Danfoss AMI 120 NL-1 Operating guide

Operating Guide
AMI 120 NL-1
AMI 120 NL-1 / 73694420
Ste m Trav el 5 mm
Travel Speed 10 (12) s/mm
MAINTENANCE
FREE
no condensing
AMI 120 NL-1+
AB-QM
=
=
AUTO
4 – 6 mm × 1 mm
AQ315252253183en-010301 | 1© Danfoss | 2021.09
AMI 120 NL-1
F1
VAR1
VAR2
RM
D3
C3
D4
R3
IC1
C5
C6
CM
CMa
LED_UP
LED_DOWN
XS
3
4
2
11 33
4
2
11 33
4422
AMI 120 NL-1
SP
SN 4 1 5
(Oponal)
~ AC 24V 50/60Hz
Note: Direc tion of actuato r stem movement is def ined with jumper p osition. Look bot tom chapter "Travel Direction".
½”
(Oponal)
R5R5LED_UP
MOTOR
F1
VAR1
RM
CMa
CM
VAR2
D4
D3
C3
IC1
R3
C6
C5
R4R4LED_DOWN
113
2
XS
4
Jumper Position “A” (Factory Setting)
On” at terminal block position “1”: Actuator drives up and valve opens, optional terminal 4 closes.
Off” at terminal block position “1”: Actuator drives down and valve closes, optional terminal 5 closes.
4
2
Jumper Position “B”
On” at terminal block position “1”: Actuator drives down and valve closes, optional terminal 4 closes.
Off” at terminal block position “1”: Actuator drives up and valve opens, optional terminal 5 closes.
AMI 120 NL-1 +
AB-QM
AQ315252253183en-010301 2 | © Danfoss | 2021.09
AMI 120 NL-1
ENGLISH
Safety Notes
To avoid personal injury and damage to the device or other property, it is necessary to read and follow these
instructions carefully.
Assembly, start-up, and maintenance work must be performed by qualified and authorized personnel.
Comply with the instructions of the system manufacturer or system operator.
Do not remove the cover befo re the power supply is switche d off.
Mounting Position
The actuator should be mounted with the valve stem in either a horizontal position or pointing upwards.
Wiring
AC 24 V
Connect via Class 2 (Nor th America)
or Safety E xtra-Low Voltage (SELV) (Europe). Failure to comply can lead to equipment damage or personal injury.
· The Jumper is factory set in position “A”
With the jumper in position “A”, an “ON” command at position 1 of the terminal block will cause the actuator spindle to extend (valve closes). An “OFF” command will cause the spindle to retract (valve opens)
· Moving the jumper to position “B” will reverse the actuator’s action
With the jumper in position “B”, an “ON” command at position 1 of the terminal block will cause the actuator spindle to retract (valve opens). An “OFF” command will cause the spindle to extend (valve closes).
Installation
1. Check the valve neck. The actuator should
be in the full up position (factory setting). If it is not, refer to the manual override instructions and reposition the actuator to its full up position ❸①.
2. The actuator is fixed to the valve body by means of a ribbed nut which requires no tools for mounting. The ribbed nut should be hand tightened only.
Manual override
(for service purposes only)
Do not use the manual over ride if power is connected!
Switch off power be fore wiring the actuator!
1. Make all wiring connections in accordance with local, national, or regional regulations.
2. For applications requiring conduit, a field supplied 1/2” trade size electrician’s fitting and lock nut can be mounted in the actuator enclosure. Use flexible metallic tubing or its equivalent with the field supplied fitting.
3. Insert wiring material through the removable plug or conduit fitting, and connect to the terminal block using the applicable wiring diagram ❷.
4. Optionally, end position feedback is available on terminal 4 and terminal 5, which indicates actuator’s end position travel. Both contacts are normally open.
Jumper position setting
Do not remove the cover befo re the power supply is fu lly switched off.
- Remove cover
- Press and hold the button (on the bottom
side of the actuator) during manual override
- Replace cover
- Install actuator on valve
Remark:
A ‘click’ sound af ter energizing the actuator indicates that the gear wheel has jumped into normal position.
Don’t di smount the ac tuator from the valve whe n it is in a stem do wn position!
If dismounted in a stem down p osition, there is a high risk that the actuator g ets stuck.
© Danfoss | 2021.09 | 3AQ315252253183en-010301
AMI 120 NL-1
ІМПОРТЕР: UA: ТОВ з ІІ «Данфосс ТОВ», вул. Вікентія Хвойки, 15/15/6, м. Київ, 04080, Україна
73694420 / AQ315252253183en-0103014 | © Danfoss | DCS-S/SI | 2021.09