Det-Tronics X3301 User Manual

4 (1)
Det-Tronics X3301 User Manual

Addendum 95-8577

HART® Communication with the

X3301Multispectrum IR Flame Detector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.1

 

 

 

 

 

 

 

Rev: 10/13

95-8577

 

 

 

 

 

 

 

Table Of Contents

 

Interconnecting the HART Communicator with the Detector. . . . . .

. 1

HART Device Description Language. . . . . . . . . . . . . . . . . . . . . . . .

. 3

Detector Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 3

HART Menu Structure.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 4

X3301 Root Menu.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 5

Device Info Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 5

General Info Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 6

HART Info Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 7

HART PV Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 8

Condensed Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 9

Status Info Menu.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 10

Hardware Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

oi Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 12

Detector Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 13

History Menu.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 13

Command Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 14

HART CMD Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 15

Device Setup Menu.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 15

Configuration Menu.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 16

Calibration Menu.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 16

Write Protect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 17

HART Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 17

Set Real Time Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 18

ADDENDUM

HART Communication

with the X3301

Multispectrum IR Flame Detector

Digital communication with the X3301 allows the operator to monitor the status of the detector, determine factory settings, adjust field settings, and initiate field tests. This addendum provides guidance for establishing HART communication, and describes the HART menu structure when using the X3301 with a HART Handheld Communicator, a PC, or other process interface device that supports DDL.

NOTE

A minimum level of understanding with regard to the operation and navigation of the HART Communicator is required. Refer to the instruction manual supplied with the HART Communicator for basic operating instructions.

INTERCONNECTING THE HART COMMUNICATOR WITH THE DETECTOR

Point-to-Point Mode

The HART Communicator can connect to the X3301 at any wiring termination point in the analog output signal loop. Connect the HART communicator in parallel with the X3301 analog signal or load resistor. The HART connections are non-polarized.

IMPORTANT WIRING NOTE

The HART Communicator does not measure loop current directly, but instead reads a voltage signal across a resistance (250 ohms) in the loop. The recommended connection point is across the input impedance of the signal receiver (PLC), which is a nominal 250 ohms. See Figures 1 to 4. If testing/ programming on a bench, a 250 ohm load resistor must be used. See Figure 5.

Switch on the HART Communicator. If a device is found, the HART Communicator displays the Main menu. If no device is found, check the connections and verify the presence of a minimum of 250 ohms load resistance in series in the loop.

3..1

©Detector Electronics Corporation 2013

Rev: 10/13

95-8577

 

PLC

600 Ω MAX*

AT

24 VDC

 

+

 

 

mA

 

+

 

24 VDC

 

 

B2262

X3301 IR DETECTOR

 

 

 

 

 

 

 

 

 

 

 

 

9

mA +

 

19

mA –

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

mA + REF

18

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

17

 

27

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

16

 

26

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

15

 

25

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

14

 

24

 

 

 

3

 

 

13

 

23

 

 

 

 

24 VDC +

 

 

 

 

 

 

2

12

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

24 VDC –

11

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 1—X3301 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sourcing)

 

PLC

600 Ω MAX*

AT

24 VDC

 

+

 

 

mA

 

+

 

24 VDC

 

 

B2264

24 VDC

 

X3301 IR DETECTOR

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

mA +

19

mA –

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

18

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

17

 

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

16

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

15

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

14

 

24

 

 

 

 

 

 

3

 

13

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

24 VDC +

12

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

24 VDC –

 

 

 

 

 

 

 

 

 

1

11

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2—X3301 Detector Wired for Isolated 0 to 20 mA Current Output (Sourcing)

 

PLC

600 Ω MAX*

AT

24 VDC

 

+

 

 

mA

 

+

 

24 VDC

 

 

B2263

X3301 IR DETECTOR

 

 

9

mA +

 

19

mA –

29

 

 

8

 

 

18

mA – REF

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

17

 

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

16

 

26

 

 

 

 

 

 

 

 

 

 

5

 

 

15

 

25

 

 

 

 

 

 

 

 

 

 

4

 

 

14

 

24

 

 

3

 

 

13

 

23

 

 

 

24 VDC +

 

 

 

 

 

2

12

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

1

24 VDC –

11

 

21

 

 

 

 

 

 

 

 

 

 

 

Figure 3—X3301 Detector Wired for Non-Isolated 0 to 20 mA Current Output (Sinking)

 

PLC

600 Ω MAX*

AT

24 VDC

 

+

 

 

mA

 

+

 

24 VDC

 

 

B2265

 

24 VDC

 

 

 

 

 

 

 

 

+

 

 

X3301 IR DETECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

mA +

 

19

mA –

29

 

 

 

 

 

 

 

 

8

 

 

18

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

17

 

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

16

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

15

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

14

 

24

 

 

 

 

 

 

 

 

3

 

 

13

 

23

 

 

 

 

 

 

 

 

 

24 VDC +

 

 

 

 

 

 

 

 

 

 

 

2

12

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

24 VDC –

11

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4—X3301 Detector Wired for Isolated 0 to 20 mA Current Output (Sinking)

*Nominal input impedance of PLC = 250 ohms.

