Det-Tronics UD10 User Manual

5 (1)

Instructions 95-8656

FlexVu® Universal Display Unit

Model UD10 DCU Emulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.2

 

 

 

 

 

 

 

Rev: 9/12

95-8656

 

 

 

 

 

 

 

Table of Contents

application . . . . . . . . . . . . . . . . . . . .

.

 

1. . .

.Appendix. . . . . G — UD10-DCU WITH pir9400 . . . . . . . . .

.G-1

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . .

.

.

1. . .

. .

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

G-1

Magnetic Switches . . . . . . . . . . . . . . .

.

.

 

 

Installation Notes . . . . . . . . . . . . . . . . . . . . . .

.G-2

2. . . . . . .

 

G-2

Device Enclosure . . . . . . . . . . . . . . . .

.

 

 

 

Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 . . . . . . .

 

G-3

Device Display . . . . . . . . . . . . . . . . .

.

 

 

 

Changing Operating Modes . . . . . . . . . . . . . . .

 

.3 . . . . . . . .

 

.G.-3. . . .

Configuration Overview

 

 

3

 

Calibration . . . . . . . . . . . . . . . . . . . . . .

.

 

 

Menu Structure

G-3

Alarms

 

 

4

 

.

 

 

 

 

 

Calibration Gas Concentration . . . . . . . . . . . . .

.

.

4

Appendix H — UD10-DCU WITH model pirecl . . . .

H-1

Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .

 

5

 

Wiring

H-1

 

 

 

 

 

 

 

 

 

 

Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H-2

IMPORTANT SAFETY NOTES . . . . . . . . . . . . . . . . .

. .

 

5

 

Calibration . . . . . . . . . . . . . . . . . . . . . .

.H.-3. . . .

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . .

.

.6. . . .

Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . .

H-4

 

 

 

Identification of Vapor(s) to be Detected

 

 

6

Appendix I — UD10-DCU WITH MODEL OPECL . .

. I-1

. .

 

 

Wiring

I-1

Identification of Detector Mounting Locations

 

 

6

 

. .

 

 

Orientation

I-3

 

 

 

 

 

WIRING

 

 

7

 

Calibration . . . . . . . . . . . . . . . . . . . . . .

. I.-3. . . . .

. .

 

 

OPECL Transmitter Lamp Fault Condition

I-4

Power Supply Requirements

 

 

7

 

. .

 

 

Menu Structure

I-4

Wiring Cable Requirements

 

 

7

 

. .

 

 

 

 

 

Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . .

. .

 

7

Appendix J — UD10-DCU WITH NTMOS H2S Sensor J-1

Shield Connections . . . . . . . . . . . . . . . .

.

.7. . .

. .

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-1

LON Address Switch Setting . . . . . . . . . .

.

 

9. . .

. .

Installation Notes . . . . . . . . . . . . . . . . . . . . . .

. J-1

 

 

 

 

 

Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . .

J-3

Recommended STARTUP Procedure . . . .

.

.

9. .

 

Calibration . . . . . . . . . . . . . . . . . . . . . .

. J.-3. . . .

S3 Configuration . . . . . . . . . . . . . . .

 

 

 

 

Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . .

J-4

. 10. . . . . . .

 

 

Troubleshooting

15

Appendix K — UD10-DCU WITH C706X GAS SENSOR . K-1

 

Wiring

K-1

 

 

 

 

 

SPECIFICATIONS

18

 

Installation . . . . . . . . . . . . . . . . . . . . . . .

.K.-3. . .

 

Calibration . . . . . . . . . . . . . . . . . . . . . .

.K.-4. . . .

Device Repair and Return

20

 

 

Menu Structure

K-4

 

 

 

 

 

Ordering Information . . . . . . . . . . . .

20. . . . Appendix. .

L — UD10-DCU with Model CGS Sensor .

.L-1

 

 

 

 

 

Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. L-1

APPENDIX A — FM Approval description

a-1

 

Important Notes . . . . . . . . . . . . . . . . . . . . . . . .

. L-1

 

Installation

L-3

 

 

 

 

 

appendix b — csa certification description . b-1

 

Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

L-4

 

K-Factor.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. L-4

 

 

 

 

 

appendix C — atex approval description . . . . .

c-1

 

Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . .

. L-4

appendix d — iec approval description

d-1

Appendix M — UD10-DCU WITH Model 505/CGS M-1

 

Wiring

M-1

 

 

 

 

 

Appendix E — Additional Approvals . . . . . . . E.-.1.

 

Installation . . . . . . . . . . . . . . . . . . . . . . .

.M.-2. . .

Appendix F — UD10-DCU with GT3000

F-1

 

Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . .

M-2

 

Calibration . . . . . . . . . . . . . . . . . . . . . .

.M.-3. . . .

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-1

 

Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . .

M-4

Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F-2

Appendix N — UD10-DCU WITH Generic 4-20 ma sensor

N-1

Live Maintenance

F-2

 

Operation

N-1

Calibration . . . . . . . . . . . . . . . . . . . . . . . F.-3. . . .

 

 

Menu Structure

N-1

Menu Structure

F-4

 

 

 

 

 

INSTRUCTIONS

FlexVu® Universal Display Unit

Model UD10 DCU Emulator

Important

Be sure to read and understand the entire instruction manual before installing or operating the gas detection system. This product can be used with a variety of Det-Tronics gas detectors to provide early warning of the presence of a toxic or explosive gas mixture. Proper device installation, operation, and maintenance is required to ensure safe and effective operation. If this equipment is used in a manner not specified in this manual, safety protection may be impaired.

Application

The FlexVu® Model UD10 DCU Emulator (UD10-DCU) is designed for applications that require a gas detector with digital readout of detected gas levels. Its LON interface board makes the UD10-DCU compatible with Eagle Quantum Premier systems by digitizing the 4-20 mA analog signal from the attached sensor/transmitter and transmitting the value as a process variable over the LON to the EQP controller.

The UD10-DCU is designed for use with most currently available Det Tronics gas detectors. Refer to the Specifications section of this manual for a list of compatible gas detectors. When furnished with the CGS interface board, the device can be used only with a CGS sensor for detection of combustible gas. The UD10/CGS combination is certified as a “Gas Detector”.

Gas concentration and unit of measurement are indicated on a digital display.

All electronics are enclosed in an explosion-proof aluminum or stainless steel housing. The display unit is used with a single detector that may be either coupled directly to the UD10-DCU, or remotely located using a sensor termination box.

