READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
The original instructions are written in English. All other languages
are translations of the original instructions.
This appliance is not intended for use by persons, including children,
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person
responsible for their safety.
Children should be supervised to ensure that they do not play with
the appliance.
INTRODUCTION
This operation manual concerns packaged air-cooled water chillers
of the Daikin EWAQ-DAYN series. These units are provided for
outdoor installation and used for cooling applications. The EWAQ
units can be combined with Daikin fan coil units or air handling units
for air conditioning purposes. They can also be used for supplying
water for process cooling.
This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local Daikin dealer.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Checks before initial
start-up" on page 7.
Operation manual
1
(1) Refer to the engineering data book for the complete list of specifications.
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 3
General EWAQ240260
Dimensions HxWxD
(mm)
2311x2000x4850
Weight
•machine weight
• operation weight
(kg)
31503250
(kg)
31893292
Connections
• chilled water inlet and outlet
•evaporator drain
3"3"
1/2"G1/2"G
Internal water volume(l)3942
Expansion vessel (only for
OPSP, OPTP and OPHP)
•volume
• pre-pressure
Safety valve
water circuit
(bar)
(bar)
(l)
5050
1.51.5
3.03.0
Pump (only for OPSP)
• type
•model (standard)
Ver tical in-line pump
TP 65-260/2TP 65-260/2
Compressor
Type
Qty x model
Speed
(rpm)
semi-hermetic scroll
compressor
2x SJ240-4 +
2x SJ300-4
29002900
4x SJ300-4
Oil typeFVC68DFVC68D
(l)
Oil charge volume
Condenser
Nominal air flow(m
2x 6.2 +
2x 6.2
3
/min)16001600
4x 6.2
No. of motors x output(W)8x 6008x 600
Evaporator
ModelDV58DV58
Electrical specifications
(1)
EWAQ080100130150
Power supplyYN
• Phase
•Frequency
•Voltage
•Voltage tolerance
(Hz)
(V)
(%)
3~
50
400
±10
Unit
• Nominal running current (A)
•Maximum running current (A)
• Recommended fuses
according to IEC 269-2
607288113
96120160177
(A)
3x 125 gL 3x 160 gL 3x 200 gL 3x 200 gL
Compressor
• Circuit 1
Circuit 2
• Phase
•Frequency
•Voltage
• Nominal running current
Circuit 1
Circuit 2
15 + 15—20 + 20—13 + 13
(hp)
(Hz)
(V)
(A)
39 + 39—51 + 51—35 + 35
(A)
13 + 13
3~
50
400
35 + 35
15 + 15
15 + 15
39 + 39
39 + 39
(hp)
Control and fan motor
• Phase
•Frequency
•Voltage
•Maximum running current (A)
(Hz)
(V)
4x 1.54x 1.54x 1.64x 2.3
1~
50
230 V
Pump
•Power
• Nominal running current (A)
(kW)
2.22.233
4.54.56.36.3
Heater tape(OP10)
• Supply voltage
•Power (standard)
(OPSP)
(OPBT)
• Optional field heater
• Recommended fuses
(V)
230 V ±10%
1x 300 W
2x 300 W
2x 300 W + 150 W
maximum 1 kW
(A)
2x 10
EWAQ180210240260
Power supplyYN
• Phase
•Frequency
•Voltage
•Voltage tolerance
(Hz)
(V)
(%)
3~
50
400
±10
Unit
• Nominal running current (A)
• Maximum running current (A)
• Recommended fuses
according to IEC 269-2
131144162181
209233262290
(A)
3x 250 gL 3x 250 gL 3x 300 gL 3x 355 gL
Compressor
• Circuit 1
Circuit 2
• Phase
•Frequency
•Voltage
• Nominal running current
Circuit 1
Circuit 2
(hp)
(Hz)
20 + 15
20 + 15
(V)
(A)
51 + 39
(A)
51 + 39
20 + 20
20 + 20
51 + 51
51 + 51
3~
50
400
25 + 20
25 + 20
65 + 51
65 + 51
25 + 25
25 + 25
65 + 65
65 + 65
(hp)
Control and fan motor
• Phase
•Frequency
•Voltage
• Maximum running current (A)
(Hz)
(V)
6x 2.36x 2.38x 1.68x 1.6
1~
50
230 V
Pump
•Power
• Nominal running current (A)
(kW)
4444
8.08.08.08.0
Heater tape(OP10)
• Supply voltage
•Power (standard)
(OPSP)
(OPBT)
• Optional field heater
• Recommended fuses
(V)
230 V ±10%
1x 300 W
2x 300 W
2x 300 W + 150 W
maximum 1 kW
(A)
2x 10
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
2
Page 4
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Refrigerant type:R410A
(1)
GWP
value:1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more
information.
DESCRIPTION
The EWAQ air-cooled water chillers are available in 8 standard sizes.
9Chilled water out (Victaulic
10Water drain evaporator23Fan39Eyebolt (for lifting the unit)
11Air purge24Safety valve
12Leaving water temperature sensor
As the refrigerant circulates through the unit, changes in its state or
condition occur. These changes are caused by the following main
components:
■Compressor
The compressor (M*C) acts as a pump and circulates the refrigerant in the refrigeration circuit. It compresses the refrigerant
vapour coming from the evaporator at the pressure at which it
can easily be liquefied in the condenser.
■Condenser
The function of the condenser is to change the state of the
20Service port30Filter
relief valve (B)
■Filter/drier
The filter installed behind the condenser removes small particles
from the refrigerant to prevent damage to the compressor and
expansion valve.
The drier takes the water out of the system.
■Expansion valve
The liquid refrigerant coming from the condenser enters the
evaporator via an expansion valve. The expansion valve brings
the liquid refrigerant to a pressure at which it can easily be
evaporated in the evaporator.
refrigerant from gaseous to liquid. The heat gained by the gas in
the evaporator is discharged through the condenser to the
ambient air, and the vapour condenses to liquid.
3
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
4
Page 6
■Evaporator
The main function of the evaporator is to take heat from the
water that flows through it. This is done by turning the liquid
refrigerant, coming from the condenser, into gaseous
refrigerant.
■Water in/outlet connection
The water inlet and outlet connection allow an easy connection
of the unit to the water circuit of the air handling unit or industrial
equipment.
Safety devices
The unit is equipped with three kinds of safety device:
1General safety devices
General safety devices shut down all circuits and stop the whole
unit. For this reason the unit has to be manually put on again
after a general safety occurred.
2Circuit safety devices
Circuit safety devices shut down the circuit they protect, while
the other circuits remain activated.
3Part safety devices
Part safety devices shut down the part they protect.
An overview of all safety devices is given below.
■Overcurrent relays
■ Overcurrent relay for compressors (only for SJ161-4) (circuit
safety device)
The overcurrent relay protects the compressor motor in case of
overload, phase failure or too low voltage.
■ Overcurrent relay for fans (part safety device)
The overcurrent relay protects the fan motors in case of overload,
phase failure or too low voltage.
■ Overcurrent relay for pump (general safety device)
The overcurrent relay protects the pump in case of overload,
phase failure or too low voltage.
When activated, the overcurrent relays have to be reset in the
switch box and the controller needs to be reset manually.
The overcurrent relays are factory set and may not be
adjusted.
■Compressor SJ161-4 thermal protector (part safety devices)
Compressor SJ161-4 is equipped with an internal overload
motor protection to protect the unit against excessive current
and temperature caused by overloading, low refrigerant flow or
phase loss. The compressor will shut down and will
automatically restart when temperature returns to normal. This
is not detected by the controller.
■Compressor SJ180-4 electronic protection module (circuit safety
device)
Compressor SJ180-4 is equipped with an electronic protection
module to provide for efficient and reliable protection against
overheating, overloading, and phase loss. The controller will
detect the shut down of the compressor. The controller needs to
be reset manually. The compressor is internally protected
against reverse phase.
■Compressors SJ240-4 and SJ300-4 electronic protection
modules (circuit safety device)
Compressors SJ240-4 and SJ300-4 are equipped with an
electronic protection module to provide for efficient and reliable
protection against overheating, overloading, phase loss and
phase reversal. The controller will detect the shut down of the
compressor. The controller needs to be reset manually.
■Reverse phase protector (general safety device)
The reverse phase protectors prevent the unit from being
operated in reverse phase. If the unit does not start, two phases
of the power supply must be inverted.
■Flowswitch (general safety devices)
The unit is protected by a flowswitch (S1L).
When the water flow becomes lower than the minimum allowed
water flow, the flowswitch shuts down the unit. When the water
flow becomes normal, the protection resets automatically but the
controller still needs to be reset manually.
■Discharge thermal protectors (circuit safety devices)
The unit is equipped with discharge thermal protectors (R*T).
The protectors are activated when the temperature of the
refrigerant leaving the compressor becomes too high. When the
temperature returns to normal the controller needs to be reset
manually.
■Freeze-up protection (general safety devices)
The freeze-up protection prevents the water in the evaporator
from freezing during operation.
■ When the outlet water temperature is too low, the controller
shuts down the compressors. When the outlet water
temperature returns to normal, the controller resets
automatically.
■ When the refrigerant temperature is too low, the controller
shuts down the unit. When the refrigerant temperature
returns to normal, the controller needs to be reset manually.
■Low pressure safety (circuit safety devices)
When the suction pressure of a circuit is too low, the circuit
controller shuts down the circuit. When the pressure returns to
normal, the safety device can be reset on the controller.
■Pressure relief safety valve (general safety devices)
The safety valve is activated when the pressure in the refrigerant
circuit becomes too high. If this occurs, shut down the unit and
contact your local dealer.
■High pressure setback (circuit safety device)
The high pressure setback prevents the high pressure to
become too high so that high pressure switch is activated.
When the high pressure is too high, the controller shuts down
the compressor. When the pressure returns to normal, the
controller resets automatically.
■High pressure switch (circuit safety devices)
Each circuit is protected by a high pressure switch (S*PH) which
measures the condenser pressure (pressure at the outlet of the
compressor).
When the pressure becomes too high, the pressure switch is
activated and the circuit stops.
When the pressure becomes normal again, the protection resets
automatically but the controller still needs to be reset manually.
The switch is factory-set and may not be adjusted.
Operation manual
5
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 7
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:
A01P...................... PCB extension
A02P.............**...... PCB communication (only for option EKACPG)
Check that the air inlet and outlet of the unit is not obstructed by
paper sheets, cardboard, or any other material.
