Data sheet
Three point controlled actuator
AMV 150
DH-SMT/SI VD.KH.A1.02 © Danfoss 0 6/2006 1
Description AMV 150 is used together with seated valve VS2
(DN 15 only) or self-acting flow controller AVQM
(DN 15 only) in district heating systems or with
3-way seated valve VMV. The seated valves have
threads for motor fitting M30 x 1.5.
The actuator AMV 150 is available for the
Danfoss ECL or any other 3-point controls.
Main data:
• Speed 24 s/mm
• 24 Vac and 230 Vac
• Built-in manual operation
• Auxillary switches (AMV 150 AS)
• Supplied with 1.5 m cable
Application principles
Indirectly connected district heating system with heat exchanger
Direct-connected district heating system with mixing facility
2 VD.KH.A1.02 © Danfoss 0 6/2006 DH-SMT/SI
Data sheet Three point controlled actuator AMV 150
Ordering
Type
Supply voltage
(Vac)
Speed
(s/mm)
Code No.
AMV 150
24
24
082G3089
AMV 150 AS 082G3091
AMV 150
230
082G3090
AMV 150 AS 082G3092
Accessories
Type
Supply voltage
Lenght Code No.
Cable
24 Vac
5 m
082G3052
230 Vac 082G3053
Tehnical data
Power supply 24 Vac, 230 Vac; +10 to –15%
Power consumption 1 VA - 24 Vac, 8 VA - 230 Vac
Frequency 50 Hz / 60 Hz
Close of force 250 N
Stroke 5 mm
Speed 24 s/mm
Max. medium temperature inside the pipe 150 °C
Protection code IP 54
Ambient temperature 0 … 55 °C
Storage and transport temperature –40 … +70 °C
Weight 0.34 kg
- marking in accordance
with standards
EMC- Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN 61000-6-1 and EN 61000-6-3
Low Voltage Directive 73/23/EEC and 93/68/EEC, EN 60730-2-14
Mounting
Wiring
230 V
24 V
Disposal The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Each actuator is supplied with the connecting
cable for the controller.