Instructions 95-8656
FlexVu® Universal Display Unit
Model UD10 DCU Emulator
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4.2 |
|
|
|
|
|
|
|
Rev: 9/12 |
95-8656 |
|||||||||||||||
|
|
|
|
|
|
|
Table of Contents
application . . . . . . . . . . . . . . . . . . . . |
. |
|
1. . . |
.Appendix. . . . . G — UD10-DCU WITH pir9400 . . . . . . . . . |
.G-1 |
|||
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . |
. |
. |
1. . . |
. . |
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
G-1 |
||
Magnetic Switches . . . . . . . . . . . . . . . |
. |
. |
|
|
Installation Notes . . . . . . . . . . . . . . . . . . . . . . |
.G-2 |
||
2. . . . . . . |
|
G-2 |
||||||
Device Enclosure . . . . . . . . . . . . . . . . |
. |
|
|
|
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
|||
.3 . . . . . . . |
|
G-3 |
||||||
Device Display . . . . . . . . . . . . . . . . . |
. |
|
|
|
Changing Operating Modes . . . . . . . . . . . . . . . |
|||
|
.3 . . . . . . . . |
|
.G.-3. . . . |
|||||
Configuration Overview |
|
|
3 |
|
Calibration . . . . . . . . . . . . . . . . . . . . . . |
|||
. |
|
|
Menu Structure |
G-3 |
||||
Alarms |
|
|
4 |
|
||||
. |
|
|
|
|
|
|||
Calibration Gas Concentration . . . . . . . . . . . . . |
. |
. |
4 |
Appendix H — UD10-DCU WITH model pirecl . . . . |
H-1 |
|||
Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. . |
|
5 |
|
Wiring |
H-1 |
||
|
|
|
|
|
||||
|
|
|
|
|
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
H-2 |
||
IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . . |
. . |
|
5 |
|
Calibration . . . . . . . . . . . . . . . . . . . . . . |
.H.-3. . . . |
||
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . |
. |
.6. . . . |
Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . |
H-4 |
||||
|
|
|
||||||
Identification of Vapor(s) to be Detected |
|
|
6 |
Appendix I — UD10-DCU WITH MODEL OPECL . . |
. I-1 |
|||
. . |
|
|
Wiring |
I-1 |
||||
Identification of Detector Mounting Locations |
|
|
6 |
|
||||
. . |
|
|
Orientation |
I-3 |
||||
|
|
|
|
|
||||
WIRING |
|
|
7 |
|
Calibration . . . . . . . . . . . . . . . . . . . . . . |
. I.-3. . . . . |
||
. . |
|
|
OPECL Transmitter Lamp Fault Condition |
I-4 |
||||
Power Supply Requirements |
|
|
7 |
|
||||
. . |
|
|
Menu Structure |
I-4 |
||||
Wiring Cable Requirements |
|
|
7 |
|
||||
. . |
|
|
|
|
|
|||
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . |
. . |
|
7 |
Appendix J — UD10-DCU WITH NTMOS H2S Sensor J-1 |
||||
Shield Connections . . . . . . . . . . . . . . . . |
. |
.7. . . |
. . |
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
J-1 |
|||
LON Address Switch Setting . . . . . . . . . . |
. |
|
9. . . |
. . |
Installation Notes . . . . . . . . . . . . . . . . . . . . . . |
. J-1 |
||
|
|
|
|
|
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
J-3 |
||
Recommended STARTUP Procedure . . . . |
. |
. |
9. . |
|
Calibration . . . . . . . . . . . . . . . . . . . . . . |
. J.-3. . . . |
||
S3 Configuration . . . . . . . . . . . . . . . |
|
|
|
|
Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . |
J-4 |
||
. 10. . . . . . . |
|
|
||||||
Troubleshooting |
15 |
Appendix K — UD10-DCU WITH C706X GAS SENSOR . K-1 |
||||||
|
Wiring |
K-1 |
||||||
|
|
|
|
|
||||
SPECIFICATIONS |
18 |
|
Installation . . . . . . . . . . . . . . . . . . . . . . . |
.K.-3. . . |
||||
|
Calibration . . . . . . . . . . . . . . . . . . . . . . |
.K.-4. . . . |
||||||
Device Repair and Return |
20 |
|
||||||
|
Menu Structure |
K-4 |
||||||
|
|
|
|
|
||||
Ordering Information . . . . . . . . . . . . |
20. . . . Appendix. . |
L — UD10-DCU with Model CGS Sensor . |
.L-1 |
|||||
|
|
|
|
|
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
. L-1 |
||
APPENDIX A — FM Approval description |
a-1 |
|
Important Notes . . . . . . . . . . . . . . . . . . . . . . . . |
. L-1 |
||||
|
Installation |
L-3 |
||||||
|
|
|
|
|
||||
appendix b — csa certification description . b-1 |
|
Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
L-4 |
|||||
|
K-Factor.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. L-4 |
|||||||
|
|
|
|
|
||||
appendix C — atex approval description . . . . . |
c-1 |
|
Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . . |
. L-4 |
||||
appendix d — iec approval description |
d-1 |
Appendix M — UD10-DCU WITH Model 505/CGS M-1 |
||||||
|
Wiring |
M-1 |
||||||
|
|
|
|
|
||||
Appendix E — Additional Approvals . . . . . . . E.-.1. |
|
Installation . . . . . . . . . . . . . . . . . . . . . . . |
.M.-2. . . |
|||||
Appendix F — UD10-DCU with GT3000 |
F-1 |
|
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
M-2 |
||||
|
Calibration . . . . . . . . . . . . . . . . . . . . . . |
.M.-3. . . . |
||||||
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
F-1 |
|
Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . |
M-4 |
||||
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
F-2 |
Appendix N — UD10-DCU WITH Generic 4-20 ma sensor |
N-1 |
|||||
Live Maintenance |
F-2 |
|||||||
|
Operation |
N-1 |
||||||
Calibration . . . . . . . . . . . . . . . . . . . . . . . F.-3. . . . |
|
|||||||
|
Menu Structure |
N-1 |
||||||
Menu Structure |
F-4 |
|
||||||
|
|
|
|
INSTRUCTIONS
FlexVu® Universal Display Unit
Model UD10 DCU Emulator
Important
Be sure to read and understand the entire instruction manual before installing or operating the gas detection system. This product can be used with a variety of Det-Tronics gas detectors to provide early warning of the presence of a toxic or explosive gas mixture. Proper device installation, operation, and maintenance is required to ensure safe and effective operation. If this equipment is used in a manner not specified in this manual, safety protection may be impaired.
Application
The FlexVu® Model UD10 DCU Emulator (UD10-DCU) is designed for applications that require a gas detector with digital readout of detected gas levels. Its LON interface board makes the UD10-DCU compatible with Eagle Quantum Premier systems by digitizing the 4-20 mA analog signal from the attached sensor/transmitter and transmitting the value as a process variable over the LON to the EQP controller.