11 Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage should correspond to the voltage on the identification
label of the unit.
12 Water connection
Check water piping system and circulating pumps.
Water supply
Fill the water piping, taking into account the minimum water volume
required by the unit. Refer to the "installation manual".
Make sure that the water is of the quality as mentioned in the
installation manual.
Purge the air at the high points of the system and check the operation
of the circulation pump and the flowswitch.
BEFOREOPERATION
Checks before initial start-up
Make sure that the circuit breaker on the power supply
panel of the unit is switched off.
After the installation of the unit, check the following before switching
on the circuit breaker:
1Field wiring
Make sure that the field wiring between the local supply panel
and the unit has been carried out according to the instructions
described in the installation manual, according to the wiring
diagrams and according to European and national regulations.
2Fuses or protection devices
Check that the fuses or the locally installed protection devices
are of the size and type specified in the installation manual.
Make sure that neither a fuse nor a protection device has been
bypassed.
3Earth wiring
Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.
4Internal wiring
Visually check the switch box for loose connections or damaged
electrical components.
5Fixation
Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.
6Damaged equipment
Check the inside of the unit for damaged components or
squeezed pipes.
7Refrigerant leak
Check the inside of the unit for refrigerant leakage. If there is a
refrigerant leak, call your local dealer.
8Oil leak
Check the compressor for oil leakage. If there is an oil leak, call
your local dealer.
Power supply connection and crankcase heating
In order to avoid compressor damage, it is necessary to
switch on the crankcase heater for at least 6 hours before
starting the compressor after a long period of standstill.
To switch on the crankcase heater proceed as follows:
1Switch on the circuit breaker on the local supply panel. Make
sure that the unit is "OFF".
2The crankcase heater is switched on automatically.
3Check the supply voltage on the supply terminals L1, L2, L3 by
means of a voltmeter. The voltage must correspond to the
voltage indicated on the identification label of the unit. If the
voltmeter reads values which are not within the ranges specified
in the technical data, check the field wiring and replace the
supply cables if necessary.
4Check if the crankcase heaters are warming up.
After 6 hours, the unit is ready for operation.
General recommendations
Before switching on the unit, read following recommendations:
1When the complete installation and all necessary settings have
been carried out, close all service panels of the unit.
2The service panels of the switch boxes may only be opened by a
licensed electrician for maintenance purposes.
3When accessibility to the digital controller is frequently
necessary, install an optional digital remote controller
(EKRUPG).
4To prevent the evaporator from freezing (when OP10 is installed)
and to avoid damage to the LCD displays of the digital controller,
never switch off the power supply during winter.
9Stop valves
Open the liquid line, discharge and suction stop valves (if
provided) completely.
Operation manual
7
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 9
OPERATION
Connection of a remote digital controller to the unit
The EWAQ units are equipped with a digital controller (located
behind the service panel) offering a user-friendly way to set up, use
and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart
from the first section, which gives a brief description of the controller
itself, each section or subsection deals with a specific task you can
perform with the unit.
Depending on the unit there are one or two cooling circuits in the
system. The units EWAQ130~260 exist out of two circuits, whereas
the units EWAQ080+100 only have one circuit. These circuits are
generally named C1 and C2 in the following descriptions. So all
information about circuit 2 (C2) is not applicable for EWAQ080+100
units.
Digital controller
User interface
The digital controller consists of an alphanumeric display, labelled
keys which you can press and a number of LEDs.
■Digital controller and digital remote controller (EKRUPG)
Figure - Digital (remote) controller
œkey, to start up or to shut down the unit.
πkey, to enter the safeties menu or to reset an alarm.
ƒkey, to enter the main menu
keys, to scroll up or down through the screens of a menu
fi
(only in case ^, v or ÷ appears) or to raise, respectively
Ì
lower a setting.
‡key, to confirm a selection or a setting.
NOTE
Temperature readout tolerance: ±1°C.
Legibility of the alphanumeric display may decrease in
direct sunlight.
How to enter a menu
Scroll through the main menu using the fi and Ì keys to go to the
menu of your choice. Push the ‡ key to enter the selected menu.
Menu
ªÒµ®
†Úæ∂Ï
Readout menu
Setpoints menu
Usersettings menu
Timers menu
History menu
Info menu
I/O status menu
Login/logout menu
Network menu
Cool/heat menu
■Access to the setpoints menu (∑) and the usersettings menu
(Å) is protected by a password, refer to "Changing the user
password" on page 19.
■The cool/heat menu is not available for EWAQ units.
Not
selected Selected
=
º
=
Ò
=
Â
=
µ
=
®
=
†
=
Ú
=
æ
=
∂
=
Ï
ª
∑
Å
Ó
‚
™
Ÿ
Æ
∆
Í
For a remote digital controller a cable length of up to 500 metres
between the remote digital controller and the unit is allowed. This
gives the opportunity to control the unit from a considerable distance.
Refer to "Cable for remote digital controller" in the installation manual
for cable specifications.
These restrictions are the same for units in a DICN configuration.
NOTE
When a remote digital controller is connected to a
stand-alone unit, the address of the remote digital
controller has to be set to SUB by means of the DIPswitches on the back of the remote digital controller.
Refer to the installation manual "Setting the addresses
on the remote digital controller" for setting the address.
Working with the unit
This chapter deals with the everyday usage of the unit. Here, you will
find how to perform routine tasks, such as:
■"Setting the language" on page 8
■"Switching the unit on" on page 8
■"Consulting actual operational information" on page 9
■"Adjusting the temperature setpoint" on page 10
■"Resetting the unit" on page 10
Setting the language
If desired, the operating language can be changed to any of the
following languages: English, German, French, Spanish or Italian.
1Enter the Å usersettings menu. Refer to chapter "How to enter
a menu" on page 8.
2Go to the Language submenu of the Å usersettings menu using
the fi and Ì keys and press the ‡ key to enter.
3Press ‡ to change the operating language until the desired
language is active.
The controller is factory set to English.
Switching the unit on
1Press the œ key on the controller.
NOTE
Depending on whether or not a remote ON/OFF switch has
been configured (refer to the installation manual), the following
conditions may occur.
When no remote ON/OFF switch is configured, the LED inside
the œ key lights up and an initialization cycle is started. Once all
the timers have reached zero, the unit starts up.
When a remote ON/OFF switch is configured, the following table
applies:
Local key
2If the water chiller does not start after a few minutes, refer to
"Troubleshooting" on page 19.
If the password protection is set to ON, the correct
password has to be given before any further
action is possible.
Remote
ON/OFF switch
ONONONON
ONOFFOFFFlashing
OFFONOFFOFF
OFFOFFOFFOFF
Unit
œ LED
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
8
Page 10
Switching the unit off
If no remote on/off switch is configured:
Press the œ key on the controller.
The LED inside the œ key goes out.
If a remote on/off switch is configured:
Press the œ key on the controller or switch the unit off using the
remote on/off switch.
The LED inside the œ key goes out in the first case and starts
blinking in the second case.
NOTE
Also consult "Customization in the service menu"
chapter "Setting of the changeable inputs and outputs"
in the installation manual.
Switching units ON/OFF in a DICN system
If the œ key is pressed on a unit with status
other units with status
NORMAL
or
STANDBY
If the œ key is pressed on a unit with status
only this unit will be ON or OFF.
NOTE
When a remote ON/OFF switch is configured, the
remote ON/OFF contact for all units with status
NORMAL
or
STANDBY
of a DICN network is the contact
connected to the master unit.
For units with status
remote contact is the contact connected to this unit.
NOTE
If the user wants 1 unit to operate on his command
only, this unit is to be set to
It is recommended not to select the master unit for this
purpose. Even if the status of the master is set to
DISCONNECT ON/OFF
connected to the master which will switch ON/OFF the
other units in
NORMAL
therefore never be possible to only switch the master
unit OFF remotely.
Switching OFF the master unit only, should in this case
be done by the local ON/OFF key on the master unit.
NORMAL
or
STANDBY
will be ON or OFF.
DISCONNECT ON/OFF
DISCONNECT ON/OFF
DISCONNECT ON/OFF
, the
.
, it will still be the contact
or
STANDBY
mode. It would
, all
Consulting actual operational information
1Enter the readout menu. Refer to the chapter "How to enter a
menu" on page 8.
The controller automatically shows the first screen of the
readout menu which provides the following information:
_v¶¡
… ≤0U4
∞11 ∞12 ≠H 012$0¢
∞21 ∞22 ≠H
• ¶cooling mode
•
§heating mode
≠fan (H high or L low)
•
•
¡low noise mode activated (only available when option
•
…pump on
•
…1/2in case of dual pump control: pump 1/2 on
•
∞11/12 circuit 1 compressor 1/2 on
•
∞21/22 circuit 2 compressor 1/2 on
•
≤alarm and last occured malfunction code (
•
13$6¢actual temperature (inlet or outlet temperature
•
12$0¢temperature setpoint (inlet or outlet temperature
013$6¢
OPIF is installed)
example)
depending on active mode)
depending on active mode)
0U4
in
2Press the Ì key to enter the next screen of the readout menu.
•
MANUAL MODE
manual/automatic control mode operation. If the automatic
control mode is selected, the controller will indicate the active
temperature setpoint. Depending on the status of the remote
contact, setpoint one or setpoint two is active.
INL WATER
•
•
OUTL WATER
•
AMBIENT
NOTE
For a DICN system, the
WATER
or
COOL INLSP1/2
: actual inlet water temperature.
: actual outlet water temperature.
: actual ambient temperature.
or
COOL OUTLSP1/2
INLET WATER
values are the values of the individual units,
not of the system. Temperatures of the system can be
consulted in the first screen of the network menu.
3Press the Ì key to enter the next screen of the readout menu.
The
TEMPERATURE
screen of the readout menu provides
information concerning the discharge temperature of the
compressors (
4Press the Ì key to enter the next screen of the readout menu.
,
The C1/
C11
and
C12/C21
C2 TEMP. READOUT
and
screen of the readout menu
C22
).
provides information concerning the refrigerant temperature
REFR
) of circuit 1/circuit 2.
(
5Press the Ì key to enter the next screen of the readout menu.
The
ACT. PRESSURES
screen of the readout menu provides
information concerning the actual pressures of circuit.
■
HP1/2
: high pressure of the refrigerant in circuit 1/2. The first
number stands for the pressure in bar, the second number
stands for the bubble point saturation temperature in degrees
Celsius.
■
LP1/2
: low pressure of the refrigerant in circuit 1/2. The first
number stands for the pressure in bar, the second number
stands for the dew point saturation temperature in degrees
Celsius.
