intrinsically safe or non-incendive field wiring
practices.
• In an Explosion-Proof/Flame-Proof installation, do not remove the
transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
Rosemount 3051S
3
Page 4
Rosemount 3051S
STEP 1: MOUNTTHE TRANSMITTER
Liquid Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the
drain/vent valves are oriented
upward.
Gas Flow Applications
1. Place taps in the top or side of
the line.
2. Mount beside or above the taps.
Steam Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
4
Page 5
Quick Installation Guide
STEP 1 CONTINUED...
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
Panel MountPipe Mount
PlantWeb™ Junction Box Remote Mount Display
Coplanar™ Flange
Traditional Flange
In-line
Housings
5
Page 6
Rosemount 3051S
STEP 2: CONSIDER HOUSING ROTATION
STEP 3: SET SWITCHESAND JUMPERS
Housing Rotation Set
Screw (3/32-inch)
Alarm
Security
Meter/
Adjustment
Module
Security
Alarm
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
To improve field access to wiring or to
better view the optional LCD display:
1. Loosen the housing rotation set
Figure 1. Transmitter Housing
Set Screw
PlantWebJunction Box
screw.
2. First rotate the housing clockwise
to the desired location. If the
desired location cannot be
achieved due to thread limit,
rotate the housing counter
clockwise to the desired location
(up to 360° from thread limit).
3. Retighten the housing rotation set
screw.
If alarm and security adjustment option is not installed, the transmitter
will operate normally with the default alarm condition alarm high and
the security off.
Figure 2. Transmitter Switch and Jumper Configuration
PlantWebJunction Box
Slide the security and alarm
switches into the preferred position
by using a small screwdriver.
(A LCD display or an adjustment
module must be in place to activate
the switches.)
6
Pull the jumpers out and rotate 90°
into desired position to set the security
and alarm.
Page 7
Quick Installation Guide
STEP 4: CONNECT WIRINGAND POWER UP
RL ≥ 250 Ω
Power
Supply
Power
Supply
RL ≥ 250 Ω
00825-0100-4801, Rev HA
February 2008
Use the following steps to wire the transmitter:
1. Remove the housing cover labeled “Field Terminals.”
2. Connect the positive lead to the “+” terminal, and the negative lead
to the “–” terminal.
NOTE
Do not connect the power across the test terminals. Power could
damage the test diode in the test connection. Twisted pairs yield best
results. For single compartment housing (Junction Box housing),
shielded signal wiring should be used in high EMI/RFI environments.
Use 24 AWG to 14 AWG wire and do not exceed 5,000 feet
(1500 meters).
3. Plug and seal the unused conduit connection.
4. If applicable, install wiring with a drip loop. Arrange the drip loop
so the bottom is lower than the conduit connections and the
transmitter housing.
5. Replace the housing cover.
The figures below show the wiring connections necessary to power a
3051S and enable communications with a hand-held HART
communicator.
Installation of the transient protection terminal block does not
provide transient protection unless the 3051S case is properly
grounded.
7
Page 8
Quick Installation Guide
STEP 4 CONTINUED...
Rosemount 3051S
00825-0100-4801, Rev HA
February 2008
Remote Display Wiring and Power Up
The Remote Mount Display and Interface system consists of a local
transmitter and a remote mount LCD display assembly. The local
3051S transmitter assembly includes a Junction Box housing with a
three position terminal block integrally mounted to a SuperModule.
The remote mount LCD display assembly consists of a dual
compartment PlantWeb housing with a seven position terminal block.
See Figure 4 on page 9 for complete wiring instructions. The following
is a list of necessary information specific to the Remote Mount Display
system:
• Each terminal block is unique for the remote display system.
• A 316 SST housing adapter is permanently secured to the remote
mount LCD display PlantWeb housing providing an external
ground and a means for field mounting with the provided mounting
bracket.
• A cable is required for wiring between the transmitter and remote
mount LCD display. The cable length is limited to 100 ft.
• 50 ft. (option M8) or 100 ft. (option M9) cable is provided for wiring
between the transmitter and remote mount LCD display. Option
M7 does not include cable; see recommended specifications
below:
Cable type: Recommend Belden 3084A DeviceNet cable or Belden
123084A Armored DeviceNet cable. Other comparable cable may be
used as long as it has independent dual twisted shielded pair wires
with an outer shield. The Power wires must be 22 AWG minimum and
the CAN communication wires must be 24 AWG minimum.
