Carrier ERVXXSVB1100, HRVXXLVU1330, HRVXXSVU1157, ERVXXLHB1200, HRVXXLHB1150 Product Data

...
0 (0)
HRVXX Heat Recovery Ventilators ERVXX Energy Recovery Ventilators
Product Data
ERVXXSVB1100, HRVXXSVB1100
ERVXXSHB1100, HRVXXSHB1100
HRVXXSVU1157
A05229
A05330
A10299
A12338
The Heat Recovery Ventilation (HRV) and Energy Recovery Ventilator (ERV) systems offered by Carrier are the finest on the market today. These units provide efficient and cost effective heat recovery during the heating season when needed most.
As temperatures drop below 23_F(--5_C), indoor air is recirculated periodically through the heat exchanger core to prevent frost from forming. Competitors’ methods of supplementary electric defrost waste energy. Unlike rotary wheel heat exchangers which mix air streams, these cross--flow or counterflow heat exchangers ensure that there is no mixing of the stale air stream with the fresh outdoor air stream.
A filter installed on the incoming outdoor air stream removes large airborne particles from the intake air stream before they enter the heat exchanger and reduces the maintenance required. The units’ acoustically engineered design make Carrier ventilators the quietest on the market and ensures that comfort is felt, not heard.
Unlatching two (2) suitcase style latches allows easy removal of the filters and core for cleaning on most units.
NOTE: The unit should not be installed in an attic or unconditioned space unless provisions are made for drain line freezing and condensation.
STANDARD FEATURES
HRV
S Energy saving defrost cycle S Cross--flow, counterflow heat exchangers S One filter on incoming air; one filter on outgoing air to
protect core
S Acoustical design S Polypropylene heat exchanger core
ERV
S Integrated airflow balancing points S Integrated furnace interlock S High pressure blowers S Onboard control for continuous high/low ventilator operation S Energy saving defrost cycle S Cross--flow, counterflow heat exchangers S One filter on incoming air; one filter on outgoing air to
protect core
S No--tools maintenance S Enthalpic heat exchanger core
HRVXXLVU1330
A12339
MODEL NUMBER NOMENCLATURE
ERV XX LHB 1 150
PRODUCT TYPE CFM
ERV --- Energy Recovery Ventilator
HRV --- Heat Recovery Ventilator VOLTAGE
1 --- 115/60/1
BRAND STYLE
XX --- Dual Branded LHB --- Large Horizontal, End Ports
Installer selects and applies logo badge HRV --- 150, 250 cfm
E R V --- 2 0 0 c f m
SVB --- Small Horizontal, Top Vertical Ports
H R V & E R V --- 1 0 0 c f m
SHB --- Small Horizontal, End Ports
H R V & E R V --- 1 0 0 c f m
SVU --- Vertical, Top Ports
H R V --- 1 5 7 c f m
LVU - -- Large Vertical, Top Ports
H R V --- 3 3 0 c f m
Energy Star Canada: All units in this document meet Energy Star Tier 2 reguirements in Canada except HRVXXLVU1330reguiremen ts in Canada except HRVXXLVU1 and ERVXXLHB1200
These products earned the ENERGY STAR energy efficiency guidelines set by Natural Resources Canada and the US EPA. They meet ENERGY STAR requirements only when used in Canada.
®
by meeting strict
Climate Map for Energy and Heat Recovery Ventilators
Helena
Salt Lake City
Edmonton
Calgary
Denver
Regina
Winnipeg
Bismark
Minneapolis
Topeka
Green Bay
Madison
Des Moines
Springfield
Timmins
Milwaukee
Chicago
Indianapolis
Detroit
Ottawa
Harrisburg
Washington D.C.
Montreal
Syracuse
Hartford
Boston
Vancouver
Salem
Sacramento
Boise
Honolulu
HRV Recommended
ERV Recommended w/HRV or ERV Wall Control
ERV Recommended
Oklahoma City
Austin
2
Baton Rouge
Nashville
Atlanta
Raleigh
Columbia
Orlando
A00099
ERVXXSVB1100, HRVXXSVB1100
A
LL PORTS FIT
DIAMETER DUCTS
5
4
4’’ (102 mm)
3
6’’ (152 mm)
(64 mm)
3
12 16”
(310 mm)
2½”
13
19 16”
(503 mm)
16¼”
(413 mm)
1
2
9
16
” (574 mm)
22
23¾” (603 mm)
1: F
RESH AIR TO BUILDING PORT
2: E
XHAUST AIR FROM BUILDING PORT
3: F
RESH AIR FROM OUTSIDE PORT
4: E
XHAUST AIR TO OUTSIDE PORT
PHYSICAL & ELECTRICAL DATA
MODEL
CAPACITY (LO---HI)
CFM L/S TYPE AIR FLOW
PORT
LOC.