■
LOWNOISE
: at the bottom of the first screen, the status of the
lownoise setting is shown (Y=active or N=not active).
6Press the Ì key to enter the next screen of the readout menu.
The
UNIT STATUS
screen of the readout menu provides
information concerning the status of the different circuits.
•
C11
and
C12
: actual status of circuit 1 (ON or
•
C21
and
C22
: actual status of circuit 2 (ON or
When the unit is on and a circuit is
OFF
, the following status
information may appear.
•
SAFETY ACT.
(refer to "Troubleshooting" on page 19).
•
FREEZEUP DIS
disable function.
•
FREEZEUP PR
•
HP SETBACK
•
MIN.RUN.TIM
active.
•
LIMIT
: the compressor is limited by the limitation function.
•
STANDBY DICN
stand by mode because there is sufficient current capacity to
maintain set point.
UNIT OFF
•
•
AREC INLET
water temperature has not risen enough compared to previous
switch off of the compressor.
FREE COOLING
•
•
TIMER BUSY
is not zero (refer to "Timers menu Ó" on page 12).
•
PUMPLEAD TIM
as the pump lead timer is counting down.
NO FLOW
•
mode.
•
NO PRIORITY
no priority. Refer to "Defining the lead-lag settings" on page 15 for
adjusting the priority.
: one of the circuit safety devices is activated
: the compressor is disabled by the freeze-up
: freeze-up prevention is active.
: high pressure setback is active.
: minimum running time of the compressor is
: when in a DICN configuration, the unit is in
: the unit is switched off.
: the compressor will not start up when the inlet
: free cooling mode is active
: the actual value of one of the compressor timers
: the compressor will wait to start up for as long
: there is no flow after pumplead, the unit is in stand-by
: This compressor will not start up because it has
and
OFF
OFF
:
OUTLET
).
).
Operation manual
9
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 11
•
CAN STARTUP
cooling load is needed.
• When none of the above mentioned messages appears, no
special functions are active and the compressor is running.
: the circuit is ready to start up when extra
The preceding messages are written down in order of priority.
The
UNIT CAPACITY
is written down on the bottom of the first
screen.
7Press the Ì key to enter the next screen of the readout menu.
The
EXTRA READOUT
screens of the readout menu are
providing the following information:
•
CURRENT
OP57 is installed)
•
VOLTAGE
•
RH11/12/21/22
•
CS11/12/21/22
•
RHP1/2
: actual current, measured in Ampere (A) (only when
: actual voltage (V) (only when OP57 is installed)
: actual running hours (h)
: number of compressor start-ups
: actual running hours (h) of the pump 1 or 2
8Press the fi key to return to the other readout menus.
Adjusting the temperature setpoint
The unit provides definition and selection of four independent
temperature setpoints. Two setpoints are reserved for inlet control,
the other two are reserved for outlet control.
■
COOL. INLSP1
■
COOL. INLSP2
■
COOL. OUTSP1
■
COOL. OUTSP2
The selection between setpoint 1 and 2 is done by a remote dual
setpoint switch (to be installed by the customer). The actual active
setpoint can be consulted in the readout menu.
NOTE
The customer is also allowed to define a setpoint in
function of an analogue input.
NOTE
Refer to "Customization in the service menu" chapter
"Setting of the changeable inputs and outputs" in the
installation manual
If the manual control mode is selected (refer to "Usersettings menu
Å" on page 11), none of the above-mentioned setpoints will be
active.
To adjust a setpoint, proceed as follows:
1Enter the setpoints menu. Refer to the chapter "How to enter a
menu" on page 8.
If the user password is disabled for setpoint modifications (refer
to "Usersettings menu Å" on page 11), the controller will
immediately enter the setpoints menu.
If the user password is enabled for setpoint modifications, enter
the correct code using the fi and Ì keys (refer to "User
password menu Æ" on page 14). Press ‡ to confirm the
password and to enter the setpoints menu.
2Select the setpoint to be adjusted using the ‡ key.
A setpoint is selected when the cursor is blinking behind the
setpoint's name.
>
" sign indicates the actual active temperature setpoint.
The "
3Press the fi and Ì keys to adjust the temperature setting.
The default, limit and step values for the cooling temperature
setpoints are:
default value
limit values
step value
(*) For glycol treated units with OPZH installed, the lower limit of the cooling
temperature setpoint can be adapted by changing the minimum operating
temperature in the service menu (refer to the installation manual).
: inlet water temperature, setpoint 1,
: inlet water temperature, setpoint 2.
: outlet water temperature, setpoint 1,
: outlet water temperature, setpoint 2.
COOLING INLET SETP COOLING OUTLET SETP
12¢7¢
(*)
7 ➞ 23¢4 ➞ 20¢
0$1¢0$1¢
4Press ‡ to save the adjusted temperature setpoint.
When the setting has been confirmed, the cursor switches to the
next setpoint.
5To adjust other setpoints, repeat from step 2.
NOTE
When a setpoint on a unit in a DICN system is set, this
setpoint will be transferred to all other units.
NOTE
Also consult "Defining the floating setpoint settings" on
page 15.
Resetting the unit
The units are equipped with three kinds of safety devices: unit
safeties, circuit safeties and network safeties.
When a unit or circuit safety occurs, the compressor is shut down.
The safeties menu will indicate which safety is activated. The
STATUS
ACTIVE
screen of the readout menu will indicate
OFF - SAFETY
. The red LED inside the π key lights up and the buzzer
inside the controller is activated.
When a network safety occurs in a DICN configuration, the slaves not
detected by the network will function as stand alone units.
■If a slave unit can not be found by the network, the red light
inside the π key of the master lights up and the buzzer inside
the control is activated.
■If the master can not be found by the network, the red light
inside the π key of all the slaves light up and the buzzer inside
their controls are activated. All units will work as stand alone
units.
If the unit has been shut down due to a power failure, it will carry out
an autoreset and restart automatically when the electrical power is
restored.
To reset the unit, proceed as follows:
1Press the π key to acknowledge the alarm.
The buzzer is deactivated.
The controller automatically switches to the corresponding
screen of the safeties menu: unit safety or circuit safety or
network safety.
2Find the cause of shutdown and correct.
Refer to "Listing activated safeties and checking the unit status"
on page 17 and "Troubleshooting" on page 19.
When a safety can be reset, the LED under the π key starts
blinking.
3Press the π key to reset the safeties that are no longer active.
If required, enter the
PASSWORD
. (Refer to the installation manual "Setting the
USER PASSWORD
or the
password for safety reset".)
Once all safety devices are deactivated and reset, the LED
under the π key goes out. If one of the safeties is still active, the
LED under the π key goes on again. In this case, return to
step 2.
4It will only be necessary to switch the œ key on again if a unit
safety occurs.
If the user shuts down the power supply in order to repair a
safety, the safety will automatically be reset after power-up.
NOTE
The history information, i.e. the number of times a unit
safety or a circuit safety occurred and the unit status at
the moment of shutdown, can be checked by means of
the history menu.
UNIT
SERVICE
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
10
Page 12
Advanced features of the digital controller
This chapter gives an overview and a brief functional description of
the screens provided by the different menus. In the following chapter,
you will find how you can set up and configure the unit using the
various menu functions.
All menus are directly accessible using the corresponding key on the
digital controller or through the main menu (refer to "How to enter a
menu" on page 8). The down arrow v on the display indicates that
you can go to the next screen of the current menu using the Ì key.
The up arrow ^ on the display indicates that you can go to the
previous screen of the current menu using the fi key. If ÷ is
displayed, this indicates that you can either return to the previous
screen or can go to the next screen.
_÷ UNIT STATUS
C11:OFF SAFETY ACT.
C12:OFF SAFETY ACT.
UNIT CAPACITY:000%
_÷ UNIT STATUS
C21:OFF SAFETY ACT.
C22:OFF SAFETY ACT.
013$6¢
To consult actual operational information about the status of the pump, the
compressor and the fans and the
temperature setpoint (depending on
active mode).
To consult actual operational information about the control mode, the inlet
and outlet water temperature.
Note that for a DICN system, the
INLET WATER
and
OUTLET WATER
values are the values of the individual
units, not of the system. Temperatures
of the system can be consulted in the
first screen of the network menu.
To consult information about the
discharge temperature of circuit 1.
To consult information about the
discharge temperature of circuit 2 (only
for EWAQ130~260).
To consult information about the
temperature of the refrigerant of
circuit 1.
To consult information about the
temperature of the refrigerant of
circuit 2 (only for EWAQ130~260).
To consult information about the actual
pressures and the fans of circuit 1 and
to check if the fans are running in
lownoise mode.
To consult information about the actual
pressures and the fans of circuit 2 (only
for EWAQ130~260).
To consult information about the unit
status of circuit 1 and the capacity of
the unit.
To consult information about the unit
status of circuit 2 (only for
EWAQ130~260).
_÷ EXTRA READOUT
C12RH:00000hCS:00000
To consult actual operational information about the total running hours and
the number of compressor stops of
circuit 1 (second screen).
_÷ EXTRA READOUT
C21RH:00000hCS:00000
To consult actual operational information about the total running hours and
the number of compressor stops of
circuit 2 (first screen) (only for
EWAQ130~260).
_÷ EXTRA READOUT
C22RH:00000hCS:00000
To consult actual operational information about the total running hours and
the number of compressor stops of
circuit 2 (second screen) (only for
EWAQ130~260).
Setpoints menu ∑
Depending upon the settings in the "advanced" usersettings menu,
the "setpoints" menu can either be entered directly or by means of
the user password.
Use the
through the menu and press the
to enter the submenu of your choice.
To define the thermostat settings.
To define the settings for manual
control.
To define the compressor lead-lag
settings.
To define the compressor capacity
limitation settings.
To define the action on all the fans in
case the unit is off.
fi and Ì keys to scroll
‡ key
_÷ EXTRA READOUT
CURRENT:055A
VOLTAGE:023V
_÷ EXTRA READOUT
C11RH:00000hCS:00000
RHP1:00001hP2:00000h
Operation manual
11
To consult actual operational information about the current (Ampere) and
voltage of the unit.
To consult actual operational information about the total running hours and
the number of compressor stops of
circuit 1 (first screen) and total running
hours of the pumps.
