Delta DVP40ES00R2, DVP32ES00R2, DVP24ES00T2, DVP14ES00T2, DVP32ES00T2 Instruction Sheet

...
http://www.delta.com .tw/industrialautomation/
2006-07-04
5011634301-YIE1
Programmable Logic
Controller
Instruction Sheet
1 WARNING
This Installation Sheet only provides descriptions for electrical specifications, function specificati ons,
installation & wiring, troubleshooting and peripherals. Other detail infromation about programming and
instructions, please see PLC Application Manual. For more information about the optional peripherals,
please refer to their individual instruction sheet or user manuals.
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, high
humidity, electric shock risk and vibration. Also, it should be equipped with protective methods such as
some special tools or keys to open the enclosure, so as to avoid the hazard to users and the damage to
the PLC. The power must be OFF before any maintenance.
Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the
PLC. Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is
properly grounded
. Do NOT touch terminals when power on.
2 INTRODUCTION
2.1. Model Name Explanation and Peripherals
Thank you very much for purchasing Delta’s DVP-ES/EX Series PLC. DVP-ES/EX Series provide the main
processing units and extension units. The processing units offer 14~60 points and the extension units offer 8~32
points. The maximum input and output can be extended up to 128 points respectively. Also, it can be used on
various applications according to input and output points, power supply, digital input and output modules.
Nameplate Explanation
PLC Model
Input Power Su pply Spec.
Output Module Spec.
Barcode and Serial Number
MCU Version
100~240Vac 50/60Hz 35VA MAX
2.0A 240Vac 50/60Hz RES LOAD
32ES00R2T5140004
VX.XX
32ES00R 2 T 5 14 0004
Production series
Production week
Production year (2005)
Production plant (Taoyuan)
Serial number of version
Production Model
Model/Serial Number Explanation
DVP
2
E
: Main Processing Unit (MPU)
X
: Exten sion Un it
S
: Standa rd
X
: A/D, D/A Functions
M
: Digital Input
N
: Digital Output
P
: Digital Input/Output
2
: Advan ced Type
R
: Rela y
T
: Transi stor
N
: No Output Module
00 :
H TYPE
01
:
L TYPE
11
:
H TYPE
C
: Non-extended
Product Series
Points (Input + Output)
Models
Model Type
AC Input DC Input DC Input
Peripherals
DVP-HPP Series: Handheld Programmable Panel WPLSoft: DVP-PLC Programming Software Tool (Windows based software) DVPACAB115: 1.5M Cable (HPP PLC, provided in DVP-HPP Series) DVPACAB215: 1.5M Cable (PC PLC) DVPACAB230: 3.0M Cable (PC PLC) DVPACAB315: 1.5M Cable (HPP PC) DVPACAB403: 30cm Cable (Main processing unit Extension unit, or Extension unit Extension I/O
signal extension cable)
2.2. Product Profile and Outline
1. DIN rail clip 9. Input / Output
2. DIN rail (35mm)
10. Status indicators: POWER, RUN, and ERROR
3. Direct mounting holes 11. Input / Output terminal cover
4. Communication Ports Cover (RS-232C) 12. Input / Output terminal cover
5. Extension Port indicators
13. Input / Output terminal nameplate panel
6. Input / Output terminals
14. Input / Output terminal nameplate panel
7. Input / Output terminals 15. RS-485 communication port
8. Input / Output indicators
2.3. DVP-ES/EX Series Models
ES Standard Main Processing Units (MPU-00)
Input Unit Output Unit
Model Name Power
Point Type Point Typ e
Profile Profile Reference
DVP14ES00R2 8 6
DVP24ES00R2 16 8 DVP32ES00R2 16 16 DVP40ES00R2 24 16
DVP60ES00R2 36 24
Relay
DVP14ES00T2 8 6 DVP24ES00T2 16 8
DVP32ES00T2 16 16
DVP40ES00T2 24 16
DVP60ES00T2
100~
240
VAC
36
DC Sink
or
Source
24
