Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5c
PC 903Catalog No. 533-070Printed in U.S.A.Form 30H-10SIPg 111-98Replaces: 30H-8SI
GENERAL
These installation instructions cover the 30HK, HL, HWA,
HWB, HWC, and HWS units. The HL and HWA are condenserless units, and the HK, HWB, HWC, and HWS units
are all fluid cooled. In addition, the 30HK and HWC units
have a standard mechanically cleanable condenser and the
30HWS unit has a mechanically cleanable condenser specifically designed for sea coast applications.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment
(Fig. 1-3) can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated
structures, etc.).
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
Be sure all power to equipment is shut off before performing maintenance or service. There may be more than
one disconnect. Tag all disconnects to alert others not to
turn on power until work is completed.
Fig. 2 — 30HWA,B Unit
Fig. 1 — 30HK,HL Unit (30HK Shown)
Fig. 3 — 30HWC,S Unit
2
INSTALLATION
Location—
because of sensitive control mechanisms and electronic
devices. Locate unit indoors. See Fig. 4-8 for unit dimensional details.
Allow 36 in. (914 mm) in front of the unit for control box
access door. Compressor can be removed from either side or
the front of the unit. Prior to installation determine which
direction compressor will be removed, and leave 3 to 4 ft
(914 to 1219 mm) clearance for removal.
On 30HK,HL units leave 7
9 ft (2.7 m) (for 050,060 units) clearance on one side for
cooler tube removal. Leave 2 ft (610 mm) clearance on the
other side for making fluid connections to cooler and water
connections to condenser. See Fig. 4 and 5.
On 30HWA,B units, leave 2 ft (610 mm) on one side for
making fluid connections to cooler and water connections to
condenser,accessing the thermostatic expansion valve (TXV),
and replacing heat exchanger(s) if necessary. See Fig. 6
and 7.
On 30HWC,S units, leave 75 in. (1905 mm) on one side
for condenser tube removal and 2 ft (610 mm) on the other
side for making fluid connections to cooler and water connections to condenser,accessing the TXV, and replacing heat
exchanger(s) if necessary. See Fig. 8.
The floor must be strong enough to support the unit operating weight (see Tables 1A-2B and Fig. 9 and 10). If necessary, add a supporting structure (steel beams or reinforced
concrete slabs) to the floor to transfer weight to nearest beams.
Additional weights of factory-installed options (30HW only)
are:
Sound enclosure — 75 lb (34 kg)
Hot gas bypass — 15 lb (7 kg)
80-amp non-fused disconnect — 15 lb (6.8 kg)
100-amp non-fused disconnect — 25 lb (11.3 kg)
200-amp non-fused disconnect — 70 lb (31.8 kg)
Be sure interconnecting piping and electrical conduits
are suspended freely, and are not in contact with any
adjacent walls. Be sure unit capillaries are not rubbing
against anything.
Do not store units in an area exposed to weather
1
⁄2ft (2.3 m) (for 040 units) or
Step 1 — Inspect Shipment — Inspectunit for dam-
age or missing parts. If damaged, or if shipment is incomplete, file a claim immediately with the shipping company.
Step 2 — Rig and Place Unit
30HK,HL UNITS — On each end of cooler, a steel loop is
provided for the preferred method of lifting unit. Use spreader
bars to keep cables away from compressor enclosure and
control box. If unit is to be moved by forklift truck, use one
of the following two methods:
1. From front or rear, lift under the cooler rails. Unit can be
either on or off skid.
2. When moving from the ends, leave unit on the skid. Lift
from under the skid.
If unit is to be dragged into final position, or moved on
rollers, it is recommended that it be left on the skid. When
dragging or rolling, apply force only to the skid, not to the
unit. Lift from above, using the lifting angles provided, to
remove unit from the skid.
30HW UNITS
NOTE: If accessory mobility package (Carrier part no.
30HW900008) is to be used, install this accessory after bringing unit into building and before moving the unit to its final
location per installation instructions provided with the
accessory.
Units Equipped WithFactory-Installed Unit Wheels —This
factory-installed option consists of 4 swivel-type wheels
mounted to the legs of the unit. See Fig. 11. For units equipped
with this option, leave the skid on until the unit is in thebuilding. Once in the building, remove the skid, and wheel
the unit to its final location.
NOTE: The wheels are equipped with a thumb-screw brake.
Units Not Equipped With Factory-Installed Unit Wheels —
Do not remove the skid until the unit has been moved to its
final location. The unit may be moved by means of rollers
under the skid, a forklift truck, or rig and slings.