The UD10-DCU is designed for use with most currently available Det Tronics gas detectors. Refer to the Specifications section of this manual for a list of compatible gas detectors. When furnished with the CGS interface board, the device can be used only with a CGS sensor for detection of combustible gas. The UD10/CGS combination is certified as a “Gas Detector”.
Gas concentration and unit of measurement are indicated on a digital display.
All electronics are enclosed in an explosion-proof aluminum or stainless steel housing. The display unit is used with a single detector that may be either coupled directly to the UD10-DCU, or remotely located using a sensor termination box.
The UD10-DCU features non-intrusive calibration. A magnet is used to perform calibration as well as to navigate the UD10-DCU’s internal menu.
Description
The UD10-DCU Universal Display can be used with various 4-20 mA gas detection devices, with or without HART. The unit provides display, output and control capabilities for the gas detector.
The UD10-DCU utilizes the following I/O:
Signal Inputs: |
4-20 mA loop from the sensing device |
User Inputs: |
Magnetic switches on the display panel |
|
S3 Software |
Signal Outputs: |
LON communication |
Visible Outputs: |
Backlit LCD display |
|
Computer running S3 Software |
4.2 |
©Detector Electronics Corporation 2012 |
Rev: 9/12 |
95-8656 |
magnetic switches
Four internal magnetic switches provide a non intrusive user interface that allows navigation through the menu. See Figure 1 for switch locations.
PREVIOUS
CANCEL / ESCAPE
ENTER / SELECT
NEXT
B2426
Figure 1—Faceplate of UD10-DCU
These switches are used for device configuration, checking status and event logs, and performing calibration. The switches are labeled as follows:
CANCEL / ESCAPE
ENTER / SELECT / Menu ACCESS
Previous or if on Main Screen:
Fault Shortcut
Next
To actuate a magnetic switch, lightly touch the magnet to the viewing window of the UD10-DCU directly over the switch icon on the faceplate.
Caution
Handle magnets with care! Personnel wearing pacemakers/defibrillators should not handle magnets. Modern magnet materials are extremely strong magnetically and somewhat weak mechanically. Injury is possible to personnel, and magnets themselves can easily get damaged if allowed to snap towards each other, or if nearby metal objects are allowed to be attracted to the magnets.
note
Det-Tronics offers two magnet options for activating internal magnetic switches. While the two magnets can usually be used interchangeably, the best results will be achieved if they are used as follows: The Magnetic Tool (p/n 009700-001) is the stronger magnet and is recommended for activating the switches on the UD10-DCU viewing window. The Calibration Magnet (p/n 102740 002) is recommended for applications that involve initiating calibration or resetting the detector by touching the side of a metal junction box or detector housing (PIRECL, OPECL, etc). Throughout this manual, the term “magnet” can refer to either device.
Access To Menus
To access the menus, use the magnet to activate the Enter/Select button. This will display the Main Menu.
The actual menu structure varies depending upon the device that is connected to the UD10-DCU. Menus for the various devices can be found in the corresponding Appendix in this manual.
Some areas of the menu contain additional information, which is indicated by the presence of an arrow on that particular line. By placing the magnet to the glass over the Enter/Select button, the next screen with the additional information will be shown.
The UD10-DCU automatically returns to the main screen after 10 minutes if no activity occurs.
4.2 |
2 |
95-8656 |
Quick Access/Shortcut: Fault Menu
To access the fault menu quickly, when a fault is present, touch the magnet to the glass by the Previous button.
Device ENCLOSURE
The UD10-DCU housing is a 5 port aluminum or stainless steel explosion proof junction box with a clear viewing window.
Device DISPLAY
The UD10-DCU is provided with a 160 x 100 dot matrix backlit LCD display. See Figure 1.
During normal operation, the LCD continuously displays the detected gas level, gas type, and units of measurement. The real time clock can also be displayed if desired.
The display shows the following alarm information:
•High gas alarm
•Low gas alarm
•Aux alarm
The display indicates the following fault information:
•Device fault
•Display fault
The UD10-DCU has smart capabilities to allow easy access to the following information:
•Detector information
•Measurement range
•Alarm setpoints
•Alarm and event logs
For detailed menu structure, refer to the appropriate Appendix.
Configuration overview
The user must select the sensor mode/type manually from the UD10-DCU display. The selection options are:
HART Device (including Generic HART Device) PIR9400
C706x
505 NTMOS CGS
Generic Device (without HART)
When “HART Device” is selected, the UD10-DCU communicates with the detector to determine the device type. The upper and lower range for the UD10-DCU display is determined by the detector type and must be selected before configuration data is sent from the EQP system. If the detector type or range is changed at the UD10-DCU, a configuration download from S3 should again be performed.
Alarm levels and calibration gas concentration level come from the S3 application. Configuration information is downloaded from S3 to the controller, which sends the data to the LON interface board in the UD10-DCU. The LON interface then sends configuration information to the main processor in the UD10-DCU for storage and display. Alarm levels and calibration gas concentration cannot be set from the UD10-DCU menu system, however, they can be viewed after download.
Status information from the UD10-DCU and attached detector is passed to the EQP controller over the LON network, and then to S3 for display.
4.2 |
3 |
95-8656 |
Alarms
The UD10-DCU has a low and high alarm that are set from the S3 configuration software and then downloaded to the UD10-DCU. Alarm status can be viewed at the UD10-DCU display, the EQP controller, or S3. Alarms are non latching at the UD10-DCU, but can be latched using logic within the EQP Controller.
With some configurations, the alarm limits on the UD10 DCU are tighter than on S3. If a value is out of range, the UD10-DCU will set the value as close as possible while remaining within the allowable range (See Table 1). After the configuration download is complete, the alarm setpoints can be viewed at the UD10-DCU under Display Status->LON Config menu.
Calibration Gas Concentration
The calibration gas concentration is programmed from S3 and downloaded to the UD10-DCU. See Table 2 for calibration gas limits. NTMOS, CGS, and PIR9400 require a gas concentration of 50% full scale. Calibration gas concentration can be viewed from the UD10-DCU menu under Display Status->LON Config.