Transistor
ES Standard Main Processing Units (MPU-01,11)
Input Unit Output Unit
Model Name Power
Point Type Point Type
Profile
DVP14ES01R2 8 6
DVP24ES01R2 16 8
DVP24ES11R2 16 8
DVP32ES01R2 16 16
Relay
DVP14ES01T2 8 6
DVP24ES01T2 16 8 DVP32ES01T2
24
VDC
16
DC Sink
or
Source
16
Transistor
EX Special Function Main Processing Units (MPU-00, MPU-11)
Input Unit Output Unit
Point Type Point Type
Model Name Power
DI AI DI AI DO AO DO AO
Profile Reference
DVP20EX00R2 8 4 6 2 Re lay
DVP20EX00T2
100~
240
VAC
8 4 6 2 Transistor
DVP20EX11R2
24
VDC
84
DC Sink
or
Source
-20mA~20 mA
or
-10V ~ +10
V
6 2 Rela y
0~20mA
or
010V
Digital I/O Extension Unit for DVP-ES/EX Series- 00
Input Unit Output Unit
Model Name Power
Point Ty pe Point Type
Profile Reference
DVP24XN00R 0 24
DVP24XP00R 16 8
DVP32XP00R 16 16
Relay
DVP24XN00T 0 24
DVP24XP00T 16 8
DVP32XP00T
100~
240
VAC
16
DC
Sink
or
Source
16
Transistor
Digital I/O Extension Unit for DVP-ES/EX Series- 01 (L TYPE)
Input Unit Output Unit
Model Name Power
Point Ty pe Point Type
Profile Profile Reference
DVP16XM01N 16 0 None
DVP16XN01R 0 16
DVP24XN01R 0 24
DVP24XP01R 16 8
DVP32XP01R 16 16
Relay
DVP16XN01T 0 16
DVP24XN01T 0 24
DVP24XP01T 16 8
DVP32XP01T
24
VDC
16
DC
Sink
or
Source
16
Transistor
Digital I/O Extension Unit for DVP-ES/EX Series-11 (H TYPE)
Input Unit Output Unit
Model Name Power
Point Ty pe Point Type
Profile Profile Reference
DVP08XM11N 8 0
DVP16XM11N 16 0
None
DVP08XN11R 0 8
DVP16XN11R 0 16
DVP24XN11R 0 24
DVP08XP11R 4 4
DVP24XP11R 16 8
DVP32XP11R 16 16
Relay
DVP08XN11T 0 8
DVP16XN11T 0 16
DVP24XN11T 0 24
DVP08XP11T 4 4
DVP24XP11T 16 8
DVP32XP11T
24
VDC
16
DC Sink
or
Source
16
Transistor
3 SPECIFICATIONS
3.1. Function Specifications
Items Specifications Remarks
Control Method
Stored program, cyclic scan system
I/O Processing Method
Batch processing (when END instruction is executed)
I/O refresh instruction is available
Execution Speed
Basic commands (several us)
Application instructions (10 ~ hundreds us)
Program Language
Instruction, Ladder Logic, SFC Including Step instructions
Items Specifications Remarks
Program Capacity
3792 Steps Built-in EEPROM
Instructions
32 basic sequential instructions (including STL / RET)
107 application instructions
Initial Step Point
10 points S0~S9
Zero Return Point
10 points S10~S19
Step Relays (Latched)
General Step Point
108 points S20~S127
General
512+232 points M0~M511+M768~M999
Latched
256 points M512~M767
Auxiliary Relays
Special
280 points M1000~M1279 64 points T0~T63 (100 ms time base)
63 points
T64~T126 (10 ms time base, when M1028 is ON)
Timers Digital
1 points T127 (1 ms time base)
General
112 points C0~C111
Latched
16 points C112~C127
Counters
High Speed
13 points 1 phase 20KHz, 2 phase 5KHz C235~C254 (all latched type)
General
408 points D0 ~ D407
Latched
192 points D408~D599
Data Registers
Special
200 points
D1000~D1143D1256~D1311
Pointers P
64 points P0~P63
Index Registers E / F
2 points
E(=D1028)F(=D1029)
Decimal K
16 bit: -32768~+32767 32 bit: -2147483648~+2147483647
Constants
Hexadecimal H
16 bit: 0000~FFFF 32 bit: 00000000~FFFFFFFF
Serial Communication
2 Ports is provided. RS-232C: Program read/write communication port, RS-485: General function communication port (controlled by RS instruction); Special drive instructions for Delta AC drive are also supported.
Protection Features
Password, I/O examination, Execution time, Illegitimate instruction or operand
Monitor / Debug
Program execution time display, Bit/Word, Device setting
Note: For more information about special relays and data registers, please refer to the Delta PLC Application Manual.