The UD10-DCU features non-intrusive calibration. A magnet is used to perform calibration as well as to navigate the UD10-DCU’s internal menu.

Description

The UD10-DCU Universal Display can be used with various 4-20 mA gas detection devices, with or without HART. The unit provides display, output and control capabilities for the gas detector.

The UD10-DCU utilizes the following I/O:

Signal Inputs:

4-20 mA loop from the sensing device

User Inputs:

Magnetic switches on the display panel

 

S3 Software

Signal Outputs:

LON communication

Visible Outputs:

Backlit LCD display

 

Computer running S3 Software

4.2

©Detector Electronics Corporation 2012

Rev: 9/12

95-8656

magnetic switches

Four internal magnetic switches provide a non intrusive user interface that allows navigation through the menu. See Figure 1 for switch locations.

PREVIOUS

CANCEL / ESCAPE

ENTER / SELECT

NEXT

B2426

Figure 1—Faceplate of UD10-DCU

These switches are used for device configuration, checking status and event logs, and performing calibration. The switches are labeled as follows:

CANCEL / ESCAPE

ENTER / SELECT / Menu ACCESS

Previous or if on Main Screen:

Fault Shortcut

Next

To actuate a magnetic switch, lightly touch the magnet to the viewing window of the UD10-DCU directly over the switch icon on the faceplate.

Caution

Handle magnets with care! Personnel wearing pacemakers/defibrillators should not handle magnets. Modern magnet materials are extremely strong magnetically and somewhat weak mechanically. Injury is possible to personnel, and magnets themselves can easily get damaged if allowed to snap towards each other, or if nearby metal objects are allowed to be attracted to the magnets.

note

Det-Tronics offers two magnet options for activating internal magnetic switches. While the two magnets can usually be used interchangeably, the best results will be achieved if they are used as follows: The Magnetic Tool (p/n 009700-001) is the stronger magnet and is recommended for activating the switches on the UD10-DCU viewing window. The Calibration Magnet (p/n 102740 002) is recommended for applications that involve initiating calibration or resetting the detector by touching the side of a metal junction box or detector housing (PIRECL, OPECL, etc). Throughout this manual, the term “magnet” can refer to either device.

Access To Menus

To access the menus, use the magnet to activate the Enter/Select button. This will display the Main Menu.

The actual menu structure varies depending upon the device that is connected to the UD10-DCU. Menus for the various devices can be found in the corresponding Appendix in this manual.

Some areas of the menu contain additional information, which is indicated by the presence of an arrow on that particular line. By placing the magnet to the glass over the Enter/Select button, the next screen with the additional information will be shown.

The UD10-DCU automatically returns to the main screen after 10 minutes if no activity occurs.

4.2

2

95-8656

Quick Access/Shortcut: Fault Menu

To access the fault menu quickly, when a fault is present, touch the magnet to the glass by the Previous button.

Device ENCLOSURE

The UD10-DCU housing is a 5 port aluminum or stainless steel explosion proof junction box with a clear viewing window.

Device DISPLAY

The UD10-DCU is provided with a 160 x 100 dot matrix backlit LCD display. See Figure 1.

During normal operation, the LCD continuously displays the detected gas level, gas type, and units of measurement. The real time clock can also be displayed if desired.

The display shows the following alarm information:

High gas alarm

Low gas alarm

Aux alarm

The display indicates the following fault information:

Device fault

Display fault

The UD10-DCU has smart capabilities to allow easy access to the following information:

Detector information

Measurement range

Alarm setpoints

Alarm and event logs

For detailed menu structure, refer to the appropriate Appendix.

Configuration overview

The user must select the sensor mode/type manually from the UD10-DCU display. The selection options are:

HART Device (including Generic HART Device) PIR9400

C706x

505 NTMOS CGS

Generic Device (without HART)

When “HART Device” is selected, the UD10-DCU communicates with the detector to determine the device type. The upper and lower range for the UD10-DCU display is determined by the detector type and must be selected before configuration data is sent from the EQP system. If the detector type or range is changed at the UD10-DCU, a configuration download from S3 should again be performed.

Alarm levels and calibration gas concentration level come from the S3 application. Configuration information is downloaded from S3 to the controller, which sends the data to the LON interface board in the UD10-DCU. The LON interface then sends configuration information to the main processor in the UD10-DCU for storage and display. Alarm levels and calibration gas concentration cannot be set from the UD10-DCU menu system, however, they can be viewed after download.

Status information from the UD10-DCU and attached detector is passed to the EQP controller over the LON network, and then to S3 for display.

4.2

3

95-8656

Alarms

The UD10-DCU has a low and high alarm that are set from the S3 configuration software and then downloaded to the UD10-DCU. Alarm status can be viewed at the UD10-DCU display, the EQP controller, or S3. Alarms are non latching at the UD10-DCU, but can be latched using logic within the EQP Controller.

With some configurations, the alarm limits on the UD10 DCU are tighter than on S3. If a value is out of range, the UD10-DCU will set the value as close as possible while remaining within the allowable range (See Table 1). After the configuration download is complete, the alarm setpoints can be viewed at the UD10-DCU under Display Status->LON Config menu.

Calibration Gas Concentration

The calibration gas concentration is programmed from S3 and downloaded to the UD10-DCU. See Table 2 for calibration gas limits. NTMOS, CGS, and PIR9400 require a gas concentration of 50% full scale. Calibration gas concentration can be viewed from the UD10-DCU menu under Display Status->LON Config.