Table 1—UD10-DCU Alarm Limits
|
UD10 Limits |
|
EQP Limits |
System Limits |
|||
|
|
|
|
|
|
|
|
Detector Type |
Low Alarm |
High Alarm |
Recommended |
Low Alarm |
High Alarm |
Low Alarm |
High Alarm |
EQP Configuration |
|||||||
|
|
|
|
|
|
|
|
GT3000 Toxic |
5-50% |
10-90% |
Universal Automatic |
10-100% |
20-100% |
10-50% |
20-90% |
|
|
|
|
|
|
|
|
GT3000 O2* |
16-20.5% v/v |
5-20.5% v/v |
Oxygen |
1.3-25% v/v |
2.5-25% v/v |
16-20.5% v/v |
5-20.5% v/v |
|
|
|
|
|
|
|
|
PIR9400 |
5-50% |
10-60% |
Explosive |
5-40% |
10-60% |
5-40% |
10-60% |
|
|
|
|
|
|
|
|
Eclipse |
5-50% |
10-60% |
Explosive |
5-40% |
10-60% |
5-40% |
10-60% |
|
|
|
|
|
|
|
|
Open Path |
5-50% |
10-90% |
Universal Automatic |
10-100% |
20-100% |
10-50% |
20-90% |
|
|
|
|
|
|
|
|
C706x |
5-50% |
10-90% |
Universal Automatic |
10-100% |
20-100% |
10-50% |
20-90% |
|
|
|
|
|
|
|
|
505/CGS |
5-50% |
10-60% |
Explosive |
5-40% |
10-60% |
5-40% |
10-60% |
|
|
|
|
|
|
|
|
NTMOS H2S |
5-50% |
10-90% |
Universal Automatic |
10-100% |
20-100% |
10-50% |
20-90% |
|
|
|
|
|
|
|
|
CGS |
5-50% |
10-60% |
Explosive |
5-40% |
10-60% |
5-40% |
10-60% |
|
|
|
|
|
|
|
|
Generic Device |
0-100% |
0-100% |
Universal Automatic |
10-100% |
20-100% |
10-100% |
20-100% |
|
|
|
|
|
|
|
|
*Sensor approved for oxygen depletion (<21% V/V) only.
Table 2—Calibration Gas Concentration Limits
Detector Type |
UD10 Limits |
Recommended EQP |
EQP Limits |
System Limits |
|
Configuration |
|||||
|
|
|
|
||
|
|
|
|
|
|
GT3000 Toxic |
30-90% |
Universal Automatic |
20-100% |
30-90% |
|
|
|
|
|
|
|
GT3000 O2 |
20.9% v/v |
Oxygen |
5-25% v/v |
20.9% v/v |
|
|
|
|
|
|
|
PIR9400 |
50% |
Explosive |
20-100% |
50% |
|
|
|
|
|
|
|
Eclipse |
30-90% |
Explosive |
20-100% |
30-90% |
|
|
|
|
|
|
|
Open Path |
30-90% |
Universal Automatic |
20-100% |
30-90% |
|
|
|
|
|
|
|
C706x |
30-90% |
Universal Automatic |
20-100% |
30-90% |
|
|
|
|
|
|
|
505/CGS |
N/A |
Explosive |
20-100% |
N/A |
|
|
|
|
|
|
|
NTMOS H2S |
50% |
Universal Automatic |
20-100% |
50% |
|
|
|
|
|
|
|
CGS |
50% |
Explosive |
20-100% |
50% |
|
|
|
|
|
|
|
Generic Device |
N/A |
Universal Automatic |
20-100% |
20-100% |
|
|
|
|
|
|
4.2 |
4 |
95-8656 |
Logging
Events that can be logged in the UD10-DCU include:
•Calibration (Date, time and success Y/N are logged for detectors that do not provide their own calibration logging capabilities.)
Faults that are logged in the UD10-DCU include:
•Detector fault
•Low power
•General fault
Alarms that are logged in the UD10-DCU for gas detector inputs include:
•High gas alarm
•Low gas alarm.
The UD10-DCU can display the detector event and calibration logs (if available). Detector calibration and event logs can also be read from the detector’s HART interface (where available).
The UD10-DCU has its own 1,000 entry event log available under the Display Status >History >Event Log menu.
The LON interface board in the UD10-DCU has eight alarm logs and eight calibration logs. These logs are available from the S3 “Point Display Screen” for the UD10 DCU.
The EQP Controller and S3 also maintain their own logs. Refer to the EQP system manual (95 8533) and/or the S3 manual (95-8560) for details.
important safety notes
CAUTION
The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local codes. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person.
CAUTION
This product has been tested and approved for use in hazardous areas. However, it must be properly installed and used only under the conditions specified within this manual and the specific approval certificates. Any device modification, improper installation, or use in a faulty or incomplete configuration will render warranty and product certifications invalid.
CAUTION
The device contains no user serviceable components. Service or repair should never be attempted by the user. Device repair should be performed only by the manufacturer.
Liabilities
The manufacturer’s warranty for this product is void, and all liability for proper function of the detector is irrevocably transferred to the owner or operator in the event that the device is serviced or repaired by personnel not employed or authorized by Detector Electronics Corporation, or if the device is used in a manner not conforming to its intended use.
Caution
Observe precautions for handling electrostatic sensitive devices.
caution
Unused conduit entries must be closed with suitably certified blanking elements upon installation.
4.2 |
5 |
95-8656 |
Installation
NOTE
For complete instructions regarding wiring, installation, and use of the Eagle Quantum Premier system, refer to manual number 95-8533.
note
The gas detector housing must be electrically connected to earth ground. A dedicated earth ground terminal is provided on the UD10-DCU.
The detector must always be installed per local installation codes.
Before installing the gas detector, define the following application details:
Identification of vapor(s) to be detected
It is necessary to identify the vapor(s) of interest at the job site. The fire hazard properties of the vapor, such as vapor density, flashpoint, and vapor pressure should be identified and used to assist in selecting the optimum detector mounting location within the area.
For cross sensitivity information, refer to each gas detector’s corresponding instruction manual. Refer to the Specifications section in this manual for a list of gas detectors and their corresponding instruction manuals.
Identification of detector mounting locations
Identification of the most likely leak sources and leak accumulation areas is typically the first step in identifying the best detector mounting locations. In addition, identification of air current/wind patterns within the protected area is useful in predicting gas leak dispersion behavior. This information should be used to identify optimum detector installation points.
If the vapor of interest is lighter than air, place the detector above the potential gas leak. Place the detector close to the floor for gases that are heavier than air. Note that air currents may cause a gas that is slightly heavier than air to rise under some conditions. Heated gases may also exhibit the same phenomenon.
The most effective number and placement of detectors varies depending on the conditions on site. The individual designing the installation must often rely on experience and common sense to determine the detector quantity and best locations to adequately protect the area. Note that it is typically advantageous to locate detectors where they are accessible for maintenance. Locations near excessive heat or vibration sources should be avoided.
Final suitability of possible gas detector locations should be verified by a job site survey.
The gas detector must be mounted with the sensor in the correct orientation as shown in Table 3.