Maximum loop impedance including input impedance of PLC = 600 ohms.

 

 

 

 

 

 

 

 

 

 

X3301 IR DETECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

mA +

 

 

19

mA –

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mA – REF

 

 

 

 

 

 

 

 

 

8

 

 

 

18

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250 Ω

7

 

 

17

 

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

16

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

15

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

14

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

13

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

24 VDC +

 

 

 

 

 

 

 

 

 

2

12

 

22

 

 

 

 

 

 

 

 

 

24 VDC

 

 

 

 

 

 

 

 

 

 

1

24 VDC –

11

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B2261

Figure 5—Wiring the X3301 for Benchtop Testing/Programming Using HART Protocol

3.1

2

95-8577

Multidrop Mode

Optical flame detectors are life safety devices and require the 4-20 mA loop for transmitting important detector status data. They should not be used in conjunction with multidrop mode. If multidrop mode is a requirement, the alarm and fault relay contacts must be connected directly to the safety system or fire panel for signalling purposes.

NOTE

This addendum covers HART wiring only. Refer to the device instruction manual for NFPA-72 compliant releasing wiring diagrams.

HART DEVICE DESCRIPTION LANGUAGE

The HART protocol incorporates a concept called the Device Description Language (DDL) that enables all suppliers of HART instruments to define and document their products in a single consistent format. This format is readable by handheld communicators, PCs and other process interface devices that support DDL. DDL enables full interoperability of devices, regardless of manufacturer, allowing full functionality from any HART device.

In the event that your Communicator does not establish communications with the X3301, ensure that the appropriate DDLs for the X3301 have been programmed into your Communicator. To review the DDLs programmed into your HART Communicator:

1.From the Main menu, access the Offline menu.

2.From the Offline menu, select New Configuration to access the list of device descriptions programmed into the HART Communicator.

3.Select Det-Tronics and review the list of models to determine if the X3301 DDLs are installed in your Communicator.

If the X3301 DDLs have not been programmed into the Memory Module, you must use the generic interface built into your HART Communicator.

The HART Communication Foundation manages a library of Manufacturer Device Descriptions, which are distributed to programming sites for inclusion in master devices. A complete listing of the HCF DD Library is available for download in manufacturer and device type sequence at http://www.hartcommproduct.com/.

DETECTOR WIRING

Refer to the X3301 instruction manual (form number 95-8527) for complete instructions regarding detector installation and wiring. However, note that the device power consumption specifications for the HART model are different than the standard model.

Power Consumption Specifications of X3301 Detector with HART Communication

Without heater: 4.7 watts at 24 Vdc nominal;

6.1watts at 24 Vdc in alarm.

5.5watts at 30 Vdc nominal;

7.4watts at 30 Vdc in alarm.

Heater only: 8 watts maximum.

Total power: 17 watts at 30 Vdc with EOL resistor installed and heater on maximum.

EOL resistor must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 1.5 watts.

3.1

3

95-8577

HART MENU STRUCTURE

X3301 Root Menu

 

Device Info Menu

1)

Fire

(Yes/No)

1)

General Info Menu

2)

Fault

(Yes/No)

2)

HART Info Menu

3)

Device Info Menu

 

3)

Status Info Menu

4)

Command Menu

4)

Detector Settings

5)

Device Setup Menu

5)

History Menu

Command Menu

1) Start Passive oi

2) Start Active oi

3) Clear oi Fault

4) Reset Latches

5) Master Reset

6) Clear Data Log

7) HART Command Menu

HART Command Menu

1)

Self Test

2)

Master Reset

3)

Loop Test

Device Setup Menu

1) Configuration Menu

2) Calibration Menu

3) Write Protect

4) HART Setup

5) Set Real Time Clock

General Info Menu

 

 

 

 

HART PV Menu

1)

Manufacturer

1)

PV Unit

2)

Model

 

2)

PV

3)

Serial Number

3)

PV SNSR Unit

4)

Part Number

4)

PV USL

5)

Manufactured Date

5)

PV LSL

6)

Snsr Fmwr Ver

6)

PV MIN SPAN

7)

HART Fmwr Ver

 

 

7)

PV DAMP

8)

Real Time Clock

 

8)

PV AO

9)

Write Protect (Y/N)

 

9)

PV AO ALRM TYP

 

 

 

 

 

 

 

10) PV % RNGE

HART Info Menu

 

 

 

 

11) PV XFER FNCTN

 

 

 

 

12) PV RNGE Unit

1)

Universal Rev

 

 

 

 

 

 

 

 

13) PV URV

2)

Field Device Rev

 

 

 

 

 

 

 

 

14) PV LRV

3)

Final Asmbly No.

