Data sheet
Modulating controlled actuators
AME 10, AME 20, AME 30
AME 13, AME 23, AME 33 - with DIN EN 14597 certified safety function (spring down)
Description
AME 10 AME 13 AME 20, AME 30 AME 23, AME 33
Ordering
Actuators with safety function (AME 13, AME 23
or AME 33) and actuators without safety function
(AME 10, AME 20 or AME 30) are mainly used with
VS, VM, VB, AVQM and VMV (only with AME 10)
valves.
Safety version is activated automatically in
case of power failure or if the power supply is
switched off by the safety thermostat.
Actuators automatically adapt stroke to valve
end positions which reduces commissioning
time.
Actuators have some special features:
• The advanced design incorporates load
related ‘switch-off’ to ensure that actuators
and valves are not exposed to overload.
• Digital feedback end position indication
signal for valve end position is available by
terminal 4 or 5.
• Robust design and low weight.
• The advanced design incorporates a
diagnostic LED and operational data capture,
• DIN EN 14597 certified safety function
Actuators
Typ e Supply voltage Code No.
AME 10
AME 20 082G3015
AME 30 082G3017
24 V
082G3005
Main data:
• 24 Vac version
• Force:
- AME 10, 13 .....................300 N
- AME 20, 23, 30, 33 .......450 N
• Speed:
- AME 10, 13 .....................14 s/mm
- AME 20, 23 .................... 15 s/mm
- AME 30, 33 ....................3 s/mm
• Max. medium temperature:
- AME 10, 13 .....................130 °C
- AME 20, 23, 30, 33 .......150 ° C
• End-position signals
Note:
The use of AME ac tuators together with VS2 D N 15 is not
recommendab le. Linear characterist ics as in VS2 DN 15 valves is
not recommendable in DHW production.
© Danfoss | 2020.03
Actuators with safety function - EN 14597
Typ e Supply voltage Code No.
AM E 13
AME 23 082G3016
AME 33 082G3018
24 V
082G3006
AI170686478826en-000803 | 1
Data sheet AME 10/20/30/13/23/33
Technical data
Typ e AME 10 AM E 13 AME 20 AME 23 AM E 30 AME 33
Power supply Vac 24; +10 to –15 %
Power consumption VA 4 9 4 9 9 14
Frequency Hz 50/60
Safety function - yes - yes - yes
Number of spring return activations - 30.000 - 30.000 - 30.000
Safety function runtime
Control input Y
Output signal X Vdc 0-10 (2-10)
Closing force N 300 450
Max. stroke mm 7 10
Speed s/mm 14 15 3
Max. medium temperature
Ambient temperature 0 … 55
Storage and transport temperature –40 … 70
Ambient humidity 5-95 % r.h., non-condensing
Protection Class II I (230V); III(24V)
Grade of enclosure IP 54
Weight kg 0.6 0.8 1.45 1.5 1.45 1. 5
- marking in accordance with standards
7 mm stroke
10 mm stroke
s -
Vdc 0-10 (2-10) Ri = 24 kΩ
mA 0-20 (4-20) Ri = 500 Ω
°C
Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14
Electromagnetic Compatibilit y Directive (EMC) 2014/30/EU: EN 61000- 6-2,
EN 61000-6 -3
8.5
- 8 8
130 150
-
-
-
-
Safety function
Note: Do not use safet y activations for
ON/OFF regulation.
The safety function will fully open or close the
valve by power failure, depending upon the
chosen safety action (SD = safety down).
Valve selection will also affect the safety action.
The safety function unit is factory fitted to the
rear of the actuator.
Valve t ype
VS SD
VM (DN 15-50) SD
VB (DN 15-50) SD
AVQM (DN 15-50) SD
VMV - SD
1)
in compliance wit h DIN EN 14597
Safety action selection will
Close port A-AB Open port A-AB
1)
1)
1)
1)
-
-
-
-
or
SD
VS, VM, VB, AVQM
=
SD
SD
VMV
2 | AI170686478826en-000803
AME 13 AME 23, AME 33
© Danfoss | 2020.03
Data sheet AME 10/20/30/13/23/33
Installation
AME 10 AME 20, AME 30
AME 13 AME 23, AME 33
Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring, which requires no tools for
mounting. The ring should be tightened by
hand.
Disposal The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
Commissioning Commissioning / testing feature
Complete the mechanical and electrical
installation and perform the necessary checks
and tests:
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Note: Two cable entries are provided for M 16×1,5
cable glands. One entry is provided with a rubber
grommet. Note that in order to maintain the
enclosure’s IP rating, appropriate cable glands must
be used.
The actuator can be driven to the fully open or
closed positions (depending on valve type) by
connecting SN to terminals 1 or 3.
• Isolate control medium. (e.g. self-adjustment
in a steam application without suitable
mechanical isolation could cause a hazard).
• Apply the power. Note that the actuator will
now perform the self-adjustment procedure.
• Apply the appropriate control signal and
check the valve stem direction is correct for
the application.
• Ensure that the actuator drives the valve over
its full stroke, by applying the appropriate
control signal. This action will set the valve
stroke length.
© Danfoss | 2020.03
The unit is now fully commissioned.
AI170686478826en-000803 | 3