_÷ MASTER SETTINGS
MODE:NORMAL
OFFSET:0000h
PUMP ON IF:UNIT ON
ADVANCED
_v ADVANCED
PASSWORD NEEDED FOR:
SETPOINT MENU:Y
UNIT ON/OFF:Y
_^ ADVANCED
MAIN MENU:GRAPHIC
LOGOUT TIMER :05min
BUZZER IF SAFETY:YES
To define the pump control settings.
To define the dual pump settings.
To define the floating setpoint.
To define the controller display
language.
To set the time and date of the system.
To define the free cooling.
The controller displays the name of the
MASTER, SLAVE1
unit:
...
SLAVE3
This name is automatically assigned
depending on the set hardware
address. Refer to "Setting the
addresses" in "Connection and setup of
a DICN system" in the installation
manual.
To define whether or not a password is
needed to enter the setpoints menu and
for switching the unit on and off.
To define the outlook of the main menu,
to set the logout timer and to define
whether or not the buzzer is to be
activated when errors occur.
Timers menu Ó
_v GENERAL TIMERS
LOADUP:000s-DWN:000s
PUMPLEAD :000s
FLOWSTOP :00s
To check the actual value of the general
software timer.
To check the actual value of the
compressor timers of circuit 1.
To check the actual value of the
compressor timers of circuit 2 (only for
EWAQ130~260).
Safety menu π
The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.
_v UNIT SAFETY
0F0:EMERGENCY STOP
_v CIRCUIT1 SAFETY
1U1:REV PHASE PROT
_v CIRCUIT2 SAFETY
1U1:REV PHASE PROT
.
_v NETWORK SAFETY
0U4:PCB COMM.PROBLEM
_v UNIT WARNING
0AE:FLOW HAS STOPPED
Along with the basic information, more detailed information screens
can be consulted while the history menu is active. Press the ‡ key.
Screens similar to the following will appear. Additionally the number
of safeties that already occurred, can be consulted on the first line of
the history screens.
_÷ UNIT HISTORY:002
0CA:OUT SENSOR ERR
22h33m00s 23/03/06
COOL INLSP1:012$0¢
To consult information about the unit
safety which caused the shutdown.
To consult information about the
circuit 1 safety which caused the
shutdown.
To consult information about the
circuit 2 safety which caused the
shutdown (only for EWAQ130~260).
To consult information about the
network safety which caused the
shutdown.
To consult information about the unit
warning which caused the shutdown.
To check the time at the moment of the
unit shutdown and to check which was
the evaporator inlet water temperature
setpoint.
To check which were the evaporator
inlet, outlet water and ambient temperature at the moment of shutdown.
To check which was the discharge
temperature of the circuits of circuit 1 at
the moment of shutdown.
To check which was the discharge
temperature of the circuits of circuit 2 at
the moment of shutdown (only for
EWAQ130~260).
To check which was the temperature of
the refrigerant of circuit 1 at the moment
of shutdown.
To check which was the temperature of
the refrigerant of circuit 2 at the moment
of shutdown (only for EWAQ130~260).
To check which were the pressures of
circuit 1 and the status of the fans at the
moment of shutdown.
Operation manual
12
Page 14
_÷ UNIT HISTORY:002
HP2:019$0b = 050$0¢
LP2:019$0b = -05$2¢
FAN2:OFF
_÷ UNIT HISTORY:002
C11:OFF SAFETY ACT.
C12:OFF SAFETY ACT.
UNITCAPACITY:000%
_÷ UNIT HISTORY:002
C21:OFF SAFETY ACT.
C22:OFF SAFETY ACT.
_÷ UNIT HISTORY:002
CURRENT:055A
VOLTAGE:023V
_÷ UNIT HISTORY:002
C11RH:00000hCS:00000
RHP1:00000hP2:00000h
_÷ UNIT HISTORY:002
C12RH:00000hCS:00000
_÷ UNIT HISTORY:002
C21RH:00000hCS:00000
_÷ UNIT HISTORY:002
C22RH:00000hCS:00000
_÷ UNIT HISTORY:002
AI1 NONE
AI2 NONE
_÷ UNIT HISTORY:002
AI3 NONE
AI4 NONE
To check which were the pressures of of
circuit 2 and the status of the fans at the
moment of shutdown (only for
EWAQ130~260).
To check which was the status of the
compressors and the unit capacity of
circuit 1 at the moment of shutdown.
To check which was the status of the
compressors and the unit capacity of
circuit 2 at the moment of shutdown
(only for EWAQ130~260).
To check which was the current
(Ampere) and voltage of the unit at the
moment of shutdown.
To check which were the total amount of
running hours of the compressor and
number of compressor stops of circuit 1
and of the pumps at the moment of
shutdown (first screen).
To check which were the total amount of
running hours of the compressor and
number of compressor stops of circuit 1
at the moment of shutdown (second
screen).
To check which were the total amount of
running hours of the compressor and
number of compressor stops of circuit 2
at the moment of shutdown (first
screen) (only for EWAQ130~260).
To check which were the total amount of
running hours of the compressor and
number of compressor stops of circuit 2
at the moment of shutdown (second
screen) (only for EWAQ130~260).
To check the changeable analogue
input status at the moment of shutdown
(first screen).
To check the changeable analogue
input status at the moment of shutdown
(second screen).
Info menu ™
_v TIME INFO
TIME: 22h05
DATE: WED 24/01/07
_÷ UNIT INFO
UNIT:AW-CO-260 C:SCL
CIR:2 EVAP:1 COILC:2
EEV:P REF:R410A
_÷ UNIT INFO
FAN:ST VA:Y 2PUMP:Y
HEATERTAPE:Y
FAN DO ST:2 DO INV:2
_^ SW INFO
MAIN:SP1710_055 V2.0
EXT :SP1559_017
REM.:SP1734_011
To consult time and date information.
To consult additional information about
the unit such as the unit type, number of
circuits and evaporators and the
refrigerant used.
To consult additional information about
the unit such as the fan type, Volt
Ampere option, if there is a second
pump or heater tape present and the
quantity of digital outputs that can
possibly be used in case of non-inverter
ST
fans (
) or inverter fans (
INV
).
To consult information about the
controller's software version.
Input/output status menu Ÿ
The "input/output status" menu gives the status of all the digital
inputs and outputs and the changeable digital inputs of the unit.
_v DIGITAL INPUTS
EMERGENCY STOP :OK
FLOWSWITCH:FLOW OK
_÷ DIGITAL INPUTS
C1 REV.PH.PROT. :OK
C1 HIGH PR.SW. :OK
INT.L C11:OK C12:OK
_÷ DIGITAL INPUTS
C1 FAN OVERC.ST1:OK
C1 FAN OVERC.ST2:OK
C1 FAN OVERC.ST3:OK
_÷ DIGITAL INPUTS
C2 REV.PH.PROT. :OK
C2 HIGH PR.SW. :OK
INT.L C21:OK C22:OK
To check whether or not the emergency
stop device is active and if there is any
water flow to the evaporator.
To check the status of the heater tape
and the state of the pump interlock and
pump.
To check the status of the high pressure
switch, the reverse phase protector and
the overcurrent relay of circuit 1.
To check the fan overcurrent status of
circuit 1.
To check the status of the high pressure
switch, the reverse phase protector and
the overcurrent relay of circuit 2 (only
for EWAQ130~260).
History menu ‚
The "history" menu contains all the information concerning the latest
shutdowns. The structure of those menus is identical to the structure
of the safeties menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safeties menu is
copied into the history menu.
Additionally, the number of safeties that has already occurred, can be
consulted on the first line of the history screens.
Operation manual
13
_÷ DIGITAL INPUTS
C2 FAN OVERC.ST1:OK
C2 FAN OVERC.ST2:OK
C2 FAN OVERC.ST3:OK
To check the fan overcurrent status of
circuit 2 (only for EWAQ130~260).
To check the status of the compressors
11/12/21/22.
To check the status of the fanspeed
relays of circuit 1.
To check the status of the fanspeed
relays of circuit 2 (only for
EWAQ130~260).
To check the status of the changeable
digital inputs. (first screen)
Note that for a unit in a DICN system,
the inputs apply to this unit.
It will be the remote input on the master
unit however, that will be determining
for the operation of the unit.
To consult the temperature setpoint, the
common entering water temperature
(entering water temperature of the
master unit).
The status screen of the network menu
shows the condition of the master unit
M
) and slave units (
(
SL1
...
SL3
).
Cool/heat menu Í
This menu is not available for EWAQ units.
2Press the ‡ key to enter the submenu of your choice.
3Go to the appropriate screen using the fi and Ì keys. If there
is only one screen, the fi and Ì keys have no effect.
4Press the ‡ key to move the cursor to the first parameter which
can now be modified.
5Select the appropriate setting using the fi and Ì keys.
6Press ‡ to confirm the selection.
When the selection has been confirmed, the cursor switches to
the next parameter which can now be modified.
7Repeat instruction 6 to modify the other parameters.
8After the last parameter the cursor is switched back to the
starting position and continue from instruction 3 onwards.
9Press the ƒ key to return to the usersettings menu and
continue from instruction 1 onwards.
Submenu: Thermostat
Defining the thermostat settings
When inlet or outlet control mode is selected, the unit uses a
thermostat function to control the cooling capacity. However, the
thermostat parameters are not fixed and can be modified.
The default, limit and step values for the thermostat parameters are
shown in "Annex I" on page 25.
NOTE
■If changed on one of the units in a DICN
configuration, this setting is transferred to all other
units in the network.
■A functional diagram showing the thermostat
parameters can be found in "Annex I" on page 25.
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Defining and activating the control mode
The unit is equipped with a thermostat which controls the cooling
capacity of the unit. Select the appropriate mode:
■
MANUAL CONTROL
:manual control mode: the operator controls
the capacity himself by setting:
•
C11/12/21/22
(capacity step in manual mode): OFF or ON of
compressors 11/12/21/22.
•
F1*, F2*
(air flow in manual mode): off, low, medium or high of
circuit 1/2.
■
INL WATER
: inlet control mode: uses the entering water
temperature to control the capacity of the unit.
■
OUTL WATER
: outlet control mode: uses the leaving water
temperature to control the capacity of the unit.
Operation manual
14
Page 16
NOTE
To activate manual control mode, select
CONTROL
as present mode. To deactivate the manual
control mode, select an other mode as present mode.
For units in a DICN configuration:
When changing the control mode on one of the units, it
is automatically transferred to all other units.
Manual control mode however can only be selected on
NOTE
units with status
The OUTLET mode is not available for DICN systems.