3.2. Electrical Specifications
Model
Item
DVP-
14ES00
DVP-
24ES00
DVP-
32ES00
DVP-
40ES00
DVP-
60ES00
DVP-
20EX00
DVP-
14ES01
DVP-
24ES□□
DVP-
32ES01
DVP-
20EX11
Power Supply Voltage
100~240VAC (-15%~10%), 50/60Hz ± 5%
24VDC (-15%~10%)
Operation Specification
The PLC start to operate at power supply of 95~100VAC. If the voltage of power supply drops to 70VAC, the PLC will stop. Maximum power loss time is 10ms or less.
Maximum power loss time is 5ms or less.
Fuse
2 A / 250VAC 2 A / 250VAC
Power Consumption
20 VA 25VA 30VA 30VA 35VA 30 VA 5.5 W 6.5 W 8 W 8 W
DC24V Supply Current
400mA 400mA 400mA 400mA 400mA 400mA
Power Protection
DC24V output short circuit DC24V input polarity
Voltage Withstand
1500VAC(Primary-secondary), 1500VAC(Primary-PE), 500VAC(Secondary-PE)
Insulation Resistance
> 5 MΩ at 500VDC (Between all inputs / outputs and earth)
Noise Immunity
ESD: 8KV Air Discharge EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V RS: 26MHz~1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole).
Environment
Operation: 0°C ~55°C (Temperature), 50~95% (Humidity), Pollution degree2; Storage: -25°C ~70°C (Temperature), 5~95% (Humidity)
Vibration / Shock Resistance
Standard: IEC1131-2, IEC 68-2-6TEST Fc/ IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (g)
400 552 580 596 750 536 260 414 430 386
Input Point Electrical Specifications
Input Point Type
Digital Input Analog Input (EX)
Input Type
DC (SINK or SOURCE)
Input Current
24VDC 5mA
Voltage input: -10V~+10V, Input Resistance: 112K Current input: -20mA~+20mA, Input Resistance: 250
OffOn above 16VDC
Active Level (Analog input resolution)
OnOff below 14.4VDC
Voltage input: 10bit Current input: 10 bit
Reaction Time (Conversion Sampling Time)
About 10ms (An adjustment range of 0~15ms could be selected through D1020 and D1021)
5ms (Time could be adjusted through D1118)
Output Point Electrical Specifications
Output Point Type
Relay-R Transistor-T
Current Specification
2A/1 point (5A/COM)
55°C 0.1A/1point, 50°C 0.15A/1 point 45°C 0.2A/1 point, 40°C 0.3A/1 point (2A/COM)
Voltage Specification
Below 250VAC, 30VDC 30VDC
75VA (Inductive)
Maximum Load
90 W (Resistive)
9W/1 point
Reaction Time
About 10 ms
OffOn 20us OnOff 30us
3.3. AD/DA Specifications
Analog Input (A/D) Analog Output (D/A)
Items
Voltage Input Current Input Voltage Output Current Output
Analog I/O Range
±10V ±20 mA 0 ~ 10V 0 ~ 20 mA
Digital Conversion Range
-512~+511 -512~+511 0 ~ 255 0 ~ 255
Resolution
10 bits(1
LSB
=19.53125 mV) 10 bits (1
LSB
=39.0625 μA) 8 bits(1
LSB
=39.0625 mV) 8 bits (1
LSB
=78.125 μA)
Input Impedance
> 112 KΩ 250Ω
Analog Input (A/D) Analog Output (D/A)
Items
Voltage Input Current Input Voltage Output Current Output
Output Impedance
0.5Ωor lower
Tolerance Carried Impedance
1KΩ~2MΩ 0~500Ω
Overall Accuracy
Non-linear accuracy: ±0.5% of full scale within the range of PLC operation temperature
Maximum deviation: ±1% of full scale at 20mA and +10V
Reaction Time
2ms × channels
Absolute Input Range
±15 V ±32 mA
Digital Data Format
2’s complementary of 16-bit, 10 Significant Bits 2’s complementary of 16-bit, 8 Significant Bits
Average Function
Provided
Isolation Method
Isolation between digital area and analog area. But no isolation among channels.
Protection
Voltage output has short circuit protection but a long period of short circuit may cause internal wire
damage and current output break.
