Daikin EKHWS050B3VJU, EKHWS080B3VJU Installation Manual

INSTALLATION MANUAL
Domestic hot water tank for air to water heat
pump system
EKHWS050B3VJU EKHWS080B3VJU
Installation manual
Domestic hot water tank for air to water heat pump system
Manuel d'installation
Ballon d'eau chaude domestique pour
Manual de instalación
Depósito de agua caliente sanitaria para
instalaciones con bomba de calor aire-agua
English
Français
Español
12 3 54
1
1x 1x 2x 4x 1x
1
2
73°
3.9 inch
(100 m
6
1x
+
m
)
11.8 inch
(300 mm)
H1
H4
H2
H3
105°
45°
30°
5°
15°
15.7 inch
(400 mm)
62°
8
3/4" FBSP
1
9
2
6
3/4" FBSP
3
1/2" FBSP
7
3/4" FBSP
4
3/4" FBSP
5
0
2
8.7 inch (220 mm)
(0~40 mm)
4.3 inch
0~1.6 inch
(110 mm)
9
Ø22.8 inch
(580 mm)
Domestic hot water tank
for air to water heat pump system
age
P
C
ONTENTS
EKHWS050B3VJU EKHWS080B3VJU
Introduction........................................................................................ 1
General information ...................................................................................1
Scope of this manual .................................................................................1
Model identification ....................................................................................1
Accessories .......................................................................................1
Accessories supplied with the domestic hot water tank............................. 1
Safety considerations ........................................................................2
Installation of the EKHWS domestic hot water tank ..........................3
Main components....................................................................................... 4
Outlook diagram......................................................................................... 5
Installation guidelines................................................................................. 5
Installing the domestic hot water tank........................................................ 5
Connecting the water circuits..................................................................... 5
Field wiring................................................................................................. 7
Maintenance......................................................................................8
Troubleshooting .................................................................................9
General guidelines.....................................................................................9
General symptoms..................................................................................... 9
Technical specifications.....................................................................9
Domestic hot water tank specifications...................................................... 9
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL BE CARRIED OUT BY A LICENSED TECHNICIAN.
BE SURE TO WEAR ADEQUATE PERSONEL PROTEC­TION EQUIPMENT (PROTECTION GLOVES, SAFETY GLASSES, ...) WHEN PERFORMING INSTALLATION, MAINTENANCE OR SERVICE TO THE UNIT.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT TEMPERATURES RANGING 39°F~95°F (4°C~35°C).
The English text is the original instruction. Other languages are translations of the original instructions.
Installation manual
NTRODUCTION
I
General information
The EKHWS domestic hot water tank with integrated 3 kW electrical booster heater can be connected to the indoor unit. The domestic hot water tank is available in 2 sizes: 50 and 80 gallons (200 and 300 litre). These domestic hot water tanks are floor standing models.
Scope of this manual
This installation manual describes the procedure for unpacking, installing and connecting the EKHWS domestic hot water tank.
Model identification
EK HWS 050 B 3 VJU
Booster heater voltage VJU = 1P, 208/230 V
Capacity booster heater: 3 kW
Series
Indication of storage capacity in gallons
Hot Water tank Stainless steel
Kit
CCESSORIES
A
Accessories supplied with the domestic hot water tank
See figure 1
1
Thermistor + connection wire (39.4 ft) (=12 m)
2
Contactor - circuit breaker assembly
3
Contactor fixing screw
4
Tapping screw
5
Installation manual
6
3-way valve + motor
EKHWS050+080B3VJU
Domestic hot water tank for air to water heat pump system
4PW56114-1
Installation manual
1
S
AFETY CONSIDERATIONS
The precautions listed here are divided into the following four types. They all cover very important topics, so be sure to follow them carefully.
Meanings of
DANGER, WARNING, CAUTION
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates situations that may result in equipment or property-damage accidents only.
and
NOTE
symbols.
Danger
Before touching electric terminal parts, turn off power switch.
When service panels are removed, live parts can be easily touched by accident.
Never leave the unit unattended during installation or servicing when the service panel is removed.
Do not touch water pipes during and immediately after operation as the pipes may be hot. Your hand may suffer burns. To avoid injury, give the piping time to return to normal temperature or be sure to wear proper gloves.
