Det-Tronics UD10 User Manual

0 (0)

Instructions 95-8661

FlexVu® Explosion-Proof

Universal Display Unit

Model UD10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.2

 

 

 

 

 

 

 

Rev: 9/12

95-8661

 

 

 

 

 

 

 

Table of Contents

application . . . . . . . . . . . . . . . . . . .

. .

.1. . .

.Appendix. . . .

H — UD10 WITH pir9400 pointwatch

. .H-1

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . .

. .

 

..1. . .

. Wiring .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

H-1

HART Communication

 

 

3

 

Installation Notes . . . . . . . . . . . . . . . . . . . . .

. .

H-2

. .

 

 

Orientation

 

H-2

Magnetic Switches . . . . . . . . . . . . . . .

.

 

 

 

. .

 

..3. . . . . .

 

 

 

Relays

 

 

4

 

Changing Operating Modes . . . . . . . . . . . . .

. .

H-3

. .

 

 

Calibration . . . . . . . . . . . . . . . . . . . . .

. .H.-3. . .

4-20 mA Output Modes

 

 

4

 

. .

 

 

Menu Structure

 

H-4

Modbus / Fieldbus Compatibility . . . . . . . .

.

 

..4. . .

 

. .

 

 

 

 

 

 

Device Enclosure . . . . . . . . . . . . . . .

. .

.4 . . . . . .

 

 

I-1

 

 

 

 

Appendix I — UD10 WITH model pirecl . . . . . . .

. .

Device Display . . . . . . . . . . . . . . . .

. .

..4 . . . . . . .

 

 

I-1

Logging

 

 

5

 

Wiring .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

. .

 

 

Orientation . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

.I-2

IMPORTant SAFETY NOTES

 

 

5

 

Calibration . . . . . . . . . . . . . . . . . . . . .

.

. .I.-3. . . .

. .

 

 

Menu Structure . . . . . . . . . . . . . . . . . . . . . . .

. .

.I-4

INSTallation . . . . . . . . . . . . . . . . . . . . . . .

. .

..6. . .

Appendix J — UD10 WITH OPEN PATH MODEL OPECL . . . J-1

 

Wiring

 

 

J-1

Identification of Vapor(s) to be Detected

 

 

6

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

. .

 

 

Orientation

 

J-3

Identification of Detector Mounting Locations

 

 

6

 

. .

. .

 

 

Calibration . . . . . . . . . . . . . . . . . . . . .

.

. J.-3. . . .

WIRING

 

 

7

 

OPECL Transmitter Lamp Fault Condition . .

. .

J-4

. .

 

 

Menu Structure . . . . . . . . . . . . . . . . . . . . . . .

. .

J-4

Power Supply Requirements . . . . . . . . . . . .

. .

 

..7.

Appendix K — UD10 WITH NTMOS H2S Sensor

 

K-1

Wiring Cable Requirements

 

 

7

. .

. .

 

 

Wiring

 

 

K-1

Shield Connections . . . . . . . . . . . . . . .

. .

.7. . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

Installation Notes

 

K-1

Jumper Setting for 4-20 mA Loop . . . . . .

.

. .7. . .

 

.

 

Orientation

 

K-4

Foundation Fieldbus

 

 

7

 

. .

. .

 

 

Calibration . . . . . . . . . . . . . . . . . . . . .

.

.K.-4. . . .

Wiring Procedure

 

 

8

 

. .

 

 

Menu Structure

 

K-5

 

 

 

 

 

. .

STaRTUP . . . . . . . . . . . . . . . . . . . . . . . . .

.

 

 

Appendix L — UD10 WITH C706X ToXIC GAS SENSOR

. L-1

..12. . . . .

 

 

 

 

Troubleshooting . . . . . . . . . . . . . . . . . . . . .

. .

 

16

 

Wiring .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

L-1

SPECIFICATIONS

 

 

19

 

Installation . . . . . . . . . . . . . . . . . . . . . .

.

. L.-3. . .

. .

 

 

Calibration . . . . . . . . . . . . . . . . . . . . .

.

. L.-4. . . .

Device Repair and Return

 

 

22.

 

. .

 

 

Menu Structure

 

L-4

Ordering Information . . . . . . . . . . .

. .22. . . . .

. .

 

 

. . .M-1

 

 

 

 

Appendix M — UD10 with Model CGS Sensor

APPENDIX A — FM Approval description . . . . a-1 appendix b — csa certification description . b-1 appendix C — atex approval description . . . . . c-1 appendix d — iecEx approval description . . . . d-1 Appendix E — Additional Approvals . . . . . . . E.-.1.

Appendix F — UD10 WITH Handheld Hart

communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1

Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . F-1

Appendix G — UD10 WITH gt3000 toxic gas detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .G-1

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-1 Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2 Live Maintenance . . . . . . . . . . . . . . . . . . . . . . . G-2 Calibration . . . . . . . . . . . . . . . . . . . . . . .G.-3. . .

Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . G-4

Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M-1 Important Notes . . . . . . . . . . . . . . . . . . . . . . . . M-1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . M-3 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . M-3 K-Factor.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. M-4 Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . . M-4

Appendix N — UD10 WITH Model 505/CGS . . . . . . . .N-1

Wiring . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . .

. . N-1

Installation . . .

. . . . . . . . . . . . . . . . . . .

. ..N.-2. .

Orientation . . . .

. . . . . . . . . . . . . . . . . . . . . . .

. N-2

Calibration . . .

. . . . . . . . . . . . . . . . . .

. .N.-3. . .

Menu Structure .

. . . . . . . . . . . . . . . . . . . . . . .

. N-4

Appendix O — UD10 WITH Generic 4-20 ma sensor O-1

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . O-1 Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . O-1

INSTRUCTIONS

FlexVu® Explosion-Proof

Universal Display Unit

Model UD10

Important

Be sure to read and understand the entire instruction manual before installing or operating the gas detection system. This product can be used with a variety of Det-Tronics gas detectors to provide early warning of the presence of a toxic or explosive gas mixture. Proper device installation, operation, and maintenance is required to ensure safe and effective operation. If this equipment is used in a manner not specified in this manual, safety protection may be impaired.

Application

The FlexVu® Model UD10 is recommended for applications that require a gas detector with digital readout of detected gas levels as well as analog 4-20 mA output with HART, relay contacts, and Modbus RS485 (foundationFieldbus option available). The UD10 Universal Display Unit is designed for use with Det Tronics gas detectors listed in Table 1.

The display unit is designed and approved as a ‘stand alone’ device and performs all the functions of a gas controller.

When furnished with the CGS interface board, the device can be used only with a CGS sensor for detection of combustible gas. The UD10/CGS combination is certified as a “Gas Detector”.

Gas concentration and unit of measurement are displayed on a digital display. The display unit provides a linear isolated/non-isolated 4-20 mA DC output signal (with HART) that corresponds to the detected gas concentration.

All electronics are enclosed in an explosion-proof aluminum or stainless steel housing. The display unit is used with a single detector that may be either coupled directly to the UD10, or remotely located using a sensor termination box.

The UD10 features non-intrusive calibration. A magnet is used to perform calibration as well as to navigate the UD10’s internal menu.

4.2©Detector Electronics Corporation 2012

Description

The UD10 Universal Display can be used with various 4-20 mA gas detection devices, with or without HART. The unit provides display, output and control capabilities for the gas detector.