DISCONNECT ON/OFF
Submenu: Compressor
Defining the lead-lag settings
In the
COMPR.LEAD-LAG
screen select the appropriate mode and
define the compressor lead-lag settings.
■MODE
•
AUTO
: the priority is depending on the running hours of the
separate compressors.
•
PRIORITY: C11>C12>C21>C22
C11 has the highest priority to startup while C22 has the lowest
priority.
the setting in this example
Defining the capacity limitation settings
In the
COMPR.CAP.LIMIT
limitation settings can be configured.
A capacity limitation can be activated:
■
MODE
:
•
NOT ACTIVE
•
CHANG.DIG.INP.:
capacity limitation.
screen up to 4 possible capacity
: the capacity limitation is not active.
when a changeable input is configured as
.
MANUAL
Submenu: Pump
Defining the pump control settings
The
PUMPCONTROL
screen of the usersettings menu allows the user
to define the pump-leadtime and pump-lagtime.
■
PUMPLEADTIME
run before the unit (or the compressor in case
COMPR ON
■
PUMPLAGTIME
running after the unit (or the compressor in case
COMPR ON
: used to define the time that the pump must
PUMP ON IF:
is selected in a DICN configuration) can start up.
: used to define the time that the pump keeps
PUMP ON IF:
is selected in a DICN configuration) has been
stopped.
■
DAILY ON
: select either Y (yes) or N (no). When Y is selected,
define the starting time (24 hour time scale).
This means that during that time, the pump will run for about
5 seconds, even when the unit is switched off.
Defining dual pump control
The
DUAL PUMP
define the steering of two pumps (for this to be possible a changeable
digital output has to be configured for a second pump in the service
menu). Refer to the installation manual.
■
MODE
two pumps. When automatic rotation is chosen the offset on
running hours also has to be entered.
•
AUTO ROTATION
offset on RH.
•
PUMP 1>PUMP 2
•
PUMP 2>PUMP 1
■
OFFSET ON RH
between the two pumps. Used to switch over between pumps
when they work in automatic rotation mode.
Submenu: Floating setpoint
screen of the usersettings menu allows the user to
: used to define which kind of control will be used for the
: pump 1 and pump 2 will alternate to the
: pump 1 will always start up first.
: pump 2 will always start up first.
: used to define the offset in running hours
NOTE
Refer to "Customization in the service menu",
chapter "Setting of the changeable digital
inputs and outputs" in the installation manual.
•
LIMIT 25%/50%/75%/SET
■in case of
CHANG.DIG.INP.
compressor must be defined (
■
OFF
: These compressors will always be switched off
: to activate capacity limitation.
or
LIMIT SET
C11/12/21/ 22
mode, each
).
■ON: These compressors will still be used by the thermostat
according to the required load.
Submenu: Fan
Defining the fan low noise settings
The
FAN LOW NOISE
screen is only available when the option
inverter fans is installed (OPIF). Refer to the manual delivered with
the option.
Fan forced on settings
Allow to run the fans even when the unit is switched off.
■
OFF
: the fans will not be activated.
■
ON
: the fans will be forced to run.
■
CH.DIG.INP.
the changeable digital input.
: the fans will run, depending on the settings of
Defining the floating setpoint settings
Setpoint signal is renamed as "floating setpoint based on changeable
analogue input".
The
FLOATING SETPOINT
the active setpoint to be modified in function of the ambient
temperature. The source and settings of the floating setpoint can be
configured by the user.
MODE
■
: used to define the mode of the floating setpoint.
•
NOT ACTIVE
•
AMBIENT
and altered accordingly.
Settings:
•
CH. AI SLOPE NTC
changeable analogue input (NTC type) and altered accordingly.
Settings:
•
CH. AI SLOPE V-A
changeable analogue input (V-A type) and altered accordingly.
Settings:
•
CH.AI MAX VALUE
changeable analogue input (V-A type) and altered accordingly.
Setting:
NOTE
: floating setpoint is based on the ambient temperature
MAXPOS, NEG, RF
MAXPOS, NEG, RF
MAXPOS, NEG, RF
MAXIMUM VALUE
A functional diagram showing the floating setpoint
working can be found in "Annex II" on page 26.
screen of the usersettings menu allows
: floating setpoint is not activated.
or
SLOPE
.
: floating setpoint is based on the
or
SLOPE
.
: floating setpoint is based on the
or
SLOPE
.
: floating setpoint is based on the
.
Operation manual
15
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 17
Submenu: Language
Defining the language
This screen allows the user to define the language of the displayed
information of the controller (on the first screen). (Push the ‡ button
repeatedly to change the operating language).
Submenu: Time and date
Defining the time and date
The
TIME AND DATE
screen of the usersettings menu allows the
user to define the time and date.
■
TIME
: used to define the present time.
■
DATE FORMAT
■
DATE
: select the name of the present day and define the
present date according to the setting of the
DD
= number of day (01~31),
MM
= number of month (01~12)
YY
= the last 2 numbers of the year (2006 = 06).
: used to define the format of the date.
DATE FORMAT
.
Submenu: Free cooling
Defining free cooling
The
FREE COOLING
user to control a 3-way water valve when the unit is in free cooling
state. To make this possible a changeable digital input or output has
to be configured for free cooling in the service menu. (Refer to the
installation manual.)
■
MODE
: used to define the free cooling mode.
•
NOT ACTIVE
•
CHDI
•
AMBIENT
•
INLET-AMBIENT
between inlet water temperature and ambient temperature.
■
SP
: setting of the free cooling setpoint.
■
DIF
: setting of the free cooling difference.
■PUMP
■ON: pump will be on when free cooling mode is active
■
OFF
: pump will be off when free cooling mode is active
■
LEAD
: time that the pump will be running before the compressor
will start operating.
NOTE
A functional diagram showing the free cooling working
can be found in "Annex III" on page 26.
screen of the usersettings menu allows the
: free cooling is not active.
: changeable digital input will activate the free cooling mode
: free cooling is based on ambient temperature.
: free cooling is based on the difference
•
STANDBY
function is then also similar to a unit defined as
unit however, will only come into operation if:
another unit is in alarm
another unit is in
the setpoint is not reached when all other units have been
running on full capacity for some time
If more than one unit is defined as
will be really standby. The unit which is really standby will be
decided by the number of running hours.
DISCONNECT ON/OFF
•
other units ON or OFF.
possible.
If the unit is put to
it will be controlled by the DICN network as a
NOTE
: The unit is considered as a
DISCONNECT ON/OFF
: Putting this unit ON or OFF will not put
MANUAL CONTROL
INLET
or
OUTLET
Put a unit to
DISCONNECT ON/OFF
NORMAL
unit and its
NORMAL
mode
STANDBY
, only 1 of the units
on such a unit is
mode, and the unit is ON,
NORMAL
when servicing
the machine. In this case it is possible to switch ON or
OFF this unit without switching ON or OFF the other
units of the network.
It is also possible then to operate the unit in
CONTROL
Put a unit to
.
DISCONNECT ON/OFF
continuously if
the operator wants to decide by himself when this unit
must operate.
Note that in this case, it makes no sense to define
■
another unit of the network as
a unit set continuously to
OFFSET
STANDBY
NORMAL
: The
unit will continuously be considered as a
unit.
OFFSET
STANDBY
DISCONNECT ON/OFF
time defines the target difference in
. Since there is
running hours between one unit and another unit with
OFFSET:0000h
. This value is important for maintenance
purposes. The difference in setting among different units should
be high enough as to avoid servicing of the units all at the same
time. The lower and upper limits are 0 and
9000
respectively. The default value is 0 hours.
■
PUMP ON IF
chiller is on (
(
COMPR ON
When
as long as the chiller is on. When
: Set if the pump must operate as long as the
UNIT ON
), or during compressor on condition only
).
UNIT ON
is selected, the pump output will remain closed
COMPR ON
is selected, the
pump output will remain closed as long as the compressor is on.
Also refer to the separate manual "Installation examples for a
DICN configuration".
NOTE
The settings on this screen of the network menu must
be executed for all chillers connected to the system.
, but this
unit.
MANUAL
, the
hours
Submenu: DICN
Only available in case DICN (option kit EKACPG) is installed (refer to
"Connection and setup of a DICN system" in the installation manual
and the installation manual of the EKACPG kit).
Defining the network settings
The
SETTINGS
the
MODE
pump must operate.
■
MODE
DISCONN ON/OFF
•
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
screen of the network menu allows the user to set
of the unit, the
: Define the mode of the unit as
OFFSET
time and the condition when the
NORMAL, STANDBY
or
.
NORMAL
unloading is decided by the central control of the netwerk. Putting
this unit ON or OFF will also put all other units ON or OFF, unless
their status is
Changing
SETTINGS
CONTROL
activating the control mode" on page 14.
: The unit is controlled by the network. Loading and
DISCONNECT ON/OFF
CONTROL SETTINGS
to this unit, will apply to all other units.
on such a unit is not possible. Refer to "Defining and
. (see further)
or
THERMOSTAT
MANUAL
Submenu: Advanced
Activating or deactivating the setpoints password and the unit
on/off password
The first
to activate or deactivate the user password needed to change the
temperature setpoint (
user does not have to enter the password each time he wants to
change the setpoint.
The first
user to activate or deactivate the user password needed to switch the
unit ON or OFF (
ADVANCED
ADVANCED
NOTE
screen of the usersettings menu allows the user
SETPOINT MENU
). When deactivated, the
screen of the usersettings menu also allows the
UNIT ON/OFF
).
If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.
Operation manual
16
Page 18
Defining controller settings
The second
the user to define settings for the controller.
■
■
■
■
■
NOTE
Submenu: Defrost
This submenu is not available for EWAQ units.
Submenu: Service menu
Only a qualified installer is allowed to enter the service menu.
Tasks of the timers menu
ADVANCED
MAIN MENU
graphical symbols or to
screen of the usersettings menu also allows
: set to
GRAPHIC
to let the main menu show the
TEXT
to let the main menu show the
names of the menus.
LOGOUT TIMER
: set the time for automatic log out, between 01
and 30 minutes.
BUZZER IF SAFETY
: to activate or deactivate the buzzer
sound when an error should occur.
BACKLIGHT TIME
: to define the time (between 01 and 30
minutes) the light of the controller display will stay on after the
last manipulation of the controller buttons.
GRAPHIC READOUT
: to define if the graphical representation of
the first screen of the read out menu is present or not.
If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.