Cable length: Up to 100 feet depending upon cable capacitance.
Cable capacitance: The capacitance from the CAN communications
line to the CAN return line as wired must be less than 5000 picofarads
total. This allows up to 50 picofarads per foot for a 100 foot cable.
8
Page 9
Quick Installation Guide
STEP 4 CONTINUED...
4-20 mA
(white) 24 AWG
(blue) 24 AWG
(black) 22 AWG
(red) 22 AWG
00825-0100-4801, Rev HA
February 2008
Intrinsic Safety Consideration: The transmitter assembly with
remote display has been approved with Belden 3084A DeviceNet
cable. Alternate cable may be used as long as the transmitter with
remote display and cable is configured according to the installation
control drawing or certificate. Refer to appropriate approval certificate
or control drawing in Appendix B of the 3051S reference manual for
remote cable IS requirements.
IMPORTANT
Do not apply power to the remote communications terminal. Follow
wiring instructions carefully to prevent damage to system components.
Figure 4. Remote Mount Display wiring diagram
Junction Box HousingRemote Mount Display
Rosemount 3051S
9
Page 10
Quick Installation Guide
STEP 4 CONTINUED...
Straight Field
Wireable
Connector
(1)(3)
Right Angle Field Wireable
Connector
(2)(3)
Coupling Nut
Cordset
(4)
Quick Connect
Housing
Quick Connect Coupling Nut
(1) Order part number
03151-9063-0001.
(2) Order part number
03151-9063-0002.
(3) Field wiring supplied by customer.
(4) Supplied by cordset vendor.
Rosemount 3051S
NOTE
Wire colors provided on page 9 are per Belden 3084A DeviceNet
cable. Wire color may vary depending on cable selected.
Belden 3084A DeviceNet cable includes a ground shield. This shield
must be connected to earth ground at either the SuperModule or the
Remote Display, but not both.
00825-0100-4801, Rev HA
February 2008
Quick Connect Wiring
As standard, the 3051S Quick Connect arrives properly assembled to
the SuperModule and is ready for installation. Cordsets and Field
Wireable Connectors (in shaded area) are sold separately.
If Quick Connect is ordered as a 300S spare housing or is removed
from the SuperModule, follow the instructions below for proper
assembly prior to field wiring.
1. Place the Quick Connect onto the SuperModule. To ensure proper
pin alignment, remove coupling nut prior to installing quick connect
onto SuperModule.
10
Page 11
Quick Installation Guide
STEP 4 CONTINUED...
“+”
“–”
Ground
No Connection
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
2. Place coupling nut over quick connect and wrench tighten to a
maximum of 300 in-lb. (34 N-m).
3. Tighten the set screw using a
3
/32-in hex wrench.
4. Install Cordset/ Field Wireable Connectors onto the Quick Connect.
Do not over tighten.
Figure 6. Quick Connect Housing Pin-Out
For other wiring
details, refer to pin-out
drawing and the
cordset
manufacturer’s
installation
instructions.
Conduit Electrical Connector Wiring (Option GE or GM)
For 3051S transmitters with conduit electrical connectors GE or GM,
refer to the cordset manufacturer’s installation instructions for wiring
details. For FM Intrinsically Safe, non-incendive or FM FISCO
Intrinsically Safe hazardous locations, install in accordance with
Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X
and IP66.) See Appendix B of the 3051S reference manual.
11
Page 12
Quick Installation Guide
STEP 4 CONTINUED...
Voltage (V dc)
Load (Ohms)
Operating
Region
1387
1000
500
0
10.52030
42.4
Voltage (V dc)
Load (Ohms)
Operating
Region
1322
1000
500
0
12.02030
42.4
Rosemount 3051S
00825-0100-4801, Rev HA
February 2008
Power Supply
The dc power supply should provide power with less than two percent
ripple. The total resistance load is the sum of the resistance of the
signal leads and the load resistance of the controller, indicator, and
related pieces. Note that the resistance of intrinsic safety barriers, if
used, must be included.
Figure 7. Load Limitation
Standard Transmitter
Maximum Loop Resistance =
43.5 * (Power Supply Voltage – 10.5)
The HART communicator requires a minimum loop
resistance of 250Ω for communication.