The UD10 utilizes the following I/O:

Signal Inputs:

4-20 mA loop from the sensing device

User Inputs:

Magnetic switches (4) on the display

 

panel

 

 

HART communication (handheld field

 

communicator or AMS)

 

 

foundationFieldbus (if selected)

Signal Outputs:

4-20 mA output loop with HART

 

Modbus RS485 or foundationFieldbus

 

Three alarm relays and one fault relay

Visible Outputs:

Backlit LCD display

 

 

HART slave interface via HART

 

 

Communicator

 

 

Rev: 9/12

95-8661

Table 1—Range and Default Values for Alarms and Calibration Gas Concentration

 

 

UD10 Alarm DaTA

 

 

Calibration

 

 

 

 

 

 

Gas Detector

 

High Alarm Value

Low Alarm Value

Aux alarm Value

Cal Gas

 

 

 

 

 

 

GT3000--

Range

10-90%

5-50%

5-90%

30-90%

Hydrogen Sulfide

Default

40%

10%

40%

50%

 

 

 

 

 

 

GT3000--

Range

10-90%

5-50%

5-90%

30-90%

Ammonia

Default

40%

10%

40%

50%

 

 

 

 

 

 

GT3000--Chlorine

Range

10-90%

5-50%

5-90%

30-90%

 

 

 

 

 

Default

40%

10%

40%

50%

 

 

 

 

 

 

 

GT3000--

Range

10-60%

5-50%

5-90%

30-90%

Hydrogen

Default

40%

10%

40%

50%

GT3000--Oxygen

Range

5-20.5% v/v

5-20.5% v/v

5-20.5% v/v

20.9% v/v

 

 

 

 

 

Default

18% v/v

18% v/v

18% v/v

20.9% v/v

 

 

 

 

 

 

 

GT3000--Carbon

Range

10-90%

5-50%

5-90%

30-90%

Monoxide

Default

40%

10%

40%

50%

 

 

 

 

 

 

GT3000--Sulfur

Range

10-90%

5-50%

5-90%

30-90%

Dioxide

Default

40%

10%

40%

50%

 

 

 

 

 

 

PIR9400

Range

10-60%

5-50%

5-90%

50%

 

 

 

 

 

Default

40%

10%

40%

50%

 

 

 

 

 

 

 

PIRECL

Range

10-60%

5-50%

5-90%

30-90%

 

 

 

 

 

Default

40%

10%

40%

50%

 

 

 

 

 

 

 

OPECL

Range

1-3 LFL-meters

0.25-3 LFL-meters

NA

NA

 

 

 

 

 

Default

2 LFL-meters

1 LFL-meter

NA

NA

 

 

 

 

 

 

 

C706x*

Range

10-90%

5-50%

5-90%

30-90%

 

 

 

 

 

Default

40%

10%

40%

50%

 

 

 

 

 

 

 

CGS

Range

10-60%

5-50%

5-90%

50%

Combustible

Default

40%

10%

40%

50%

 

 

 

 

 

 

Model 505/CGS

Range

10-60%

5-50%

5-90%

N/A

Combustible

Default

40%

10%

40%

N/A

 

 

 

 

 

 

NTMOS--

Range

10-90%

5-50%

5-90%

50%

Hydrogen Sulfide

Default

40%

10%

40%

50%

 

 

 

 

 

 

Generic Detector

Range

10-90%

5-50%

5-90%

N/A

 

 

 

 

 

Default

40%

10%

40%

50%

 

 

 

 

 

 

 

Notes: All values are a percentage of full scale with the exception of Oxygen, which is the actual percent of Oxygen, and OPECL, which is the value in LFL-meters.

low alarm must be less than or equal to the high alarm.

Changing the Measurement Range will reset all alarm and Cal Gas values to the default settings for the selected range.

Alarm relays are selectable for either normally energized or normally de-energized coils, with selectable latching or non-latching contacts. Fault relay is normally energized (with no faults).

*Does not support C7064C hydrogen sulfide or C7065E oxygen, but includes C7064E hydrogen sulfide, C7067E chlorine, C7066E carbon monoxide, and C7068E sulfur dioxide.

4.2

2

95-8661

HART communication

A HART interface provides device status information and field programming capability.

magnetic switches

Four internal magnetic switches provide a non intrusive user interface that allows navigation through the menu and adjustment of configuration parameters in the field without the use of a HART handheld device. See Figure 1 for switch locations.

PREVIOUS

CANCEL / ESCAPE

ENTER / SELECT

NEXT

B2426

Figure 1—Faceplate of UD10

These switches are used for device configuration, checking status and event logs, and performing calibration. The switches are labeled as follows:

CANCEL / ESCAPE

ENTER / SELECT / MeNU ACCESS

PrEVIOUS or if on Main Screen:

Fault Shortcut

Next

To actuate a magnetic switch, lightly touch the magnet to the viewing window of the UD10 directly over the switch icon on the faceplate.

Caution

Handle magnets with care! Personnel wearing pacemakers/defibrillators should not handle magnets. Modern magnet materials are extremely strong magnetically and somewhat weak mechanically. Injury is possible to personnel, and magnets themselves can easily get damaged if allowed to snap towards each other, or if nearby metal objects are allowed to be attracted to the magnets.

note

Det-Tronics offers two magnet options for activating internal magnetic switches. While the two magnets can usually be used interchangeably, the best results will be achieved if they are used as follows: The Magnetic Tool (p/n 009700-001) is the stronger magnet and is recommended for activating the switches on the UD10 viewing window. The Calibration Magnet (p/n 102740 002) is recommended for applications that involve initiating calibration or resetting the detector by touching the side of a metal junction box or detector housing (PIRECL, OPECL, etc). Throughout this manual, the term “magnet” can refer to either device.

Access To Menus

To access the menus, use the magnet to activate the Enter/SeLECT button. This will display the Main Menu.

The actual menu structure varies depending upon the device that is connected to the UD10. Menus for the various devices can be found in the corresponding Appendix in this manual.

Some areas of the menu contain additional information, which is indicated by the presence of an arrow on that particular line. By placing the magnet to the glass over the Enter/SeLECT button, the next screen with the additional information will be shown.

The UD10 automatically returns to the main screen after 10 minutes if no activity occurs.

Quick Access/Shortcut: Fault Menu

To access the fault menu quickly, when a fault is present, touch the magnet to the glass by the PrEVIOUS button.

4.2

3

95-8661

Relays

The display unit has 4 output relays — high alarm, low alarm, auxiliary alarm, and fault. The relays have form C (SPDT) contacts. Low, auxiliary and high alarm relay contacts are selectable for latching or non latching operation, as well as normally energized or normally de energized (default) coils. During normal operation, the fault relay is energized.

IMportant

Direct connection of 120/240 VAC to the relay terminals inside the UD10 enclosure is not allowed, since switching relay contacts can induce electrical noise into the electronic circuitry, possibly resulting in a false alarm or other system malfunction. If the application requires that AC powered equipment be controlled by the transmitter, the use of externally located relays is recommended.

External relays, solenoids, motors, or other devices that can cause inductive transients should be transient suppressed. Place a diode across the coil for DC devices. See Figure 2.

+

 

POSITIVE

 

 

 

 

1N4004

DCV LOADS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TYPICAL

 

 

 

 

NEGATIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B0179

 

 

 

 

 

 

 

 

 

 

Figure 2—Transient Suppression for Inductive Loads

4-20 mA OuTpuT Modes

The UD10 offers two operating modes for its 4-20 mA output circuit.

Note

A minimum output of 1 mA is required for proper HART communication.

In the Standard (default) Mode, the linear 4-20 mA output corresponds to 0-100% full scale gas detected at the sensor, with 3.8 mA indicating calibrate mode, and 3.6 mA or lower indicating a fault condition. This mode ensures that the current level is always high enough to support HART communication and must be selected when using HART communication for fault diagnostics.

In Replicate Mode, the output of the UD10 matches the output of the connected detector (except for loop test/trim, response test, calibration, or if the UD10 has an internal fault). This mode can be used with

detectors such as PIR9400 or PIRECL where multiple current levels below 4 mA are used for fault diagnostic purposes.

UD10 with Model PIRECL

PIRECL supports two fault modes: PIR9400 and Eclipse mode. PIR9400 fault mode uses fault codes below 1 mA, while Eclipse mode uses no levels below 1 mA. In the Standard (default) mode, the UD10 programs the PIRECL for Eclipse fault mode to ensure proper HART communication in the event of a fault. In the Replicate mode, the UD10 programs the PIRECL for PIR9400 fault mode.

MODBUS / fieldbus COMpATIBILITY

The UD10 supports RS485 Modbus RTU communication. See Addendum number 95-8639 for details. A model with Modbus RS485 or foundationFieldbus communication (field selectable via jumpers) is also available.

DeviCE ENCLOSURE

The UD10 housing is a 5 port aluminum or stainless steel explosion proof junction box with a clear viewing window.

Device DISPLAY

The UD10 is provided with a 160 x 100 dot matrix backlit LCD display. See Figure 1.

During normal operation, the LCD continuously displays the detected gas level, gas type, and units of measurement. The real time clock can also be displayed if desired.

The display shows the following alarm information:

High gas alarm

Low gas alarm

Aux alarm

The display indicates the following fault information:

Device fault

Display fault

The UD10 has smart capabilities to allow easy access to the following information:

Detector information

Measurement range

Alarm setpoints

Alarm and event logs

For detailed HART menu structure, refer to the appropriate Appendix.

4.2

4

95-8661

Logging

Events that can be logged in the UD10 include:

Calibration (Date, time and success Y/N are logged for detectors that do not provide their own calibration logging capabilities.)

