Carrier 30HL050, 30HW018-040, 60, 30HK040-060 User Manual

Reciprocating Liquid Chillers
Installation, Start-Up and
Service Instructions
30HK040-060
30HL050,060
30HW018-040
50/60 Hz
CONTENTS
Page
GENERAL ....................................2
SAFETY CONSIDERATIONS .....................2
INSTALLATION ..............................3-25
Location ......................................3
Step 1 — Inspect Shipment .....................3
30HK,HL UNITS
30HW UNITS
Step 3 — Place the Unit
30HK,HL UNITS
30HW UNITS
Step 4 — Check Compressor Mounting and Connections
Step 5 — Make Piping Connections .............13
30HK,HWC,HWS CONDENSER DESCRIPTION
30HL,HWA SYSTEM CONDENSER
30HWB CONDENSER DESCRIPTION
30HK,HWC,HWS CONDENSER(S)
30HWB CONDENSER
30HK,HWB,HWC,HWS UNITS
COOLER DESCRIPTION
COOLER PIPING
Step 6 — Make Electrical Connections
30HK,HL UNITS
30HW UNITS
ALL UNITS
PRE-START-UP
Initial Check .................................25
Check Refrigerant Charge .....................26
LIQUID CHARGING METHOD
Check Oil Charge
TO ADD OIL
• TO REMOVE OIL
START-UP AND OPERATION ..................27-30
Operation Checks ............................27
Operating Limitations .........................27
HIGH COOLER LEAVING CHILLED WATER (FLUID)
TEMPERATURES (LCWT)
LOW COOLER LCWT
MAIN POWER SUPPLY
Check Refrigerant Feed Components
THERMOSTATIC EXPANSION VALVE (TXV)
FILTER DRIER
MOISTURE-LIQUID INDICATOR
LIQUID LINE SERVICE VALVE
DISCHARGE LINE CHECK VALVE
HOT GAS BYPASS VALVE
LIQUID LINE SOLENOID VALVE (30HL ONLY)
PRESSURE RELIEF DEVICES
Compressor and Unit Protective Devices
CIRCUIT BREAKER
..................................3
.............................25-27
........................3
...........19
.............................27
............27
.........28
COMPRESSOR INTERNAL THERMAL PROTECTION
CRANKCASE HEATER
OIL PRESSURE SAFETY SWITCH (OPS)
Check Unit Safeties
CONTROL MODULE
HIGH-PRESSURE SWITCH
LOW-PRESSURE SWITCH
CHILLED FLUID TEMPERATURE CONTROLLER
FREEZE-UP PROTECTION
LOSS-OF-COOLER-FLOW PROTECTION
COMPRESSOR GROUND FAULT SENSOR
UNIT OPERATION
Capacity Control and Operating Sequence .......30
30HK,HL UNITS
30HW UNITS
SERVICE
Compressor Replacement ......................32
Circuit Breaker(s) .............................32
Brazed-Plate Cooler and Condenser
Heat Exchanger Replacement .................32
Brazed-Plate Cooler and Condenser
Heat Exchanger Cleaning .....................32
Shell-and-Tube Condenser Cleaning .............32
Thermistor ...................................33
THERMISTOR REPLACEMENT, 30HK,HL UNITS
THERMISTOR REPLACEMENT, 30HW UNITS
SERVICING COOLER (30HK,HL ONLY)
Tube Plugging ...............................36
RETUBING
Tightening Cooler Head Bolts
GASKET PREPARATION
BOLT TORQUES
TROUBLESHOOTING
Complete Unit Stoppage and Restart ............37
GENERAL POWER FAILURE
UNIT ON-OFF SWITCH IS OPEN
CONTACTS OF ANY AUXILIARY INTERLOCKS ARE
OPEN
CHILLED FLUID PROOF-OF-FLOW SWITCH(ES) OPEN
OPEN LOW-PRESSURE SWITCH
TEMPERATURE CONTROLLER SHUTS UNIT DOWN ON
OUT-OF-RANGE
OPEN HIGH-PRESSURE SWITCH(ES)
OPEN COMPRESSOR INTERNAL THERMAL
PROTECTION
OPEN OIL PRESSURE SWITCH
OPEN CONTACTS ON COMPRESSOR GROUND-
CURRENT SENSOR(S) (Accessory)
OPEN 24-V CONTROL CIRCUIT BREAKER(S)
COOLING LOAD SATISFIED
THERMISTOR FAILURE
START-UP CHECKLIST FOR CHILLER SYSTEMS
..................................32-35
...........................28
...........................30-32
.........36,37
..................36
........................37-39
...................CL-1 to CL-4
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-070 Printed in U.S.A. Form 30H-10SI Pg 1 11-98 Replaces: 30H-8SI
GENERAL
These installation instructions cover the 30HK, HL, HWA, HWB, HWC, and HWS units. The HL and HWA are con­denserless units, and the HK, HWB, HWC, and HWS units are all fluid cooled. In addition, the 30HK and HWC units have a standard mechanically cleanable condenser and the 30HWS unit has a mechanically cleanable condenser spe­cifically designed for sea coast applications.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment (Fig. 1-3) can be hazardous due to system pressures, elec­trical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service technicians should install, start up, and service this equipment.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
Be sure all power to equipment is shut off before per­forming maintenance or service. There may be more than one disconnect. Tag all disconnects to alert others not to turn on power until work is completed.