Step 3 — Place the Unit
30HK,HL UNITS — When unit is in final position, remove
skid, level the unit (using a level), and bolt the unit to floor
or pad.
NOTE: These units are not suitable for unprotected outdoor
use.
Carrier recommends that these units be located in the basement or on the ground floor. However, if it is necessary to
locate the unit on an upper floor, be sure the structure has
been designed to support the unit weight. If necessary, add
structural support to floor. Also, be sure the surface for installation is level. Refer to Fig. 4 and 5 for space requirements and Fig. 9 for weight distribution.
Only electrical power connections, water connections for
condenser, and fluid connections for cooler are required for
30HK installation. Installation of 30HL units varies only in
field piping required for the remote condenser.
30HW UNITS — When the unit is in its final position, remove the skid (from units not equipped with factorymounted wheels), or remove the wheels (if equipped). Re-
3
⁄8-in. wheel nuts to remove wheels from unit legs.
move
Level the unit (using a level), and bolt the unit to the floor
or pad.
If unit is to be mounted on unit external vibration isolators, follow the mounting instructions included with the accessory vibration isolator (Carrier part numbers 30HW900001 and -002).
Step 4 — Check Compressor Mounting and
Connections—
by special self-locking nuts (Fig. 12). After unit is installed,
loosen the self-locking nuts one at a time until compressor
floats freely. Do not remove nuts, as they are self-locking
and will hold their locked position.
As shipped, the compressor is held down
3
TOP VIEW
FRONT VIEWRIGHT SIDE VIEW
UNIT
30HK
040
050,060
DIMENSIONS — in. (mm)
ABCD
1
5
⁄
4
(133)90(2286)
3
10
⁄
4
(273)
108
(2743)
149⁄
(370)
1
20
(510)
16
715⁄
(202)
⁄
16
9
13
(344)
LEGEND
COMP — Compressor
K.O.— Knockout
MTG— Mounting
SAE— Society of Automotive Engineers (U.S.A.)
NOTES:
1. Standard unit shown with the sound enclosure
accessory.
2. Dimensions are in inches unless otherwise
indicated.
Dimensions in ( ) are in millimeters.
3. Service clearance for the control box is 36-in.
HWB12.515.017.518.523.2———
HWC,S35.037.042.042.047.0———
HK — Ckt 1—————35/40†45/45†45/45†
HK − Ckt 2—————35/35†35/45†45/45†
COMPRESSOR
Model No.06DG53706E2150**06E726506E7175**06E729906E2150
Nominal Hp152025303520 (ea)20,3030 (ea)
Quantity11111 21(ea)2
Cylinders Per Compressor646664(ea)6,46 (ea)
Capacity Control — Standard
No. of Steps32333 4 4 4
Minimum Step Capacity (%)33503333332520††33
Capacity Control — With Optional
Hot Gas Bypass
No. of Steps43444 5 5 5
Minimum Step Capacity (%)1010101010101010
Part No.LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664
Dry Weight — lb6981105105145657726726
Fluid Side — psig300300300300300150150150
Refrigerant Side — psig430430430430430235235235
Net Fluid Volume — Gal.1.41.62.12.13.313.115.215.2
(includes nozzles)
Fluid Connections — in.Grooved End
Inlet1
Outlet1
CONDENSER
30HWB (Water Cooled)
Part No. LL01S-D001D002D003D004E004———
Dry Weight — lb48627987153———
Water Side — psig300300300300300———
Refrigerant Side — psig430430430430430———
Net Water Volume — Gal.0.91.21.61.83.3———
(includes nozzles)
Water Connections — in.Grooved End
Inlet1
Outlet11⁄
30HWC (Water Cooled)
Part No. 09RW-400007400007400011400011400009———
Dry Weight — lb532532560560624———
Water Side — psig300300300300300———
Refrigerant Side — psig365365365365365———
Net Water Volume — Gal.2.62.64.04.07.3———
Relief Valve Flow Rate — lb air/min24.624.624.624.624.6−——
Water Connections — in.Weld
Inlet2
Outlet21⁄
30HWS (Water Cooled)
Part No. 09RW-400017400017400019400019400018———
Dry Weight — lb532532560560624———
Water Side — psig300300300300300———
Refrigerant Side — psig335335335335335———
Net Water Volume — Gal.2.62.64.04.07.3———
Relief Valve Flow Rate — lb air/min22.622.622.622.622.6−——
Water Connections — in.Weld
Inlet2
Outlet21⁄
30HK (Water Cooled)
Part No. 09RP-—————022/022†022/027†027/027†
Dry Weight — lb—————100010951190
Water Side — psig—————250250250
Refrigerant Side — psig—————385385385
Net Water Volume — Gal.—————4.4/4.4†4.4/5.2†5.2/5.2†
*Unless otherwise noted, data is for HWB, HWC, and HWS units.