Faults that are logged in the UD10 include:

Detector fault

Low power

General fault

Alarms that are logged in the UD10 for gas detector inputs include:

High gas alarm

Low gas alarm

Aux alarm.

The UD10 has its own battery backed real time clock (RTC) and its own event logs. The RTC in the UD10 can be set from the UD10 display, Modbus or HART interfaces. The RTC in the gas detector (any HART detector having an RTC) can be set independently using the UD10 menu, or by using the synchronize command, which will set the detector RTC to the same time as the UD10 RTC. See Figure 3.

The UD10 can display the detector event and calibration logs (if available). The UD10 has its own 1,000 entry event log available under the Display Status >History >Event Log menu.

UD10 event logs can be read from the HART interface or the Modbus interface.

Detector calibration and event logs can also be read from the detector HART interface (where available).

 

 

MODBUS

CONTROL

 

 

or

SYSTEM

 

 

FOUNDATION FIELDBUS

PLC/DCS

 

 

 

GAS

HART

UD10

 

DETECTOR

 

 

 

 

 

 

 

CONTROL

 

 

HART

SYSTEM

 

 

PLC/DCS

 

HART

 

 

 

AMS

 

Handheld

 

 

 

 

 

 

HART

 

 

 

Handheld

 

important safety notes

CAUTIOn

The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local codes. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person.

CAUTIOn

This product has been tested and approved for use in hazardous areas. However, it must be properly installed and used only under the conditions specified within this manual and the specific approval certificates. Any device modification, improper installation, or use in a faulty or incomplete configuration will render warranty and product certifications invalid.

CAUTIOn

The device contains no user serviceable components. Service or repair should never be attempted by the user. Device repair should be performed only by the manufacturer.

LiabiLIties

The manufacturer’s warranty for this product is void, and all liability for proper function of the detector is irrevocably transferred to the owner or operator in the event that the device is serviced or repaired by personnel not employed or authorized by Detector Electronics Corporation, or if the device is used in a manner not conforming to its intended use.

Caution

Observe precautions for handling electrostatic sensitive devices.

caution

Unused conduit entries must be closed with suitably certified blanking elements upon installation.

Figure 3—UD10 Logging

4.2

5

95-8661

Installation

note

The gas detector housing must be electrically connected to earth ground. A dedicated earth ground terminal is provided on the UD10.

Note

Refer to the Model UD10 Safety Manual (number 95-8668) for specific requirements and recommendations applicable to the proper installation, operation, and maintenance of SILCertified Model UD10 displays.

The detector must always be installed per local installation codes.

Before installing the gas detector, define the following application details:

IdENTIFICATION of vapoR(s) to be detected

It is necessary to identify the vapor(s) of interest at the job site. The fire hazard properties of the vapor, such as vapor density, flashpoint, and vapor pressure should be identified and used to assist in selecting the optimum detector mounting location within the area.

For cross sensitivity information, refer to each gas detector’s corresponding instruction manual. Refer to Table 5 in the Specifications section for a list of gas detectors and their corresponding instruction manuals.

IdENTIFICATION of detector moUNTINg loCATIONS

Identification of the most likely leak sources and leak accumulation areas is typically the first step in identifying the best detector mounting locations. In addition, identification of air current/wind patterns within the protected area is useful in predicting gas leak dispersion behavior. This information should be used to identify optimum detector installation points.

If the vapor of interest is lighter than air, place the detector above the potential gas leak. Place the detector close to the floor for gases that are heavier than air. Note that air currents may cause a gas that is slightly heavier than air to rise under some conditions. Heated gases may also exhibit the same phenomenon.

The most effective number and placement of detectors varies depending on the conditions on site. The individual designing the installation must often rely on experience and common sense to determine the detector quantity and best locations to adequately protect the area. Note that it is typically advantageous to locate detectors where they are accessible for maintenance. Locations near excessive heat or vibration sources should be avoided.

Final suitability of possible gas detector locations should be verified by a job site survey.

The gas detector must be mounted with the sensor in the correct orientation as shown in Table 2.

If the UD10 faceplate is not correctly oriented, it can be rotated at 90 degree increments by pulling the electronic module from the four mounting posts that secure it to the junction box and repositioning it as desired. Note that the module is held in place by a compression fitting – no screws are involved.

 

Table 2—Device Orientation

 

 

 

Device

 

Orientation

 

 

 

GT3000

 

Vertical with Sensor Pointing Down

 

 

 

PIR9400

 

Horizontal

 

 

 

PIRECL

 

Horizontal

 

 

 

OPECL

 

Horizontal (Fixed to a vertical post)

 

 

 

CGS

 

Vertical with Sensor Pointing Down

 

 

 

505/CGS

 

Vertical with Sensor Pointing Down

 

 

 

C706X

 

Vertical with Sensor Pointing Down

 

 

 

NTMOS

 

Vertical with Sensor Pointing Down

 

 

 

4.2

6

95-8661

WIRING

power SUPply requiremeNTS

Calculate the total gas detection system power consumption rate in watts from cold start-up. Select a power supply with adequate capability for the calculated load. Ensure that the selected power supply provides regulated and filtered 24 Vdc output power for the entire system. If a back-up power system is required, a float type battery charging system is recommended. If an existing source of 24 Vdc power is being utilized, verify that system requirements are met. The acceptable voltage range is 18-30 Vdc measured at the input to the UD10.

note

The power supply must meet the noise requirements for HART systems. If noise or ripple on the main power source could interfere with the HART function, an isolated power source (Figure 11) is recommended. (For detailed information regarding power supply specifications, refer to the HART Communication Foundation’s document “FSK Physical Layer Specification” HCF_SPEC-54.)

Wiring cable requiremeNTS

Always use proper cabling type and diameter for input power as well as output signal wiring. 14 to 18 AWG shielded stranded copper wire is recommended. Correct wire size depends on the device and wire length. Refer to the appropriate Appendix for additional information. The maximum cable length from power source to UD10 is 2000 feet. Maximum cable length from UD10 to sensor is 2000 feet.

note

The use of shielded cable in conduit or shielded armored cable is highly recommended. In applications where the wiring is installed in conduit, dedicated conduit is recommended. Avoid low frequency, high voltage, and non signaling conductors to prevent nuisance EMI problems.

caution

The use of proper conduit installation techniques, breathers, glands, and seals is required to prevent water ingress and/or maintain the explosion-proof rating.

ShIEld CoNNECTIONS

The UD10 provides terminals for proper grounding of wiring cable shields (located on the sensor, 4-20 mA, and operating power terminal blocks). These shield terminals are not connected internally, but are connected to ground through capacitors. The capacitors ensure an RF ground, while preventing 50/60 Hz ground loops.

Ground all shields as shown in the wiring examples throughout this manual.

important

For proper grounding, all junction boxes / metal enclosures must be connected to earth ground.

The following are required for installations requiring CE Mark compliance:

For shielded cable installed in conduit, attach the wire shields to the “shield” connections on the terminal blocks, or to earth ground on the case.

For installations without conduit, use double shielded cable. Terminate the outer shield to earth ground on the case. Terminate the inner shield to the “shield” connection on the terminal blocks.

JumpeR SeTTINg for 4-20 mA Loop

In order for the 4-20 mA current loop to operate properly, +24 Vdc must be applied to terminal P1-3. This can be accomplished in one of two ways:

For a non-isolated 4-20 mA loop, set jumper plug as shown in Figure 4. This applies +24 Vdc to P1-3 via an internal connection to terminals P2-2 and P2-5.

If the 4-20 mA loop will receive power from a source other than the UD10’s main power source (isolated), set the jumper plug as shown in Figure 5 to remove the internal connection.

FoUNDATION FiEldbus (Optional)

Some UD10 models allow the use of either RS485/ MODBUS or Foundation Fieldbus communication via connection to J2 on the terminal board. Four jumpers are provided to select between the two protocols. If the device is equipped for Foundation Fieldbus, it will be shipped from the factory with the jumpers preset for that mode. If the user wants to switch to RS485/MODBUS (for example, to retrieve logs), the four jumpers can easily be moved. Figures 6 and 7 show the jumper settings for each mode of communication.

Note that the pin identification for the J2 connector is different for each communication protocol. For Foundation Fieldbus it is “– +”. For RS485/MODBUS it is “B A com”.

