Data sheet
Actuators for three point control
AMV 25, AMV 35
Description
Ordering
AMV electric actuators are used with, VRB, VRG,
VF, VL valves with additional adapter
(Code No.
065Z0311, not supplied) and VFS 2 valves up to
DN 50 diameter.
Actuators
Typ e
AMV 25 230 082G3024
AMV 25 24 082G3023
AMV 35 230 082G3021
AMV 35 24 082G3020
Supply voltage
(VAC )
Code No.
The actuator automatically adapts its
stroke to valve end positions which reduces
commissioning time. Optional auxiliary switches,
feedback potentiometer and valve stem heater
are available.
The actuator has some special features:
• The advanced design incorporates load
related ‘switch-off’ to ensure that actuators
and valves are not exposed to overload;
• Digitale feedback end position indication
signal for valve end position is available by
terminal 4 or 5;
• Low weight and robust;
Main data:
• Nominal voltage:
- 24 VAC, 50 Hz/60 Hz
- 230 VAC, 50 Hz/60 Hz
• Control input signal:
3 point
• Force: 450 N
• Stroke: 15 mm
• Speed: 15 s /mm
• Max. medium temperature: 150 °C
• End-position signals
Accessories
Typ e Code No.
Additional switch (2×) 082H7015
Additional switch (2×)
and potentiometer (10 kΩ)
Additional switch (2×)
and potentiometer (1 kΩ)
Adapter for VFS 2 valves DN 15-50
(for media temp. over 150 °C)
Stem heater (for valves DN 15-50) 06 5B2171
Adapter for valves VRB/ VRG/VF/VL (2009)
DN 15-50
Clutch AMV(E) 25, AMV(E) 35
* Need to be orde red separately.
082 H7016
08 2H7017
065Z 7548
06 5Z03 11*
003G6396
Technical data
Typ e AMV 25 AMV 35
Power supply V 24 AC, 230 AC; +10 to –15 %
Power consumption VA 2 7
Frequency Hz 50/60
Control input 3-point
Closing force N 1000 600
Max. stroke mm 15
Speed by 50 Hz (60 Hz) s/mm 11 (8, 8) 3 (2,4)
Max. medium temperature
Ambient temperature 0 … 55
Storage and transport temperature –40 … 70
Grade of enclosure IP 54
Weight kg 1,55
- marking in accordance with standards
°C
150 (200 - with adapter or mounted horizontally)
Low Voltage Directive 73/23/EEC,
EMC-Directive 2006/95/EEC: EN 60730-1, EN 60730-2-14
© Danfoss | 2020.11 AI117586475830en-010903 | 1
Data sheet Actuators for three point control AMV 25, AMV 35
Installation
T
≤150°C for AMV 25, 35
max
and VRB, VRG, VF and VL
T
= 200°C for AMV 25, 35
max
and VFS
T
≤150°C for AMV 25, 35
max
and VFS
Adapter for VFS
(Code No.065Z7548)
o
≈5
Mechanical
Use 4 mm Allan key (not part of actuator
delivery) to mount actuator on the valve.
Installation of the valve with the actuator is
allowed in horizontal position or upwards.
Installation downwards is not allowed.
The actuator must not be installed in an
explosive atmosphere, at ambient temperature
lower than 0 °C or at ambient temperature higher
than 55 °C. It must not be subject to steam jets,
water jets or dripping liquid as well.
Note: the actuator may be rotated up to 360° with
respect to the valve stem by loosening the retaining
fixture. Once the actuator is placed, retighten the
fixture.
o
≈5
Electrical
Electrical connections can be accessed by
removing the actuator cover. Two cable gland
entries with thread (M20 x 1.5 and M16 x 1.5) are
prepared for cable glands.
Note: Cable and cable gland used must not
compromise the actuator’s IP rating, and must
ensure the connectors are fully strain relieved.
Please observe local rules and regulations as well.
Disposal The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
2 | AI117586475830en-010903 © Danfoss | 2020.11