3.1Mounting and Cable Penetrations................................................................................................................... 1
3.2Power and I/O Connections............................................................................................................................ 2
3.2.1 AC Power.................................................................................................................................2
3.2.2 DC Power ................................................................................................................................2
3.2.3 Serial Input Connection...........................................................................................................2
4. System Operation...................................................................................................................................4
4.2Unit Setup Main Menu ................................................................................................................................... 5
4.2.1 Set Number of Channels ..........................................................................................................5
Drawings and Diagrams ............................................................................................................................................ 13
Figure 4 Front Panel ........................................................................................................................................5
Model RD-8X-N4X Operator Manual Rev. 1.0 iii
RD-8X-N4X Operators Manual
This page left intentionally blank
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
H • Hsales@detcon.comU
RD-8X-N4X Operators Manual
1. Description
The Model RD-8X is a read only remote display unit designed to operate with Modbus™ RS485 sensors or
control systems from Detcon. The unit displays real time channel information on the backlit LCD. Display
information includes the channel number, the gas type, and the gas concentration. The unit will also
display the current Alarm/Fault status via the front panel LED indicators.
Housed in a NEMA 4 water proof enclosure, the Model RD-8X has a built in power supply, providing
multiple power options. 115/230VAC 50/60Hz or 11.5-30VDC can provide power to the unit.
2. Specifications
Capacity
16 Input Channels
Sensor Inputs
Accuracy
Outputs
Electrical
Power Input
Power Consumption
Display
Electrical Classification
Dimensions
Physical
Operating Temperature Range
Warranty
3. Installation
RS-485 Modbus RTU From Control Systems
± 1% Full Scale Range
Qty 4 Relays: 1 Form C Contacts per relay
Rated for 5A @ 30VDC, 5A @ 250VAC
RS-485 Modbus™ Slave
115-230VAC 50/60Hz
11.5-30VDC
Nominal: 1 Watts @ 24VDC
Maximum: 2 Watts @ 24VDC
1”x5” Backlit LCD
NEMA 4X
15-3/8”W x 12-3/8”H x 8-1/2”D
-40F to +167F
-40C to +75C
One year
3.1 Mounting and Cable Penetrations
Securely mount the Model RD-8X enclosure per the mounting dimensions provided in Figure 1.
NOTE: AC power should be kept separate from DC power and signals within conduit runs.
Model RD-8X-N4X Operator Manual Rev. 1.0 Page 1 of 14
RD-8X-N4X Operators Manual
RESET
Model RD-8X-N4X
Remote Display
9.85"8.95"
ON/OFF
8"
11.75"
Mounting Flange
Mounting Flange
6.45"
6.85"
Figure 1 Dimensional Overview
3.2 Power and I/O Connections
Power and I/O connections are made on back of the PCB. Plug-in male connectors are provided for input
wiring terminations. This connector style provides for quick disconnect convenience during replacement or
servicing (refer to Figure 3).
3.2.1 AC Power
Connect the 115 or 230VAC input wiring to the terminals at P1labeled “VAC IN” (refer to Figure 3).
3.2.2 DC Power
For optional DC power input, connect 11.5-30VDC to the terminals at P2, labeled “VDC IN” (refer to
Figure 3). This input can be used for primary power or back-up power in the event of a VAC power
failure.
3.2.3 Serial Input Connection
The serial RS-485 connection to sensors or control systems should be terminated at P4 Labeled “COM2”
the RS-485 Master port of the remote display (refer to Figure 3).
Model RD-8X-N4X Operator Manual Rev. 1.0 Page 2 of 14
RD-8X-N4X Operators Manual
Power Switch
12
SW2
34
FAULT ALARM3 ALARM2 ALARM1
NC NONC NONC NO
NC NO
P9P8P7P6
CONTROLLER PCA
RESET
P5
Yel 18AWG
Yel 18AWG
Figure 2 Wiring Diagram
P10
P1
P11
P2
P5
P5
RESET SWITCH
SW1
12
ACV IN
VDC IN
COM 1COM 2
Ground
Neutral (L2)
120VAC (L1)
VDC - (Return)
VDC + (11.5~30VDC)
Customer
Supplied
Wiring
RS-485 Shield
RS-485 - B
RS-485 - A
Customer
Supplied
Wiring
E
L2
L1
+
S
B
A
S
B
A
Figure 3 Controller PCB Connections
Model RD-8X-N4X Operator Manual Rev. 1.0 Page 3 of 14
RD-8X-N4X Operators Manual
3.2.4 Relay Outputs
The Model RD-8X provides four single pole double throw (SPDT) Form C contact relays. The relay
terminals (P6 through P9) are labeled “FAULT”, “ALM3”, “ALM2”, and “ALM1” (refer to Figure 3). The
relays can be used to control annunciating devices or as signal input/outputs to other control devices.
Connections are labeled COM (common), NO (normally open) and NC (normally closed). The current
ratings of the relay contacts are 5A @ 30VDC, and 5A @ 250VAC, these ratings should not be exceeded.
Note: ALM3 is not used when the unit is used with the 10B control units.
3.3 Start-up
The power switch is located on the outside of the enclosure, on the right side of the unit, and is marked as
“ON” and “OFF”. To apply power to the unit, turn the switch to the “ON” position.
NOTE: Before applying power, check to make sure that all the wiring connections and external
devices are installed correctly.
NOTE: Applying power with devices hooked up incorrectly may cause damage to the equipment.
When power is applied to the unit, the unit will display the firmware revision and properties for several
seconds. For this controller that information should be:
DETCON INC COM 1 MODBUS SLAVE
MODBUS CONTROLLER
VERSION XX.XXX COM 2 MODBUS MASTER
PCWH X.XXX
After unit initialization, the unit will begin normal operation. If the unit has been properly setup, the unit
will display the current status of the devices that it is connected to.
4. System Operation
4.1 Front Panel
The Main Display is a 1¼”x 6” backlit LCD that has 4 lines by 40 characters. In normal operation the
channel’s information will be shown as “01> XXXX ppm GAS” will be displayed. If any channel is in
any gas alarm condition, “01> XXXX IN ALARM ” will be displayed. If any gas channels are in Fault,
they will display “01> XXXX IN FAULT ”. If any channels are not communicating with their
appropriate 12B controller, then they will display as “01> XXXX COMM ERROR ”.
Four LED indicators on the front panel show alarm and fault relay status. The LED’s represent ALM 1
(yellow), ALM 2 (amber), ALM 3 (red) and FAULT (blue) and are labeled respectively.
The RD-8X user interface consists of four function keys on the front panel. These keys are labeled:
“PROG”, “u” (Up Arrow), “v” (Down Arrow), and “ENTER”. The “ENTER” key doubles as a
“RESET/ACK” key, but “RESET/ACK” has no functionality in this firmware revision.
NOTE: The Remote Display automatically times out of Menu Mode and returns to the Main
Display after 15 seconds of inactivity. While in Menu Mode, there are no updates to gas readings.
Model RD-8X-N4X Operator Manual Rev. 1.0 Page 4 of 14
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.