Actuators for three point control AMV 130, AMV 140, AMV 130H, AMV 140H
DH-SMT/SI VD.KG.Y1.02 © Danf oss 06/2006 1
Description AMV 130/140 and AMV 130H/140H actuators are
used with VZ, VZL and VRBZ valves. The actuator can be used with fan coil units, induction units, small reheaters, recoolers and zone applications in which hot/cold water is the controlled medium.
Main data:
3-point versions
Force switch-off at stem down position
prevents overload of actuator and valve
No tools required for mounting
Maintenance free during lifetime
Low noise operation
Supplied with 1.5 m cable
Ordering
AMV 130H, AMV 140H
AMV 130, AMV 140
Type
Supply
voltage
Speed Code No.
AMV 130
24 V~
24 s/mm 082H8036
AMV 140 12 s/mm 082H8038
AMV 130H 24 s/mm 082H8040
AMV 140H 12 s/mm 082H8042
AMV 130
230 V~
24 s/mm 082H8037
AMV 140 12 s/mm 082H8039
AMV 130H 24 s/mm 082H8041
AMV 140H 12 s/mm 082H8043
Technical data
Type AMV 130, AMV 130H AMV 140, AMV 140H
Power supply 24 Vac, 230 Vac; +10 to –15%
Power consumption 1 VA - 24 Vac; 8 VA - 230 Vac
Frequency 50 Hz/60 Hz
Close of force 200 N
Stroke 5.5 mm
Speed 24 s/mm 12 s/mm
Max. medium temperature inside the pipe 130 °C
Ambient temperature 0 … 55 °C
Storage and transport temperature –40 … +70 °C
Protection code IP 42
Weight 0.3 kg
- marking in accordance with standards
EMC- Directive 89/336/EEC, 92/31/EEC, 93/68/EEC, EN 61000-6-1 and EN 61000-6-3 Low Voltage Directive 73/23/EEC and 93/68/EEC, EN 60730-2-14
Spare parts
Type
Code No.
Cable (5m) - 24 V
082H8052
Cable (5m) - 230 V
082H8053
2 VD.KG.Y1.02 © Danf oss 06/2006 DH-SMT/SI
Data sheet Actuators for three point control AMV 130, AMV 140, AMV 130H, AMV 140H
Installation Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.
The actuator is fixed to the valve body by means of a mounting ring which requires no tools for mounting. The ring should be tightened by hand.
Electrical
Important: It is strongly recommended that the mechanical installation is completed before the electrical installation.
Each actuator is supplied with the connecting cable for the controller.
Wiring
AMV 130/140, AMV 130H/140H - 230V
AMV 130/140, AMV 130H/140H - 24V
Commissioning The factory setting of the spindle is the fully
stem up position because of easier mechanical connection of the actuator on the valve.
Disposal The actuator must be dismantled and the
elements sorted into various material groups before disposal.