Table 1—UD10-DCU Alarm Limits

 

UD10 Limits

 

EQP Limits

System Limits

 

 

 

 

 

 

 

 

Detector Type

Low Alarm

High Alarm

Recommended

Low Alarm

High Alarm

Low Alarm

High Alarm

EQP Configuration

 

 

 

 

 

 

 

 

GT3000 Toxic

5-50%

10-90%

Universal Automatic

10-100%

20-100%

10-50%

20-90%

 

 

 

 

 

 

 

 

GT3000 O2*

16-20.5% v/v

5-20.5% v/v

Oxygen

1.3-25% v/v

2.5-25% v/v

16-20.5% v/v

5-20.5% v/v

 

 

 

 

 

 

 

 

PIR9400

5-50%

10-60%

Explosive

5-40%

10-60%

5-40%

10-60%

 

 

 

 

 

 

 

 

Eclipse

5-50%

10-60%

Explosive

5-40%

10-60%

5-40%

10-60%

 

 

 

 

 

 

 

 

Open Path

5-50%

10-90%

Universal Automatic

10-100%

20-100%

10-50%

20-90%

 

 

 

 

 

 

 

 

C706x

5-50%

10-90%

Universal Automatic

10-100%

20-100%

10-50%

20-90%

 

 

 

 

 

 

 

 

505/CGS

5-50%

10-60%

Explosive

5-40%

10-60%

5-40%

10-60%

 

 

 

 

 

 

 

 

NTMOS H2S

5-50%

10-90%

Universal Automatic

10-100%

20-100%

10-50%

20-90%

 

 

 

 

 

 

 

 

CGS

5-50%

10-60%

Explosive

5-40%

10-60%

5-40%

10-60%

 

 

 

 

 

 

 

 

Generic Device

0-100%

0-100%

Universal Automatic

10-100%

20-100%

10-100%

20-100%

 

 

 

 

 

 

 

 

*Sensor approved for oxygen depletion (<21% V/V) only.

Table 2—Calibration Gas Concentration Limits

Detector Type

UD10 Limits

Recommended EQP

EQP Limits

System Limits

Configuration

 

 

 

 

 

 

 

 

 

GT3000 Toxic

30-90%

Universal Automatic

20-100%

30-90%

 

 

 

 

 

GT3000 O2

20.9% v/v

Oxygen

5-25% v/v

20.9% v/v

 

 

 

 

 

PIR9400

50%

Explosive

20-100%

50%

 

 

 

 

 

Eclipse

30-90%

Explosive

20-100%

30-90%

 

 

 

 

 

Open Path

30-90%

Universal Automatic

20-100%

30-90%

 

 

 

 

 

C706x

30-90%

Universal Automatic

20-100%

30-90%

 

 

 

 

 

505/CGS

N/A

Explosive

20-100%

N/A

 

 

 

 

 

NTMOS H2S

50%

Universal Automatic

20-100%

50%

 

 

 

 

 

CGS

50%

Explosive

20-100%

50%

 

 

 

 

 

Generic Device

N/A

Universal Automatic

20-100%

20-100%

 

 

 

 

 

4.2

4

95-8656

Logging

Events that can be logged in the UD10-DCU include:

Calibration (Date, time and success Y/N are logged for detectors that do not provide their own calibration logging capabilities.)

Faults that are logged in the UD10-DCU include:

Detector fault

Low power

General fault

Alarms that are logged in the UD10-DCU for gas detector inputs include:

High gas alarm

Low gas alarm.

The UD10-DCU can display the detector event and calibration logs (if available). Detector calibration and event logs can also be read from the detector’s HART interface (where available).

The UD10-DCU has its own 1,000 entry event log available under the Display Status >History >Event Log menu.

The LON interface board in the UD10-DCU has eight alarm logs and eight calibration logs. These logs are available from the S3 “Point Display Screen” for the UD10 DCU.

The EQP Controller and S3 also maintain their own logs. Refer to the EQP system manual (95 8533) and/or the S3 manual (95-8560) for details.

important safety notes

CAUTION

The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaranteed. Be certain that all wiring complies with the NEC as well as all local codes. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by a properly trained person.

CAUTION

This product has been tested and approved for use in hazardous areas. However, it must be properly installed and used only under the conditions specified within this manual and the specific approval certificates. Any device modification, improper installation, or use in a faulty or incomplete configuration will render warranty and product certifications invalid.

CAUTION

The device contains no user serviceable components. Service or repair should never be attempted by the user. Device repair should be performed only by the manufacturer.

Liabilities

The manufacturer’s warranty for this product is void, and all liability for proper function of the detector is irrevocably transferred to the owner or operator in the event that the device is serviced or repaired by personnel not employed or authorized by Detector Electronics Corporation, or if the device is used in a manner not conforming to its intended use.

Caution

Observe precautions for handling electrostatic sensitive devices.

caution

Unused conduit entries must be closed with suitably certified blanking elements upon installation.

4.2

5

95-8656

Installation

NOTE

For complete instructions regarding wiring, installation, and use of the Eagle Quantum Premier system, refer to manual number 95-8533.

note

The gas detector housing must be electrically connected to earth ground. A dedicated earth ground terminal is provided on the UD10-DCU.

The detector must always be installed per local installation codes.

Before installing the gas detector, define the following application details:

Identification of vapor(s) to be detected

It is necessary to identify the vapor(s) of interest at the job site. The fire hazard properties of the vapor, such as vapor density, flashpoint, and vapor pressure should be identified and used to assist in selecting the optimum detector mounting location within the area.

For cross sensitivity information, refer to each gas detector’s corresponding instruction manual. Refer to the Specifications section in this manual for a list of gas detectors and their corresponding instruction manuals.

Identification of detector mounting locations

Identification of the most likely leak sources and leak accumulation areas is typically the first step in identifying the best detector mounting locations. In addition, identification of air current/wind patterns within the protected area is useful in predicting gas leak dispersion behavior. This information should be used to identify optimum detector installation points.

If the vapor of interest is lighter than air, place the detector above the potential gas leak. Place the detector close to the floor for gases that are heavier than air. Note that air currents may cause a gas that is slightly heavier than air to rise under some conditions. Heated gases may also exhibit the same phenomenon.

The most effective number and placement of detectors varies depending on the conditions on site. The individual designing the installation must often rely on experience and common sense to determine the detector quantity and best locations to adequately protect the area. Note that it is typically advantageous to locate detectors where they are accessible for maintenance. Locations near excessive heat or vibration sources should be avoided.

Final suitability of possible gas detector locations should be verified by a job site survey.

The gas detector must be mounted with the sensor in the correct orientation as shown in Table 3.

If the UD10-DCU faceplate is not correctly oriented, it can be rotated at 90 degree increments by pulling the electronic module from the four mounting posts that secure it to the junction box and repositioning it as desired. Note that the module is held in place by a compression fitting – no screws are involved.