4.2

7

95-8661

Wiring Procedure

NOTE

The following section shows the output of the UD10 wired to a generic 4-20 mA signal receiver in various configurations. Since the UD10 can be used with a variety of different detection devices, information that is specific to each detector model (wiring, calibration, HART menus, etc.) is covered in an Appendix that is dedicated to that device. Refer to the appropriate Appendix at the back of this manual for specific information when wiring the detection system. For information on devices not covered in an Appendix, refer to the manual provided by the device’s manufacturer.

Figure 4 shows jumper plug P12 positioned to power the 4-20 mA loop from the main power source (non isolated output).

Figure 5 shows jumper plug P12 positioned for powering the 4-20 mA loop from an external wire/jumper of from a separate power source (isolated output).

Figure 6 shows the correct jumper positions and J2 terminal identification for using Foundation Fieldbus communication.

Figure 7 shows the correct jumper positions and J2 terminal identification for using MODBUS communication.

Refer to Figure 8 for an illustration of the UD10 wiring terminal board (see Figure 6 for Foundation Fieldbus connections).

Figure 9 shows a UD10 Wired to a PLC using 3-Wire Shielded Cable with a 4-20 mA Non-Isolated Sourcing Output.

Figure 10 shows a UD10 Wired to a PLC using 4-Wire Shielded Cable with a 4-20 mA Non-Isolated Sourcing Output.

Figure 11 shows a UD10 Wired to a PLC with a 4-20 mA Isolated Sourcing Output.

GREASE/LUBRICATION

To ease installation and future removal, ensure that all junction box covers and sensor threads are properly lubricated. If the need arises for additional lubrication, use either Lubriplate grease (see Ordering Information for part number) or Teflon tape. Avoid the use of silicone grease.

WHEN P12 IS

IN THIS POSITION, P1-3 IS INTERNALLY CONNECTED TO P2-2 AND P2-5

Sensor Connector

 

 

 

 

 

-1

-2

-3

-4

-5

 

J3

 

 

 

 

 

 

 

J3

 

J3

J3

 

J3

 

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

CALIBRATE

24 VDC –

 

4-20 mA

 

24 VDC +

 

 

 

 

 

 

4-20 mA +

 

 

HIGH ALARM COM

J4-1

 

P1-3

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NC

J4-2

Output

P1-2

4-20 mA –

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NO

J4-3

Loop

 

 

 

 

 

 

 

P3

 

 

 

 

 

 

 

 

 

AUX ALARM COM

J4-4

Connector

P1-1

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NC

J4-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NO

J4-6

 

J2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM COM

J4-7

Fieldbus

J2-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NC

J4-8

Connector

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NO

J4-9

J2-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT COM

J4-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NC

J4-11

P5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NO

J4-12

P9

 

 

 

 

 

–VDC24

 

+VDC24

 

 

SHIELD

 

 

VDC24–

 

+VDC24

 

SHIELD

 

J4

 

 

 

 

P7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-6

 

-5

-4

 

-3

 

-2

 

-1

P2

 

 

 

 

 

P12

 

P2

 

P2

 

P2

 

 

P2

 

P2

 

P2

 

 

Power Supply Connector

Relay Connector

B2525

WHEN P12 IS IN

THIS POSITION, A SEPARATE POWER SOURCE IS REQUIRED TO POWER THE

4-20 MA LOOP

Sensor Connector

 

 

 

 

 

 

 

 

 

 

-1

-2

-3

-4

-5

 

J3

 

 

 

 

 

 

 

 

 

 

 

J3

 

J3

J3

 

J3

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

CALIBRATE

24 VDC –

 

4-20 mA

24 VDC +

 

HIGH ALARM COM

 

P1-3

4-20 mA +

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NC

Output

P1-2

4-20 mA –

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Loop

 

 

 

 

 

 

 

 

 

 

 

 

P3

 

 

 

 

 

 

AUX ALARM COM

Connector

P1-1

SHIELD

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NO

 

 

J2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM COM

Fieldbus

 

J2-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NC

Connector

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NO

 

J2-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2-1

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NC

P5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P9

 

 

 

 

 

 

 

 

P7

 

 

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VDC–

 

24VDC+

 

24VDC

 

24VDC+

 

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-6

 

-5

-4

 

-3

-2

 

-1

P2

 

 

 

 

 

 

 

 

P12

 

 

P2

 

P2

P2

 

P2

 

P2

 

P2

 

Power Supply Connector

J4-1

 

J4-2

 

J4-3

 

J4-4

Connector

J4-5

J4-6

 

J4-7

Relay

J4-8

J4-9

 

J4-10

 

J4-11

 

J4-12

 

J4

 

B2526

Figure 4—Position of Jumper P12 for Non-Isolated 4-20 mA Loop Output

Figure 5—Position of Jumper P12 for Isolated 4-20 mA Loop Output

4.2

8

95-8661

Sensor Connector

 

 

 

J3-1

J3-2

 

J3-3

J3-4

J3-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

CALIBRATE

 

24 VDC –

4-20 mA

24 VDC +

 

P1-3

4-20 mA +

 

 

 

 

 

 

 

Output

 

4-20 mA –

 

 

 

 

 

 

 

P1-2

 

 

 

 

 

 

 

Loop

 

 

 

 

 

 

 

 

 

 

 

 

 

P3

 

 

 

 

 

 

 

 

 

 

 

Connector

P1-1

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

 

 

Fieldbus

 

 

 

 

 

 

 

 

 

 

J2-3

 

 

 

 

 

 

 

 

 

Connector

 

 

 

 

 

 

 

 

 

 

J2-2

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2-1

 

 

 

 

 

P5

 

 

 

 

 

 

P9

P7

+

SHIELD

+

 

 

24 VDC

24 VDC

24 VDC

24 VDC

 

P12

P2-6

P2-5

P2-4

P2-3

P2-2

 

 

 

 

 

 

J3

HIGH ALARM COM

J4-1

HIGH ALARM NC

 

J4-2

 

 

HIGH ALARM NO

J4-3

 

 

AUX ALARM COM

J4-4

 

 

AUX ALARM NC

J4-5

 

 

AUX ALARM NO

J4-6

 

 

LOW ALARM COM

J4-7

 

 

LOW ALARM NC

J4-8

 

 

LOW ALARM NO

J4-9

 

 

 

 

 

 

FAULT COM

J4-10

 

 

 

 

 

 

FAULT NC

J4-11

 

 

FAULT NO

 

 

 

J4-12

 

 

 

 

 

 

 

J4

SHIELD

 

 

 

-1

 

P2

 

 

 

P2

 

 

 

 

 

 

 

 

 

Relay Connector

NOTE: FOUNDATION FIELDBUS IS AVAILABLE ON SELECT MODELS. REFER TO THE MODEL MATRIX IN THE ORDERING INFORMATION SECTION FOR DETAILS.

 

Power Supply Connector

JUMPERS P3, P5, P7, AND P9 MUST BE POSITIONED AS SHOWN

 

 

C2527

 

FOR FOUNDATION FIELDBUS COMMUNICATION

Figure 6—Foundation Fieldbus Communication

Sensor Connector

 

 

 

J3-1

J3-2

 

J3-3

J3-4

J3-5

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

CALIBRATE

 

24 VDC –

4-20 mA

24 VDC +

 

P1-3

4-20 mA +

 

 

 

 

 

 

Output

 

4-20 mA –

 

 

 

 

 

 

P1-2

 

 

 

 

 

 

Loop

 

 

 

 

 

 

 

 

 

 

 

P3

 

 

 

 

 

 

 

 

 

Connector

P1-1

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

 

MODBUS

J2-3

COM

 

 

 

 

 

 

Connector

 

RS485 A

 

 

 

 

 

 

J2-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485 B

 

 

 

 

 

 

 

J2-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P5

 

 

 

 

 

 

P9

P7

+

SHIELD

+

 

 

24 VDC

24 VDC

24 VDC

24 VDC

 

P12

P2-6

P2-5

P2-4

P2-3

P2-2

 

 

 

 

 

 

J3

HIGH ALARM COM

J4-1

HIGH ALARM NC

 

J4-2

 

 

HIGH ALARM NO

J4-3

 

 

AUX ALARM COM

J4-4

 

 

AUX ALARM NC

J4-5

AUX ALARM NO

J4-6

 

 

LOW ALARM COM

J4-7

 

 

LOW ALARM NC

J4-8

LOW ALARM NO

J4-9

 

 

 

 

 

 

FAULT COM

J4-10

 

 

 

 

 

 

FAULT NC

J4-11

 

 

FAULT NO

 

 

 

J4-12

 

 

 

J4

SHIELD

 

 

 

-1

 

P2

 

 

 

P2

 

 

 

 

 

 

 

 

 

Relay Connector

 