If the UD10-DCU faceplate is not correctly oriented, it can be rotated at 90 degree increments by pulling the electronic module from the four mounting posts that secure it to the junction box and repositioning it as desired. Note that the module is held in place by a compression fitting – no screws are involved.
|
Table 3—Device Orientation |
|
|
|
|
Device |
|
Orientation |
|
|
|
GT3000 |
|
Vertical with Sensor Pointing Down |
|
|
|
PIR9400 |
|
Horizontal |
|
|
|
PIRECL |
|
Horizontal |
|
|
|
OPECL |
|
Horizontal (Fixed to a vertical post) |
|
|
|
CGS |
|
Vertical with Sensor Pointing Down |
|
|
|
505/CGS |
|
Vertical with Sensor Pointing Down |
|
|
|
C706X |
|
Vertical with Sensor Pointing Down |
|
|
|
NTMOS |
|
Vertical with Sensor Pointing Down |
|
|
|
4.2 |
6 |
95-8656 |
WIRING
power SUPPLY requirements
Calculate the total gas detection system power consumption rate in watts from cold start-up. Select a power supply with adequate capability for the calculated load. Ensure that the selected power supply provides regulated and filtered 24 Vdc output power for the entire system. If a back-up power system is required, a float type battery charging system is recommended. If an existing source of 24 Vdc power is being utilized, verify that system requirements are met. The acceptable voltage range is 18-30 Vdc measured at the input to the UD10-DCU.
Wiring cable requirements
Always use proper cabling type and diameter for input power as well as output signal wiring. 14 to 18 AWG shielded stranded copper wire is recommended. Correct wire size depends on the device and wire length. Refer to the appropriate Appendix for additional information. The maximum cable length from power source to UD10-DCU is 2000 feet. Maximum cable length from UD10-DCU to sensor is 2000 feet.
note
The use of shielded cable in conduit or shielded armored cable is highly recommended. In applications where the wiring is installed in conduit, dedicated conduit is recommended. Avoid low frequency, high voltage, and non signaling conductors to prevent nuisance EMI problems.
caution
The use of proper conduit installation techniques, breathers, glands, and seals is required to prevent water ingress and/or maintain the explosion-proof rating.
Wiring Procedure
NOTE
Since the UD10-DCU can be used with a variety of different detection devices, information that is specific to each detector model (wiring, calibration, HART menus, etc.) is covered in an Appendix that is dedicated to that device. Refer to the appropriate Appendix at the back of this manual for specific information when wiring the detection system. For information on devices not covered in an Appendix, refer to the manual provided by the device’s manufacturer.
Connect 24 vdc power lead wires and communication network cable to the appropriate terminal block. Refer
to Figure 2 for an illustration of the UD10-DCU wiring terminal board.
COM 1 - Communication network connections: Connect to COM 2 terminals of the next device on the loop, A to A and B to B.
COM 2 - Communication network connections: Connect to COM 1 terminals of the previous device on the loop, A to A and B to B.
24 VDC - Connect the “+” terminal to the positive side of the 24 vdc power source. (Both “+” terminals are connected internally.)
Connect the “–” terminal to the negative side of the 24 vdc power source. (Both “–” terminals are connected internally.)
Figure 3 shows a UD10-DCU Wired to a generic sensing device. Refer to the appropriate Appendix for information regarding a specific detector.
Grease/Lubrication
To ease installation and future removal, ensure that all junction box covers and sensor threads are properly lubricated. If the need arises for additional lubrication, use either Lubriplate grease (see Ordering Information for part number) or Teflon tape. Avoid the use of silicone grease.
Shield Connections
The UD10 provides terminals for proper grounding of wiring cable shields (located on the sensor, 4-20 mA, and operating power terminal blocks). These shield terminals are not connected internally, but are connected to ground through capacitors. The capacitors ensure an RF ground, while preventing 50/60 Hz ground loops.
Ground all shields as shown in the wiring examples throughout this manual.
important
For proper grounding, all junction boxes / metal enclosures must be connected to earth ground.
The following are required for installations requiring CE Mark compliance:
•For shielded cable installed in conduit, attach the wire shields to the “shield” connections on the terminal blocks, or to earth ground on the case.
•For installations without conduit, use double shielded cable. Terminate the outer shield to earth ground on the case. Terminate the inner shield to the “shield” connection on the terminal blocks.
4.2 |
7 |
95-8656 |
FACTORY USE ONLY
LON ADDRESS SELECTION SWITCHES
2 1 |
1 ON |
2 |
3 |
4 |
|
4 |
16 |
8 |
6 5 |
32 |
|
8 7 |
64 |
128 |
VALUES OF ALL SWITCHES IN THE
ON POSITION ARE ADDITIVE.
Sensor Connector
-1 |
-2 |
-3 |
-4 |
-5 |
J4 |
|
J4 |
J4 |
J4 |
J4 |
J4 |
||
|
||||||
SHIELD |
CALIBRATE |
24 VDC – |
4-20 mA |
24 VDC + |
|
|
|
|
|
|
|
|
SHIELD |
|
|
J2 |
|
|
|
|
2 B COM |
|
|
|
|
|
|
2 A COM |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
SHIELD |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON |
|
|
|
|
1 B COM |
|
|
|
SW3 |
|
|
|
1 A COM |
|
|
|
|
|
|
|
||
24 VDC – |
|
24 VDC + |
SHIELD |
24 VDC – |
24 VDC + |
SHIELD |
|
|
|
|
|
|
|
|
|
J7-6 |
|
J7-5 |
J7-4 |
J7-3 |
J7-2 |
J7-1 |
J7 |
|
|
|
|
|
|
|
|
Power Supply Connector
UD10
DISPLAY UNIT
J3-1 |
Connector |
|
|
J3-4 |
|
J3-2 |
|
J3-3 |
|
|
LON |
J3-5 |
|
|
|
J3-6 |
|
|
|
J3
A2509
Figure 2—Wiring Terminal Board
UD10
DISPLAY UNIT
Sensor Connector
|
|
|
|
|
|
|
|
|
|
|
|
-1 |
-2 |
-3 |
-4 |
-5 |
J4 |
||||||
J4 |
J4 |
J4 |
J4 |
J4 |
|||||||
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
SHIELD |
CALIBRATE |
VDC24 – |
20-4mA |
VDC24 + |
SEE NOTE 1 |
||||||
|
|
|
|
|
|
|
|
|
|
J2
|
ON |
|
|
|
|
|
SW3 |
|
|
|
|
24 VDC – |
24 VDC + |
SHIELD |
24 VDC – |
24 VDC + |
SHIELD |
J7-6 |
J7-5 |
J7-4 |
J7-3 |
J7-2 |
J7-1 |
Power Supply Connector
SHIELD |
J3-1 |
2 B COM |
J3-2 |
2 A COM |
J3-3 |
SHIELD |
J3-4 |
1 B COM |
J3-5 |
1 A COM |
J3-6 |
|
J3 |
J7
Connector |
SHIELD |
SHIELD |
|
|
B |
|
A |
LON |
B |
|
|
|
A |
|
24 VDC |
+ –
A2510
GENERIC
GAS DETECTOR SEE NOTE 3
CALIBRATE 24 VDC –
4-20 MA SIGNAL
24 VDC +
GROUND
LON FROM PREVIOUS DEVICE
LON TO NEXT DEVICE
NOTE 1 CONNECT THE SENSOR GROUND LEAD TO THE CHASSIS GROUND LUG ON THE
INSIDE BOTTOM OF THE DISPLAY ENCLOSURE.
NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
NOTE 3 GENERIC SENSOR SHOWN AS EXAMPLE. REFER TO THE APPROPRIATE APPENDIX
FOR SPECIFIC SENSOR WIRING INFORMATION.
Figure 3—UD10-DCU Wired to a Generic Gas Detector
4.2 |
8 |
95-8656 |
LON Address Switch Setting
Each device on the LON/SLC must be assigned a unique address. This is accomplished by setting DIP switches on the module’s circuit board. See Figure 2. Each rocker switch has a specific binary value. The node address is equal to the added value of all rocker switches in the “ON” position. All “OFF” switches are ignored. The valid address range is from 5 to 250.
The switch value is read at power-up. If a change is made with power applied (not recommended), power must be cycled before the change will be recognized. The LON address can be read from the UD10-DCU menu under Display Status->LON Config.
For additional information, refer to the Eagle Quantum Premier system manual (number 95-8533).
Recommended Startup
Procedure
1.Check the UD10-DCU LON address switches for proper setting.
2.Check all system wiring for proper connection.
3.With power applied to the system, select the correct sensor type or mode. See “Detector Type/Mode Selection Procedure” for details.
Note
A fault may be displayed until the configuration is downloaded.
4.Note the units on the main UD10-DCU display. (This will typically be PPM or %.)
5.Record the LON address, range, and units for each detector.
6.Complete the steps in the “S3 Configuration” section of this manual to configure the LON network from S3.
Detector Type/mode selection procedure
After power has been applied and the warm-up period is complete, select the UD10-DCU operating mode. To do this:
1.Access the Main Menu by touching the magnet to the ENTER/SELECT button. From there, navigate to the “Mode Select” menu.
Main Menu |
|
|
|
|
|
|
|
|
Display Setup |
|
|
Mode Select |
|
Process Vars |
|
|
|
|
||
|
|
Mode Select |
|
|
HART Device |
|
Display Status |
|
|
|
|
||
|
|
General Options |
|
|
PIR9400 |
|
Device Status |
|
|
|
|
||
|
|
RTC |
|
|
C706X |
|
Display Setup |
|
|
|
|
||
|
|
Input Loop Cal |
|
|
505 |
|
Device Setup |
|
|
|
|||
|
|
Contrast Contrl |
|
|
NTMOS |
|
Device Cal |
|
|
|
|
||
|
|
Backlight Ctrl |
|
|
CGS |
|
Display Test |
|
|
|
|
||
|
|
Write Protect |
|
|
Generic Device |
|
Device Test |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2.From the “Mode Select” menu, select and enter the appropriate operating mode based on the type of detector being used.
note
If using a PIR9400, note that changing the gas type on the UD10-DCU does not change the gas type at the PIR9400. This change is made using a switch located in the PIR9400. Refer to the PIR9400 instruction manual (95 8440) for details.
NOTE
If using a C706X detector, navigate to the “Device Setup” menu and select the appropriate gas type and unit of measurement.
3.To exit, activate Cancel/Escape three times to return to the main display screen.
note
If the detector is replaced with another detector type, the UD10-DCU will not recognize it until the mode is changed.
Note
If the UD10-DCU Display is in PIR9400 mode and if:
a.The connection between PIR9400 and the UD10 DCU is removed, the UD10-DCU will show a FAULT on the Gas Screen. When the connection between PIR9400 and UD10 DCU is restored, the UD10-DCU will remove the FAULT indication when current increases beyond 3.6 mA.
b.Someone removes the PIR9400 & connects a HART enabled Gas Detector, it will not be recognized by the UD10-DCU Display until the mode is changed to HART.
4.2 |
9 |
95-8656 |
S3 Configuration
Create a new DCU point with the correct LON address/ point number. See Figure 4.
Figure 4—Point Type Selection Screen
4.2 |
10 |
95-8656 |
The DCU configuration software supports six detector types:
Explosive
Oxygen
Universal (Automatic Calibration) Universal (Manual Calibration) Pointwatch
Ductwatch
Table 4 shows the recommended settings for each detector type.
Table 4—Recommended Settings for each Detector Type
Detector Type |
Recommended Configuration |
Comments |
|
|
|
|
|
GT3000 - All but O2 |
Universal Automatic |
Enter the proper range for the detector. Enter PPM for |
|
units. Then select the alarm and calibration levels. |
|||
|
|
||
|
|
|
|
GT3000 O2 |
Oxygen |
Units and range will automatically be set. Cal level must be |
|
set to 20.9%. |
|||
|
|
||
|
|
|
|
Eclipse |
Explosive |
Proper range and units are automatically set. Alarms are |
|
limited to approval requirements. |
|||
|
|
||
|
|
|
|
Open Path |
Universal Automatic |
Enter the proper range and units (LFL-M) for the detector. |
|
|
|
|
|
|
|
Proper range and units are automatically set. Alarms are |
|
PIR9400 |
Explosive |
limited to approval requirements. Calibration gas must be |
|
|
|
set to 50%. |
|
|
|
|
|
C706x |
Universal Automatic |
Enter the proper range for the detector and PPM for units. |
|
Then select the alarm and calibration levels. |
|||
|
|
||
|
|
|
|
505 |
Explosive |
Alarms are limited to approval requirements. Uses %LFL |
|
for units. |
|||
|
|
||
|
|
|
|
NTMOS |
Universal Automatic |
Enter the proper range (0-100) and units (PPM) for the |
|
detector. Calibration gas must be set to 50%. |
|||
|
|
||
|
|
|
|
|
|
Proper range and units are automatically set. Alarms are |
|
CGS |
Explosive |
limited to approval requirements. Calibration gas must be |
|
|
|
set to 50%. |
|
|
|
|
|
|
|
Enter the proper range and units for the detector. |
|
Generic |
Universal Automatic |
Calibration is not supported, so 50% should be used as |
|
|
|
the default. |
|
|
|
|
4.2 |
11 |
95-8656 |
Enter the appropriate data on the DCU Editor Screen. See Figure 5. The units and range entered at S3 will be seen in S3 and the Controller, but are not sent to the UD10-DCU. It is the user’s responsibility to ensure that S3 matches the actual detector type.
The alarm and calibration gas setpoints are downloaded to the UD10-DCU.
Figure 5—DCU Editor Screen
The LON parameters can be checked at the UD10 DCU display under the “LON Config” menu.
Main Menu |
|
|
|
|
|
||
Process Vars |
|
Display Status |
|
|
|
||
|
|
LON Config |
|||||
Display Status |
|
|
|
General Info |
|
|
|
|
|
|
Hgh Alarm Level |
||||
Device Status |
|
|
|
Fault/Status |
|
|
|
|
|
|
Low Alarm Level |
||||
Display Setup |
|
|
|
LON Config |
|
|
|
|
|
|
|
|
Cal Gas Conc |
||
Device Setup |
|
|
|
History |
|
|
|
|
|
|
Status Rate |
||||
Device Cal |
|
|
|
Display Info |
|
|
|
|
|
|
Lon Address |
||||
Display Test |
|
|
|
Debug Menu |
|
|
|
|
|
|
|
||||
Device Test |
|
|
|
|
|
||
|
|
|
|
||||
|
|
|
|
|
|
|
|
4.2 |
12 |
95-8656 |
RTC
Time and date for the UD10-DCU is automatically set by the EQP controller via the LON network. Changes to the time on the S3 computer will be reflected at the UD10-DCU when the controller RTC is set.