Checking the actual value of the software timers
As a protective measure and to ensure correct operation, the
controller's software features several countdown timers:
■LOADUP (
counting when a thermostat step change has occurred. During
the countdown, the unit is not able to enter a higher thermostat
step.
■LOADDOWN (
counting when a thermostat step change has occurred. During
the countdown, the unit will not be able to go to a lower thermostat step.
■FLOWSTART (
water flow through the evaporator is continuous and the unit is in
standby. During the countdown, the unit cannot start up.
■FLOWSTOP (
water flow through the evaporator stops after the flowstart timer
has reached zero. If the water flow has not restarted during the
countdown, the unit will shut down.
■PUMPLEAD (
starts counting whenever the unit is switched on. During the
countdown, the unit cannot start up.
■PUMPLAG (
starts counting whenever the unit is switched off. During the
countdown, the pump keeps running.
■GUARDTIMER (
when the compressor (circuit 1/2) has been shut down. During
the countdown, the compressor cannot be restarted.
■ANTIRECYCLING (
counting when the compressor (circuit 1/2) has started. During
the countdown, the compressor cannot be restarted.
■MINIMUM RUNNING TIME (
when the compressor has started. During the count down, the
compressor will not be switched off by the thermostat function.
LOADUP
– refer to the thermostat parameters): starts
DWN
– refer to the thermostat parameters): starts
FLOWSTART
FLOWSTOP
PUMPLEAD
PUMPLAG
GRD11/12/21/22
– 15 sec): counts down when the
– 5 sec): starts counting when the
– refer to the pump control settings):
– refer to the pump control settings):
– 180 sec): starts counting
AREC11/12/21/22
M.RT
– 300 sec): starts
- 120 sec) starts counting
To check the actual value of the software timers, proceed as follows:
1Enter the
TIMERS MENU
. (Refer to the chapter "How to enter a
menu" on page 8.)
The controller displays the actual value of the
TIMERS
: the loadup timer, the loaddown timer, the flowstart
GENERAL
timer, the flowstop timer (when the unit is on and the flowstart
timer has reached zero), the pumplead timer and the pumplag
timer.
2Press the Ì key to check the compressor timers.
The controller shows the actual value of the
TIMERS
: the guard timers (one per circuit) and the antirecycling
COMPRESSOR
timers (one per circuit).
Tasks of the safety menu
Listing activated safeties and checking the unit status
If the alarm buzzer is activated and the user presses the π key, the
controller automatically enters the safeties menu.
All active safeties are displayed:
NETWORK SAFETY
.
■The controller will show the
UNIT/CIRCUIT 1/2, WARNING
UNIT SAFETY
screen of the
or
safeties menu when a unit safety was the cause of shutdown.
■The controller will show the
CIRCUIT 1/2 SAFETY
screen of
the safeties menu when a safety of the circuit 1/2 was activated.
■The controller will show the
NETWORK SAFETY
screen of the
safeties menu when a safety of the network was activated.
■The controller will show the
UNIT WARNING
screen of the
safeties menu when a unit warning was activated.
1Press the π key when the alarm buzzer is activated.
The appropriate safety screen with the basic information
appears. Press the ‡ key to go directly to the history menu and
see the detailed information. These screens provide information
about the unit status at the moment of shutdown (see "Safety
menu π" on page 12).
2If more than one kind of safety is active (indicated by means of
^, v or ÷), use the fi and Ì keys to consult them.
Tasks of the history menu
Checking the safety info and the unit status after a reset
The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the circuit.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest shutdown.
To check the safety info and the unit status, proceed as follows:
1Enter the
a menu" on page 8.)
The controller enters the last
basic information of the moment of this shutdown.
2Press the fi and Ì keys to consult the other present
screens.
3Press the ‡ key to see the detailed information.
HISTORY MENU
. (Refer to the chapter "How to enter
HISTORY
screen which contains
HISTORY
Operation manual
17
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 19
Tasks of the info menu
Consulting additional unit information
1Enter the
chapter "How to enter a menu" on page 8).
The controller enters the
following information: the
2Press Ì to consult the first
This screen contains information about the unit name, number of
circuits, evaporators and coils, EEV and the refrigerant used.
3Press Ì to consult the second
This screen contains information about the fans, volt/ampere
and if there is a second pump or heater tape applied.
4Press Ì to consult the
This screen contains information about the PCB software
versions.
Tasks of the input/output menu
INFO MENU
through the main menu. (Refer to the
SW INFO
TIME INFO
TIME
UNIT INFO
screen which contains the
and
DATE
UNIT INFO
(software information) screen.
.
screen.
screen.
Checking the status of the inputs and outputs
The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.
The locked digital inputs are:
■
EMERGENCY STOP
pressed (only effective if there is an emergency stop present).
■
FLOWSWITCH
flow).
■
HEATER TAPE
■
PUMPINTERLOCK
is open or closed.
■
PUMP
: indicates if the pump is on or off.
C1/2 REV.PH.PROT.
■
actual status of this safety of circuit 1/2.
■
C1/2 HIGH PR.SW.
actual status of this safety of circuit 1/2.
■
INT.L C11/C12/C21/22
the actual status of this safety of circuit1/2.
■
C1/2 FANOVERC. ST. 1/2/3
step 1/2/3) indicates the actual status of this safety of circuit 1/2.
The locked relay outputs are:
■
C11/12/21/22
■
C1/2 FANSTEP 1/2/3
the circuit 1/2 are on or not.
: whether the emergency button has been
: indicates the status of the flowswitch (flow/no
: indicates if the heater tape is activated or not.
: indicates if the status of the pump interlock
: (reverse phase protector) indicates the
: (high pressure switch) indicates the
: (interlock to compressor) indicates
: (fan overcurrent status
: indicates whether the circuit 1/2 is on or off.
: indicates if the fans of fanstep 1/2/3 for
Checking the status of the digital changeable inputs and
outputs
The possible settings for the changeable digital inputs are:
■
NONE
: indicates there is no function selected for this input
■
STATUS
: indicates the position of the connected switch.
■
DUAL SETPOINT
setpoint switch: setpoint 1 or setpoint 2.
■
REMOTE ON/OFF
switch.
■
CAP LIMIT 25%/50%/75%/SET
"enable/disable capacity limitation" switches.
■
LOW NOISE
■
FREE COOLING REQ
or not requested.
■
FAN FORCED ON
not activated.
: indicates the position of the remote dual
: indicates the position of the remote on/off
: indicates the position of the
: indicates the status of the low noise mode.
: indicates if the free cooling is requested
: indicates if the fan forced on is activated or
The possible settings for the changeable relay outputs are:
■
NONE (OPEN)
■
CLOSED
■
2ND PUMP
■
100% CAPACITY
■
FULL CAPACITY
maximum capacity, example reached 100% capacity or reached
maximum capacity because of safety limitation.
■
FREE COOLING
when the unit is in free cooling state.
■
GEN.OPERATION
■
SAFETY+W (NO)
(Normal Open contact).
■
SAFETY+W (NC)
(Normal Closed contact).
■
SAFETY (NO)
contact).
SAFETY (NC)
■
contact).
■
C1/2 SAFETY
■
WARNING
■
C1/2 OPERATION
active.
: Digital output open.
: Digital output closed.
: indicates the status of the second pump.
: indicates when the unit is working at 100%.
: indicates when the unit is working at
: indicates the status of the 3-way water valve
: indicates when the unit is active.
: indicates when safety or warning is active
: indicates when safety or warning is active
: indicates when safety is active (Normal Open
: indicates when safety is active (Normal Closed
: indicates when circuit 1/2 safety is active.
: indicates when warning is active.
: indicates when circuit 1/2 operation is
Checking the status of the analogue changeable inputs and
output
The possible settings for the analogue changeable inputs and output
are:
■
NONE
: no function is appointed to the changeable analogue
input.
■
STATUS
■
FLOATING SETP
analogue input
■
TEMPERATURE
outlet temperature
■
DI***
inputs. (*** can be any of the following:
SETPOINT
FREE COOLING REQ
: only displays the status by means of test
: floating setpoint based on ambient or
: only displays the (by example) condenser
: refer to the possible functions for changeable digital
STATUS, DUAL
,
REMOTE ON/OFF, CAP. LIMIT, LOW NOISE
or
FAN FORCED ON
.)
Checking the communication inputs and outputs (option
EKACPG)
The communication inputs and outputs are:
■
RS232 ONLINE
active.
■
RS485 ONLINE
active.
■
DIII ONLINE
active.
To check the inputs and outputs, proceed as follows:
1Enter the
enter a menu" on page 8.)
The controller enters the first
2Consult the other screens of the input/output menu using the fi
and Ì keys.
: indicates if the RS232 communication line is
: indicates if the RS485 communication line is
: indicates if the DIII communication line is
I/O STATUS MENU
. (Refer to the chapter "How to
DIGITAL INPUTS
screen.
,
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
18
Page 20
Tasks of the login/logout menu
TROUBLESHOOTING
Changing the user password
Access to the usersettings menu and the setpoints menu is protected
by the user password (a 4-digit number between
After the password is entered, other protected screens do no longer
require the entering of the password.
To log out, go to the login/logout menu and alter the login status and
the logout setting.
NOTE
The default user password is
To change the user password, proceed as follows:
1Enter the
USERPASSWORD MENU
. (Refer to the chapter "How
to enter a menu" on page 8).
The controller will request the password.
2Enter the actual correct password using the fi, Ì and ‡ keys.
For each of the 4 digits:
- Use the fi and Ì keys to select the correct number.
- Press the ‡ key to enter and select the next number.
When pressing the ‡ key on the last number, the complete
password is entered.
3After the ‡ key has been pressed to confirm the password, the
controller shows the first login/logout screen.
The login status is shown.
The logout is set to NO.
4When the setting for logout must change to
- Press the ‡ key to position the cursor behind
- Press the fi or Ì keys to change the setting to
- Press the ‡ key to confirm the setting.
The controller leaves the login/logout screen and shows the first
screen of the read out menu.
5When the setting for logout stays NO, press the Ì key to enter
the second login/logout screen.
The controller requests for a new password.
6Press the ‡ key to position the cursor behind
7Enter the new password using the fi, Ì and ‡ keys.
For each of the 4 digits:
- Use the fi and Ì keys to select the correct number.
- Press the ‡ key to enter and select the next number.
When pressing the ‡ key on the last number, the complete
new password is entered and the cursor is positioned behind
CONFIRM
The controller requests to confirm the new password.
.
8Enter the new password again using the fi, Ì and ‡ keys.