Power Supply Connector

JUMPERS P3, P5, P7, AND P9 MUST BE POSITIONED AS SHOWN

 

 

B2528

 

FOR MODBUS/RS485 COMMUNICATION

Figure 7—MODBUS Communication

4.2

9

95-8661

Output Loop

Connector

P1-3 4-20 mA +

P1-2 4-20 mA –

P1-1 SHIELD

P1

J2

J2-3 COM

J2-2 RS485 A

J2-1 RS485 B

MODBUS

Connector

Sensor Connector

-1

-2

-3

-4

-5

 

J3

 

J3

 

J3

 

J3

 

J3

 

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

CALIBRATE

 

24 VDC –

 

4-20 mA

 

24 VDC +

HIGH ALARM COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NC

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NO

 

 

 

 

 

 

 

 

 

 

AUX ALARM COM

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NC

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NO

 

 

 

 

 

 

 

 

 

 

LOW ALARM COM

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NC

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NO

 

 

 

 

 

 

 

 

 

 

 

 

FAULT COM

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NC

 

+

 

SHIELD

 

+

 

SHIELD

FAULT NO

 

24 VDC

 

24 VDC

 

 

24 VDC

 

24 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-6

 

-5

 

-4

 

-3

 

-2

 

-1

P2

 

P2

 

P2

 

P2

 

P2

 

P2

 

P2

 

 

 

 

 

 

 

Power Supply Connector

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J4

Relay Connector

C2399

Figure 8—Wiring Terminals on UD10 Terminal Board

PLC 4-20 mA INPUT CARD

 

INPUT

4-20 mA

 

250-600

24 VDC

OHMS

+

Notes: Resistor may be external if voltage input card is used. Sinking resistance at PLC must be 250-600 ohms

for HART communication.

UD10

DISPLAY UNIT

Sensor Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-1

-2

-3

-4

 

 

-5

 

 

 

J3

 

 

 

 

 

 

 

 

J3

 

J3

 

J3

 

J3

 

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Loop

SHIELD

 

CALIBRATE

 

VDC24 –

 

20-4mA

 

VDC24 +

 

 

 

 

 

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-20 mA +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM COM

J4-1

 

 

P1-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NC

J4-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1-2

4-20 mA –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NO

J4-3

 

 

P1-1

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM COM

J4-4

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NC

J4-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NO

J4-6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM COM

J4-7

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NC

J4-8

 

J2-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NO

J4-9

 

 

J2-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT COM

J4-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2-1

RS485 B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NC

J4-11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NO

 

 

 

 

 

 

 

 

 

+

 

SHIELD

 

 

+

 

SHIELD

J4-12

 

 

MODBUS

 

 

 

 

 

 

 

 

 

 

VDC24

 

VDC24

 

 

 

VDC24

 

 

VDC24

 

 

J4

 

 

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-6

 

-5

 

-4

 

-3

 

-2

 

-1

P2

 

 

 

 

 

 

 

 

 

P2

 

P2

 

P2

 

 

P2

 

 

P2

 

P2

 

 

 

 

P12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply Connector

D2439

Figure 9—UD10 Wired to PLC using 3-Wire Shielded Cable with 4-20 mA Non-Isolated Sourcing Output

4.2

10

95-8661

UD10

DISPLAY UNIT

Sensor Connector

 

 

Output Loop

 

 

Connector

 

 

P1-3

4-20 mA +

 

 

P1-2

4-20 mA –

PLC 4-20 mA INPUT CARD

P1-1

SHIELD

 

 

 

 

P1

 

 

 

J2

 

 

INPUT

J2-3

COM

 

 

 

4-20 mA

J2-2

RS485 A

 

 

 

J2-1

RS485 B

 

 

 

250-600

24 VDC

MODBUS

OHMS

+

Connector

 

 

 

P12

Notes: Resistor may be external if voltage input card is used. Sinking resistance at PLC must be 250-600 ohms

for HART communication.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-1

-2

-3

-4

 

-5

 

 

J3

 

 

J3

 

J3

 

J3

 

J3

 

J3

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

CALIBRATE

 

24 VDC –

 

4-20 mA

 

24 VDC +

 

 

 

 

 

HIGH ALARM COM

J4-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J4-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NO

J4-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM COM

J4-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NC

J4-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NO

J4-6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM COM

J4-7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NC

J4-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NO

J4-9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT COM

J4-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NC

J4-11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NO

 

 

 

+

 

 

 

 

+

 

 

J4-12

 

 

 

SHIELD

 

 

 

SHIELD

 

 

 

 

VDC24

 

VDC24

 

 

 

VDC24

 

 

VDC24

 

 

J4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-6

 

-5

 

-4

 

-3

 

-2

 

-1

P2

 

 

 

P2

 

P2

 

P2

 

 

P2

 

 

P2

 

P2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply Connector

Relay Connector

E2440

Figure 10—UD10 Wired to PLC using 4-Wire Shielded Cable with 4-20 mA Non-Isolated Sourcing Output

UD10

DISPLAY UNIT

Sensor Connector

 

 

Output Loop

 

 

Connector

 

 

P1-3

4-20 mA +

 

 

P1-2

4-20 mA –

PLC 4-20 mA INPUT CARD

P1-1

SHIELD

 

 

 

 

P1

 

 

 

J2

 

 

INPUT

J2-3

COM

 

 

 

4-20 mA

J2-2

RS485 A

 

 

 

J2-1

RS485 B

 

 

 

250-600

24 VDC

MODBUS

OHMS

+

Connector

 

 

 

P12

Notes: Resistor may be external if voltage input card is used. Sinking resistance at PLC must be 250-600 ohms

for HART communication.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-1

-2

-3

-4

 

-5

 

 

J3

 

 

 

J3

 

J3

 

J3

 

J3

 

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

CALIBRATE

 

24 VDC –

 

4-20 mA

 

24 VDC +

 

 

 

 

 

 

HIGH ALARM COM

J4-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J4-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH ALARM NO

J4-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM COM

J4-4

Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NC

J4-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX ALARM NO

J4-6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM COM

J4-7

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NC

J4-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW ALARM NO

J4-9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT COM

J4-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NC

J4-11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT NO

 

 

 

 

+

 

 

 

 

+

 

 

J4-12

 

 

 

 

SHIELD

 

 

 

SHIELD

 

 

 

 

 

VDC24

 

VDC24

 

 

 

VDC24

 

 

VDC24

 

 

J4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-6

 

-5

 

-4

 

-3

 

-2

 

-1

P2

 

 

 

 

P2

 

P2

 

P2

 

 

P2

 

 

P2

 

P2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply Connector

+

24 VDC

D2441

Figure 11—UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output

Important

Isolated operation is highly recommended to prevent noise or ripple on the main power source from interfering with the HART function.

4.2

11

95-8661

Startup

After power has been applied and the warm-up period is complete, select the UD10 operating mode. To do this:

1.Access the Main Menu by touching the magnet to the ENTER/SELECT button. From there, navigate to the “Mode Select” menu.

Main Menu

 

 

 

 

 

 

 

 

Display Setup

 

 

Mode Select

Process Vars

 

 

 

 

 

 

Write Protect

 

 

HART Device

Display Status

 

 

 

 

 

 

Alarm Setting

 

 

PIR9400

Device Status

 

 

 

 

 

 

Mode Select

 

 

C706X

Display Setup

 

 

 

 

 

 

HART Option

 

 

505

Device Setup

 

 

 

 

 

RTC

 

 

NTMOS

Device Cal

 

 

 

 

 

 

Display RS485

 

 

CGS

Display Test

 

 

 

 

 

 

Input Loop Cal

 

 

Generic Device

Device Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTC

note

The UD10 is set at the factory for US Central Standard time.

To display and set the Real Time Clock and Date for the UD10:

1.Using the magnet to activate the switches on the UD10 display, navigate to the RTC menu.

Main Menu

 

 

 

 

 

 

 

 

Display Setup

 

 

RTC

Process Vars

 

 

 

 

 

 

Write Protect

 

 

Displayed

Display Status

 

 

 

 

 

 

Alarm Setting

 

 

Seconds

Device Status

 

 

 

 

 

 

Mode Select

 

 

Minutes

Display Setup

 

 

 

 

 

 

HART Option

 

 

Hours

Device Setup

 

 

 

 

 

 

RTC

 

 

Day

Device Cal

 

 

 

 

 

 

Display RS485

 

 

Month

Display Test

 

 

 

 

 

 

Input Loop Cal

 

 

Year

Device Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.From the “Mode Select” menu, select and enter the appropriate operating mode based on the type of detector being used.

note

If using a PIR9400, note that changing the gas type on the UD10 does not change the gas type at the PIR9400. This change is made using a switch located in the PIR9400. Refer to the PIR9400 instruction manual (95 8440) for details.