When used with the GT3000, the RTC for the GT3000 can be synchronized to the RTC of the display by going through the Main Menu->Device Setup->RTC->“Sync W/Disp”.
4-20 ma input loop Calibration
If the detector connected to the UD10-DCU is HART enabled, its 4-20 mA output signal can be trimmed. (A detector calibration should be performed prior to trimming the detector output or UD10-DCU input).
HART Detector Signal Calibration
Navigate down the menu to Device Test > D/A (Digital to Analog) Trim.
Main Menu |
|
|
|
|
|
|
Process Vars |
|
|
|
|
|
|
Display Status |
|
|
Device Test |
|
|
|
Device Status |
|
|
Self Test |
|
|
D/A Trim |
Display Setup |
|
|
Response Test |
|
|
Zero Trim |
|
|
|||||
Device Setup |
|
|
Loop Test |
|
|
Gain Trim |
Device Cal |
|
|
D/A Trim |
|
|
|
|
|
|
|
|
||
Display Test |
|
|
|
|
|
|
Device Test |
|
|
|
|
|
|
Select Zero Trim. When this screen is entered, a warning message is presented. Select ENTER to continue. When the message “Connect Reference Meter” is presented, install the current meter on the mA line between the detector and UD10-DCU. Select ENTER to continue. When the message “Set Input Current to 4mA?” is presented, select ENTER to begin the Zero Trim function. The detector will now set its 4 mA output value. If the value indicated on the current meter is not 4.00 mA, enter the measured value into the UD10-DCU using the Previous and Next switches. The UD10-DCU calculates and corrects for the difference between the actual and entered values. When the current meter value is at the desired 4.00 mA, select ENTER to accept the new zero trim value.
Select Gain Trim. Follow the same procedure for gain/ span calibration.
UD10-DCU Input Trim
When the UD10-DCU is used with a detector that supports HART communication, an automated process can be used to trim the UD10-DCU input. Navigate down the menu to “Input Loop Cal”.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Setup
Mode Select
General Options
RTC
Input Loop Cal
Contrast Contrl
Backlight Ctrl
Write Protect
Upon entering Input Loop Cal, the UD10-DCU commands the detector to output 4 mA, and then automatically calibrates its own input. The UD10-DCU then commands the detector to output 20 mA and subsequently calibrates its own input.
If a non-HART detector is being used, the Input Loop Cal may be performed with a mA current source or loop calibrator connected to the UD10-DCU Sensor Connector. Follow the loop calibration instructions shown by the UD10-DCU for this procedure.
4.2 |
13 |
95-8656 |
Optional System Tests
The following tests are available for verifying proper operation of various functions of the gas detection system:
–The Self Test and Response Test are accessed from the “Display Test” screen. (A “Device Test” screen is available for performing the same tests on HART enabled detectors.)
–The Proof Test is performed by applying test gas to the sensor. It is not accessed from the “Display Test” screen and does not inhibit the outputs.
Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test
Display Test
Self Test
Response Test
Self-Test
This test commands the UD10-DCU to perform a fully automatic internal test. At the completion of the test, the UD10-DCU will indicate a pass or fail.
Response Test
This test inhibits the UD10-DCU’s outputs, thereby providing a means of testing the system by applying gas to the detector without activating any alarms or affecting the output.
note
If the Response Test is not terminated by the operator, the test will automatically time out after ten minutes and the UD10-DCU will return to normal operation.
Proof Test
A Proof Test (bump test) can be performed at any time to verify proper operation and calibration of the system. Since this test does not inhibit the UD10-DCU’s outputs, secure any output devices prior to performing the test to prevent unwanted actuation.
History
There are two separate histories, one for the display and one for the detector (if available). Both will state the number of hours that the unit has been operating, and the highest and lowest recorded temperature (with time and date stamp).
Display Backlight Operation
The UD10 can be programmed to turn on the backlight feature of the digital display when an alarm or fault occurs or a magnetic switch is activated. Navigate to the Backlight Ctrl screen.
Main Menu |
|
|
|
|
|
|
Process Vars |
|
|
|
|
|
|
|
|
Display Setup |
|
|
|
|
Display Status |
|
|
|
|
|
|
|
|
|
|
Backlight Ctrl |
||
|
|
Mode Select |
|
|
||
Device Status |
|
|
|
|
||
|
|
General Options |
|
|
Off |
|
Display Setup |
|
|
|
|
||
|
|
Input Loop Cal |
|
|
On |
|
Device Setup |
|
|
|
|
||
|
|
Contrast Contrl |
|
|
Automatic |
|
Device Cal |
|
|
|
|
||
|
|
Backlight Ctrl |
|
|
|
|
Display Test |
|
|
|
|
|
|
|
|
|
|
|
|
|
Device Test |
|
|
|
|
|
|
Off = The backlight is always off.
On = The backlight is always on.
Automatic = Normal operation – Backlight is off Alarm – Backlight flashes on and off Fault – Backlight is on steady
Magnetic Switch – Backlight is on steady
The backlight automatically turns off 10 minutes after the last Magnetic Switch activation.
If the backlight is on following a magnetic switch activation and then an alarm condition occurs, the backlight will remain on steady and not flash until the 10 minute time-out is complete. Then it will begin flashing.
4.2 |
14 |
95-8656 |
Troubleshooting
If a Fault condition is indicated on the UD10-DCU faceplate, the nature of the fault can be determined by using the magnetic tool to navigate to the appropriate Fault screen.
NOTE
Refer to the Menu in the appropriate Appendix of this manual for the path to the proper Fault screen.
Shortcut: From the main display screen, touch the magnet to the “Previous” switch to go directly to the Fault screen.
Example:
For a Display (UD10-DCU) related fault:
Main Menu > Display Status > Fault/Status > Fault
For a Device (Sensor) related fault:
Main Menu > Device Status > Fault/Status > Sensor Fault
When the active fault has been identified, refer to the Troubleshooting Tables for a description of the fault and suggested corrective action.
Refer to Table 5 for Display Faults and Table 6 for Device Faults.