For each of the 4 digits:
- Use the fi and Ì keys to select the correct number.
- Press the ‡ key to enter and select the next number.
When pressing the ‡ key on the last number, the
confirmation of the new password is completed.
NOTE
The actual password will only be changed when the
new password and the confirmed password have the
same value.
If changed on one of the units in a DICN configuration,
this setting is automatically transferred to all the other
units in the network.
1234
0000
and
9999
.
YES
.
LOGOUT?
YES
.
NEW PASSWORD
).
This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will
save you time and money.
When carrying out an inspection on the supply panel or on
the switch box of the unit, always make sure that the circuit
breaker of the unit is switched off.
Overview of safety messages
Message safety menuSymptom
UNIT SAFETY0AE:FLOW HAS STOPPED
0AE:PUMPINTERLOCK
0A4:FREEZE UP
0A4:FREEZE UP C1
0A4:FREEZE UP C2
0A9:EEV PCB COMM ERR
0A9:EEV PCB ERR
0C9:INL SENSOR ERR
0CA:OUT SENSOR ERR
0H9:AMB T SENSOR ERR
0U4:EXTPCB COMM.ERR
0U4:MAINPCB COMM.ERR
0U5:PCB COMM.PROBLEM
0C9:INL SENSOR ERR
0U4:PCB COMM.PROBLEM
0U4:SW VERSION ERR
5.2
7
5.7
5.4
5.4
5.4
5.7
5.4
5.4
5.4
7
12
13
When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other
than the factory setting. If the cause of the problem cannot be found,
call your local dealer.
Symptom 1: The unit does not start, but the ON LED lights up
POSSIBLECAUSESCORRECTIVEACTION
The temperature setting is not
correct.
The flowstart timer is still running.The unit will start after approx. 15
The circuit can not start up.Refer to Symptom 4: The circuit
Unit is in manual mode (all
compressors at 0%).
Power supply failure.Check the voltage on the supply
Blown fuse or interrupted protection
device.
Loose connections.Inspect connections of the field
Shorted or broken wires.Test circuits using a tester and repair
Symptom 2: The unit does not start, but the ON LED is flashing
POSSIBLECAUSESCORRECTIVEACTION
The remote ON/OFF input is
enabled and the remote switch is off.
Symptom 3: The unit does not start and the ON LED does not light up
3
POSSIBLECAUSESCORRECTIVEACTION
The unit is in failure mode.Refer to Symptom 5: Safety devices
One of the following safety devices is
activated:
• Flowswitch (S8L,S9L)
•Emergency stop
The ON LED is broken.Contact your local dealer.
Check the controller setpoint.
seconds. Make sure that water is
flowing through the evaporator.
does not start up.
Check on the controller.
panel.
Inspect fuses and protection
devices. Replace by fuses of the
same size and type (refer to
"Electrical specifications" on
page 2).
wiring and the internal wiring of the
unit. Tighten all loose connections.
if necessary.
Put the remote switch on or disable
the remote ON/OFF input.
are activated and alarm messages
are displayed.
Refer to Symptom 5: Safety devices
are activated and alarm messages
are displayed.
Symptom 4: The circuit does not start up
POSSIBLECAUSESCORRECTIVEACTION
One of the following safety devices is
activated:
• Compressor thermal protector (Q*M)
•Overcurrent relay (K*S)
• Discharge thermal protector
•Low pressure
• High pressure switch (S*PH)
•Reverse phase protector
•Freeze-up
Check on the controller and refer to
Symptom 5: Safety devices are
activated and alarm messages are
displayed.
The anti-recycling timer is still active. The circuit can only start up after
approximately 5 minutes.
The guard timer is still active.The circuit can only start up after
approximately 3 minutes.
The circuit is limited to 0%.Check the enable/disable capacity
limitation remote contact.
Symptom 5: Safety devices are activated and alarm messages are
displayed
Symptom 5.1: Freeze-up protection is activated
5.1
0A4:FREEZE UP
(
)
POSSIBLECAUSESCORRECTIVEACTION
Water flow too low.Increase the water flow.
Inlet temperature to the evaporator is
Increase the inlet water temperature.
too low.
Flow switch is not working or no
water flow.
Check the flow switch and the water
pump.
RESET After temperature increase the
freeze-up is reset automatically, but
the circuit controller needs to be
Symptom 5.2: Flowswitch is activated
5.2
0AE:FLOW HAS STOPPED
(
reset.
)
POSSIBLECAUSESCORRECTIVEACTION
No water flow or too low water flow.Check the water pump filter and the
water circuit for obstructions.
RESET After finding the cause, the
flowswitch is reset automatically, but
Symptom 5.3: Pump interlock contact is open
5.3
0AE:PUMPINTERLOCK
(
the controller still needs to be reset.
)
POSSIBLECAUSESCORRECTIVEACTION
The pump interlock contact is not
closed.
Make sure a pump interlock contact
is wired correctly and closed when
the pump starts operating.
RESET Only if a pump contactor is
present: Switch the black handle on
the pump fuse inside the switchbox
Symptom 5.4: Fan overcurrent is activated
5.4
153/253:FAN OVERC. 1/2/3
(
and reset the controller.
)
POSSIBLECAUSESCORRECTIVEACTION
Mechanical failure (fan is blocked).Check that the fan rotates freely.
Air flow in the unit too low or outdoor
temperature too high.
Clean the air heat exchanger
properly.
RESET Push the blue button on the fan fuse
inside the switchbox and reset the
Symptom 5.5: EEV driver is not operating
5.5
0A9:EEV PCB (COMM) ERR, 1A9/2A9:EEV ERR
(
controller.
)
POSSIBLECAUSESCORRECTIVEACTION
The EEV driver is not operating.Check the power supply to the EEV
driver.
Check if the address setting by
DIP-switch is according to the
wiring diagram.
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
20
Page 22
Symptom 5.6: Superheat temperature is not correct
5.6
1A9/2A9:SUPERHEAT ERR
(
)
POSSIBLECAUSESCORRECTIVEACTION
Superheat temperature is too high.Check if the unit has enough
refrigerant (no foaming visible in
sight glass).
Check if the suction temperature
sensor of the EEV driver is in the
holder in the suction tube and not
hanging loose.
Superheat temperature is too low.Check if the EEV driver or the control
motor of EEV is wired correctly and
operating.
The sensed suction temperature is
more than 2°C higher than the
entering water temperature of the
evaporator.
Symptom 5.7: High-pressure switch and high pressure setback
5.7
1E3/2E3:HIGH PRESSURE SW, 1E3/2E3:HP SETBACK
(
Check if the suction temperature
sensor of the controller is in its
holder and not hanging loose.
)
POSSIBLECAUSESCORRECTIVEACTION
Condenser fan does not operate
properly.
Check that the fans turn freely. Clean
if necessary.
Dirty or partially blocked condenser.Remove any obstacle and clean
condenser coil using brush and
blower.
Inlet air temperature of the
condenser is too high.
The air temperature measured at the
inlet of the condenser may not
exceed 43°C.
Fan turning in the wrong direction.Two phases of the power supply to
the fan motor must be inverted (by a
licensed electrician).
RESET After pressure rise, this safety resets
automatically, but the controller still
Symptom 5.8: Low pressure
5.8
1E4/2E4:LOW PRESSURE
(
needs to be reset.
)
POSSIBLECAUSESCORRECTIVEACTION
Water flow to water heat exchanger
Increase the water flow.
too low.
Shortage of refrigerant.Check for leaks and refill refrigerant,
if necessary.
Unit is working out of its operation
range.
Inlet temperature to the water heat
Check the operation conditions of
the unit.
Increase the inlet water temperature.
exchanger is too low.
Dirty evaporator.Clean the evaporator, or call your
local dealer.
Low pressure safety setting too high. Refer to the installation manual
"Customization in the service menu",
paragraph "Setting of the minimum
outlet water temperature" for correct
values.
Flowswitch is not working or no
water flow.
Check the flowswitch and the water
pump.
RESET After pressure rise, this safety resets
automatically, but the controller still
Symptom 5.9a: The compressor does not work (only for SJ161-4)
5.9a
(Compressor thermal protection is activated)
needs to be reset.
POSSIBLECAUSESCORRECTIVEACTION
The compressor motor coil
temperature is too high because the
compressor motor takes
(demands/needs) too much current
and is not sufficiently cooled by
refrigerant.
Make sure there are no refrigerant
leaks.
After repairing leaks, charge the unit
with additional refrigerant until the
sight glass in the liquid line shows no
foaming.
Make sure the unit operates within
its operating range (too high ambient
or too high water temperature).
Make sure the compressor motor is
not locked.
RESET After temperature decrease the
thermal protector is reset
automatically and the compressor
will start again. This is not detected
by the controller.
If the protector is activated
frequently, call your local dealer.
Symptom 5.9b: Compressor safety (only for SJ161-4)
5.9b
1E6/2E6:COMPR 1/2 SAFETY)
(
POSSIBLECAUSESCORRECTIVEACTION
Failure of one of the phases.Check fuses on the supply panel or
measure the supply voltage.
Voltage too low.Measure the supply voltage.
The unit is working out of its range.Make sure the unit operates within
its operating range.
Overload of motor.Reset. If the failure persists, call your
local dealer.
There is a short circuit.Check the wiring.
RESET Pull the black handle on the
compressor fuse inside the switch
Symptom 5.10: Compressor safety (only for SJ180-4~SJ240-4 and SJ300-4)
5.10
1E6/2E6:COMPR 1/2 SAFETY
(
box and reset the controller.
)
POSSIBLECAUSESCORRECTIVEACTION
The compressor motor coil
temperature is too high because the
compressor motor takes
(demands/needs) too much current
and is not sufficiently cooled by
refrigerant.
Make sure there are no refrigerant
leaks.
After repairing leaks, charge the unit
with additional refrigerant until the
sight glass in the liquid line shows no
foaming.
Make sure the unit operates within
its operating range (too high ambient
or too high water temperature).
Make sure the compressor motor is
not locked.
RESET After temperature decrease, a 5
minute delay is activated. After this
delay the relay in the electronic
protection module (EPM) is pulled in.
The controller needs to be reset
manually.
Failure of one of the phases.Check fuses on the supply panel or
measure the supply voltage.
Voltage too low.Measure the supply voltage.
The unit is working out of its range.Make sure the unit operates within
its operating range.
Overload of motor.Reset. If the failure persists, call your
local dealer.
The compressor is running in
reverse phase (only for SJ240-
Check the wiring.