HART Diagnostics Transmitter
(option code DA1)
Maximum Loop Resistance =
43.5 * (Power Supply Voltage – 12.0)
12
Page 13
Quick Installation Guide
STEP 5: VERIFY CONFIGURATION
00825-0100-4801, Rev HA
February 2008
Use any HART-compliant master to communicate with and verify
configuration of the 3051S. For the HART Diagnostics transmitter
(option code DA1), DD revision 3051S HDT Dev. 1 Rev. 1 is required.
A check (⻫) indicates the basic configuration parameters. At a
minimum, these parameters should be verified as part of the
configuration and startup procedure.
Ta g 1, 3, 1
Temperature Alert Configuration 1, 4, 3, 5, 4
⻫
Transfer Function
(Setting Output Type)
Transmitter Security (Write Protect)1, 3, 4, 5
⻫
Units (Process Variable)1, 3, 2
Upper Sensor Trim1, 2, 3, 3, 3
Zero Trim1, 2, 3, 3, 1
February 2008
1, 3, 5
14
Page 15
Quick Installation Guide
STEP 6: TRIM THE TRANSMITTER
00825-0100-4801, Rev HA
February 2008
Transmitters are shipped fully calibrated per request or by the factory
default of full scale (lower range value = zero, upper range value =
upper range limit).
Rosemount 3051S
Zero Trim
A zero trim is a single-point adjustment used for compensating
mounting position and line pressure effects. When performing a zero
trim, ensure that the equalizing valve is open and all wet legs are filled
to the correct level.
If zero offset is less than 3% of true zero, follow the “Using the HART
Communicator” instructions below to perform a zero trim. If zero offset
is greater than 3% of true zero, follow the “Using the Transmitter Zero
Adjustment Button” instructions below to rerange. If hardware
adjustments are not available, see the 3051S Reference Manual
(document number 00809-0100-4801) to perform a rerange using the
HART Communicator.
Using the HART Communicator
HART Fast Keys Steps
1, 2, 3, 3, 11. Equalize or vent the transmitter and connect HART
communicator.
2. At the menu, input the HART Fast Key sequence.
3. Follow the commands to perform a zero trim.
15
Page 16
Quick Installation Guide
Span
Zero
Span
Zero
Rosemount 3051S
Using the Transmitter Zero Adjustment Button
Push and hold the zero adjustment button for at least two seconds but
no longer than ten seconds.
Figure 8. Transmitter Adjustment Buttons
PlantWebJunction Box
00825-0100-4801, Rev HA
February 2008
16
Page 17
Quick Installation Guide
SAFETY INSTRUMENTED SYSTEMS
Revision #’s
Fld Dev Rev7
Software Rev7
Hardware Rev16
00825-0100-4801, Rev HA
February 2008
Additional Safety Instrumented Systems information is available in the
Rosemount 3051S reference manual (document number
00809-0100-4801). The manual is available electronically on
www.rosemount.com or by contacting an Emerson Process
Management representative.
Rosemount 3051S
3051S Safety-Certified Identification
All 3051S transmitters must be identified as safety-certified before
installing into SIS systems.
NOTE
There are two versions of safety-certified 3051S pressure transmitters.
For transmitters with a yellow SIS circuit board installed and output
code B in the model number, please refer to Manual Supplement
00809-0700-4801.
To identify a safety-certified 3051S:
1. Connect a HART host to the transmitter.
2. Check the software to verify that the software revision is 7 or
higher.
Fast Key Sequence - 1, 5
3. Verify that option code QT is included in the transmitter model
code.
17
Page 18
Quick Installation Guide
Rosemount 3051S
00825-0100-4801, Rev HA
February 2008
Installation
No special installation is required in addition to the standard
installation practices outlined in this document. Always ensure a
proper seal by installing the electronics housing covers so that metal
contacts metal.
The loop should be designed so the terminal voltage does not drop
below 10.5 Vdc when the transmitter output is 23.0 mA.
If hardware security switches are installed, the security switch should
be in the “ON” position during normal operation. See Figure 2 on
page 6. If hardware security switches are not installed, security should
be “ON” in the software to prevent accidental or deliberate change of
configuration data during normal operation.