ERVXXSVB1100 35 --- 105 17 --- 50 Top
transfer media
Enthalpic
CORE
WEIGHT
LBS. [KG]
VOLTAGE
Cross Flow 45 [20] 115/60/1 104 1.0
HRVXXSVB1100 35 --- 105 17 --- 50 Top Polypropylene Cross Flow 42 [19] 115/60/1 100 0.85
MAX
POWER
WATTS
MAX
AMPS
DEFROST OPERATION
OUTSIDE TEMPERATURE DEFROST CYCLE (MIN.)
MODEL
ERVXXSVB1100
HRVXXSVB1100
_C _F Defrosting
--- 5 t o --- 27 23 to --- 17 9 28
B e l o w --- 27 B e l o w --- 17 10 22
--- 5 t o --- 27 23 to --- 17 8 25
B e l o w --- 27 B e l o w --- 17 10 22
Operation Time Between
Each Defrost Cycle
A12327
HVI RATED ENERGY PERFORMANCE
MODEL MODE
ERVXXSVB1100
HRVXXSVB1100
SUPPLY
TEMP
_C _F L/S CFM
0 32 23 49 42 67 79 0.61
Heat
0 32 30 64 60 65 75 0.55 0 32 40 84 72 63 71 0.48
--- 2 5 --- 1 3 21 45 58 60 75 0.60
Cool 35 95 21 44 42 50
0 32 23 50 43 65 74 0.01
Heat
0 32 30 64 58 62 70 0.01 0 32 39 83 70 59 66 0.01
--- 2 5 --- 1 3 21 45 56 60 78 0.01
Cool 35 95
NET
AIR FLOW
VENTILATION PERFORMANCE
EXT. STATIC
MODEL
PRESSURE
Pa In w.g. L/S CFM L/S CFM L/S CFM
25 0.1 54 115 55 117 55 117 50 0.2 53 112 54 115 54 114
ERVXXSVB1100
100 0.4 49 105 50 106 50 106 200 0.8 42 89 43 92 42 88 250 1.0 38 81 39 82 38 81
25 0.1 53 111 53 112 57 120 50 0.2 51 107 51 108 54 114
HRVXXSVB1100
100 0.4 46 98 47 99 49 105 200 0.8 37 79 38 80 40 85 250 1.0 34 71 34 72 36 76
NOTE: For additional data points, refer to HVI Directory at www.hvi.org
NET SUPPLY AIR
FLOW
POWER
CONSUMED
(WATTS)
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVE-
NESS
RECOVERY MOISTURE TRANSFER
GROSS AIR FLOW
SUPPLY EXHAUST
LATENT
TOTAL
RECOVERY
EFFICIENCY
3
ALL PORTS FIT 5
DIAMETER DUCTS
6”
(152 mm)
1
4” (102 mm)
ERVXXSHB1100, HRVXXSHB1100
1
27 /
16” (688 mm)
9
22 /16” (574 mm)
2
(349 mm)
13¾”
13
19 /16” (503 mm)
3
4
3
12 /16
(310 mm)
1: FRESH AIR TO BUILDING PORT 2: EXHAUST AIR FROM BUILDING PORT
2” (51 mm)
3: FRESH AIR FROM OUTSIDE PORT 4: EXHAUST AIR TO OUTSIDE PORT
PHYSICAL & ELECTRICAL DATA
MODEL
CAPACITY (LO---HI)
CFM L/S TYPE AIR FLOW
PORT
LOC.