SJ300)
There is a short circuit.Check the wiring.
RESET Pull the black handle on the
compressor fuse inside the switch
Symptom 5.11: Discharge thermal protector is activated
5.11
1F3/2F3:HIGH DISCH TEMP1/2
(
box and reset the controller.
)
POSSIBLECAUSESCORRECTIVEACTION
Unit is working outside the operation
range.
Check the operation condition of the
unit.
The unit is undercharged.Check if there are no refrigerant
leaks.
After repairing leaks, charge the unit
with additional refrigerant until the
sight glass in the liquid line shows no
foaming.
RESET After temperature decrease, the
Symptom 5.12: Reverse phase protector is activated
5.12
1U1/2U1:REV PHASE PROT
(
safety resets automatically but the
controller still needs to be reset.
)
POSSIBLECAUSESCORRECTIVEACTION
Tw o phases of the power supply are
connected in the wrong phase
position.
One phase is not connected
Invert two phases of the power
supply (by licensed electrician).
Check the connection of all phases.
properly.
Voltage too low.Measure the supply voltage.
RESET After inverting two phases or fixing
the power supply cables properly,
the protector is reset automatically,
but the controller still needs to be
reset.
Operation manual
21
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 23
Symptom 6: Unit stops soon after operation
One of the safety devices is
activated.
Voltage is too low.Test the voltage in the supply panel
Symptom 7: Sensor error
The sensor is broken or not correctly
wired.
Symptom 8: The alarm message shows
The software for the wired remote
controller (A4P or A5P) is corrupt or
absent.
Symptom 9: The alarm message shows
The extension PCB (A01P) can not
be found.
6
POSSIBLECAUSESCORRECTIVEACTION
Check safety devices (refer to
Symptom 5: Safety devices are
activated and alarm messages are
displayed).
and, if necessary, in the electrical
compartment of the unit (voltage
drop due to supply cables is too
high).
0C9/0CA/0H9:*** SENSOR ERR
7
POSSIBLECAUSESCORRECTIVEACTION
Check if the wiring is according to
the wiring diagram.
Call your local dealer.
0U3:REMOCON SW ERR
8
POSSIBLECAUSESCORRECTIVEACTION
Check if the wiring to the main PCB
(A11P) is according to the wiring
diagram.
Check if the "address setting" and
the "terminator resistor setting" by
DIP-switch is according to the setting
mentioned in the wiring diagram.
Call your local dealer.
0U4:EXT PCB COMM.ERR
9
POSSIBLECAUSESCORRECTIVEACTION
Check if the wiring to the extension
PCB (A01P) is according to the
wiring diagram.
Call your local dealer.
Symptom 13: The
NETWORK SAFETY
alarm message shows
0U4:SW VERSION ERR
13
POSSIBLECAUSESCORRECTIVEACTION
All units in the DICN system
(EKACPG) do not have the same
software version.
Symptom 14: The water pressure can not be maintained
POSSIBLECAUSESCORRECTIVEACTION
There is a leak in the water circuit.Check for any leaks in the water
The expansion vessel is broken or
does not work properly.
Check the software version of each
unit.
Call your local dealer in case a
software upgrade is necessary.
circuit.
Replace the expansion vessel.
MAINTENANCE
In order to ensure optimal availability of the unit, a number of checks
and inspections on the unit and the field wiring have to be carried out
at regular intervals.
If the unit is used for air conditioning application, the described
checks must be executed at least once a year. In case the unit is
used for other applications, the checks must be executed every
4 months.
Before carrying out any maintenance or repair activity,
always switch off the circuit breaker on the supply panel,
remove the fuses or open the protection devices of the
unit.
Never clean the unit with water under pressure.
Maintenance activities
Symptom 10: The alarm message shows
The main PCB of circuit 2 (A21P)
can not be found.
Symptom 11: The alarm message shows
The wired remote controller (A4P or
A5P (EKRUPG)) has no correct
communication with the main PCB
(A11P).
Symptom 12: The
10
POSSIBLECAUSESCORRECTIVEACTION
Check if the wiring to the main PCB
of circuit 2 (A21P) is according to the
wiring diagram.
Check if the "address setting" and
the "terminator resistor setting" by
DIP-switch is according to the setting
mentioned in the wiring diagram.
Call your local dealer.
11
POSSIBLECAUSESCORRECTIVEACTION
Check if the wiring to the main PCB
(A11P) is according to the wiring
diagram.
Check if the "address setting" and
the "terminator resistor setting" by
DIP-switch is according to the setting
mentioned in the wiring diagram.
Call your local dealer.
NETWORK SAFETY
0U4:PCB COMM.PROBLEM
12
POSSIBLECAUSESCORRECTIVEACTION
The unit can not be found by the
DICN system (EKACPG)
Check if the wiring between units is
according to the wiring diagram.
• Make sure all the units in the DICN system
• Make sure that the correct number of slave
• Make sure that the correct unit address
0U4:MAINPCB COMM.ERR
0U5:PCB COMM.PROBLEM
alarm message shows
are powered up.
units is defined in the master unit.
setting is defined in each unit (refer to the
installation manual).
The wiring and power supply must be checked by a
licensed electrician.
■Air heat exchanger
Remove dust and any other contaminant from the coil fins using
a brush and a blower. Blow from the inside of the unit. Take care
not to bend or damage the fins.
■Field wiring and power supply
• Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage marked on the identification label of the unit.
• Check the connections and make sure they are properly fixed.
• Check the proper operation of the circuit breaker and the earth
leak detector provided on the local supply panel.
■Internal wiring of the unit
Visually check the switch boxes on loose connections (terminals
and components). Make sure that the electrical components are
not damaged or loose.
■Earth connection
Make sure that the earth wires are still connected properly and
that the earth terminals are tightened.
■Refrigerant circuit
• Check for leaks inside the unit. In case a leak is detected, call
your local dealer.
• Check the working pressure of the unit. Refer to "Switching the
unit on" on page 8.
■Compressor
• Check on oil leaks. If there is an oil leak, call your local dealer.
• Check for abnormal noises and vibrations. If the compressor is
damaged, call your local dealer.
■Fan motor
• Clean the cooling ribs of the motor.
• Check on abnormal noises. If the fan or motor are damaged, call
your local dealer.
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
22
Page 24
■Water supply
• Check if the water connection is still well fixed.
• Check the water quality (refer to the installation manual of the unit
for specifications of the water quality).
■Water filters
• Make sure to clean the water filter in front of the evaporator water
inlet once every 4 months.
• Check the filter for any possible damage and make sure that the
hole diameter size all over the filter surface is still 1.0 mm
maximum.
■Water sensors
Check that all the water sensors are correctly fixed into the inlet
and outlet water pipe.
■Flowswitch
Make sure that there is no dirt accumulating on the paddle of the
flowswitch.
■Water pressure
Check if the water pressure is within acceptable range. Refer to
the installation manual delivered with the unit.
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
NOTES
Operation manual
23
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 25
NOTES
EWAQ080~260DAYN
Packaged air-cooled water chillers
4PW35556-1F – 2014.03
Operation manual
24
Page 26
ANNEX I
a/2
a/2
a/2
a/2
a/2
a/2
Thermostat parameters
Water temperature control
The figures below show the thermostat diagram in case of inlet water temperature control.
■Stand alone thermostat
a/2
a/2
a/2
a/2
cc
cc
Inlet setpoint
(1)
(inlet or outlet)
a/2
a/2
a/2
a/2
cc
cc
Outlet setpoint
■DICN thermostat
Load up request of 1 compressor
no action
Load down request of 1 compressor
The default value and the upper and lower limits of the
thermostat parameters are listed in the table below.
Default value
Units 1
(sec)
(sec)
(°C)
(sec)
(sec)
(°C)
(K)
(K)
(K)
(K)
circuit
Units 1
circuit
INLET CONTROL
Step difference - a
Steplength - c
Loadup timer
Loaddown timer
Setpoint
(*) can only be modified in the service menu
OUTLET CONTROL
Step difference - a
Steplength - c
Loadup timer
Loaddown timer
Setpoint
(*) can only be modified in the service menu
4.0
(*)
0.2
Units 2
circuits
(*)
2.0
Lower
limit
(*)
——
——
18015300
3015300
12.07.023.0
Default value
4.0
(*)
0.2
Units 2
circuits
(*)
2.0
Lower
limit
(*)
——
——
3015300
1515300
7.04.020.0
Upper
limit
Upper limit
The default value and the upper and lower limits of the
thermostat parameters are listed in the table below.
INLET CONTROLDefault value Lower limitUpper limit
Step difference - a
Step difference - b
Step difference - c
Loadup timer
Loaddown timer
Setpoint
(*) can only be modified in the service menu
■If the temperature is below the setpoint, the thermostat control
will check every LOADDOWN TIMER.
According to the deviation to the setpoint, no action, load up,
down is required.
■If the temperature is above the setpoint, the thermostat control
will check every LOADUP TIMER.
According to the deviation to the setpoint, no action, load up,
down is required.
(1)
(inlet)
a/2
a/2 a/2
a/2
bb
bb
cccc
cccc
Inlet setpoint
(K)
(K)
(K)
(sec)
(sec)
(°C)
Load up request of 4 compressors
Load up request of 3 compressors
Load up request of 2 compressors
Load up request of 1 compressor
no action
Load down request of 1 compressor
Load down request of 2 compressors
Load down request of 3 compressors
Load down request of 4 compressors
(*)
4.0
3.6
0.4
(*)
(*)
——
——
——
18015300
18015300
12.07.023.0
Operation manual
25
(1) Loadup request of 1 compressor: request to add one additional compressor.
Loadup request of 2 compressors: request to add 2 additional compressors (with interval of 15 seconds inbetween).
The maximum number of compressors that can possibly be added in 1 request is limited to the total number of units that are present in the DICN setup:
Example: A DICN setup with 2 units means load up requests of maximum 2 compressors at a time.
Packaged air-cooled water chillers
EWAQ080~260DAYN
4PW35556-1F – 2014.03
Page 27
ANNEX II
Floating setpoint working
The diagrams and table below show the default value of the floating
setpoint parameters on the evaporator and an example on the inlet
setpoint of 12.0°C.
Legend
SLOPEThe rise in floating setpoint value for a 10°C drop (floating
AActive setpoint
BSetpoint
■Floating setpoint based on ambient
A
B
■Floating setpoint based on NTC
A
B
setpoint based on ambient or NTC) or a drop of 100 (floating
setpoint based on voltage or milliampere).