Data sheet Built-in function module AMES
Application
Ordering
Data
AMES is designed for modulating motor
voltage control via a controller. The control
voltage from the controller to AMES must be
within ranges 0 - 10 V or 0 - 20 mA.
Travel direction can be changed in relation to
rise of fall of control voltage.
Total control voltage ranges or partial ranges
and travel direction can be selected by
microswitches.
AMES
AMES incorporates a facility for override.
The built-in function module AMES is used
together with gearmotors AMV 323, 423 and
523.
Type Supply voltage Code nos.
AMES 24 V ~ 082B3328
AMES 230 V ~ 082B3329
Supply voltage 24V~ ± 10%
Frequency 50 Hz
Consumption 3 VA
Control signal input 0 - 10V DC
Enclosure IP 20
Ambient temperature Min 0 °C, max 50 °C
Transport and storage temperature Min –40 °C, max 70 °C
Weight 0.3 kg
- marking
in accordance with the standards
230/240 V~ +6%/–10%
0 - 5 V DC
5 - 10 V DC
0 - 20 mA
EMC-Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN 50081-1 and EN 50082-1
Low Voltage Directive 73/23/EEC and 93/68/EEC
BC-HM ED.95.B5.02 © Danfoss 4/96 1
Data sheet Built-in function module AMES
Wiring
Terminal 6, 7: Supply voltage.
Terminal 1, 2, 3, 4, 5: Supply voltage from AMES to AMV motor.
Terminal 10: 10 V output, max. 1 mA.
Terminal 12: Earth.
Terminal 40, 41: Control voltage input from controller. Input 40 has higher priority than input 41.
If control signal from connected controller is to be overridden, control signal
must be connected to terminal 40.
Setting microswitches
Wire lengths
0 - 50 m 0.75 0.4
> 100 m 1.5 0.75
Recommended wire-cross section Recommended wire-cross section
for 24 V systems for 230 V system
2 ED.95.B5.02 © Danfoss 4/96 BC-HM