 

Table 3—Device Orientation

 

 

 

Device

 

Orientation

 

 

 

GT3000

 

Vertical with Sensor Pointing Down

 

 

 

PIR9400

 

Horizontal

 

 

 

PIRECL

 

Horizontal

 

 

 

OPECL

 

Horizontal (Fixed to a vertical post)

 

 

 

CGS

 

Vertical with Sensor Pointing Down

 

 

 

505/CGS

 

Vertical with Sensor Pointing Down

 

 

 

C706X

 

Vertical with Sensor Pointing Down

 

 

 

NTMOS

 

Vertical with Sensor Pointing Down

 

 

 

4.2

6

95-8656

WIRING

power SUPPLY requirements

Calculate the total gas detection system power consumption rate in watts from cold start-up. Select a power supply with adequate capability for the calculated load. Ensure that the selected power supply provides regulated and filtered 24 Vdc output power for the entire system. If a back-up power system is required, a float type battery charging system is recommended. If an existing source of 24 Vdc power is being utilized, verify that system requirements are met. The acceptable voltage range is 18-30 Vdc measured at the input to the UD10-DCU.

Wiring cable requirements

Always use proper cabling type and diameter for input power as well as output signal wiring. 14 to 18 AWG shielded stranded copper wire is recommended. Correct wire size depends on the device and wire length. Refer to the appropriate Appendix for additional information. The maximum cable length from power source to UD10-DCU is 2000 feet. Maximum cable length from UD10-DCU to sensor is 2000 feet.

note

The use of shielded cable in conduit or shielded armored cable is highly recommended. In applications where the wiring is installed in conduit, dedicated conduit is recommended. Avoid low frequency, high voltage, and non signaling conductors to prevent nuisance EMI problems.

caution

The use of proper conduit installation techniques, breathers, glands, and seals is required to prevent water ingress and/or maintain the explosion-proof rating.

Wiring Procedure

NOTE

Since the UD10-DCU can be used with a variety of different detection devices, information that is specific to each detector model (wiring, calibration, HART menus, etc.) is covered in an Appendix that is dedicated to that device. Refer to the appropriate Appendix at the back of this manual for specific information when wiring the detection system. For information on devices not covered in an Appendix, refer to the manual provided by the device’s manufacturer.

Connect 24 vdc power lead wires and communication network cable to the appropriate terminal block. Refer

to Figure 2 for an illustration of the UD10-DCU wiring terminal board.

COM 1 - Communication network connections: Connect to COM 2 terminals of the next device on the loop, A to A and B to B.

COM 2 - Communication network connections: Connect to COM 1 terminals of the previous device on the loop, A to A and B to B.

24 VDC - Connect the “+” terminal to the positive side of the 24 vdc power source. (Both “+” terminals are connected internally.)

Connect the “–” terminal to the negative side of the 24 vdc power source. (Both “–” terminals are connected internally.)

Figure 3 shows a UD10-DCU Wired to a generic sensing device. Refer to the appropriate Appendix for information regarding a specific detector.

Grease/Lubrication

To ease installation and future removal, ensure that all junction box covers and sensor threads are properly lubricated. If the need arises for additional lubrication, use either Lubriplate grease (see Ordering Information for part number) or Teflon tape. Avoid the use of silicone grease.

Shield Connections

The UD10 provides terminals for proper grounding of wiring cable shields (located on the sensor, 4-20 mA, and operating power terminal blocks). These shield terminals are not connected internally, but are connected to ground through capacitors. The capacitors ensure an RF ground, while preventing 50/60 Hz ground loops.

Ground all shields as shown in the wiring examples throughout this manual.

important

For proper grounding, all junction boxes / metal enclosures must be connected to earth ground.

The following are required for installations requiring CE Mark compliance:

For shielded cable installed in conduit, attach the wire shields to the “shield” connections on the terminal blocks, or to earth ground on the case.

For installations without conduit, use double shielded cable. Terminate the outer shield to earth ground on the case. Terminate the inner shield to the “shield” connection on the terminal blocks.

4.2

7

95-8656

FACTORY USE ONLY

LON ADDRESS SELECTION SWITCHES

2 1

1 ON

2

3

4

 

4

16

8

6 5

32

8 7

64

128

VALUES OF ALL SWITCHES IN THE

ON POSITION ARE ADDITIVE.

Sensor Connector

-1

-2

-3

-4

-5

J4

J4

J4

J4

J4

J4

 

SHIELD

CALIBRATE

24 VDC –

4-20 mA

24 VDC +

 

 

 

 

 

 

 

 

SHIELD

 

 

J2

 

 

 

 

2 B COM

 

 

 

 

 

 

2 A COM

 

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

1 B COM

 

 

SW3

 

 

 

1 A COM

 

 

 

 

 

 

24 VDC –

 

24 VDC +

SHIELD

24 VDC –

24 VDC +

SHIELD

 

 

 

 

 

 

 

 

 

J7-6

 

J7-5

J7-4

J7-3

J7-2

J7-1

J7

 

 

 

 

 

 

 

 

Power Supply Connector

UD10

DISPLAY UNIT

J3-1

Connector

 

J3-4

J3-2

 

J3-3

 

 

LON

J3-5

 

 

J3-6

 

 

 

J3

A2509

Figure 2—Wiring Terminal Board

UD10

DISPLAY UNIT

Sensor Connector

 

 

 

 

 

 

 

 

 

 

 

-1

-2

-3

-4

-5

J4

J4

J4

J4

J4

J4

 

 

 

 

 

 

 

 

 

 

 

 

SHIELD

CALIBRATE

VDC24 –

20-4mA

VDC24 +

SEE NOTE 1

 

 

 

 

 

 

 

 

 

 

J2

 

ON

 

 

 

 

 

SW3

 

 

 

24 VDC –

24 VDC +

SHIELD

24 VDC –

24 VDC +

SHIELD

J7-6

J7-5

J7-4

J7-3

J7-2

J7-1

Power Supply Connector

SHIELD

J3-1

2 B COM

J3-2

2 A COM

J3-3

SHIELD

J3-4

1 B COM

J3-5

1 A COM

J3-6

 

J3

J7

Connector

SHIELD

SHIELD

 

B

 

A

LON

B

 

 

A

 

24 VDC

+ –

A2510

GENERIC

GAS DETECTOR SEE NOTE 3

CALIBRATE 24 VDC –

4-20 MA SIGNAL

24 VDC +

GROUND

LON FROM PREVIOUS DEVICE

LON TO NEXT DEVICE

NOTE 1 CONNECT THE SENSOR GROUND LEAD TO THE CHASSIS GROUND LUG ON THE

INSIDE BOTTOM OF THE DISPLAY ENCLOSURE.

NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.

NOTE 3 GENERIC SENSOR SHOWN AS EXAMPLE. REFER TO THE APPROPRIATE APPENDIX

FOR SPECIFIC SENSOR WIRING INFORMATION.

Figure 3—UD10-DCU Wired to a Generic Gas Detector

4.2

8

95-8656

LON Address Switch Setting

Each device on the LON/SLC must be assigned a unique address. This is accomplished by setting DIP switches on the module’s circuit board. See Figure 2. Each rocker switch has a specific binary value. The node address is equal to the added value of all rocker switches in the “ON” position. All “OFF” switches are ignored. The valid address range is from 5 to 250.

The switch value is read at power-up. If a change is made with power applied (not recommended), power must be cycled before the change will be recognized. The LON address can be read from the UD10-DCU menu under Display Status->LON Config.

For additional information, refer to the Eagle Quantum Premier system manual (number 95-8533).

Recommended Startup

Procedure

1.Check the UD10-DCU LON address switches for proper setting.

2.Check all system wiring for proper connection.

3.With power applied to the system, select the correct sensor type or mode. See “Detector Type/Mode Selection Procedure” for details.

Note

A fault may be displayed until the configuration is downloaded.

4.Note the units on the main UD10-DCU display. (This will typically be PPM or %.)

5.Record the LON address, range, and units for each detector.

6.Complete the steps in the “S3 Configuration” section of this manual to configure the LON network from S3.

Detector Type/mode selection procedure

After power has been applied and the warm-up period is complete, select the UD10-DCU operating mode. To do this:

1.Access the Main Menu by touching the magnet to the ENTER/SELECT button. From there, navigate to the “Mode Select” menu.

Main Menu

 

 

 

 

 

 

 

 

Display Setup

 

 

Mode Select

Process Vars

 

 

 

 

 

 

Mode Select

 

 

HART Device

Display Status

 

 

 

 

 

 

General Options

 

 

PIR9400

Device Status

 

 

 

 

 

 

RTC

 

 

C706X

Display Setup

 

 

 

 

 

 

Input Loop Cal

 

 

505

Device Setup

 

 

 

 

 

Contrast Contrl

 

 

NTMOS

Device Cal

 

 

 

 

 

 

Backlight Ctrl

 

 

CGS

Display Test

 

 

 

 

 

 

Write Protect

 

 

Generic Device

Device Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.From the “Mode Select” menu, select and enter the appropriate operating mode based on the type of detector being used.

note

If using a PIR9400, note that changing the gas type on the UD10-DCU does not change the gas type at the PIR9400. This change is made using a switch located in the PIR9400. Refer to the PIR9400 instruction manual (95 8440) for details.

NOTE

If using a C706X detector, navigate to the “Device Setup” menu and select the appropriate gas type and unit of measurement.

3.To exit, activate Cancel/Escape three times to return to the main display screen.

note

If the detector is replaced with another detector type, the UD10-DCU will not recognize it until the mode is changed.

Note

If the UD10-DCU Display is in PIR9400 mode and if:

a.The connection between PIR9400 and the UD10 DCU is removed, the UD10-DCU will show a FAULT on the Gas Screen. When the connection between PIR9400 and UD10 DCU is restored, the UD10-DCU will remove the FAULT indication when current increases beyond 3.6 mA.

b.Someone removes the PIR9400 & connects a HART enabled Gas Detector, it will not be recognized by the UD10-DCU Display until the mode is changed to HART.

4.2

9

95-8656

S3 Configuration

Create a new DCU point with the correct LON address/ point number. See Figure 4.

Figure 4—Point Type Selection Screen

4.2

10

95-8656

The DCU configuration software supports six detector types:

Explosive

Oxygen

Universal (Automatic Calibration) Universal (Manual Calibration) Pointwatch

Ductwatch

Table 4 shows the recommended settings for each detector type.

Table 4—Recommended Settings for each Detector Type

Detector Type

Recommended Configuration

Comments

 

 

 

GT3000 - All but O2

Universal Automatic

Enter the proper range for the detector. Enter PPM for

units. Then select the alarm and calibration levels.

 

 

 

 

 

GT3000 O2

Oxygen

Units and range will automatically be set. Cal level must be

set to 20.9%.

 

 

 

 

 

Eclipse

Explosive

Proper range and units are automatically set. Alarms are

limited to approval requirements.

 

 

 

 

 

Open Path

Universal Automatic

Enter the proper range and units (LFL-M) for the detector.

 

 

 

 

 

Proper range and units are automatically set. Alarms are

PIR9400

Explosive

limited to approval requirements. Calibration gas must be

 

 

set to 50%.

 

 

 

C706x

Universal Automatic

Enter the proper range for the detector and PPM for units.

Then select the alarm and calibration levels.

 

 

 

 

 

505

Explosive

Alarms are limited to approval requirements. Uses %LFL

for units.

 

 

 

 

 

NTMOS

Universal Automatic

Enter the proper range (0-100) and units (PPM) for the

detector. Calibration gas must be set to 50%.

 

 

 

 

 

 

 

Proper range and units are automatically set. Alarms are

CGS

Explosive

limited to approval requirements. Calibration gas must be

 

 

set to 50%.

 

 

 

 

 

Enter the proper range and units for the detector.

Generic

Universal Automatic

Calibration is not supported, so 50% should be used as

 

 

the default.

 

 

 

4.2

11

95-8656

Enter the appropriate data on the DCU Editor Screen. See Figure 5. The units and range entered at S3 will be seen in S3 and the Controller, but are not sent to the UD10-DCU. It is the user’s responsibility to ensure that S3 matches the actual detector type.

The alarm and calibration gas setpoints are downloaded to the UD10-DCU.

Figure 5—DCU Editor Screen

The LON parameters can be checked at the UD10 DCU display under the “LON Config” menu.

Main Menu

 

 

 

 

 

Process Vars

 

Display Status

 

 

 

 

 

LON Config

Display Status

 

 

 

General Info

 

 

 

 

 

Hgh Alarm Level

Device Status

 

 

 

Fault/Status

 

 

 

 

 

Low Alarm Level

Display Setup

 

 

 

LON Config

 

 

 

 

 

 

 

Cal Gas Conc

Device Setup

 

 

 

History

 

 

 

 

 

Status Rate

Device Cal

 

 

 

Display Info

 

 

 

 

 

Lon Address

Display Test

 

 

 

Debug Menu

 

 

 

 

 

 

Device Test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.2

12

95-8656

RTC

Time and date for the UD10-DCU is automatically set by the EQP controller via the LON network. Changes to the time on the S3 computer will be reflected at the UD10-DCU when the controller RTC is set.