Table 5—Troubleshooting Guide - Display Faults
Display Faults |
Description |
Recommended Action |
|
|
|
|
|
|
|
Check sensor wiring. |
|
Input Loop FLT |
Fault in sensor or sensor loop |
Calibrate sensor. |
|
|
|
Ensure that sensor type matches configuration. |
|
|
|
|
|
EE Fault |
Fault in non-volatile memory |
Return to factory. |
|
|
|
|
|
ADC Ref Fault |
ADC reference voltage too high or low |
Return to factory. |
|
|
|
|
|
24V Fault |
Problem in 24 volt power supply or power wiring |
Check power wiring and output voltage of power |
|
supply. |
|||
|
|
||
|
|
|
|
Flash Fault |
FLASH memory Fault |
Return to factory. |
|
|
|
|
|
RAM Fault |
Fault in volatile memory |
Return to factory. |
|
|
|
|
|
WDT Fault |
Watchdog timer is non-functional |
Return to factory. |
|
|
|
|
|
12V Fault |
12 volt internal power supply out of tolerance |
Check power source. |
|
Return to factory. |
|||
|
|
||
|
|
|
|
5V Fault |
5 volt internal power supply out of tolerance |
Check power source. |
|
Return to factory. |
|||
|
|
||
|
|
|
|
3V Fault |
3 volt internal power supply out of tolerance |
Check power source. |
|
Return to factory. |
|||
|
|
||
|
|
|
Note: A fault condition will cause an oxygen detector to generate an alarm output as the decreasing 4-20 mA signal passes through the alarm range.
