Danfoss AME 10, AME 20 y AME 30, AME 13, AME 23, AME 33 Data sheet

Data sheet
Modulating controlled actuators
AME 10, AME 20, AME 30 AME 13, AME 23, AME 33 - with DIN EN 14597 certified safety function (spring down)
Description
AME 10 AME 13 AME 20, AME 30 AME 23, AME 33
Ordering
Actuators with safety function (AME 13, AME 23 or AME 33) and actuators without safety function (AME 10, AME 20 or AME 30) are mainly used with VS, VM, VB, AVQM and VMV (only with AME 10) valves. Safety version is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat. Actuators automatically adapt stroke to valve end positions which reduces commissioning time.
Actuators have some special features:
• The advanced design incorporates load related ‘switch-off’ to ensure that actuators and valves are not exposed to overload.
• Digital feedback end position indication signal for valve end position is available by terminal 4 or 5.
• Robust design and low weight.
• The advanced design incorporates a diagnostic LED and operational data capture,
• DIN EN 14597 certified safety function
Actuators
Typ e Supply voltage Code No.
AME 10 AME 20 082G3015 AME 30 082G3017
24 V
082G3005
Main data:
• 24 Vac version
• Force:
- AME 10, 13 .....................300 N
- AME 20, 23, 30, 33 .......450 N
• Speed:
- AME 10, 13 .....................14 s/mm
- AME 20, 23 .................... 15 s/mm
- AME 30, 33 ....................3 s/mm
• Max. medium temperature:
- AME 10, 13 .....................130 °C
- AME 20, 23, 30, 33 .......150 ° C
• End-position signals
Note:
The use of AME ac tuators together with VS2 D N 15 is not recommendab le. Linear characterist ics as in VS2 DN 15 valves is not recommendable in DHW production.
© Danfoss | 2020.03
Actuators with safety function - EN 14597
Typ e Supply voltage Code No.
AM E 13 AME 23 082G3016 AME 33 082G3018
24 V
082G3006
AI170686478826en-000803 | 1
Data sheet AME 10/20/30/13/23/33
Technical data
Typ e AME 10 AM E 13 AME 20 AME 23 AM E 30 AME 33
Power supply Vac 24; +10 to –15 % Power consumption VA 4 9 4 9 9 14 Frequency Hz 50/60 Safety function - yes - yes - yes Number of spring return activations - 30.000 - 30.000 - 30.000
Safety function runtime
Control input Y
Output signal X Vdc 0-10 (2-10) Closing force N 300 450 Max. stroke mm 7 10 Speed s/mm 14 15 3 Max. medium temperature Ambient temperature 0 … 55 Storage and transport temperature –40 … 70 Ambient humidity 5-95 % r.h., non-condensing Protection Class II I (230V); III(24V) Grade of enclosure IP 54 Weight kg 0.6 0.8 1.45 1.5 1.45 1. 5
- marking in accordance with standards
7 mm stroke
10 mm stroke
s -
Vdc 0-10 (2-10) Ri = 24 kΩ mA 0-20 (4-20) Ri = 500 Ω
°C
Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14 Electromagnetic Compatibilit y Directive (EMC) 2014/30/EU: EN 61000- 6-2, EN 61000-6 -3
8.5
- 8 8
130 150
-
-
-
-
Safety function
Note: Do not use safet y activations for
ON/OFF regulation.
The safety function will fully open or close the valve by power failure, depending upon the chosen safety action (SD = safety down). Valve selection will also affect the safety action. The safety function unit is factory fitted to the rear of the actuator.
Valve t ype
VS SD VM (DN 15-50) SD VB (DN 15-50) SD AVQM (DN 15-50) SD VMV - SD
1)
in compliance wit h DIN EN 14597
Safety action selection will
Close port A-AB Open port A-AB
1)
1)
1)
1)
-
-
-
-
or
SD
VS, VM, VB, AVQM
=
SD
SD
VMV
2 | AI170686478826en-000803
AME 13 AME 23, AME 33
© Danfoss | 2020.03
Data sheet AME 10/20/30/13/23/33
Installation
AME 10 AME 20, AME 30
AME 13 AME 23, AME 33
Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.
The actuator is fixed to the valve body by means of a mounting ring, which requires no tools for mounting. The ring should be tightened by hand.
Disposal The actuator must be dismantled and the
elements sorted into various material groups before disposal.
Commissioning Commissioning / testing feature
Complete the mechanical and electrical installation and perform the necessary checks and tests:
Electrical
Important: It is strongly recommended that the mechanical installation is completed before the electrical installation.
Note: Two cable entries are provided for M 16×1,5 cable glands. One entry is provided with a rubber grommet. Note that in order to maintain the enclosure’s IP rating, appropriate cable glands must be used.
The actuator can be driven to the fully open or closed positions (depending on valve type) by connecting SN to terminals 1 or 3.
• Isolate control medium. (e.g. self-adjustment in a steam application without suitable mechanical isolation could cause a hazard).
• Apply the power. Note that the actuator will now perform the self-adjustment procedure.
• Apply the appropriate control signal and check the valve stem direction is correct for the application.
• Ensure that the actuator drives the valve over its full stroke, by applying the appropriate control signal. This action will set the valve stroke length.
© Danfoss | 2020.03
The unit is now fully commissioned.