When used with the GT3000, the RTC for the GT3000 can be synchronized to the RTC of the display by going through the Main Menu->Device Setup->RTC->“Sync W/Disp”.

4-20 ma input loop Calibration

If the detector connected to the UD10-DCU is HART enabled, its 4-20 mA output signal can be trimmed. (A detector calibration should be performed prior to trimming the detector output or UD10-DCU input).

HART Detector Signal Calibration

Navigate down the menu to Device Test > D/A (Digital to Analog) Trim.

Main Menu

 

 

 

 

 

 

Process Vars

 

 

 

 

 

 

Display Status

 

 

Device Test

 

 

 

Device Status

 

 

Self Test

 

 

D/A Trim

Display Setup

 

 

Response Test

 

 

Zero Trim

 

 

Device Setup

 

 

Loop Test

 

 

Gain Trim

Device Cal

 

 

D/A Trim

 

 

 

 

 

 

 

 

Display Test

 

 

 

 

 

 

Device Test

 

 

 

 

 

 

Select Zero Trim. When this screen is entered, a warning message is presented. Select ENTER to continue. When the message “Connect Reference Meter” is presented, install the current meter on the mA line between the detector and UD10-DCU. Select ENTER to continue. When the message “Set Input Current to 4mA?” is presented, select ENTER to begin the Zero Trim function. The detector will now set its 4 mA output value. If the value indicated on the current meter is not 4.00 mA, enter the measured value into the UD10-DCU using the Previous and Next switches. The UD10-DCU calculates and corrects for the difference between the actual and entered values. When the current meter value is at the desired 4.00 mA, select ENTER to accept the new zero trim value.

Select Gain Trim. Follow the same procedure for gain/ span calibration.

UD10-DCU Input Trim

When the UD10-DCU is used with a detector that supports HART communication, an automated process can be used to trim the UD10-DCU input. Navigate down the menu to “Input Loop Cal”.

Main Menu

Process Vars

Display Status

Device Status

Display Setup

Device Setup

Device Cal

Display Test

Device Test

Display Setup

Mode Select

General Options

RTC

Input Loop Cal

Contrast Contrl

Backlight Ctrl

Write Protect

Upon entering Input Loop Cal, the UD10-DCU commands the detector to output 4 mA, and then automatically calibrates its own input. The UD10-DCU then commands the detector to output 20 mA and subsequently calibrates its own input.

If a non-HART detector is being used, the Input Loop Cal may be performed with a mA current source or loop calibrator connected to the UD10-DCU Sensor Connector. Follow the loop calibration instructions shown by the UD10-DCU for this procedure.

4.2

13

95-8656

Optional System Tests

The following tests are available for verifying proper operation of various functions of the gas detection system:

The Self Test and Response Test are accessed from the “Display Test” screen. (A “Device Test” screen is available for performing the same tests on HART enabled detectors.)

The Proof Test is performed by applying test gas to the sensor. It is not accessed from the “Display Test” screen and does not inhibit the outputs.

Main Menu

Process Vars

Display Status

Device Status

Display Setup

Device Setup

Device Cal

Display Test

Device Test

Display Test

Self Test

Response Test

Self-Test

This test commands the UD10-DCU to perform a fully automatic internal test. At the completion of the test, the UD10-DCU will indicate a pass or fail.

Response Test

This test inhibits the UD10-DCU’s outputs, thereby providing a means of testing the system by applying gas to the detector without activating any alarms or affecting the output.

note

If the Response Test is not terminated by the operator, the test will automatically time out after ten minutes and the UD10-DCU will return to normal operation.

Proof Test

A Proof Test (bump test) can be performed at any time to verify proper operation and calibration of the system. Since this test does not inhibit the UD10-DCU’s outputs, secure any output devices prior to performing the test to prevent unwanted actuation.

History

There are two separate histories, one for the display and one for the detector (if available). Both will state the number of hours that the unit has been operating, and the highest and lowest recorded temperature (with time and date stamp).

Display Backlight Operation

The UD10 can be programmed to turn on the backlight feature of the digital display when an alarm or fault occurs or a magnetic switch is activated. Navigate to the Backlight Ctrl screen.

Main Menu

 

 

 

 

 

 

Process Vars

 

 

 

 

 

 

 

 

Display Setup

 

 

 

Display Status

 

 

 

 

 

 

 

 

 

Backlight Ctrl

 

 

Mode Select

 

 

Device Status

 

 

 

 

 

 

General Options

 

 

Off

Display Setup

 

 

 

 

 

 

Input Loop Cal

 

 

On

Device Setup

 

 

 

 

 

 

Contrast Contrl

 

 

Automatic

Device Cal

 

 

 

 

 

 

Backlight Ctrl

 

 

 

Display Test

 

 

 

 

 

 

 

 

 

 

 

Device Test

 

 

 

 

 

 

Off = The backlight is always off.

On = The backlight is always on.

Automatic = Normal operation – Backlight is off Alarm – Backlight flashes on and off Fault – Backlight is on steady

Magnetic Switch – Backlight is on steady

The backlight automatically turns off 10 minutes after the last Magnetic Switch activation.

If the backlight is on following a magnetic switch activation and then an alarm condition occurs, the backlight will remain on steady and not flash until the 10 minute time-out is complete. Then it will begin flashing.

4.2

14

95-8656

Troubleshooting

If a Fault condition is indicated on the UD10-DCU faceplate, the nature of the fault can be determined by using the magnetic tool to navigate to the appropriate Fault screen.

NOTE

Refer to the Menu in the appropriate Appendix of this manual for the path to the proper Fault screen.

Shortcut: From the main display screen, touch the magnet to the “Previous” switch to go directly to the Fault screen.

Example:

For a Display (UD10-DCU) related fault:

Main Menu > Display Status > Fault/Status > Fault

For a Device (Sensor) related fault:

Main Menu > Device Status > Fault/Status > Sensor Fault

When the active fault has been identified, refer to the Troubleshooting Tables for a description of the fault and suggested corrective action.