Configuration
Use any HART-compliant master to communicate with and verify
configuration of the 3051S Safety-Certified Pressure Transmitter (see
Table 1 on page 13 and 14 to verify configuration).
User-selected damping will affect the transmitters ability to respond to
changes in the applied process. The damping value + response time
should not exceed the loop requirements.
18
Page 19
Quick Installation Guide
Normal Operation
4 mA
20 mA
20.8 mA
high saturation
21.75
(2)
3.9 mA
low saturation
3.75 mA
(1)
Normal Operation
4 mA
20 mA
20.5 mA
high saturation
22.5
(2)
3.8 mA
low saturation
3.6 mA
(1)
Normal Operation
4 mA
20 mA
20.1 - 20.5 mA
high saturation
20.2 - 23.0
(2)
3.7 - 3.9 mA
low saturation
3.6 - 3.8 mA
(1)
00825-0100-4801, Rev HA
February 2008
NOTES
1. Transmitter output is not safety-rated during the following:
configuration changes, multidrop, loop test. Alternative means should
be used to ensure process safety during transmitter configuration and
maintenance activities.
2. DCS or safety logic solver should be configured to match transmitter
configuration. Figure 9 identifies the three alarm levels available and
their operation values.
Rosemount 3051S
Figure 9. Alarm Levels
Rosemount Alarm Level
Namur Alarm Level
Custom Alarm Level
(1) Transmitter Failure, hardware or software alarm in LO position.
(2) Transmitter Failure, hardware or software alarm in HI position.
(3) High alarm must be at least 0.1 mA higher than the high saturation value.
(4) Low alarm must be at least 0.1 mA lower than the low saturation value.
(3)(4)
19
Page 20
Quick Installation Guide
Rosemount 3051S
Setting the alarm values and direction is dependent on whether or not
the hardware switch option is installed. You can use a HART master or
communicator to set the Alarm and Saturation values.
Switches installed
1. If using a communicator, use the following fast key sequence to set
the Alarm and Saturation values.
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
2. Manually set the direction for the Alarm to HI or LO using the
ALARM switch as shown in Figure 2 on page 6.
Switches not installed
If using a communicator, use the following fast key sequence to set the
Alarm and Saturation values and the Alarm Direction:
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
Alarm Direction Fast Key; 1, 4, 2, 7, 6
00825-0100-4801, Rev HA
February 2008
20
Page 21
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
Operation and Maintenance
Proof Test and Inspection
The following proof tests are recommended. Proof test results
and corrective actions taken must be documented at
www.emersonprocess.com/rosemount/safety/certtechdocumentation.
htm in the event that an error is found in the safety functionality.
Use "Table 1: HART Fast Key Sequence" to perform a Loop Test,
Analog Output Trim, or Sensor Trim. See the 3051S reference manual
for additional information.
Proof Test 1
Conducting an analog output Loop Test satisfies the proof test
requirements and will detect more than 52% of DU failures not
detected by the 3051S_C or 3051S_L automatic diagnostics, and
more than 62% of DU failures not detected by the 3051S_T automatic
diagnostics.
Required tools: HART host/communicator and mA meter.
1. On HART host/communicator enter the Fast Key Sequence 1, 2, 2.
2. Select “4 Other.”
3. Enter the milliampere value representing a high alarm state.
4. Check the reference meter to verify the mA output corresponds to
the entered value.
5. Enter the milliampere value representing a low alarm state.
6. Check the reference meter to verify the mA output corresponds to
the entered value.
7. Document the test results per your requirements.
21
Page 22
Quick Installation Guide
Rosemount 3051S
Proof Test 2
This proof test, when combined with the Proof Test 1, will detect over
92% of DU failures not detected by the 3051S_C or 3051S_L
automatic diagnostics, and over 95% of DU failures not detected by
the 3051S_T automatic diagnostics.
Required tools: HART host/communicator and pressure calibration
equipment.
1. Perform a minimum two point sensor calibration check using the
4-20mA range points as the calibration points.
2. Check the reference mA meter to verify the mA output corresponds
to the pressure input value.
3. If necessary, use one of the “Trim” procedures available in the
3051S reference manual to calibrate.
4. Document the test results per your requirements.
NOTE
The user determines the proof-test requirements for impulse piping.
Visual Inspection
Not required.
Special Tools
Not required.