4.2 |
15 |
95-8656 |
Table 6—Troubleshooting Guide - Device Faults
Device Faults |
Description |
Recommended Action |
|
|
|
|
|
Loop Fault |
Current loop below fault threshold |
Check 4-20 mA loop wiring for shorts or opens. |
|
|
|
|
|
Supply Voltage |
24 volt power supply voltage too low |
Verify proper wiring to the device and correct |
|
Fault |
voltage output from the power supply. |
||
|
|||
|
|
|
|
|
|
This fault can be caused if the calibration is |
|
|
|
allowed to time out. If so, recalibrate. |
|
|
|
Ensure that there is enough gas in the calibration |
|
Calibration Fault |
Bad calibration |
bottle to complete the calibration. |
|
|
|
Ensure that the gas being used for calibration is |
|
|
|
the correct type and concentration. It must match |
|
|
|
the configured setting. |
|
|
|
|
|
Memory Fault |
Self-detected memory fault |
Return to factory. |
|
|
|
|
|
ADC Fault |
Self-detected ADC fault |
Return to factory. |
|
|
|
|
|
Internal Voltage |
Self-detected voltage fault |
Check supply voltage. |
|
Fault |
Return to factory. |
||
|
|||
|
|
|
|
|
|
Device may have been calibrated with background |
|
Zero Drift |
Sensor signal has drifted negative |
gas present. Recalibrate the detector. Purge with |
|
|
|
clean air if needed. |
|
|
|
|
|
Temperature |
Temperature sensor is out of range |
Return to factory. |
|
Sensor Fault |
|||
|
|
||
|
|
|
|
Wrong Sensor |
Wrong sensor type is installed |
Sensor type must match configuration. Change |
|
Type |
sensor or configuration. |
||
|
|||
|
|
|
|
Lamp Fault |
Open or shorted lamp |
Replace lamp. |
|
Return to factory. |
|||
|
|
||
|
|
|
|
Alignment Fault |
Open path alignment problem |
Align the device as specified in the instruction |
|
manual. |
|||
|
|
||
|
|
|
|
Blocked Optic |
Optical path is blocked |
Locate and remove obstruction from the optical |
|
Fault |
path. |
||
|
|||
|
|
|
|
Cal Line Active |
Cal line is active at start-up |
Ensure that the Cal line wiring is not shorted and |
|
the switch is open. |
|||
|
|
||
|
|
|
|
Low Cal Line |
Cal line is shorted. |
Check wiring. |
|
|
|
|
|
|
|
Check sensor wiring. |
|
Sensor Fault |
Self-detected fault with the sensor |
Calibrate sensor. |
|
|
|
Ensure that sensor type matches configuration. |
|
|
|
|
|
Noise Fault* |
Excessive noise on signal |
Check OPECL alignment. |
|
|
|
|
|
Align ADC Fault* |
Alignment ADC saturated |
Check OPECL alignment. |
|
|
|
|
|
Align Fault* |
Alignment fault |
Check OPECL alignment. |
|
|
|
|
|
Align Warning* |
Alignment warning |
Check OPECL alignment. |
|
|
|
|
|
DAC Fault |
DAC fault detected |
Return to factory. |
|
|
|
|
|
General Fault |
Unspecified fault |
Verify correct power wiring and supply voltage. |
|
Consult the factory. |
|||
|
|
||
|
|
|
|
High Fault |
Detector output is higher than specified limit |
Verify correct sensor type and calibration. |
|
|
|
|
|
Low Fault |
Detector output is lower than specified limit |
Verify correct sensor type and calibration. |
|
|
|
|
|
Dirty Optics |
Detector optics are dirty |
Perform the cleaning procedure as described in |
|
the detector manual, then perform calibration. |
|||
|
|
||
|
|
|
|
Start Cal Fault |
Calibration fault |
Verify correct sensor type and calibrate. |
|
|
|
|
|
*OPECL only. |
|
|
4.2 |
16 |
95-8656 |
Table 6—Troubleshooting Guide - Device Faults, Continued
Device Faults |
Description |
Recommended Action |
|
|
|
|
|
|
|
Power may have been interrupted while the device |
|
EE Fault |
Fault in non-volatile memory |
was updating its internal data logs. Recycle |
|
|
|
power. |
|
|
|
|
|
Ref ADC Sat |
Sensor signal level is outside the range of the AD |
Return to factory. |
|
converter |
|||
|
|
||
|
|
|
|
Active ADC Sat |
Sensor signal level is outside the range of the AD |
Return to factory. |
|
converter |
|||
|
|
||
|
|
|
|
24V Fault |
Problem in 24 volt power supply or power wiring |
Check power wiring and output voltage of power |
|
supply. |
|||
|
|
||
|
|
|
|
Flash CRC Fault |
Memory fault |
Return to factory. |
|
|
|
|
|
RAM Fault |
Fault in volatile memory |
Return to factory. |
|
|
|
|
|
Low Voltage |
Power supply voltage outside of limits |
Check power supply voltage. |
|
Return to factory. |
|||
|
|
||
|
|
|
|
Temp Fault |
Temperature sensor fault |
Return to factory. |
|
|
|
|
|
Software Fault |
Internal software fault |
Return to factory. |
|
|
|
|
|
EE Safety Fault |
Internal configuration fault |
Return to factory. |
|
|
|
|
|
|
|
Device may have been calibrated with background |
|
Gas Under Range |
Sensor signal has drifted negative |
gas present. Recalibrate the detector. Purge with |
|
|
|
clean air if needed. |
|
|
|
|
|
Sensor Mismatch |
Wrong sensor type is installed |
Sensor type must match configuration. Change |
|
sensor or configuration. |
|||
|
|
||
|
|
|
|
ADC CNTR Fault |
Internal hardware fault |
Return to factory. |
|
|
|
|
|
3V Fault |
3 volt internal power supply out of tolerance |
Return to factory. |
|
|
|
|
|
Comm Fault |
Communication fault |
Check detector wiring and power supply. |
|
|
|
|
|
GEN Fault |
Unspecified fault |
Verify correct power wiring and supply voltage. |
|
Consult the factory. |
|||
|
|
||
|
|
|
|
12V Fault |
12 volt internal power supply out of tolerance |
Return to factory. |
|
|
|
|
|
5V Fault |
5 volt internal power supply out of tolerance |
Return to factory. |
|
|
|
|
4.2 |
17 |
95-8656 |
Specifications
operating voltage—
24 Vdc nominal, operating range is 18 to 30 Vdc. Ripple cannot exceed 0.5 volt P-P.
operating power—
Heater off: |
1.3 watts nominal @ 24 Vdc with |
|
backlit display off. |
|
2 watts @ 24 Vdc with backlit display on. |
Heater on: |
4 watts additional. |
CGS model: |
Add 4 watts with CGS interface |
|
board and CGS sensor installed. |
Maximum power with heater and display on:
6 watts @ 30 Vdc (Standard model)
10 watts @ 30 Vdc (CGS model).
note
Heater turns on when the internal temperature drops below –10°C (default operation).
Lon communication —
Digital communication, transformer isolated (78.5 kbps).
EQP/UD10 System Accuracy—
<1 ppm error. <1 %LFL error.
With CGS sensor: ±3 %LFL, 0-50 range, ±5 %LFL 51-100 range.
EQP/UD10 System Response—
Toxic gas: T90 < 10 sec.
Combustible gas: T90 < 10 sec.
With CGS sensor: T90 < 12 sec.
Table 7—Gas Detectors Compatible with the UD10-DCU
Device |
Toxic1 |
Catalytic |
IR2 |
Instruction |
|
Combustible |
Combustible |
Manual |
|||
|
|
||||
|
|
|
|
|
|
GT3000 |
X |
|
|
95-8616 |
|
|
|
|
|
|
|
PIR9400 |
|
|
X |
95-8440 |
|
|
|
|
|
|
|
PIRECL |
|
|
X |
95-8526 |
|
|
|
|
|
|
|
OPECL |
|
|
X |
95-8556 |
|
|
|
|
|
|
|
CGS |
|
X |
|
90-1041 |
|
|
|
|
|
|
|
505/CGS |
|
X |
|
95-8472 |
|
|
|
|
|
|
|
|
|
|
|
95-8396 |
|
C706X3 |
X |
|
|
95-8411 |
|
|
|
95-8414 |
|||
|
|
|
|
||
|
|
|
|
95-8439 |
|
|
|
|
|
|
|
NTMOS4 |
X |
|
|
95-8604 |
1Hydrogen sulfide, Ammonia, Chlorine, Hydrogen, Oxygen, Carbon Monoxide, and Sulfur Dioxide.
2Methane, Ethane, Ethylene, Propane, and Propylene.
3C7065E Oxygen detector is not supported.
4Hydrogen sulfide only.
Detector compatibility—
The UD10-DCU can be used with the Det Tronics gas detectors listed in Table 7.
Unit of Measurement—
PPM, % LFL, % V/V, LFLM, or Mg/M3.
Operating temperature—
–40°C to +75°C.
Storage Temperature—
–55°C to +75°C.
Humidity Range—
5 to 95% RH (Det-Tronics verified).
electro-magnetic compatibility—
EMC Directive 2004/108/EC EN55011 (Emissions) EN50270 (Immunity)
DIMENSIONS—
See Figures 6 and 7.
5.86
(14.9)
5.2
(13.2)
2.7
(6.9)
4.7
(11.9)
3.46
(8.8)
3.77
(9.6)
1.28
(3.3)
C2281
Figure 6—Dimensions of Model STB Termination Box in Inches (Centimeters)
4.2 |
18 |
95-8656 |
Wiring terminals— |
Certification— |
||
14 to 18 AWG wire can be used. |
For complete approval details, refer to the appropriate |
||
|
|
Appendix: |
|
Conduit Entries— |
|
|
|
3/4” NPT or M25. |
FM |
|
|
|
|
® |
|
ENCLOSURE MATERIAL— |
APPROVED |
|
|
|
|
||
Epoxy coated aluminum or 316 stainless steel. |
Appendix A – FM |
||
|
|
||
SHIPPING WEIGHT— |
Appendix B – CSA |
||
Aluminum: |
4.15 pounds (1.88 kilograms). |
Appendix C – ATEX |
|
Stainless steel: |
10.5 pounds (4.76 kilograms). |
Appendix D – IECEx |
|
|
|
Appendix E – INMETRO |
WARRANTY—
12 months from date of installation or 18 months from date of shipment, whichever occurs first.
6.48 |
4.7 |
(16.5) |
(11.9) |
|
3.46 |
|
(8.8) |
|
5.2 |
|
(13.2) |
|
5.86 |
|
(14.9) |
11.28 |
|
(28.7) |
|
|
R0.175 |
A2442
Figure 7—Dimensions of UD10-DCU with GT3000 in Inches (Centimeters)
4.2 |
19 |
95-8656 |
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure.
Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. The RMI number should be clearly marked on the outside of the box.
note
Inadequate packaging that ultimately causes damage to the returned device during shipment will result in a service charge to repair the damage incurred during shipment.
Return all equipment transportation prepaid to the factory in Minneapolis.
NOTE
It is highly recommended that a spare be kept on hand for field replacement to ensure continuous protection.
ORDERING INFORMATION
Sensor module, transmitter module and termination boxes (if used) must be ordered separately.
Refer to the UD10-DCU Model Matrix for ordering details.
Replacement Parts
Part Number |
Description |
009700-001 |
Magnetic Tool |
010535-001 |
Electronics Module, DCU |
101197-001* |
Stop Plug, 3/4" NPT, AL |
101197-004* |
Stop Plug, 3/4" NPT, SS |
101197-005 |
Stop Plug, M25, AL, IP66 |
101197-003 |
Stop Plug, M25, SS, IP66 |
010816-001 |
Stop Plug, 20PK, 3/4" NPT, AL |
010817-001 |
Stop Plug, 20PK, 3/4" NPT, SS |
010818-001 |
Stop Plug, 20PK, M25, AL, IP66, EXDE |
010819-001 |
Stop Plug, 20PK, M25, SS, IP66, EXDE |
104190-001 |
Stop Plug, M25, AL, INMETRO |
104190-002 |
Stop Plug, 3/4" NPT, AL, INMETRO |
104190-003 |
Stop Plug, M25, SS, INMETRO |
104190-004 |
Stop Plug, 3/4" NPT, SS, INMETRO |
102804-001 |
Reducer, M25 to M20, AL |
102804-003 |
Reducer, M25 to M20, SS |
103922-001 |
475 Field Communicator |
005003-001 |
Lubriplate grease, 1 oz. |
*NEMA/Type 4X, IP66 rating requires addition of Teflon tape.
4.2 |
20 |
95-8656 |