External Wiring Diagram
CH0
CH3
56K
56K
28K
28K
250
V+
V-
I+
I-
-10V~+10V
-20mA~+20mA
Volta
g
e Input
Current Input
Grounding
Grounding
CH0
CH1
V+
V-
I+
I-
Grounding
AC Drive
4 INSTALLATION & WIRING
Dimensions
Model Name (mm) H H1 W W1
W2
(H Type)
W3
(L Type)
DVP14ES00(01)[11]R2/T2 100 95 99 104 82 50
DVP24ES00(01)[11]R2/T2 100 95 150 155 82 50
DVP32ES00(01)[11]R2/T2 100 95 150 155 82 50
DVP40ES00R2/T2 100 95 150 155 82 -
DVP60ES00[11]R2/T2 90 85.5 180.5 185 89.6 -
DVP20EX00[11]R2/T2 100 95 150 155 82 -
W2
H
W1
DVP
W3
H1
W
Terminal Wiring
14ES
X7X6X5
X4
X3X2X1X0
Y0 Y1
Y2
Y3
C2C1C0
( AC Power IN, DC Signal IN )
00
01
S/S
( DC Power IN, DC Signal IN )
Y0
Y1
C0
C1
C3
X4S/S
X0
Y4
Y5
20EX
00
X7X6X5X4
X3X2X1X0
Y0 Y1
Y2
Y3 Y4
Y5C1C0
( AC Power IN, DC Signal IN )
S/S
11
( DC Power IN, DC Signal IN )
24ES
X17X16X15X14X13X12X11X10
X7X6X5X4X3X2X1X0
Y0 Y1
Y2
Y3
Y4 Y5
Y6
C6C2C1C0
( AC Power IN, DC Signal IN )
00
S/S
01
S/S
( DC Power IN, DC Signal IN )
Y0
Y1 Y2
C0
C1
Y7
C3 C4 C5 C7
32ES
00
X17X16X15X14X13X12X11X10
X7X6X5X4X3X2X1X0
Y0 Y1
Y2 Y3
Y4 Y5
Y6 C3C2C1C0 Y7 Y12 Y13 Y16 Y17
Y15Y14Y11Y10
( AC Power IN, DC Signal IN )
S/S
01
S/S
( DC Power IN, DC Signal IN )
Y0
Y1 Y4
C0 Y2
Y3
40ES
X16X14X12X10X6X4X2X0
X17X15X13X11X7X5X3X1
Y0
Y1 Y3
C1 C3Y7Y2 Y5 Y10 Y12 Y15 Y17
Y14Y13Y11Y6
( AC Power IN, DC Signal IN )
S/S
X21 X23 X25
X20 X22 X24
X27
X26
C0
Y16C2Y4
60ES
S/S X22 X23 X24 X25 X26 X27 X30X31 X32 X33 X34 X35X36 X37X40 X41 X42 X43
X21X20X17X16X15X14X13X12X11X10X7X6X5X4X3X2X1X0
Y0 Y1 Y2 Y3 Y4 Y5
Y6C4C3C2C1C0 Y7 C5 Y12 Y13 Y16 Y17 Y22 Y23C6 C7 C8 Y26 Y27
Y25Y24Y21Y20Y15Y14Y11Y10
( AC Power IN, DC Signal IN )
00
PLC Mounting Arrangements and Installation Notes
DIN Rail Installation
The DVP-PLC can be secured to a cabinet by using the DIN rail that is 35mm high with a depth of 7.5mm. When mounting the PLC on the DIN rail, ensure to use the end bracket to stop any side-to-side motion of the PLC, thus to reduce the chance of the wires being pulled loose. On the bottom of the PLC is a small retaining clip. To secure the PLC to the DIN rail, place it onto the rail and gently push up on the clip. To remove it, use a slotted screwdriver, place it on the groove of the retaining clip and press gently, then pull down on the retaining clip and gently pull the PLC away from the DIN rail.
For heat dissipation,ensure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet. (as the figure shown below)
DVP MPU
> 50mm> 50mm
> 50mm
> 50mm
Direct mounting : Use the specified dimensions and install with M4 screws.
Wiring
To suit M3.5 screw terminals
Below 6.2
Below 6.2
1. Please use O-type or Y-type terminals for I/O wiring terminals. The specification for the terminals is shown as the figure on the left. PLC terminal screws should be tightened to between 5~8 kg-cm (4.3~6.9 in-lbs). Only can use 60/75°C copper conducting wire.