Fig. 2 — 30HWA,B Unit
Fig. 1 — 30HK,HL Unit (30HK Shown)
Fig. 3 — 30HWC,S Unit
2
INSTALLATION
Location—
because of sensitive control mechanisms and electronic devices. Locate unit indoors. See Fig. 4-8 for unit dimen­sional details.
Allow 36 in. (914 mm) in front of the unit for control box access door. Compressor can be removed from either side or the front of the unit. Prior to installation determine which direction compressor will be removed, and leave 3 to 4 ft (914 to 1219 mm) clearance for removal.
On 30HK,HL units leave 7 9 ft (2.7 m) (for 050,060 units) clearance on one side for cooler tube removal. Leave 2 ft (610 mm) clearance on the other side for making fluid connections to cooler and water connections to condenser. See Fig. 4 and 5.
On 30HWA,B units, leave 2 ft (610 mm) on one side for making fluid connections to cooler and water connections to condenser,accessing the thermostatic expansion valve (TXV), and replacing heat exchanger(s) if necessary. See Fig. 6 and 7.
On 30HWC,S units, leave 75 in. (1905 mm) on one side for condenser tube removal and 2 ft (610 mm) on the other side for making fluid connections to cooler and water con­nections to condenser,accessing the TXV, and replacing heat exchanger(s) if necessary. See Fig. 8.
The floor must be strong enough to support the unit op­erating weight (see Tables 1A-2B and Fig. 9 and 10). If nec­essary, add a supporting structure (steel beams or reinforced concrete slabs) to the floor to transfer weight to nearest beams.
Additional weights of factory-installed options (30HW only) are:
Sound enclosure — 75 lb (34 kg)
Hot gas bypass — 15 lb (7 kg)
80-amp non-fused disconnect — 15 lb (6.8 kg)
100-amp non-fused disconnect — 25 lb (11.3 kg)
200-amp non-fused disconnect — 70 lb (31.8 kg)
Be sure interconnecting piping and electrical conduits are suspended freely, and are not in contact with any adjacent walls. Be sure unit capillaries are not rubbing against anything.
Do not store units in an area exposed to weather
1
⁄2ft (2.3 m) (for 040 units) or
Step 1 — Inspect Shipment — Inspectunit for dam-
age or missing parts. If damaged, or if shipment is incom­plete, file a claim immediately with the shipping company.
Step 2 — Rig and Place Unit
30HK,HL UNITS — On each end of cooler, a steel loop is provided for the preferred method of lifting unit. Use spreader
bars to keep cables away from compressor enclosure and control box. If unit is to be moved by forklift truck, use one
of the following two methods:
1. From front or rear, lift under the cooler rails. Unit can be
either on or off skid.
2. When moving from the ends, leave unit on the skid. Lift
from under the skid.
If unit is to be dragged into final position, or moved on
rollers, it is recommended that it be left on the skid. When
dragging or rolling, apply force only to the skid, not to the unit. Lift from above, using the lifting angles provided, to
remove unit from the skid. 30HW UNITS NOTE: If accessory mobility package (Carrier part no.
30HW900008) is to be used, install this accessory after bring­ing unit into building and before moving the unit to its final location per installation instructions provided with the accessory.