Do not touch any switch with wet fingers. Touching a switch with wet fingers can cause electrical shock.
Before touching electrical parts, turn off all applicable power supply.
Warning
Tear apart and throw away plastic packaging bags so that children will not play with them.
Children playing with plastic bags face danger of death by suffocation.
Safely dispose of packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Be aware that the domestic hot water temperature can/will be higher than the user set point for domestic hot water depending on the selected values of certain field settings (example 2). Refer to the field settings in the installation manual of the indoor unit EKHBH/X or outdoor unit EBLQ, EBHQ, EDLQ, EDHQ.
If this high domestic hot water temperature can be a potential risk for human injuries, a mixing valve (field supply) shall be installed at the hot water outlet connection of the domestic hot water tank. This mixing valve shall secure that the hot water temperature at the hot water tap never rise above a set maximum value. This maximum allowable hot water temperature shall be selected according to local laws and regulations.
Caution
Ground the unit. Grounding resistance should be according to local laws and
regulations. Do not connect the ground wire to gas or water pipes,
lightning conductor or telephone ground wire. Incomplete grounding may cause electric shocks.
Gas pipe. Ignition or explosion may occur if the gas leaks.
Water pipe. Hard vinyl tubes are not effective grounds.
Lightning conductor or telephone ground wire. Electric potential may rise abnormally if struck by a lightning bolt.
Install the power wire at least 3.28 ft (1 meter) away from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.28 ft (1 meter) may not be sufficient to eliminate the noise.)
Do not rinse the unit. This may cause electric shocks or fire.
Do not install the unit in places such as the following:
Where there is mist of mineral oil, oil spray or vapour. Plastic parts may deteriorate, and cause them to fall out or water to leak.
Where corrosive gas, such as sulphurous acid gas, is produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Where there is machinery which emits electromagnetic waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled. Such gases may cause a fire.
Where the air contains high levels of salt.
Where voltage fluctuates a lot, such as that in factories.
In vehicles or vessels.
Where acidic or alkaline vapour is present.
Installation manual
2
Domestic hot water tank for air to water heat pump system
EKHWS050+080B3VJU
4PW56114-1
I
NSTALLATION OF THE
WATER TANK
CAUTION
The total system (indoor and outdoor unit) is designed for combination with a domestic hot water tank. In case another tank is being used in combination with the unit, Daikin cannot guarantee neither good operation nor reliability of the system. For those reasons Daikin cannot give warranty of the system in such case.
The equipment is not intended for use in a potentially explosive atmosphere.
Only this tank can be used in combination with the solar kit option (EKSOLHW*).
Domestic hot water quality must be according to "Safe Drinking water Act (42 U.S.C. 300f)".
Do not connect to any heating system or component previously used with a non potable water heating appliance.
Do not introduce toxic chemicals, such as used for boiler treatment, into the system.
Fill system only with water (EKHBH, EKHBX, EDLQ, EBLQ) or water with propylene glycol and inhibitor (only for EDLQ, EBLQ), having a toxicity rating or Class of 1, as listed in Clinical Toxicology of Commercial products, 5th edition.
If glycol is used, limit the pressure in the system to 30 psi (2.07 bar) by means of an approved pressure relief valve. Refer to the figure in "Safety devices" on page 4.
It is not allowed to add ethylene glycol to the water circuit. Adding ethylene glycol might lead to contamination of the domestic water if a leakage would occur in the heat exchanger coil.
EKHWS
DOMESTIC HOT
CAUTION
In case of limited consumption of domestic hot water, e.g. at holiday residences or at houses that are occasionally not occupied, the domestic hot water tank installation must be fitted with a shunt pump.
The shunt pump can be time-controlled,
the shunt pump must operate to circulate the complete volume of the domestic hot water tank 1.5 times per hour,
and the shunt pump must operate, or be programmed for operation, during 2 uninterrupted hours per day at least.
2
3
1 Cold water
connection
2 Hot water connection 3 Shunt pump
(field supply)
4 Non-return valve
(field supply)
1
4
In case of very long field water piping between the domestic hot water tank and the hot water end point (shower, bath, etc.) it can take more time before the hot water from the domestic hot water tank reaches the hot water end point.