2. DO NOT wire to the No Function terminals ‧ . I/O signal wires or power supply should not run through the same multi-wire cable or conduit.
3. When tightening the screws and performing the wiring, please avoid that metallic
particles fell into PLC. After completing wiring, please remove the label which is used to obstruct the metallic particles on the ventilation hole for well heat dissipation.
Installation Notes
Incorrect installation may result in a PLC malfunction or premature failure of the PLC. Ensure to observe the following items when selecting a mounting location.
1. Do not mount the PLC in a location subjected to corrosive or flammable gases, liquids, or airborne dust or metallic particles.
2. Do not mount the PLC in a location where temperatures and humidity will exceed specification.
3. Do not mount the PLC in a location where vibration and shock will exceed specification.
Power Input Wiring
There are two power inputs provided in DVP series PLC, AC input and DC input. Please pay particular attention to the following notes:
1. Connect the AC input (100VAC~240VAC) to terminals L and N. Any AC110V or AC220V connected to the +24V terminal or input points will permanently damage the PLC.
2. The AC power inputs for the MPU and the I/O Expansion Unit should be ON or OFF at the same time.
3. Please use wires of 1.6mm or above for the grounding of the MPU.
4. If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too long or the power voltage drops, the PLC will stop operating and all the outputs will be OFF. Once the power is restored, the PLC will return to operate automatically. (There are latched auxiliary relays and registers inside of the PLC, please be aware when programming.)
AC Input Type
S/S X0 X1 X2
24G
N
L
DC/DC
2.0A
5V
100~240VAC
The +24V supply output is rated at 0.4A from MPU. DO NOT connect external power supply to this terminal. Moreover, it takes 5~7mA to drive each input point, so total of 100mA is needed for 16 input points. As a result, the output loads of +24V should not exceeds 300mA.
5. When DC voltage is supplied to the PLC, ensure the power is at terminals 24VDC and 0V (power range is
20.4VDC~26.4VDC). When the voltage is lower than 17.5VDC, PLC will stop operating, all outputs will turn OFF and the ERROR LED will flash continuously.
DC Input Type
S/S X0 X1 X2+24V 24G
OV24VDC
DC/DC
2.5A
5V
20VDC~26VDC
Safety Wiring
Since the PLC is in control of numerous devices, operation of either one device could affect the operation of other devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto control system, and danger will thus be resulted. Please use the recommended wiring below for the power input:
Power supply for AC loads
Fuse for circuit protection (3A Limit)
Power On pilot indicator
Emergency stop: PLC must provide a quick manual method to disconnect all system power.
Circuit isolation device (System Power Disconnect): Utilize the electromagnetic contactor and the relay to be the isolation unit of the power circuit to prevent the possible instability of the system when the power is supplied on and off.
DVP PLC MPU (main processing unit)
Grounding resistance: 100Ω or less
OV24VDC
MC
MC
NL
1
1
2
3
4
5
66
7
8
Guard Limit
Power supply: AC: 100~240VAC, 50/60Hz, DC: 24VDC
Input Point Wiring
The input signal of the input point is the DC power DC input. There are two types of DC type wiring: SINK and SOURCE, defined as follows:
Definition
Sink = Current flows
into the common
terminal S/S
S/S
X0
Sinking
Source = Current
flows out of the
common terminal S/S
S/S
X0
Sourcing
Wiring
Input Point Loop Equivalent Circuit Wiring Loop
DC Type
DC Signal IN
SINK Mode
+24V
24G
S/S
X0
24VDC
SINK
+5V
+24V
24G
Sink Type
X1 X2S/S X0
Input Point Loop Equivalent Circuit Wiring Loop
DC Type
DC Signal IN
SOURCE Mode
+24V
24G
S/S
X0
24VDC
SOURCE
+5V
+24V
24G
Source Type
X1 X2S/S X0
Practical Rela y Output Wiring
Surge absorbing diode: increases relay contact life
Emergency stop: use an external switch
Fuse: use the fuse with a 5~10A capacity at the common end of the output contact to protect the output circuit.
Surge absorber: reduces noise on AC inductive loads
Unused terminal: do not connect
DC supply
Indicator: neon indicator
AC supply
Incandescent lamp (resistive loading)
C0 Y0 Y1 C1 Y4 Y5 Y6 Y7
5
MC1
MC2
2
6
3
1
9
10
7
4
3
8
2
Mutually exclusive outputs: use external hardware interlocks, as well as those in the PLC program, for maximum safety.