†60 Hz/50 Hz units.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
⁄
2
1
⁄
2
1
⁄
2
2
1
⁄
2
2
1
⁄
2
2
11⁄
11⁄
11⁄
11⁄
21⁄
21⁄
21⁄
21⁄
2
2
2
2
2
2
2
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid
in the heat exchangers.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
21⁄
21⁄
21⁄
21⁄
21⁄
21⁄
21⁄
21⁄
2
2
2
2
2
2
2
2
2830/
2875†
333
333
———
———
———
———
———
———
1
⁄
2
1
⁄
2
3138/
3340†
06E6175,
06E2150
1
2
⁄
2
1
2
⁄
2
3340/
3400†
06E6175
1
2
⁄
2
1
2
⁄
2
10
Table 1B — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — SI
OPERATING WT (Approximate) − kg
UNIT 30HW-018*HW-025*HW-028*HW-035*HW-040*HK040HK050HK060
HWB360431483492594———
HWC,S554611668679766———
HK—————
REFRIGERANT — kgR-22
HWB5.76.87.98.410.5———
HWC,S15.916.819.119.121.3———
HK — Ckt 1—————15.9/18.1†20.4/20.4†20.4/20.4†
HK — Ckt 2—————15.9/15.9†15.9/20.4†20.4/20.4†
COMPRESSOR
Model No.06DG53706E2150**06E726506E7175**06E729906E2150
Nominal kW11.114.918.722.426.114.9 (ea)14.9,22.422.4 (ea)
Quantity11111 21(ea)2
Cylinders Per Compressor646664(ea)6,46 (ea)
Capacity Control — Standard
No. of Steps32333 4 4 4
Minimum Step Capacity (%)33503333332520††33
Capacity Control — With Hot Gas Bypass
No. of Steps43444 5 5 5
Minimum Step Capacity (%)1010101010101010
Relief Valve Flow Rate — kg air/min—6.86.86.86.86.86.86.8
COOLER
Part No.LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664
Dry Weight — kg31.336.747.647.665.7297330330
Fluid Side — kPa20692069206920692069103410341034
Refrigerant Side — kPa29652965296529652965162016201620
Net Fluid Volume — L5.36.18.08.012.549.957.557.5
(includes nozzles)
Fluid Connections — in.Grooved End
Inlet1
Outlet11⁄
CONDENSER
30HWB (Water Cooled)
Part No. LL01S-D001D002D003D004E004———
Dry Weight — kg21.828.135.839.569.4———
Water Side — kPa20692069206920692069———
Refrigerant Side — kPa29652965296529652965———
Net Water Volume — L3.44.56.16.812.5———
(includes nozzles)
Water Connections — in.Grooved End
Inlet1
Outlet1
30HWC (Water Cooled)
Part No. 09RW-400007400007400011400011400009———
Dry Weight — kg241241254254283———
Water Side — kPa20692069206920692069———
Refrigerant Side — kPa25172517251725172517———
Net Water Volume — L9.89.815.415.427.6———
Relief Valve Flow Rate — kg air/min11.211.211.211.211.2———
Water Connections — in.Weld
Inlet2
Outlet2
30HWS (Water Cooled)
Part No. 09RW-400017400017400019400019400018———
Dry Weight — kg241241254254283———
Water Side — kPa20692069206920692069———
Refrigerant Side — kPa23102310231023102310———
Net Water Volume — L9.89.815.415.427.6———
Relief Valve Flow Rate — kg air/min10.310.310.310.310.3———
Water Connections — in.Weld
Inlet2
Outlet2
30HK (Water Cooled)
Part No. 09RP-—————022/022†022/027†027/027†
Dry Weight — kg—————454497540
Water Side — kPa—————172417241724
Refrigerant Side — kPa—————265526552655
Net Water Volume — L—————17/17†17/20†20/20†
(includes nozzles)
Relief Valve Flow Rate — kg air/min—————11.711.711.7
Water Connections — in.Weld
Inlet—————2
Outlet—————2
LEGEND
ODS — Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units.