Refer to Table 5 for Display Faults and Table 6 for Device Faults.

Table 5—Troubleshooting Guide - Display Faults

Display Faults

Description

Recommended Action

 

 

 

 

 

Check sensor wiring.

Input Loop FLT

Fault in sensor or sensor loop

Calibrate sensor.

 

 

Ensure that sensor type matches configuration.

 

 

 

EE Fault

Fault in non-volatile memory

Return to factory.

 

 

 

ADC Ref Fault

ADC reference voltage too high or low

Return to factory.

 

 

 

24V Fault

Problem in 24 volt power supply or power wiring

Check power wiring and output voltage of power

supply.

 

 

 

 

 

Flash Fault

FLASH memory Fault

Return to factory.

 

 

 

RAM Fault

Fault in volatile memory

Return to factory.

 

 

 

WDT Fault

Watchdog timer is non-functional

Return to factory.

 

 

 

12V Fault

12 volt internal power supply out of tolerance

Check power source.

Return to factory.

 

 

 

 

 

5V Fault

5 volt internal power supply out of tolerance

Check power source.

Return to factory.

 

 

 

 

 

3V Fault

3 volt internal power supply out of tolerance

Check power source.

Return to factory.

 

 

 

 

 

Note: A fault condition will cause an oxygen detector to generate an alarm output as the decreasing 4-20 mA signal passes through the alarm range.

4.2

15

95-8656

Table 6—Troubleshooting Guide - Device Faults

Device Faults

Description

Recommended Action

 

 

 

Loop Fault

Current loop below fault threshold

Check 4-20 mA loop wiring for shorts or opens.

 

 

 

Supply Voltage

24 volt power supply voltage too low

Verify proper wiring to the device and correct

Fault

voltage output from the power supply.

 

 

 

 

 

 

This fault can be caused if the calibration is

 

 

allowed to time out. If so, recalibrate.

 

 

Ensure that there is enough gas in the calibration

Calibration Fault

Bad calibration

bottle to complete the calibration.

 

 

Ensure that the gas being used for calibration is

 

 

the correct type and concentration. It must match

 

 

the configured setting.

 

 

 

Memory Fault

Self-detected memory fault

Return to factory.

 

 

 

ADC Fault

Self-detected ADC fault

Return to factory.

 

 

 

Internal Voltage

Self-detected voltage fault

Check supply voltage.

Fault

Return to factory.

 

 

 

 

 

 

Device may have been calibrated with background

Zero Drift

Sensor signal has drifted negative

gas present. Recalibrate the detector. Purge with

 

 

clean air if needed.

 

 

 

Temperature

Temperature sensor is out of range

Return to factory.

Sensor Fault

 

 

 

 

 

Wrong Sensor

Wrong sensor type is installed

Sensor type must match configuration. Change

Type

sensor or configuration.

 

 

 

 

Lamp Fault

Open or shorted lamp

Replace lamp.

Return to factory.

 

 

 

 

 

Alignment Fault

Open path alignment problem

Align the device as specified in the instruction

manual.

 

 

 

 

 

Blocked Optic

Optical path is blocked

Locate and remove obstruction from the optical

Fault

path.

 

 

 

 

Cal Line Active

Cal line is active at start-up

Ensure that the Cal line wiring is not shorted and

the switch is open.

 

 

 

 

 

Low Cal Line

Cal line is shorted.

Check wiring.

 

 

 

 

 

Check sensor wiring.

Sensor Fault

Self-detected fault with the sensor

Calibrate sensor.

 

 

Ensure that sensor type matches configuration.

 

 

 

Noise Fault*

Excessive noise on signal

Check OPECL alignment.

 

 

 

Align ADC Fault*

Alignment ADC saturated

Check OPECL alignment.

 

 

 

Align Fault*

Alignment fault

Check OPECL alignment.

 

 

 

Align Warning*

Alignment warning

Check OPECL alignment.

 

 

 

DAC Fault

DAC fault detected

Return to factory.

 

 

 

General Fault

Unspecified fault

Verify correct power wiring and supply voltage.

Consult the factory.

 

 

 

 

 

High Fault

Detector output is higher than specified limit

Verify correct sensor type and calibration.

 

 

 

Low Fault

Detector output is lower than specified limit

Verify correct sensor type and calibration.

 

 

 

Dirty Optics

Detector optics are dirty

Perform the cleaning procedure as described in

the detector manual, then perform calibration.

 

 

 

 

 

Start Cal Fault

Calibration fault

Verify correct sensor type and calibrate.

 

 

 

*OPECL only.

 

 

4.2

16

95-8656

Table 6—Troubleshooting Guide - Device Faults, Continued

Device Faults

Description

Recommended Action

 

 

 

 

 

Power may have been interrupted while the device

EE Fault

Fault in non-volatile memory

was updating its internal data logs. Recycle

 

 

power.

 

 

 

Ref ADC Sat

Sensor signal level is outside the range of the AD

Return to factory.

converter

 

 

 

 

 

Active ADC Sat

Sensor signal level is outside the range of the AD

Return to factory.

converter

 

 

 

 

 

24V Fault

Problem in 24 volt power supply or power wiring

Check power wiring and output voltage of power

supply.

 

 

 

 

 

Flash CRC Fault

Memory fault

Return to factory.

 

 

 

RAM Fault

Fault in volatile memory

Return to factory.

 

 

 

Low Voltage

Power supply voltage outside of limits

Check power supply voltage.

Return to factory.

 

 

 

 

 

Temp Fault

Temperature sensor fault

Return to factory.

 

 

 

Software Fault

Internal software fault

Return to factory.

 

 

 

EE Safety Fault

Internal configuration fault

Return to factory.

 

 

 

 

 

Device may have been calibrated with background

Gas Under Range

Sensor signal has drifted negative

gas present. Recalibrate the detector. Purge with

 

 

clean air if needed.

 

 

 

Sensor Mismatch

Wrong sensor type is installed

Sensor type must match configuration. Change

sensor or configuration.

 

 

 

 

 

ADC CNTR Fault

Internal hardware fault

Return to factory.

 

 

 

3V Fault

3 volt internal power supply out of tolerance

Return to factory.

 

 

 

Comm Fault

Communication fault

Check detector wiring and power supply.

 

 

 

GEN Fault

Unspecified fault

Verify correct power wiring and supply voltage.