 

 

 

 

 

 

 

 

15) PV SNSR S/N

4)

Tag

 

 

 

 

 

 

 

 

 

 

 

 

5)

Date

 

 

 

 

 

Condensed Status

6)

Descriptor

 

 

 

 

7)

Message

 

 

1)

Xmtr Addstatus 0

8)

Num Req Preams

 

2)

Xmtr Addstatus 1

9)

HART PV Menu

 

 

3)

Xmtr Addstatus 2

 

 

10) Condensed Status

4)

Xmtr Addstatus 3

 

 

 

5)

Operating Mode

Status Info Menu

6)

Operating Mode 2

 

 

 

 

 

 

1) Warmup (Y/N)

 

 

 

 

 

 

2)

Fire (Y/N)

 

 

 

 

 

 

 

3) Auto oi Fault (Y/N)

 

 

 

 

Hardware Menu

4)

Dim Detect Fault (Y/N)

 

 

 

 

5)

Detect Disable Flt (Y/N)

1)

Heater Power

6)

Snsr Hdwr Fault (Y/N)

2)

Heater Setpoint

7) HIB Hdwr Fault (Y/N)

3)

Temperature

8) Int Comm Fault

 

 

 

4)

Temp Setpoint

9) Incompatible Flt

 

5)

Temp Range Fault

10) Voltage Fault (Y/N)

 

6)

Voltage

11) Hardware Menu

 

7)

Volt Range Fault

12) oi Menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

oi Menu

Detector Settings

 

1)

Left oi

1)

Fire Relay

(L/NL)

 

2)

Middle oi

2)

Fire Relay

(NDE/NE)

 

3)

Right oi

3)

Fault Relay

(L/NL)

 

 

 

 

4)

Cons oi Fails

4)

Fault Relay

(NDE/NE)

5)

No. oi Failures

5) Aux Relay

(L/NL)

6)

oi Cal Active

6) Aux Relay (NDE/NE)

7)

oi Cal Fault

7)

Sensitivity

(VH/H/M/L)

8)

Manual oi Active

8)

Response

(.5/3/6/9)

9)

Manual oi Fail

History Menu

1)Alarm Log

2)Fault Log

3)General Log

Configuration Menu

1)Edit Cons oi Fails

2)Edit Temp Setpoint

3)Edit Heater Setpoint

Calibration Menu

1)Loop Test

2)D/A Trim

3)Calibrate oi

Write Protect

1)Set Password

2)Set Write Protect

3)Write Protect (Y/N)

HART Setup

1)Polling Address

2)Final Asmbly No.

3)Tag

4)Date

5)Descriptor

6)Message

Set Real Time Clock

1)Seconds

2)Minutes

3)Hours

4)Date

5)Month

6)Year

3.1

4

95-8577

X3301 ROOT MENU

When HART communication is established, the first menu displayed is the X3301 Root menu:

X3301 Root Menu

1)Fire (Yes/No)

2)Fault (Yes/No)

3)Device Info Menu

4)Command Menu

5)Device Setup Menu

1)

Fire (Yes/No)

Indicates “Y” if the device is in a fire alarm status — analog output is at 20 mA, fire alarm

 

 

relay is actuated and LED is red.

2)

Fault (Yes/No)

Indicates “Y” if a fault condition exists. Go to “Device Info” and select “Status Info” to

 

 

determine the nature of the fault.

3)

Device Info Menu

Provides access to manufacturer and HART information, current device status, factory

 

 

settings, and history logs.

4) Command Menu

This menu allows the operator to initiate a manual oi test and also to perform various reset/

 

 

clear functions.

5)

Device Setup Menu

This menu allows various setup, configuration and calibration functions.

DEVICE INFO MENU

This menu allows access to a variety of “read only” information.

X3301 Root Menu

 

Device Info Menu

1)

Fire

(Yes/No)

1)

General Info Menu

2)

Fault

(Yes/No)

 

 

2)

HART Info Menu

3)

Device Info Menu

 

3)

Status Info Menu

4)

Command Menu

4)

Detector Settings

5)

Device Setup Menu

5)

History Menu

1) General Info Menu

Factory information.

2) HART Info Menu

HART Specific Variables.

3)Status Info Menu Current operating status and/or diagnostic information.

4)Detector Settings Factory settings relating to relay operation, detector sensitivity and response.

5) History Menu

Display log files: Alarm, Fault, General.

3.1

5

95-8577

Loading...
+ 14 hidden pages