AME 10, AME 20, AME 30
AME 13, AME 23, AME 33 - with DIN EN 14597 certified safety function (spring down)
Description
AME 10 AME 13 AME 20, AME 30 AME 23, AME 33
Ordering
Actuators with safety function (AME 13, AME 23
or AME 33) and actuators without safety function
(AME 10, AME 20 or AME 30) are mainly used with
VS, VM, VB, AVQM and VMV (only with AME 10)
valves.
Safety version is activated automatically in
case of power failure or if the power supply is
switched off by the safety thermostat.
Actuators automatically adapt stroke to valve
end positions which reduces commissioning
time.
Actuators have some special features:
• The advanced design incorporates load
related ‘switch-off’ to ensure that actuators
and valves are not exposed to overload.
• Digital feedback end position indication
signal for valve end position is available by
terminal 4 or 5.
• Robust design and low weight.
• The advanced design incorporates a
diagnostic LED and operational data capture,
• DIN EN 14597 certified safety function
Actuators
Typ eSupply voltageCode No.
AME 10
AME 20082G3015
AME 30082G3017
24 V
082G3005
Main data:
• 24 Vac version
• Force:
- AME 10, 13 .....................300 N
- AME 20, 23, 30, 33 .......450 N
• Speed:
- AME 10, 13 .....................14 s/mm
- AME 20, 23 .................... 15 s/mm
- AME 30, 33 ....................3 s/mm
• Max. medium temperature:
- AME 10, 13 .....................130 °C
- AME 20, 23, 30, 33 .......150 ° C
• End-position signals
Note:
The use of AME ac tuators together with VS2 D N 15 is not
recommendab le. Linear characterist ics as in VS2 DN 15 valves is
not recommendable in DHW production.
Power supplyVac24; +10 to –15 %
Power consumptionVA4 94 9 914
FrequencyHz50/60
Safety function-yes-yes-yes
Number of spring return activations-30.000-30.000-30.000
Safety function runtime
Control input Y
Output signal XVdc0-10 (2-10)
Closing forceN300450
Max. strokemm710
Speeds/mm14153
Max. medium temperature
Ambient temperature0 … 55
Storage and transport temperature–40 … 70
Ambient humidity5-95 % r.h., non-condensing
Protection ClassIII (230V); III(24V)
Grade of enclosureIP 54
Weightkg0.60.81.451.51.451. 5
- marking in accordance with standards
7 mm stroke
10 mm stroke
s-
Vdc0-10 (2-10) Ri = 24 kΩ
mA0-20 (4-20) Ri = 500 Ω
°C
Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14
Electromagnetic Compatibilit y Directive (EMC) 2014/30/EU: EN 61000- 6-2,
EN 61000-6 -3
8.5
-88
130150
-
-
-
-
Safety function
Note: Do not use safet y activations for
ON/OFF regulation.
The safety function will fully open or close the
valve by power failure, depending upon the
chosen safety action (SD = safety down).
Valve selection will also affect the safety action.
The safety function unit is factory fitted to the
rear of the actuator.
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring, which requires no tools for
mounting. The ring should be tightened by
hand.
DisposalThe actuator must be dismantled and the
elements sorted into various material groups
before disposal.
CommissioningCommissioning / testing feature
Complete the mechanical and electrical
installation and perform the necessary checks
and tests:
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Note: Two cable entries are provided for M 16×1,5
cable glands. One entry is provided with a rubber
grommet. Note that in order to maintain the
enclosure’s IP rating, appropriate cable glands must
be used.
The actuator can be driven to the fully open or
closed positions (depending on valve type) by
connecting SN to terminals 1 or 3.
• Isolate control medium. (e.g. self-adjustment
in a steam application without suitable
mechanical isolation could cause a hazard).
• Apply the power. Note that the actuator will
now perform the self-adjustment procedure.
• Apply the appropriate control signal and
check the valve stem direction is correct for
the application.
• Ensure that the actuator drives the valve over
its full stroke, by applying the appropriate
control signal. This action will set the valve
stroke length.
The actuator has a selection of DIP switches
under the removable cover.
The switch provides the following functions:
DIP1: U/I - Input signal type selector:
• If set to OFF position, input signal Y is set to
voltage (Y).
If set to ON position, input signal Y is set to be
current (mA).