†60 Hz/50 Hz units.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
⁄
2
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid
in the heat exchangers.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
1284/
1305†
333
333
———
———
———
———
———
———
1
⁄
2
1
⁄
2
1424/
1514†
06E6175,
06E2150
1
2
⁄
2
1
2
⁄
2
1514/
1542†
06E6175
1
2
⁄
2
1
2
⁄
2
11
Table 2A — Physical Data; 30HL, HWA Condenserless Units — English
UNIT 30HWA018HWA025HWA028HWA035HWA040HL050HL060
OPERATING WT (Approximate) − lb7408809609751080
REFRIGERANT† — lbR-22
1.62.02.42.43.06.3/4.2**5.3/5.3**
COMPRESSOR
Model No.06DG53706E225006E726506E727506E7299
Nominal Hp152025303525,2030 (ea)
Quantity111111(ea)2
Cylinders Per Compressor646666,4 6
Capacity Control — Standard
No. of Steps32333 4 4
Minimum Step Capacity (%)335033333320††33
Capacity Control — With Optional
Hot Gas Bypass
No. of Steps43444 5 5
Minimum Step Capacity (%)10101010101010
Part No.LL01SB006LL01SB007LL01SB009LL01SB009LL01SC00510HA40065410HA400664
Dry Weight — lb6981105105145726726
Fluid Side — psig300300300300300150150
Refrigerant Side — psig430430430430430235235
Net Fluid Volume — Gal.1.41.62.12.13.313.115.2
(includes nozzles)
Fluid Connections — in.Grooved End
Inlet1
Outlet11⁄
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS
Discharge Line ODS11⁄
LEGEND
ODS — Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown.
**Ckt 1/Ckt 2.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
⁄
2
2
7
⁄
8
8
11⁄
11⁄
11⁄
2
2
7
⁄
8
8
11⁄
2
11⁄
2
7
⁄
8
13⁄
8
NOTE: Operating weight includes refrigerant operating charge and weight of
fluid in the heat exchangers.
11⁄
2
11⁄
2
7
⁄
8
13⁄
8
21⁄
2
21⁄
2
7
⁄
8
15⁄
8
2070/
2120*
06E6275,
06E2250
33
33
7
⁄
8
13⁄
8
2130/
2190*
06E6275
7
⁄
8
13⁄
8
Table 2B — Physical Data; 30HL, HWA Condenserless Units — SI
UNIT 30HWA018HWA025HWA028HWA035HWA040HL050HL060
OPERATING WT (Approximate) − kg335399435442490
REFRIGERANT† — kgR-22
0.70.91.11.11.42.9/1.9**2.4/2.4**
COMPRESSOR
Model No.06DG53706E225006E726506E727506E7299
Nominal kW11.214.918.722.426.118.7,14.922.4 (ea)
Quantity111111(ea)2
Cylinders Per Compressor646666,4 6
Capacity Control — Standard
No. of Steps32333 4 4
Minimum Step Capacity (%)335033333320††33
Capacity Control — With Optional Hot Gas Bypass
No. of Steps43444 5 5
Minimum Step Capacity (%)10101010101010
Relief Valve Flow Rate — kg air/min—6.86.86.86.86.86.8
COOLER
Part No.LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664
Dry Weight — kg31.336.747.647.665.7330330
Fluid Side — kPa2069206920692069206910341034
Refrigerant Side — kPa2965296529652965296516201620
Net Fluid Volume — L5.36.18.08.012.549.957.5
(includes nozzles)
Fluid Connections — in.Grooved End
Inlet1
Outlet1
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS
Discharge Line ODS11⁄
LEGEND
ODS — Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown.
**Ckt 1/Ckt 2.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
⁄
2
1
⁄
2
11⁄
2
11⁄
2
7
⁄
8
8
11⁄
2
11⁄
2
NOTE: Operating weight includes refrigerant operating charge and weight of
fluid in the heat exchangers.
11⁄
2
11⁄
2
7
⁄
8
13⁄
8
21⁄
21⁄
15⁄
2
2
7
⁄
8
8
938/
961†
06E6275,
06E2250
33
33
7
⁄
8
13⁄
8
966/
993†
06E6175
7
⁄
8
13⁄
8
12
THUMB-SCREW
BRAKE
Fig. 11 — Factory-Installed Unit Wheels (4)
Fig. 12 — Compressor Mounting
Step 5 — Make Piping Connections — See
Fig. 13 and 14 for typical piping applications.