Practical Transistor Output Wiring
DC supply
Emergency stop
Fuse for circuit protection
As all outputs of the transistor modules are Open Collectors, if the setting of Y0 is pulse train output (using PLSY command), its pull-up resistor must remain an output current of greater than 0.1A for normal operation of the transistor modules.
As all outputs of the transistor modules are Open Collectors, if the setting of Y1 is pulse train output (using PWM command), its pull-up resistor must remain an output current of greater than 0.1A for normal operation of the transistor modules.
Mutually exclusive outputs: use external hardware interlocks, as well as those in the PLC program, for maximum safety.
5
MC1
MC2
2
3
1
C0 Y0 Y1 C1 Y4 Y5 Y6 Y7
4
6 76
3
Unused terminal: do not connect
5 TRIAL RUN
Power Indication
1. The “POWER” LED at the front of the MPU or the Extension Units will be lit (in green) if the power is on. If the indicator is not on when the MPU is powered up, it means that there is abnormal condition on the DC power supply of the PLC. It is thus necessary to check the wiring on terminals +24V and 0V. If the ERROR LED is blinking swiftly, it indicates that the +24V power supply of the PLC is insufficient.
2. The “LOW V.” LED on the Expansion Unit is an indication that the input power voltage is insufficient, thus all outputs of the expansion unit should be turned off.
Operation and Test
1. If the ERROR LED of the MPU is not blinking, use the peripheral device to give the RUN command, and the
RUN indicator will then be on.
2. HPP could be utilized to monitor the timer (T), the counter (C) and the data register (D) during operation, and moreover, to force the output contacts to conduct the On/Off action. If the ERROR LED is on (but not blinking), it indicates that the setting of the user’s program has exceeded the preset overtime limit, thus users have to double check the program and perform the On/Off function again. (The PLC is at this moment back to STOP status automatically).
PLC Input/Output Reaction Time:
The total reaction time from the input signal to the output operation is calculated as follows: Reaction Time = input delay time + program scan time + output delay time
Input delay time
Default 10ms. Please refer to the usage of special registers D1020~D1021.
Program scan time
Please refer to the usage of special register D1010.
Output delay time
Relay module: 10ms. Transistor module: 20~30us.
6 TROUBLESHOOTING
udge the errors by the indicators on the front panel. When errors occurred on DVP series PLC, please check:
“POWER” LED
There is a “POWER” LED at the front of the MPU. The “POWER” LED will be lit (in green) when the power in connected to MPU. If the indicator is not on when the MPU is powered up and with the input power being normal, it indicates that the PLC is out of order. Please have this machine replaced or repaired at a distributor near you.
PLC “RUN” LED
Identify the status of the PLC. When the PLC is in operation, this light will be on, and the user could thus use HPP or the editing program of the ladder diagram to give commands to make the PLC “RUN” or “STOP”.
“ERROR” LED
If an incorrect program is input to the MPU, or the instruction and the device exceed the allowable range, the indicator will blink. At this moment, the user should check the error code saved in the MPU data register D1004 to correct the program. Find out the cause of the error and modify the programs. Then, re-send the correct program to the MPU.
If the ERROR LED is blinking swiftly, it suggests that the +24VDC power supply of the PLC is insufficient. Please check whether the power supply of 24VDC is normal or not.
When the ERROR LED is on (not blinking), it indicates that the execution time of the program loop has exceeded the time-out setting (set by D1000). Please check the program loop or use ”WDT” instruction to solve the problem. When the ERROR LED is on, please power down the MPU and start up it one time, and then check if the RUN LED is off. If the RUN LED is not off, please check if there is any noise and interference and check if any conductive material falling into the PLC.
“Input” LED
The On/Off signals of the input point could be displayed through the “Input” LED. Also, the status signal of the input point could be monitored through the device monitoring function of HPP. As long as the input point is activated, the LED is on. Therefore, if an error is detected, please check HPP, the LED indicator and the input signal circuits. Please pay particular attention to check if an electrical switch with significant leakage current is used as it often results in the unexpected operation of input point.
“Output” LED
Output LED indicates if the output signals are on or off. Please check the following items when the LED On/Off indication does not correspond to the commands:
1. Output contacts may be melted and stuck together due to a short circuit or current overload.
2. Check wiring and verify that the screws are tight and secure.