Product Repair
All failures detected by the transmitter diagnostics or by the proof-test
must be reported. Feedback can be submitted electronically at
The 3051S is repairable by major component replacement. Follow the
instructions in the 3051S reference manual (document number
00809-0100-4801) for additional information.
00825-0100-4801, Rev HA
February 2008
22
Page 23
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
Reference
Certification
The 3051S Safety-Certified Pressure Transmitter was designed,
developed, and audited to be compliant to IEC 61508 safety-certified
SIL 2 Claim Limit.
Specifications
The 3051S Safety-Certified Pressure Transmitter must be operated in
accordance to the functional and performance specifications provided
in the 3051S reference manual.
Failure Rate Data
The FMEDA report includes failure rates and common cause Beta
factor estimates. This report is available at
Self-diagnostics Test Interval: At least once per hour
Product Life
50 years – based on worst case component wear-out mechanisms –
not based on wear-out process wetted materials.
(1)
(1) A 2% variation of the transmitter mA output is allowed before a safety trip. Trip
values in the DCS or safety logic solver should be derated by 2%.
23
Page 24
Quick Installation Guide
PRODUCT CERTIFICATIONS
Rosemount 3051S
00825-0100-4801, Rev HA
February 2008
Approved Manufacturing Locations
Rosemount Inc. — Chanhassen, Minnesota USA
Fisher-Rosemount GmbH & Co. — Wessling, Germany
Emerson Process Management Asia Pacific Private Limited — Singapore
Beijing Rosemount Far East Instrument Co., LTD — Beijing, China
Emerson Process Management LTDA — Sorocaba, Brazil
Emerson Process Management (India) Pvt. Ltd. — Daman, India
European Directive Information
The EC declaration of conformity can be found on page 32. The most
recent revision can be found at www.rosemount.com.
Ordinary Location Certification for FM Approvals
As standard, the transmitter has been examined and tested to determine
that the design meets basic electrical, mechanical, and fire protection
requirements by FM Approvals, a nationally recognized testing laboratory
(NRTL) as accredited by the Federal Occupational Safety and Health
Administration (OSHA).
24
Page 25
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
Hazardous Locations Certifications
North American Certifications
FM Approvals
E5Explosion proof for Class I, Division 1, Groups B, C, and D;
dust-ignition proof for Class II and Class III, Division 1, Groups E,
F, and G; hazardous locations; enclosure Type 4X, conduit seal
not required when installed according to Rosemount drawing
03151-1003.
I5Intrinsically Safe for use in Class I, Division 1, Groups A, B, C,
and D; Class II, Division 1, Groups E, F, and G; Class III, Division
1; Class I, Zone 0 AEx ia IIC when connected in accordance with
Rosemount drawing 03151-1006; Non-incendive for Class I,
Division 2, Groups A, B, C, and D, Enclosure Type 4X
For entity parameters see control drawing 03151-1006.
Canadian Standards Association (CSA)
E6Explosion-Proof for Class I, Division 1, Groups B, C, and D;
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups
E, F, and G; suitable for Class I, Division 2, Groups A, B, C, and
D, when installed per Rosemount drawing 03151-1013, CSA
Enclosure Type 4X; conduit seal not required.
I6Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D
when connected in accordance with Rosemount drawings
03151-1016;
For entity parameters see control drawing 03151-1016.
25
Page 26
Quick Installation Guide
Rosemount 3051S
00825-0100-4801, Rev HA
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: BAS01ATEX1303X II 1 G
EEx ia IIC T4 (T
1. The apparatus, excluding the Types 3051 S-T and 3051 S-C
(In-line and Coplanar SuperModule Platforms respectively), is
not capable of withstanding the 500V test as defined in Clause
6.4.12 of EN 50020. This must be considered during
installation.
2. The terminal pins of the Types 3051 S-T and 3051 S-C must
be protected to IP20 minimum.
N1ATEX Type n
Certificate No.: BAS01ATEX3304X II 3 G
EEx nL IIC T4 (T
Ui = 45 Vdc max
IP66
= -60 °C to 70 °C)
a
= -40 °C TO 70 °C)
a
February 2008
26
Page 27
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Special Conditions for Safe Use (x)
The apparatus is not capable of withstanding the 500V insulation
test required by Clause 9.1 of EN 50021: 1999. This must be
taken into account when installing the apparatus.