NOTE

If using a C706X detector, navigate to the “Device Setup” menu and select the appropriate gas type and unit of measurement.

3.To exit, activate Cancel/Escape three times to return to the main display screen.

4.If the detector is replaced with another detector type, the UD10 will not recognize it until the mode is changed.

5.If the UD10 Display is in PIR9400 mode and if:

a.The connection between PIR9400 and the UD10 is removed, the UD10 will show a FAULT on the Gas Screen. When the connection between PIR9400 and UD10 is restored, the UD10 will remove the FAULT indication when current increases beyond 3.6 mA.

b.Someone removes the PIR9400 & connects a HART enabled Gas Detector, it will not be recognized by the UD10 Display until the mode is changed to HART.

2.The first item on the RTC screen is “Displayed”.

Y (Yes) or N (NO) is shown to indicate whether the time and date will be displayed on the main screen. To change the setting, use the Enter/ SeLECT button to go to the next screen, then use the PrEVIOUS or Next buttons to toggle between

Y and N. Once the chosen input is selected, use the Enter/SeLECT button to enter the selection. Use the Cancel/EsCAPE button to exit without changing.

3.Use the same method to set time and date.

Specifically for the GT3000 Transmitter, the RTC for the transmitter can be synchronized to the RTC of the display by going through the Main Menu->Device Setup->RTC-> 1st slot “Sync W/Disp”.

Latching Alarms

The high, auxiliary and low alarm relay settings are programmable and can be set for latching or non latching operation. Alarm configuration can be done using the local display menu or external HART interface. Latched alarms on the display can be cleared through the Display Setup > Alarm Setting submenu using the magnet or external HART interface.

4.2

12

95-8661

4-20 ma loOp CaliBRATION

Both the input and output current loops of the UD10 are trimmed at the factory. They can also be trimmed in the field for maximum accuracy using the following procedures. If the detector connected to the UD10 is HART enabled, its 4-20 mA output signal can also be trimmed.

When the UD10 is used with a detector that supports HART communication, the output of the detector should be calibrated first.

HART Detector Signal Calibration

Navigate down the menu to Device Test > D/A (Digital to Analog) Trim.

Main Menu

 

 

 

 

 

 

Process Vars

 

 

 

 

 

 

Display Status

 

 

Device Test

 

 

 

Device Status

 

 

Self Test

 

 

D/A Trim

Display Setup

 

 

Response Test

 

 

Zero Trim

 

 

Device Setup

 

 

Loop Test

 

 

Gain Trim

Device Cal

 

 

D/A Trim

 

 

 

 

 

 

 

 

Display Test

 

 

 

 

 

 

Device Test

 

 

 

 

 

 

Select Zero Trim. When this screen is entered, a warning message is presented. Select ENTER to continue. When the message “Connect Reference Meter” is presented, install the current meter on the mA line between the detector and UD10. Select ENTER to continue. When the message “Set Input Current to 4mA?” is presented, select ENTER to begin the Zero Trim function. The detector will now set its 4 mA output value. If the value indicated on the current meter is not 4.00 mA, enter the measured value into the UD10 using the Previous and Next switches. The UD10 calculates and corrects for the difference between the actual and entered values. When the current meter value is at the desired 4.00 mA, select ENTER to accept the new zero trim value.

Select Gain Trim. Follow the same procedure for gain/ span calibration.

UD10 Input Trim

When the UD10 is used with a detector that supports HART communication, an automated process can be used to trim the UD10 input. Navigate down the menu to “Input Loop Cal”.

Main Menu

Process Vars

Display Status

Device Status

Display Setup

Device Setup

Device Cal

Display Test

Device Test

Display Setup

Alarm Setting

Mode Select

HART Option

RTC

RS485

Input Loop Cal

Upon entering Input Loop Cal, the UD10 commands the detector to output 4 mA, and then automatically calibrates its own input. The UD10 then commands the detector to output 20 mA and subsequently calibrates its own input.

If a non-HART detector is being used, the Input Loop Cal may be performed with a mA current source or loop calibrator connected to the UD10 Sensor Connector. Follow the loop calibration instructions shown by the UD10 for this procedure.

4.2

13

95-8661

UD10 Output Trim

To calibrate the UD10 output loop, navigate down the menu to Display Test > D/A Trim.

Main Menu

 

 

 

 

 

 

Process Vars

 

 

 

 

 

 

Display Status

 

 

Display Test

 

 

 

Device Status

 

 

Self Test

 

 

D/A Trim

Display Setup

 

 

Response Test

 

 

Zero Trim

 

 

Device Setup

 

 

Loop Test

 

 

Gain Trim

Device Cal

 

 

D/A Trim

 

 

 

 

 

 

 

 

Display Test

 

 

 

 

 

 

Device Test

 

 

 

 

 

 

Select Zero Trim. When this screen is entered, a warning message is presented. Select ENTER to continue. When the message “Connect Reference Meter” is presented, install the current meter on the UD10 mA output. Select ENTER to continue. When the message “Set Output Current to 4mA?” is presented, select ENTER to begin the Zero Trim function. The UD10 will now set its 4 mA output value. If the measured value on the current meter is not 4.00 mA, enter the measured value into the UD10 using the Previous and Next switches. The UD10 calculates and corrects for the difference between the actual and entered values. When the current meter value is at the desired 4.00 mA, select ENTER to accept the new zero trim value.

Select Gain Trim. Follow the same procedure for gain/ span calibration.

OptIONAl SystEm TeSTS

The following tests are available for verifying proper operation of various functions of the gas detection system:

The Self Test, Response Test, and Loop Test are accessed from the “Display Test” screen. (A “Device Test” screen is available for performing the same tests on HART enabled detectors.)

The Proof Test is performed by applying test gas to the sensor. It is not accessed from the “Display Test” screen and does not inhibit the outputs.

Main Menu

Process Vars

Display Status

Device Status

Display Setup

Device Setup

Device Cal

Display Test

Device Test

Display Test

Self Test

Response Test

Loop Test

D/A Trim

Self-Test

This test commands the UD10 to perform a fully automatic internal test. At the completion of the test, the UD10 will indicate a pass or fail.

Response Test

This test inhibits the UD10’s outputs, thereby providing a means of testing the system by applying gas to the detector without activating any alarms or affecting the output.

note

If the Response Test is not terminated by the operator, the test will automatically time out after ten minutes and the UD10 will return to normal operation.

Loop Test

This test temporarily forces the UD10’s 4-20 mA output to a specific level. This is an easy way to test the output signal of the UD10 for accuracy, to verify the capabilities of the system, and to verify the input signal of a receiver. To perform this test, connect a current meter to the output loop. Navigate to Display Test and select Loop Test, then follow the prompts on the UD10 Screen.

note

If the Loop Test is not terminated by the operator, the test will automatically time out after one minute and the UD10 will return to normal operation.

Proof Test

A Proof Test (bump test) can be performed at any time to verify proper operation and calibration of the system. Since this test does not inhibit the UD10’s outputs, secure any output devices prior to performing the test to prevent unwanted actuation.

HiSTORy

There are two separate histories, one for the display and one for the detector (if available). Both will state the number of hours that the unit has been operating, and the highest and lowest recorded temperature (with time and date stamp).

4.2

14

95-8661

PasswoRD prOTECTION

The UD10 allows the use of a password for restricting changes to configuration parameters and limiting access to safety critical commands. The UD10 is shipped from the factory with the password protection (Write Protect) feature disabled.

The following are locked when Write Protect security is enabled:

Alarm Setting screen – All options except “RST Latch Alarms”

Mode Select screen – All options HART Option – All options

RTC – All options except Displayed Y/N

Output Mode

Display Test screen – All options

To enable the Write Protect feature, navigate to the Write Protect screen.

 

 

 

Display Setup

 

 

 

Main Menu

 

 

Alarm Setting

 

 

 

Process Vars

 

 

Mode Select

 

 

 

 

 

HART Option

 

 

 

Display Status

 

 

 

 

Write Protect

 

 

RTC

 

 

Device Status

 

 

 

 

Change State

 

 

RS485

 

 

Display Setup

 

 

 

 

Change Password

 

 

Input Loop Cal

 

 

Device Setup

 

 

 

 

Write Protect xxx

 

 

Contrast Contrl

 

 

Device Cal

 

 

 

 

 

 

 

Output Mode

 

 

 

Display Test

 

 

 

 

 

 

 

Backlight Ctrl

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Write Protect

 

 

 

 

 

 

 

 

 

 

Select “Change State” to toggle between Enabled and Disabled.