1 Shower
1
2
2 Recirculation pump
If required connect a recirculation pump in between the hot water end point and the recirculation hole in the domestic hot water tank.
NOTE
A drain device should be installed on the cold water connection on the domestic hot water tank.
It is important that the storage capacity of the domestic hot water tank meets normal daily fluctuations in consumption of domestic hot water without any fall of the water outlet temperature during use.
Immediately after installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.
EKHWS050+080B3VJU
Domestic hot water tank for air to water heat pump system
4PW56114-1
Installation manual
3
Main components
1 Pressure relief valve
14
5
15
6 7
8
9
F
10
13
NOTE
T-piece (field supply)(1) is only necessary if a pressure relief valve is required on the hot water side and the temperature and pressure relief
2
1
H
3
4
valve connection (14) is already used for a temperature and pressure relief valve.
Temperature and pressure relief valve connection (14) shall be used in case a temperature and pressure relief valve (field supply) is required according to local laws and regulations.
Safety devices
CAUTION
The domestic hot water tank relief valve connections may not be used for other purpose.
Do not install heaters without thermal cut-outs.
15
16
Thermal protector — The booster heater in the domestic hot water tank is equipped with a thermal protector. The thermal protector is activated when the temperature becomes too high. When activated, the protector has to be reset on the domestic hot water tank by pressing the red button (for access, remove the electrical box lid).
CAUTION
The electrical box lid must only be opened by a licensed electrician.
Switch off the power supply before opening the electrical box lid.
11
R
12
C
1
Field supply
2
Hot water connection (H)
3
Pressure relief valve connection
4
Pressure relief valve (field supply)
5
Electrical box
6
Electrical box lid
7
Recirculation hole
8
Thermistor socket
9
Flow inlet connection (F) (from the main unit)
10
Heat exchanger coil
11
Return outlet connection (R) (to the main unit)
12
Cold water connection (C)
13
Threaded thermistor hole for use with the solar kit option. Refer to the installation manual EKSOLHW*.
14
Temperature and pressure relief valve connection
15
Thermal protectors (Q2L, Q3L)
16
Booster heater
Pressure relief valve — A pressure relief valve (field supply) in accordance with relevant local laws and regulations, and with an opening pressure of maximum 145 psi (10 bar) must be connected to the pressure relief valve connection.
If a discharge pipe is connected to the pressure relief device it must be installed in a continuously downward direction and in a frost-free environment. It must be left open to the atmosphere.
If glycol is used, an approved pressure relief valve with an opening pressure of maximum 30 psi (2.07 bar) (field supply) must be installed in the inlet of the tank as shown in the figure below.
1
Flow direction
Installation manual
4
Domestic hot water tank for air to water heat pump system
EKHWS050+080B3VJU
4PW56114-1
Outlook diagram
Installing the domestic hot water tank
Outlook diagram, see figure 2.
1
Hot water and pressure relief valve connection
2
Recirculation hole
3
Flow inlet connection (from the main unit)
4
Return outlet connection (to the main unit)
5
Cold water connection
6
Thermistor socket
7
Threaded thermistor hole for use with solar kit option. See Installation manual EKSOLHW*.
8
Temperature and pressure relief valve connection
9
Remove the protection tape from the domestic hot water tank
Domestic hot water tank model H1 H2 H3 H4
EKHWS050B3VJU
EKHWS080B3VJU
(inch) 45.3 24.8 7.9 32.7 (mm) 1150 630 200 830 (inch) 63.0 24.8 7.9 32.7 (mm) 1600 630 200 830
Installation guidelines
Keep in mind the following guidelines when installing the domestic hot water tank:
The installation location is frost-free.
Make sure to make the piping in size 1" or more (and reduce to 3/4" at the inlet of the tank) as to have sufficient water volume in the piping between unit and domestic hot water tank.
Locate the domestic hot water tank in a suitable position to facilitate ease of maintenance; remember access is required to the electrical box. Refer to the grey-coloured zones indicated in figure 2.
Provide a connection for the pressure relief valve blow-off and drain.
To avoid back siphonage it is advised to install a non-return valve on the water inlet of the domestic hot water tank in accordance with local laws and regulations.