ND ATEX Dust
Certificate No.: BAS01ATEX1374X II 1 D
T105°C (-20 °C ≤ T
= 42.4 volts max
V
max
A = 24 mA
IP66
1180
Special Conditions for safe use (x):
1. The user must ensure that the maximum rated voltage and
current (42.4 volts, 22 milliampere, DC) are not exceeded. All
connections to other apparatus or associated apparatus shall
have control over this voltage and current equivalent to a
category “ib” circuit according to EN 50020.
2. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking plugs
which maintain the ingress protection of the enclosure to at
least IP66.
4. Cable entries and blanking plugs must be suitable for the
ambient range of the apparatus and capable of withstanding a
7J impact test.
5. The 3051S must be securely screwed in place to maintain the
ingress protection of the enclosure. (The 3051S SuperModule
must be properly assembled to the 3051S housing to maintain
ingress protection.)
amb
≤ 85 °C)
Rosemount 3051S
27
Page 28
Quick Installation Guide
Rosemount 3051S
E1ATEX Flame-Proof
Certificate No.: KEMA00ATEX2143X II 1/2 G
EEx d IIC T6 (-50 °C ≤ T
EEx d IIC T5 (-50 °C ≤ T
= 42.4V
V
max
1180
Special conditions for safe use (x)
This device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the environmental
conditions to which the diaphragm will be subjected. The
manufacturer’s instructions for installation and maintenance
shall be followed in detail to assure safety during its expected
lifetime. The Model 3051S pressure transmitter must include a
Series 300S housing integrally mounted to a Series Model
3051S Sensor module as per Rosemount drawing 03151-1023.
Certification No.: AUS Ex 3798X
Ex d IIC T6 (T
DIP A21 TA T6 (T
Conditions for safe use (X)
1. It is a condition of safe use that each housing shall be
connected to external circuits via suitable conduit of Standards
Australia certified cable glands. Where only one entry is used
for connection to external circuits, the unused entry shall be
closed by means of the blanking plug supplied by the
equipment manufacturer or by a suitable Standards Australia
certified blanking plug.
2. It is a condition of safe use that dielectric strength test shall be
applied whenever the terminal block is changed or replaced in
either the dual compartment or single compartment housings.
The breakdown current shall be less than 5 mA, when 500 V,
47 to 62 Hz, is applied for one minute. Note: if tested with an
optional T1 transient protector terminal block fitted, the
protection will operate and hence there will be no current
indicated.
3. It is a condition of safe use that each transmitter module shall
be used with a Model 300S housing, in order to comply with
Flame-Proof requirements.
4. It is a condition of safe use that each Model 300S housing
fitted with a transmitter module shall be marked with the same
certification marking code information. Should the housing be
replaced after initial supply to another Model 300S housing,
the replacement housing shall have the same certification
marking code information as the housing it replaces.
1. The 3051S HART 4-20mA, 3051S F
3051S Profibus and 3051S FISCO are not capable of
withstanding the 500V test as defined in clause 6.4.12 of IEC
60079-11. This must be taken into account during installation.
2. The terminal pins of the Types 3051S-T and 3051S-C must be
protected to IP20 minimum.
N7IECEx Type n
Certificate No.: IECExBAS04.0018X
Ex nC IIC T4 (Ta = -40 °C to 70 °C)
Ui = 45 Vdc MAX
IP66
Conditions for safe use (X)
The apparatus is not capable of withstanding the 500 V
insulation test required by Clause 8 of IEC 79-15: 1987.
= -60 °C to 70 °C)
a
00825-0100-4801, Rev HA
February 2008
OUNDATION fieldbus,
30
Page 31
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is
specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval types.
Permanently mark the approval label to distinguish it from unused
approval types.
K1Combination of E1, I1, N1, and ND
K5Combination of E5 and I5
K6Combination of E6 and I6
K7Combination of E7, I7, and N7
KA Combination of E1, I1, E6, and I6
KB Combination of E5, I5, I6 and E6
KC Combination of E5, E1, I5 and I1
KD Combination of E5, I5, E6, I6, E1, and I1
31
Page 32
Rosemount 3051S
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
DOC
32
Page 33
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
33
Page 34
Rosemount 3051S
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
34
Page 35
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
35
Page 36
Rosemount 3051S
NOTES
Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.