Consult the factory.

 

 

 

 

 

12V Fault

12 volt internal power supply out of tolerance

Return to factory.

 

 

 

5V Fault

5 volt internal power supply out of tolerance

Return to factory.

 

 

 

4.2

17

95-8656

Specifications

operating voltage—

24 Vdc nominal, operating range is 18 to 30 Vdc. Ripple cannot exceed 0.5 volt P-P.

operating power—

Heater off:

1.3 watts nominal @ 24 Vdc with

 

backlit display off.

 

2 watts @ 24 Vdc with backlit display on.

Heater on:

4 watts additional.

CGS model:

Add 4 watts with CGS interface

 

board and CGS sensor installed.

Maximum power with heater and display on:

6 watts @ 30 Vdc (Standard model)

10 watts @ 30 Vdc (CGS model).

note

Heater turns on when the internal temperature drops below –10°C (default operation).

Lon communication —

Digital communication, transformer isolated (78.5 kbps).

EQP/UD10 System Accuracy—

<1 ppm error. <1 %LFL error.

With CGS sensor: ±3 %LFL, 0-50 range, ±5 %LFL 51-100 range.

EQP/UD10 System Response—

Toxic gas: T90 < 10 sec.

Combustible gas: T90 < 10 sec.

With CGS sensor: T90 < 12 sec.

Table 7—Gas Detectors Compatible with the UD10-DCU

Device

Toxic1

Catalytic

IR2

Instruction

Combustible

Combustible

Manual

 

 

 

 

 

 

 

GT3000

X

 

 

95-8616

 

 

 

 

 

PIR9400

 

 

X

95-8440

 

 

 

 

 

PIRECL

 

 

X

95-8526

 

 

 

 

 

OPECL

 

 

X

95-8556

 

 

 

 

 

CGS

 

X

 

90-1041

 

 

 

 

 

505/CGS

 

X

 

95-8472

 

 

 

 

 

 

 

 

 

95-8396

C706X3

X

 

 

95-8411

 

 

95-8414

 

 

 

 

 

 

 

 

95-8439

 

 

 

 

 

NTMOS4

X

 

 

95-8604

1Hydrogen sulfide, Ammonia, Chlorine, Hydrogen, Oxygen, Carbon Monoxide, and Sulfur Dioxide.

2Methane, Ethane, Ethylene, Propane, and Propylene.

3C7065E Oxygen detector is not supported.

4Hydrogen sulfide only.

Detector compatibility—

The UD10-DCU can be used with the Det Tronics gas detectors listed in Table 7.

Unit of Measurement—

PPM, % LFL, % V/V, LFLM, or Mg/M3.

Operating temperature—

–40°C to +75°C.

Storage Temperature—

–55°C to +75°C.

Humidity Range—

5 to 95% RH (Det-Tronics verified).

electro-magnetic compatibility—

EMC Directive 2004/108/EC EN55011 (Emissions) EN50270 (Immunity)

DIMENSIONS—

See Figures 6 and 7.

5.86

(14.9)

5.2

(13.2)

2.7

(6.9)

4.7

(11.9)

3.46

(8.8)

3.77

(9.6)

1.28

(3.3)

C2281

Figure 6—Dimensions of Model STB Termination Box in Inches (Centimeters)

4.2

18

95-8656

Det-Tronics UD10 User Manual

Wiring terminals—

Certification—

14 to 18 AWG wire can be used.

For complete approval details, refer to the appropriate

 

 

Appendix:

 

Conduit Entries—

 

 

3/4” NPT or M25.

FM

 

 

 

®

ENCLOSURE MATERIAL—

APPROVED

 

 

 

Epoxy coated aluminum or 316 stainless steel.

Appendix A – FM

 

 

SHIPPING WEIGHT—

Appendix B – CSA

Aluminum:

4.15 pounds (1.88 kilograms).

Appendix C – ATEX

Stainless steel:

10.5 pounds (4.76 kilograms).

Appendix D – IECEx

 

 

Appendix E – INMETRO

WARRANTY—

12 months from date of installation or 18 months from date of shipment, whichever occurs first.

6.48

4.7

(16.5)

(11.9)

 

3.46

 

(8.8)

 

5.2

 

(13.2)

 

5.86

 

(14.9)

11.28

 

(28.7)

 

 

R0.175

A2442

Figure 7—Dimensions of UD10-DCU with GT3000 in Inches (Centimeters)

4.2

19

95-8656

DEVICE REPAIR AND RETURN

Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure.

Pack the unit properly. Always use sufficient packing material. Where applicable, use an antistatic bag as protection from electrostatic discharge. The RMI number should be clearly marked on the outside of the box.

note

Inadequate packaging that ultimately causes damage to the returned device during shipment will result in a service charge to repair the damage incurred during shipment.

Return all equipment transportation prepaid to the factory in Minneapolis.

NOTE

It is highly recommended that a spare be kept on hand for field replacement to ensure continuous protection.

ORDERING INFORMATION

Sensor module, transmitter module and termination boxes (if used) must be ordered separately.

Refer to the UD10-DCU Model Matrix for ordering details.

Replacement Parts

Part Number

Description

009700-001

Magnetic Tool

010535-001

Electronics Module, DCU

101197-001*

Stop Plug, 3/4" NPT, AL

101197-004*

Stop Plug, 3/4" NPT, SS

101197-005

Stop Plug, M25, AL, IP66

101197-003

Stop Plug, M25, SS, IP66

010816-001

Stop Plug, 20PK, 3/4" NPT, AL

010817-001

Stop Plug, 20PK, 3/4" NPT, SS

010818-001

Stop Plug, 20PK, M25, AL, IP66, EXDE

010819-001

Stop Plug, 20PK, M25, SS, IP66, EXDE

104190-001

Stop Plug, M25, AL, INMETRO

104190-002

Stop Plug, 3/4" NPT, AL, INMETRO

104190-003

Stop Plug, M25, SS, INMETRO

104190-004

Stop Plug, 3/4" NPT, SS, INMETRO

102804-001

Reducer, M25 to M20, AL

102804-003

Reducer, M25 to M20, SS

103922-001

475 Field Communicator

005003-001

Lubriplate grease, 1 oz.

*NEMA/Type 4X, IP66 rating requires addition of Teflon tape.

4.2

20

95-8656

Loading...
+ 49 hidden pages