Ta ke care that in the event of a leak, water can not cause any damage to the installation space and surroundings.
1
Check if all domestic hot water tank accessories (see "Accessories" on page 1) are enclosed.
2
Place the domestic hot water tank on a level surface.
3
Remove the protection tape from the domestic hot water tank (See (8) in figure 2).
4
Apply thermal paste to the thermistor and insert the thermistor as deep as possible in the thermistor socket. Fix using the nut provided.
Connecting the water circuits
Refer to the chapter "Typical application examples" described in the installation manual delivered with the indoor unit for details on connecting the water circuits and the motorised 3-way valve.
EKHWS050+080B3VJU
Domestic hot water tank for air to water heat pump system
4PW56114-1
Connecting the 3-way valve
1
Refer to the figure below before making the connection. Values between brackets are the conversion from inch to mm.
1.73
1.73
Installation manual
3.03 (77)
14.37 (111)
0.51 (13)
1.50 (38)
2.64 (67)
(44)
(44)
5
2
Installation position. It is advised to connect the 3-way valve as close as possible to
the unit. It can be installed in accordance with one of the following four configurations.
1
1
2
NOTE
If the valve is not positioned in this way before mount­ing the motor, the valve will give way to both domestic water and room heating during operation.
5
When installing in accordance with figure A or figure D, open the valve motor cover by loosening the screw and change the jumper so as to change the rotation direction of the valve.
By default the jumper is factory set to apply for installation in accordance with figure B and figure C.
3
Installation in accordance with
figure A and figure D
Installation in accordance with
figure B and figure C
3
figure A figure B
1
2
3
figure C figure D
1
From indoor unit
2
To domestic hot water tank
3
To room heating
3
Unpack the 3-way valve body and 3-way valve motor. Ver ify that following accessories are provided with the motor.
2
1
Sleeve
2
Valve motor cover
3
Screw
4 Scale
1
3
1
3
2
4
2
DIR
2P
Y
N
L
Rotation direction of the valve
6
Push the motor on the motor sleeve. Make sure not to rotate the sleeve during this action, so as to
maintain the valve position as set during step 4.
7
8
Put the scale on the valve as shown below.
Domestic hot
water tank Room heating Room heating
Installation in accordance with
figure B and figure C
9
Make sure to firmly fix the power supply cord onto the 3-way
Installation in accordance with
valve body with a field supplied cable tie like in illustration below.
Domestic hot
water tank
figure A and figure D
4
Install the 3-way valve body in the pipework.
• Make sure the shaft will be positioned in such a way that the motor can be mounted and replaced.
• Put the sleeve on the valve and turn the valve to the middle position of the scale plate. Check that the valve is positioned as in the figure below. It shall be blocking the outlet connection to the domestic hot water for 50% and the outlet connection to the room heating also for 50%.
Installation in accordance with
figure A and figure B
Installation manual
Installation in accordance with
figure C and figure D
6
10
Perform the wiring in the unit in accordance with the following figure:
8910
3-way valve
BRN
BLU
BLK
LNY
Refer also to the drawing on page 8.
11
Connect the water inlet and water outlet.
12
Connect the hot and cold water supply tubes.
Domestic hot water tank for air to water heat pump system
EKHWS050+080B3VJU
4PW56114-1
13 Connect the pressure relief valve (field supply, opening pressure
maximum 145 psi (10 bar)) and drain.
CAUTION
If a discharge pipe is connected to the pressure relief device it must be installed in a continuously downward direction and in a frost-free environment. It must be left open to the atmosphere.
2 Make sure to ensure strain relief of the cable by correct use of
the PG nipple and PG nut (mounted on the domestic hot water tank).
Field wiring
CAUTION
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local laws and regulations.
All field wiring and components must be installed by a licensed electrician and must comply with relevant local laws and regulations.
The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below.
The domestic hot water tank must be grounded via the indoor unit.
Be sure to use a dedicated power supply. Never use a power supply shared by another appliance.
Make sure all field wiring is insulated from the tank body and heater element or can resist temperatures to 194°F (90°C).
Select the power cable in accordance with relevant local laws and regulations.
Be sure to install the required fuse or circuit breaker.