30HK, HWC, HWS CONDENSER DESCRIPTION — All
30HWC and HWS units use a shell-and-tube condenser with
removable heads for easy tube servicing. Refrigerant is contained within the shell, and water flows through the tubes.
The 30HK and HWC units use a steel shell condenser(s) with
steel tube sheets and copper tubes. The 30HWS units are
designed for sea coast applications and use a steel shell condenser with cupronickel tube sheets and tubes. In addition,
the 30HWS water heads utilize ‘‘sacrificial’’ zinc anodes for
condenser corrosion protection.
IMPORTANT:Inspect the zinc anodes every 3 months
for deterioration and replace as needed. Galvanic protection of the condenser is lost if the anodes are not
replaced prior to complete deterioration.
The number of tubes in the condenser(s) varies depending
on the unit size.The condensers have internal subcoolers which
provide approximately 8 F (4.4 C) for 30HK, HL units or 13 F
(7.2 C) for 30HW units subcooling at ARI (Air Conditioning and Refrigeration Institute, U.S.A.) rating conditions.
30HL, HWA SYSTEM CONDENSER — For detailed condenser piping installation instructions for 30HL and HWA
systems, refer to separate instructions packaged with the remote condenser unit(s).
Condenser refrigerant piping for 30HLandHWAunitsshould
be sized to minimize the amount of refrigerant required.
The 30HL and HWA units that use an air-cooled evaporative condenser(s) must have adequate means for head pressure control when operating below 60 F (15.6 C).
Carrier recommends that a field-supplied pressure relief
device be installed after the muffler in each discharge line.
Most local codes require the relief valve to be vented directly to the outdoors. The vent must not be smaller than the
relief valve outlet.
30HWB CONDENSER DESCRIPTION —All 30HWB units
use a brazed-plate heat-exchanger-type condenser. These heat
exchangers are made of embossed plates of acid-resistant stainless steel. Every other plate is reversed so that the ridges of
the herringbone pattern intersect one another on adjacent plates,
forming a lattice of contact points. These plates are vacuumbrazed together to form a compact and pressure-resistant heat
exchanger.
After brazing, the impressions in the plates form 2 separate systems of channels where the refrigerant and water flows
are counter-current. The number of plates varies depending
on unit tonnage. The condensers provide approximately 14°
to 18° F (8° to 10° C) liquid subcooling at the standard
Air Conditioning and Refrigeration Institute (ARI) rating
condition.
30HK, HWC, HWS CONDENSER(S) — When facing the
front of the unit, the condenser(s) is in the uninsulated shell(s)
located across the bottom of the unit. The water connections
are such that the water inlet is located on the left-hand side
(30HK) or right-hand side (30HW) of the unit. The water
inlet mustALWAYS be on the bottom of the condenser(s) to
provide the proper subcooling. The water outlet is located
on the right-hand side (30HK) or left-hand side (30HW) of
the unit. The water connections can be reversed by rotating
the heads and gaskets 180 degrees ON BOTH ENDS OF
THE CONDENSER(S).
IMPORTANT: THE WATER INLET MUST ALWAYS BE ON THE CONDENSER HEAD(S) THAT
HAS THE NOZZLE CONNECTION AT THE BOTTOM OF THE HEAD. Incorrect inlet connection will
result in poor system performance due to incorrect
subcooling.
The LIQUID-IN and LIQUID-OUT labels indicate water
connections AS SUPPLIED FROM THE FACTORY.
It is recommended that strainer with a minimum of 20 mesh
be installed ahead of the condenser water inlet(s) to prevent
debris from clogging or damaging the heat exchanger(s).
There is a pressure-relief device on the condenser(s) of all
30HK, HWC, and HWS units. Most local codes require that
this relief be vented directly to the outdoors.
NOTE: The relief line must not be smaller than the relief
valve outlet. Be sure to provide a way of draining and servicing the unit.
13
LEGEND
Airflow Through Condenser
Airflow Through Air
Handling Unit
Power Wiring
Control Wiring
Chilled Water Piping
ST — Field-Supplied Starter
Flow Switch
FD — Field-Supplied Disconnect
FS — Field-Supplied Differential
*Field Supplied.
14
to maintain proper compressor oil return.
levelly
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping
NOTES:
1. Chiller must be installed
shown are for a quick overview of system and are not in accordance with recognized standards.
of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society
Fig. 13 — Typical Piping with Fluid-Cooled 30HWB Unit Shown
volume.
5. See Table 3 on page 17 for minimum system fluid volume. This system may require the addition of a holding tank to ensure adequate
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.