ERVXXSHB1100 35 --- 105 17 --- 50 Ends
transfer media
Enthalpic
CORE
WEIGHT
LBS. [KG]
VOLTAGE
Cross Flow 45 [20] 115/60/1 104 1.0
HRVXXSHB1100 35 --- 105 17 --- 50 Ends Polypropylene Cross Flow 42 [19] 115/60/1 100 0.85
MAX
POWER
WATTS
MAX
AMPS
DEFROST OPERATION
OUTSIDE TEMPERATURE DEFROST CYCLE (MINUTES)
MODEL
ERVXXSHB1100
HRVXXSHB1100
_C _F Defrosting
--- 5 t o --- 27 23 to --- 17 9 28
B e l o w --- 27 B e l o w --- 17 10 22
--- 5 t o --- 27 23 to --- 17 8 25
B e l o w --- 27 B e l o w --- 17 10 22
Operation Time Between
Each Defrost Cycle
HVI RATED ENERGY PERFORMANCE
MODEL MODE
ERVXXCSHB1100
HRVXXSHB1100
SUPPLY
TEMP
NET AIR
FLOW
_C _F L/S CFM
POWER
CONSUMED
(WATTS)
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVE-
NESS
0 32 23 49 42 67 79 0.61
Heat
0 32 30 64 60 65 75 0.55 0 32 40 84 72 63 71 0.48
--- 2 5 --- 1 3 21 45 58 60 75 0.60
Cool 35 95 21 44 42 50
0 32 23 50 43 65 74 0.01
Heat
0 32 30 64 58 62 70 0.01 0 32 39 83 70 59 66 0.01
--- 2 5 --- 1 3 21 45 56 60 78 0.01
Cool 35 95
LATENT
RECOVERY
MOISTURE
TRANSFER
TOTAL
RECOVERY
EFFICIENCY
VENTILATION PERFORMANCE
MODEL
EXT. STATIC
PRESSURE
NET SUPPLY AIR
FLOW
Pa In w.g. L/S CFM L/S CFM L/S CFM
25 0.1 54 115 55 117 55 117 50 0.2 53 112 54 115 54 114
ERVXXSHB1100
100 0.4 49 105 50 106 50 106 200 0.8 42 89 43 92 42 88 250 1.0 38 81 39 82 38 81
25 0.1 53 111 53 112 57 120 50 0.2 51 107 51 108 54 114
HRVXXSHB1100
100 0.4 46 98 47 99 49 105 200 0.8 37 79 38 80 40 85 250 1.0 34 71 34 72 36 76
NOTE: For additional data points, refer to HVI Directory at www.hvi.org
SUPPLY EXHAUST
GROSS AIR FLOW
A12328
4
ERVXXLHB1200, HRVXXLHB1150, HRVXXLHB1250
39” (991 mm)
34” (864 mm)
3
ERV
4
1. Fresh air to house.
2. Exhaust air from house.
3. Fresh air from outside.
4. Exhaust air to outside.
35” (891 mm)
30¼” (768 mm)
3
HRV
4
PHYSICAL & ELECTRICAL DATA
MODEL
CFM L/S TYPE AIR FLOW
ERVXXLHB1200 80 --- 198 38 --- 93 Ends
CAPACITY (LO---HI)
PORT
LOC.
transfer media
HRVXXLHB1150 66 --- 163 31 --- 77 Ends Polypropylene Cross flow 65 [30] 115/60/1 160 1.5 HRVXXLHB1250 82 --- 204 39 --- 96 Ends Polypropylene Cross flow 65 [30] 115/60/1 195 2.1
Enthalpic
CORE
WEIGHT
LBS. [KG]
VOLTAGE
Cross flow 76 [35] 115/60/1 200 2.1
17¼” (438 mm)
2
17¼” (438 mm)
2
MAX
POWER
WATTS
1
6”
(152 mm)
1
6”
(152 mm)
AMPS
17”
(432 mm)
17”
(432 mm)
A12341
MAX
DEFROST OPERATION
MODEL
ERVXXLHB1200
HRVXXLHB1150
HRVXXLHB1250
OUTSIDE TEMPERATURE DEFROST CYCLE (MIN.)
Operation Time
_C _F Defrosting
Between Each
Defrost Cycle
EXTENDED DEFROST CYCLES
(MIN.)
Operation Time
Defrosting
Between Each
Defrost Cycle
--- 5 23 10 60 10 30
--- 1 5 5 10 30 10 20
--- 2 7 --- 1 7 10 20 10 15
--- 5 23 7 50 10 30
--- 1 5 5 7 25 10 20
--- 2 7 --- 1 7 10 20 10 15
--- 5 23 6 50 10 30
--- 1 5 5 6 25 10 20
--- 2 7 --- 1 7 10 20 10 15
5
Loading...