Select “Change Password” to enter a new password.

“Write Protect” indicates whether password protection is Enabled or Disabled.

The default password is 1*******.

IMportant

Take care not to lose the password. Future changes cannot be made without a password.

DiSplay BaCklighT OpeRATION

The UD10 can be programmed to turn on the backlight feature of the digital display when an alarm or fault occurs or a magnetic switch is activated. Navigate to the Backlight Ctrl screen.

 

 

 

Display Setup

 

 

 

Main Menu

 

 

Alarm Setting

 

 

 

Process Vars

 

 

Mode Select

 

 

 

Display Status

 

 

HART Option

 

 

 

 

 

 

 

Backlight Ctrl

Device Status

 

 

RTC

 

 

 

 

 

 

Off

Display Setup

 

 

RS485

 

 

 

 

 

 

On

Device Setup

 

 

Input Loop Cal

 

 

 

 

 

 

Automatic

Device Cal

 

 

Contrast Contrl

 

 

 

 

 

 

 

Display Test

 

 

Output Mode

 

 

 

Device Test

 

 

Backlight Ctrl

 

 

 

 

 

 

Write Protect

 

 

 

Off = The backlight is always off.

On = The backlight is always on.

Automatic = Normal operation – Backlight is off Alarm – Backlight flashes on and off Fault – Backlight is on steady

Magnetic Switch – Backlight is on steady

The backlight automatically turns off 10 minutes after the last Magnetic Switch activation.

If the backlight is on following a magnetic switch activation and then an alarm condition occurs, the backlight will remain on steady and not flash until the 10 minute time-out is complete. Then it will begin flashing.

4.2

15

95-8661

Troubleshooting

If a Fault condition is indicated on the UD10 faceplate, the nature of the fault can be determined by using the magnetic tool to navigate to the appropriate Fault screen.

NoTE

Refer to the Menu in the appropriate Appendix of this manual for the path to the proper Fault screen.

Shortcut: From the main display screen, touch the magnet to the “Previous” switch to go directly to the Fault screen.

Example:

For a Display (UD10) related fault:

Main Menu > Display Status > Fault/Status > Fault

For a Device (Sensor) related fault:

Main Menu > Device Status > Fault/Status > Sensor Fault

When the active fault has been identified, refer to the Troubleshooting Tables for a description of the fault and suggested corrective action.

Refer to Table 3 for Display Faults and Table 4 for Device Faults.

Table 3—Troubleshooting Guide - Display Faults

Display Faults

Description

Recommended Action

 

 

 

 

 

Check sensor wiring.

Input Loop FLT

Fault in sensor or sensor loop

Calibrate sensor.

 

 

Ensure that sensor type matches configuration.

 

 

 

Output Loop FLT

Fault in 4-20 mA output loop

Check 4-20 mA loop wiring for shorts or opens.

 

 

 

EE Fault

Fault in non-volatile memory

Return to factory.

 

 

 

ADC Ref Fault

ADC reference voltage too high or low

Return to factory.

 

 

 

24V Fault

Problem in 24 volt power supply or power wiring

Check power wiring and output voltage of power

supply.

 

 

 

 

 

Flash Fault

FLASH memory Fault

Return to factory.

 

 

 

RAM Fault

Fault in volatile memory

Return to factory.

 

 

 

WDT Fault

Watchdog timer is non-functional

Return to factory.

 

 

 

12V Fault

12 volt internal power supply out of tolerance

Check power source.

Return to factory.

 

 

 

 

 

5V Fault

5 volt internal power supply out of tolerance

Check power source.

Return to factory.

 

 

 

 

 

3V Fault

3 volt internal power supply out of tolerance

Check power source.

Return to factory.

 

 

 

 

 

Note: A fault condition will cause an oxygen detector to generate an alarm output as the decreasing 4-20 mA signal passes through the alarm range.

4.2

16

95-8661

Table 4—Troubleshooting Guide - Device Faults

Device Faults

Description

Recommended Action

 

 

 

Loop Fault

Current loop below fault threshold

Check 4-20 mA loop wiring for shorts or opens.

 

 

 

Supply Voltage

24 volt power supply voltage too low

Verify proper wiring to the device and correct

Fault

voltage output from the power supply.

 

 

 

 

 

 

This fault can be caused if the calibration is

 

 

allowed to time out. If so, recalibrate.

 

 

Ensure that there is enough gas in the calibration

Calibration Fault

Bad calibration

bottle to complete the calibration.

 

 

Ensure that the gas being used for calibration is

 

 

the correct type and concentration. It must match

 

 

the configured setting.

 

 

 

Memory Fault

Self-detected memory fault

Return to factory.

 

 

 

ADC Fault

Self-detected ADC fault

Return to factory.

 

 

 

Internal Voltage

Self-detected voltage fault

Check supply voltage.

Fault

Return to factory.

 

 

 

 

 

 

Device may have been calibrated with background

Zero Drift

Sensor signal has drifted negative

gas present. Recalibrate the detector. Purge with

 

 

clean air if needed.

 

 

 

Temperature

Temperature sensor is out of range

Return to factory.

Sensor Fault

 

 

 

 

 

Wrong Sensor

Wrong sensor type is installed

Sensor type must match configuration. Change

Type

sensor or configuration.

 

 

 

 

Lamp Fault

Open or shorted lamp

Replace lamp.

Return to factory.

 

 

 

 

 

Alignment Fault

Open path alignment problem

Align the device as specified in the instruction

manual.

 

 

 

 

 

Blocked Optic

Optical path is blocked

Locate and remove obstruction from the optical

Fault

path.

 

 

 

 

Cal Line Active

Cal line is active at start-up

Ensure that the Cal line wiring is not shorted and

the switch is open.

 

 

 

 

 

Low Cal Line

Cal line is shorted.

Check wiring.

 

 

 

 

 

Check sensor wiring.

Sensor Fault

Self-detected fault with the sensor

Calibrate sensor.

 

 

Ensure that sensor type matches configuration.

 

 

 

Noise Fault*

Excessive noise on signal

Check OPECL alignment.

 

 

 

Align ADC Fault*

Alignment ADC saturated

Check OPECL alignment.

 

 

 

Align Fault*

Alignment fault

Check OPECL alignment.

 

 

 

Align Warning*

Alignment warning

Check OPECL alignment.

 

 

 

DAC Fault

DAC fault detected

Return to factory.

 

 

 

General Fault

Unspecified fault

Verify correct power wiring and supply voltage.

Consult the factory.

 

 

 

 

 

High Fault

Detector output is higher than specified limit

Verify correct sensor type and calibration.

 

 

 

Low Fault

Detector output is lower than specified limit

Verify correct sensor type and calibration.

 

 

 

Dirty Optics

Detector optics are dirty

Perform the cleaning procedure as described in

the detector manual, then perform calibration.

 

 

 

 

 

Start Cal Fault

Calibration fault

Verify correct sensor type and calibrate.

 

 

 

*OPECL only.

 

 

4.2

17

95-8661

Table 4—Troubleshooting Guide - Device Faults, Continued

Device Faults

Description

Recommended Action

 

 

 

 

 

Power may have been interrupted while the device

EE Fault

Fault in non-volatile memory

was updating its internal data logs. Recycle

 

 

power.

 

 

 

Ref ADC Sat

Sensor signal level is outside the range of the AD

Return to factory.

converter

 

 

 

 

 

Active ADC Sat

Sensor signal level is outside the range of the AD

Return to factory.

converter

 

 

 

 

 

24V Fault

Problem in 24 volt power supply or power wiring

Check power wiring and output voltage of power

supply.

 

 

 

 

 

Flash CRC Fault

Memory fault

Return to factory.

 

 

 

RAM Fault

Fault in volatile memory

Return to factory.

 

 

 

Low Voltage

Power supply voltage outside of limits

Check power supply voltage.

Return to factory.

 

 

 

 

 

Temp Fault

Temperature sensor fault

Return to factory.

 

 

 

Software Fault

Internal software fault

Return to factory.

 

 

 

EE Safety Fault

Internal configuration fault

Return to factory.

 

 

 

 

 

Device may have been calibrated with background

Gas Under Range

Sensor signal has drifted negative

gas present. Recalibrate the detector. Purge with

 

 

clean air if needed.