For cable requirements and specifications, refer to "Field wiring" in the indoor unit installation manual supplied with the EKHBX unit.
Thermistor cable
The distance between the thermistor cable and power supply cable must always be at least 2 inch (5 cm) to prevent electromagnetic interference on the thermistor cable.
DANGER
Switch off all relevant power supply (outdoor unit, backup heater, booster heater) before changing the connector.
Connections to be made in the domestic hot water tank electrical box
1 Refer to the wiring diagram sticker in the domestic hot water
tank switch box.
4 3 2 1
Cable entry:
1 Power supply booster heater (X6M) 2 Power supply to EKSOLHW* pump (X8M, grounding, 1-2) 3 Power supply from EKHBH/X or EBLQ, EBHQ, EDLQ, EDHQ
for EKSOLHW* (X8M, grounding, 1-2)
4 Thermal protector (Q3L, 3-4)
The power supply cable towards the booster heater X4MX6M and the cable towards the thermal protector X2M (13-14)Q3L (4-3) are separated. However, if allowed according to local laws and regulations, these 2 cables can be combined in 1 cable (5 wires).
Connections to be made in the indoor unit switch box 3 Mount the prewired contactor (K3M), circuit breaker (F2B) and
terminal blocks (X3M, X4M). The contactor must be fixed with the 2 supplied contactor screws and the terminal blocks must be fixed with the 2x 2 supplied tapping screws.
4 Plug the connector connected to the contactor K3M in the
socket X13A on the PCB.
5 Plug the thermistor cable connector in the socket X9A on the
PCB.
6 Connect the prewired ground wires of the terminal block X3M
and X4M to the grounding screw.
7 Connect the booster heater power supply and thermal protection
cable (field supply) to terminal X4M ground, 1, 2, and X2M 13,
14.
8 Connect the booster heater power supply cable to the terminal
block X3M.
9 Fix the cables to the cable tie mountings with cable ties to
ensure strain relief.
10 Set DIP switch SS2-2 on the PCB to ON. 11 When routing out cables, make sure that these do not obstruct
mounting of the indoor unit cover.
EKHWS050+080B3VJU
Domestic hot water tank for air to water heat pump system
4PW56114-1
Installation manual
7
Note: only relevant field wiring and not all implemented parts are
A11P
K3M
F2B
X2M
X9A
X3M
X4M
shown.
For EXHBH/X units only
For EDH, EBH, EDL, EBL units only
X8M
TR1
K1M K2M
TR2
X9A
A1P
X13A
A4P
X2M X4M
K5M
K3M K6M
F2B F3B F1B
K3M
K3M
BRN
L
N Y
X2M
LNY
M3S
BLU
98
BLK
10
X13A
A11P
A11P
X9A
X9A
X2M
X2M
(>50 mm)
X4M
X4M
X3M
X3M
L1 L2
VJU
208/230 V AC
3 kW
X4M
X6M
F2B
F2B
X2M
2
2
4 3 Q3L
The power supply cable towards the booster heater X4MX6M and the cable towards the thermal protector X2M (13-14)Q3L (4-3) are separated. However, if allowed according to local laws and regulations, these 2 cables can be combined in 1 cable (5 wires).
>2 inch
>2 inch
(>50 mm)
BRN
L
X2M
LNY
BLU
BLK
N Y
10
98
M3S
X1M
X2M
4
Q3L
MAINTENANCE
In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out
X3M
X3M
X4M
2
L1 L2
VJU
208/230 V AC
3 kW
2
3
X6M
at regular intervals.
CAUTION
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the circuit breaker, protection devices of the unit.
Make sure that before starting any maintenance or repair activity, also the power supply to the outdoor unit is switched off.
The described checks must be executed at least once a year. 1 Domestic hot water tank pressure relief valve (field supply)
and/or temperature and pressure relief valve (field supply) Check for correct operation of the pressure relief valve and/or
temperature and pressure relief valve on the domestic hot water tank.
2 Domestic hot water tank booster heater
It is advisable to remove lime buildup on the booster heater to extend its life span, especially in regions with hard water. To do so, drain the domestic hot water tank, remove the booster heater from the domestic hot water tank and immerse in a bucket (or similar) with lime-removing product for 24 hours.