DIP2: 0/2 - Input signal range selector:
• If set to OFF position, the input signal is in the
range from 2 V to 10 V (voltage input) or from
4 mA to 20 mA (current input). If set to ON
position, the input signal is in the range from
0 V to 10 V (voltage input) or from 0 mA to 20
mA (current input).
DIP3: D/I - Direct or inverse acting selector:
• If set to OFF position, the actuator is direct
acting (actuator’s stem extends by voltage
increase). If actuator is set to ON position the
actuator is inverse acting (actuator’s stem
retracts by voltage increase).
DIP4: —/Seq - Normal or sequential mode
selector:
• Two actuators can be set to work parallel with
one control signal. If the SEQUENTIAL is set
than an actuator responds to split control
signal (see 0(2) V … 5(6 V) / 5(6) V … 10 V).
Note: This co mbination works in combin ation with DIP 5:
0(2) V … 5(6 V) / 5(6) V … 10 V
DIP5: 0-5 V/5-10 V - Input signal range in
sequential mode:
• This function is available if
DIP 4: --- / Sequential is set. Actuator can be
set to match the range of the control signal:
2 … 6 V (DIP 2: 2 V … 10)
0 … 5 V (DIP 2: 0 V … 10)
4 … 12 mA (DIP 2: 2 V … 10)
0 … 10 mA (DIP 2: 0 … 10)
OR
6 … 10 V (DIP 2: 2 V … 10)
5 … 10 V (DIP 2: 0 V … 10)
12 … 20 mA (DIP 2: 2 V … 10)
10 … 20 mA (DIP 2: 0 … 10)
DIP6: Prop./3-pnt - Modulating or 3-point
mode selector:
Actuator can operate in modulating (DIP 6
to OFF) or in “simple” 3-point mode, if the
3-point function is selected (DIP 6 to ON).
Modulating mode; DIP 6 set to OFF
(factory setting)
• After the actuator has been connected to
power supply, the actuator will start the
self-adjustment procedure. The indicator LED
flashes until self-adjustment is finished.
• Actuator’s stem will run to its totally extended
or retracted position by bridging SN signal
to terminals 1 or 3 and will remain in this
positron as long as potential is present.
It is not allowed to bridge SP to terminal 1
or 3 when DIP 6 is set to OFF.
3-point mode; DIP 6 set to On
Look carefully wiring diagrams as wiring is
different for controllers with triacs output
(ECL) in comparison to controllers with
relay output.
• Connect SN (Neutral) and power supply
(24Vac) via controller to terminals 1 or 3.
• Return signal X (depends on DIP 2, 3, 4 & 5) is
possible if connected power supply to SP and
SN.
DIP7: LOG/LIN - Not in use.
DIP8: 100 % KVS/Reduced KVS - Not in use.
DIP9: Reset:
• Changing this switch position will cause the
actuator to go through a self-adjustment
procedure.
Actuator needs to perform
Self-adjustment prior changing
DIP 6 to ON.
Output signa l depends on DIP 2, 3&5
setting.
DIP 6 = OFF
DIP 6 = ON
Wiring for modulating mode
SN0 VNeutral
SP24 VacPower supply
Y
1
3
X0(2)-10 VdcOutput
0(2)-10 Vdc
0(4) -20 mA
SNInput
Wiring for 3-point floating mode / Controller with relay output
SN0 VNeutral
SP24 VacPower supply
1
SPInput
3
Input
* Only for ac tuators with safety fun ction
* Only for ac tuators with safety fun ction
**R1, **R2=2.6 kΩ (0. 5W)
DIP 6 = ON
X0(2)-10 VdcOutput
Wiring for 3-point floating mode / Controller with triacs output
SN 0 VNeutral
SP24 VacPower supply
1
SPInput
3
X0(2)-10 VdcOutput
6 | AI170686478826en-000803
Automatic self-adjustment feature
When power is first applied, the actuator will
automatically adjust to the length of the valve
stroke. Subsequently, the self-adjustment feature
can be re-initialised by changing position of SW9.
Wiring length
0-50 m0.75 mm
> 50 m1. 5 mm
Recommended
square of the wiring
2
2
Diagnostic LED
The red diagnostic LED is located on the pcb
under the cover. It provides indication of three
operational states:
• Actuator Healthy (Permanently ON),
• Self Stroking (Flashes once per second),
• Error (Flashes 3 times per second - seek
technical assistance).
* The use of AME ac tuators together with VS2 DN 15 is not recomm endable. Linear chara cteristics as in VS2 DN 15 valves is not
recommendable in DHW production.