 

 

 

Sensor Mismatch

Wrong sensor type is installed

Sensor type must match configuration. Change

sensor or configuration.

 

 

 

 

 

ADC CNTR Fault

Internal hardware fault

Return to factory.

 

 

 

3V Fault

3 volt internal power supply out of tolerance

Return to factory.

 

 

 

Comm Fault

Communication fault

Check detector wiring and power supply.

 

 

 

GEN Fault

Unspecified fault

Verify correct power wiring and supply voltage.

Consult the factory.

 

 

 

 

 

12V Fault

12 volt internal power supply out of tolerance

Return to factory.

 

 

 

5V Fault

5 volt internal power supply out of tolerance

Return to factory.

 

 

 

4.2

18

95-8661

Specifications

operating voltAGE—

24 Vdc nominal, operating range is 18 to 30 Vdc. Ripple cannot exceed 0.5 volt P-P.

operating power—

Standard model, with heater and backlight off:

No alarm:

1.5 watts @ 24 Vdc.

Alarm:

3 watts @ 24 Vdc (20 mA current

 

loop output, and all 3 alarm relays

 

energized.)

Backlight on:

0.5 watt additional.

Heater on:

3.5 watts additional.

CGS model:

Add 4 watts with CGS interface

 

board and CGS sensor installed.

Maximum power in alarm, with heater and backlight on: 7 watts @ 30 Vdc (Standard model) 11 watts @ 30 Vdc (CGS model)

note

Heater turns on when the internal temperature drops below –10°C (default operation). Heater function can be disabled to save power.

note

Appropriate relays will be activated when a fault or alarm occurs.

CURRENT OUTPUT—

Linear isolated 4-20 mA output with HART. 3.8 mA indicates calibrate mode.

3.6 mA or less indicates a fault condition.

Maximum loop resistance is 600 ohms at 18 to 30 Vdc.

CURRENT OUTPUT Response Time—

Toxic gas mode:

T90

≤5 seconds.

Combustible gas mode:

T90

≤4 seconds.

Combustible gas - open path mode: T90

≤4 seconds.

UD10 with CGS:

T90

<12 seconds.

Current Output AccuraCy—

 

Toxic gas mode:

<1% error.

Combustible gas mode:

<1% error.

Combustible gas - open path mode: ≤0.01 LFL-m.

UD10 with CGS:

±3% LFL 0-50 range,

 

±5% LFL 51-100 range.

RELAY CONTACTS—

Three Alarm Relays: Form C, 5 amperes at 30 Vdc. Selectable energized/de-energized. Selectable latching or non latching. Refer to Table 1 for range and default settings.

Warning

When in non-latching mode, the control device must latch the alarm output.

One Fault Relay:

Form C, 5 amperes at 30 Vdc.

 

Normally energized for no fault

 

condition with power applied.

Relay Response Time—

≤ 2 seconds.

Wiring terminals—

14 to 18 AWG wire can be used.

OPERATing temperature—

–55°C to +75°C.

StorAGE TeMPERATURE—

–55°C to +75°C.

HuMidity Range—

5 to 95% RH (Det-Tronics verified).

electro-magnetic compatibility—

EMC Directive 2004/108/EC EN55011 (Emissions) EN50270 (Immunity)

DIMENSIONS—

See Figures 12 and 13.

4.2

19

95-8661

Det-Tronics UD10 User Manual

6.48

4.7

(16.5)

(11.9)

 

3.46

 

(8.8)

 

5.2

 

(13.2)

 

5.86

 

(14.9)

11.28

 

(28.7)

 

 

R0.175

A2442

Figure 12—Dimensions of UD10 with GT3000 in Inches (Centimeters)

CondUit EntRies—

WARRANTY—

3/4” NPT or M25.

12 months from date of installation or 18 months from

 

 

date of shipment, whichever occurs first.

ENCLOSURE MATERIAL—

 

Epoxy coated aluminum or 316 stainless steel.

Detector compatibility—

 

 

The UD10 can be used with the Det Tronics gas

SHIPPInG WEIGHT—

detectors listed in Table 5.

Aluminum:

4.15 pounds (1.88 kilograms).

 

Stainless steel:

10.5 pounds (4.76 kilograms).

Unit of Measurement—

 

 

PPM, % LFL, % V/V, LFL-m, or mg/m3.

4.2

20

95-8661

4.7

(11.9)

3.46

(8.8)

3.77

(9.6)

1.28

(3.3)

5.86

(14.9)

5.2

(13.2)

2.7

(6.9)

Certification—

For complete approval details, refer to the appropriate Appendix:

FM

®

APPROVED

 

Appendix A – FM

Appendix B – CSA

Appendix C – ATEX

Appendix D – IECEx

Appendix E – INMETRO

SIL Approval - IEC 61508

Certified SIL 2 Capable.

For specific information regarding SIL safety certification, refer to the Model UD10 Safety Reference Manual (form 95-8668).

C2281

Figure 13—Dimensions of Model STB Termination Box in Inches (Centimeters)

Table 5—Gas Detectors Compatible with the UD10

Device

Toxic1

Catalytic

IR2

Instruction

Combustible

Combustible

Manual

 

 

 

 

 

 

 

GT3000

X

 

 

95-8616

 

 

 

 

 

PIR9400

 

 

X

95-8440

 

 

 

 

 

PIRECL

 

 

X

95-8526

 

 

 

 

 

OPECL

 

 

X

95-8556

 

 

 

 

 

CGS

 

X

 

90-1041

 

 

 

 

 

505/CGS

 

X

 

95-8472

 

 

 

 

 

 

 

 

 

95-8396

C706X3

X

 

 

95-8411

 

 

95-8414

 

 

 

 

 

 

 

 

95-8439

 

 

 

 

 

NTMOS4

X

 

 

95-8604

1Hydrogen sulfide, Ammonia, Chlorine, Hydrogen, Oxygen, Carbon Monoxide, and Sulfur Dioxide.

2Methane, Ethane, Ethylene, Propane, and Propylene.

3C7065E Oxygen detector is not supported.

4Hydrogen sulfide only.

4.2

21

95-8661

DEVICE REPAIR AND RETURN

Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure.

Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. The RMI number should be clearly marked on the outside of the box.

note

Inadequate packaging that ultimately causes damage to the returned device during shipment will result in a service charge to repair the damage incurred during shipment.

Return all equipment transportation prepaid to the factory in Minneapolis.

NoTE

It is highly recommended that a spare be kept on hand for field replacement to ensure continuous protection.

ORDERING INFORMATion

Sensor module, transmitter module and termination boxes (if used) must be ordered separately.

Refer to the UD10 Model Matrix for ordering details.

aCCESSORIES

Part Number

Description

009700-001

Magnetic Tool

103922-001

475 Field Communicator

010268-001

Gas Inspector CD

010204-001

W6300G1003 Gas Inspector Connector

005003-001

Lubriplate grease, 1 oz.

101197-001*

Stop Plug, 3/4” NPT, AL

101197-004*

Stop Plug, 3/4” NPT, SS

101197-005

Stop Plug, M25, AL, IP66

101197-003

Stop Plug, M25, SS, IP66

010816-001

Stop Plug, 20PK, 3/4” NPT, AL

010817-001

Stop Plug, 20PK, 3/4” NPT, SS

010818-001

Stop Plug, 20PK, M25, AL, IP66, EXDE

010819-001

Stop Plug, 20PK, M25, SS, IP66, EXDE

104190-001

Stop Plug, M25, AL, INMETRO

104190-002

Stop Plug, 3/4” NPT, AL, INMETRO

104190-003

Stop Plug, M25, SS, INMETRO

104190-004

Stop Plug, 3/4” NPT, SS, INMETRO

102804-001

Reducer, M25 to M20, AL

102804-003

Reducer, M25 to M20, SS

*NEMA/Type 4X, IP66 rating requires addition of Teflon tape.

ReplaCEmeNT Parts

Part Number Description

010569-001 Electronics Module - Relay/4-20 mA

010550-001 Electronics Module - Foundation Fieldbus

AsSISTANCE

For assistance in ordering a system to meet the needs of a specific application, please contact:

Detector Electronics Corporation 6901 West 110th Street

Minneapolis, Minnesota 55438 USA Operator: (952) 941-5665 or (800) 765-FIRE Customer Service: (952) 946-6491

Fax: (952) 829-8750

Web site: www.det-tronics.com E-mail: det-tronics@det-tronics.com

4.2

22

95-8661

Loading...
+ 53 hidden pages