Detcon Sensor Duct Mount Kit User Manual

Model 700
DETCON, Inc.
Sensor Duct Mount Kit
Operator’s Installation and Instruction Manual
Covers 975-000020-893, 975-R00020-893
4055 Technology Forest Blvd. Suite 100,
The Woodlands, Texas 77381
www.detcon.com
November 19, 2012 • Document #3256 • Revision 1.2
This page left intentionallyblank
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
www.detcon.com
sales@detcon.com
700 Duct Mount
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas 77381
Model 700 Duct Mount Kit ii
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
700 Duct Mount
Table of Contents
1.0 Description..........................................................................................................................................1
2.0 Principle of Operation........................................................................................................................1
3.0 Installation..........................................................................................................................................2
4.0 Calibration..........................................................................................................................................4
5.0 Maintenance........................................................................................................................................4
6.0 Warranty.............................................................................................................................................4
7.0 Revision Log........................................................................................................................................5
Table of Figures
Figure 1 Sample flow diagram .....................................................................................................................1
Figure 2 Duct cutout dimensions..................................................................................................................2
Figure 3 Side view of installation, Square Duct, Round Duct........................................................................3
Figure 4 Cal Port..........................................................................................................................................4
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas 77381
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.comsales@detcon.com
Model 700 Duct Mount Kit iii
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
This page left intentionallyblank
700 Duct Mount
Model 700 Duct Mount Kit iv
700 Duct Mount
1.0 Description
The Detcon Sensor Duct Mount Kit for Model 700 gas detection sensors allows a Detcon Model 700 gas sensor assembly to be mounted so that its sensor is located inside of an air duct, while its transmitter, located outside the duct, is still accessible for calibration and other adjustments. This method of installation is much more economical than the typical sample draw type system that is normally used in such applications. This instruction manual explains the installation, calibration, and maintenance procedures of the duct mount con­figuration. Reference the instruction manual that came with your Detcon sensor assembly for further infor­mation.
2.0 Principle of Operation
In operation, air flow through the duct enters the duct mount chamber through ports facing the oncoming flow of air. Once inside the chamber the sample passes by the sensor and then exits through similar ports that face the opposite direction. If any target gas is present in the chamber, the sensor output signals and/or alarm functions, will respond accordingly as described in the sensor assembly instruction manual.
Figure 1 Sample flow diagram
Model 700 Duct Mount Kit Rev. 1.2 Page 1 of 5
700 Duct Mount
3.0 Installation
1. Cut clearance hole in duct as shown below. Cutout is the same for square or round ducts. Minimum suggested diameter for round duct is 10 inches to adapt with normal mounting techniques. Adapting to an 8” diameter duct is possible with special mounting techniques. Below 8” diameter is not practical for mounting.
2. Mount the duct mount kit using four 1/4” sheet metal bolts or other appropriate hardware.
3. If necessary you may enhance mounting integrity by using the two holes on the upper right portion of the duct mount plate. Use standoffs and 1/4” sheet metal bolts or other appropriate hardware.
4. Perform installation wiring as described in the sensor assembly instruction manual. Use flexible conduit to allow for future maintenance.
Figure 2 Duct cutout dimensions
Model 700 Duct Mount Kit Rev.1.2 Page 2 of 5
700 Duct Mount
Figure 3 Side view of installation, Square Duct, Round Duct
Model 700 Duct Mount Kit Rev. 1.2 Page 3 of 5
700 Duct Mount
4.0 Calibration
CAUTION: In high velocity air ducts, air flow may need to be shut down before calibration takes place.
1. Verify that there is no air flow through the duct.
2. Remove the cal port plug.
3. Apply the target gas to the cal port at a flow rate of 500 milliliter per minute for combustible (FP series) and solid state H2S (TP series) sensors. Apply a flow rate of 1000 ml/m for toxic gas (DM series) sensors.
4. Follow calibration instructions provided in the sensor instruction manual.
5. Remove the target gas and apply a zero air standard for clearing.
6. If necessary, repeat items 3-5 as indicated in the sensor instruction manual.
7. Replace the cal port plug. Calibration is complete.
Figure 4 Cal Port
5.0 Maintenance
To remove the sensor for replacement or maintenance, perform the following steps:
1. Remove the two bolts that hold the sensor condulet to the duct mount plate.
2. Pull the sensor out of the duct mount chamber and perform necessary maintenance.
3. Reverse the procedure to replace the sensor. If necessary, lubricate the O-rings inside the duct mount chamber so that the sensor rain shield will slide into the chamber easily.
6.0 Warranty
Detcon, Inc., as manufacturer, warrants each sensor duct mount kit for a period of one year under the condi­tions described as follows: The warranty period begins on the date of shipment to the original purchaser and ends one year thereafter. Should any part fail return the defective part to Detcon, Inc., for necessary repairs or replacement.
Model 700 Duct Mount Kit Rev.1.2 Page 4 of 5
7.0 Revision Log
Revision
Date
Changes made
1.105/07
/10Previous release
1.2
11/19/12
Added notation regarding
minimum round duct diameter.
700 Duct Mount
Model 700 Duct Mount Kit Rev. 1.2 Page 5 of 5
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.comsales@detcon.com