Units Equipped WithFactory-Installed Unit Wheels —This factory-installed option consists of 4 swivel-type wheels mounted to the legs of the unit. See Fig. 11. For units equipped with this option, leave the skid on until the unit is in the building. Once in the building, remove the skid, and wheel the unit to its final location.
NOTE: The wheels are equipped with a thumb-screw brake. Units Not Equipped With Factory-Installed Unit Wheels —
Do not remove the skid until the unit has been moved to its final location. The unit may be moved by means of rollers under the skid, a forklift truck, or rig and slings.
Step 3 — Place the Unit
30HK,HL UNITS — When unit is in final position, remove skid, level the unit (using a level), and bolt the unit to floor or pad.
NOTE: These units are not suitable for unprotected outdoor
use.
Carrier recommends that these units be located in the base­ment or on the ground floor. However, if it is necessary to locate the unit on an upper floor, be sure the structure has been designed to support the unit weight. If necessary, add structural support to floor. Also, be sure the surface for in­stallation is level. Refer to Fig. 4 and 5 for space require­ments and Fig. 9 for weight distribution.
Only electrical power connections, water connections for condenser, and fluid connections for cooler are required for 30HK installation. Installation of 30HL units varies only in field piping required for the remote condenser.
30HW UNITS — When the unit is in its final position, re­move the skid (from units not equipped with factory­mounted wheels), or remove the wheels (if equipped). Re-
3
⁄8-in. wheel nuts to remove wheels from unit legs.
move Level the unit (using a level), and bolt the unit to the floor or pad.
If unit is to be mounted on unit external vibration isola­tors, follow the mounting instructions included with the ac­cessory vibration isolator (Carrier part numbers 30HW900­001 and -002).
Step 4 — Check Compressor Mounting and Connections—
by special self-locking nuts (Fig. 12). After unit is installed, loosen the self-locking nuts one at a time until compressor floats freely. Do not remove nuts, as they are self-locking and will hold their locked position.
As shipped, the compressor is held down
3
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
UNIT
30HK
040
050,060
DIMENSIONS — in. (mm)
ABCD
1
5
4
(133)90(2286)
3
10
4
(273)
108
(2743)
149⁄ (370)
1
20 (510)
16
715⁄ (202)
16
9
13 (344)
LEGEND
COMP — Compressor K.O. Knockout MTG Mounting SAE Society of Automotive Engineers (U.S.A.)
NOTES:
1. Standard unit shown with the sound enclosure accessory.
2. Dimensions are in inches unless otherwise indicated. Dimensions in ( ) are in millimeters.
3. Service clearance for the control box is 36-in.
Fig. 4 — 30HK040-060 (Fluid Cooled)
16
16
LEFT SIDE VIEW
4
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
LEGEND
CLY Cylinder COMP — Compressor CONN — Connection K.O. Knockout
NOTES:
1. Standard unit shown withthesounden­closure accessory.
2. Dimensions are in inches unless oth­erwiseindicated.Dimensions in ( ) are in millimeters.
LEFT SIDE VIEW
Fig. 5 — 30HL050,060 (Condenserless)
5
LEFT SIDE VIEW
REAR VIEW
UNIT
30HWA
018
025
028
035
040
DISCONNECT
(Amps)
DISC. — Disconnect K.O. Knockout
ABCDEFG
12.58 (320)
12.82 (326)
12.64 (321)
12.87 (327)
12.66 (322)
80
100
200
LEGEND
DIMENSIONS — in. (mm)
19.20 (488)
18.98 (482)
18.31 (465)
18.62 (473)
18.64 (473)
20.48 (520)
20.57 (522)
20.73 (527)
20.81 (529)
21.30 (541)
33.85 (860)
33.85 (860)
33.85 (860)
33.85 (860)
34.15 (867)
11.72 (298)
11.72 (298)
11.72 (298)
11.72 (298)
11.34 (288)
5.75
(146)
5.75
(146)
5.75
(146)
5.75
(146)
8.22
(209)
17.95 (456)
17.95 (456)
17.95 (456)
17.95 (456)
17.36 (441)
RIGHT SIDE VIEW
LOCATION — in. (mm) MODEL 30HWA (See Table Below)
J K L M 018--- 025--- 028--- 035--- 040---
3.33 (85)
4.33
(110)
7.46
(189)
2.98 (76)
4.98
(126)
11.19 (284)
NOTES:
1. Denotes center of gravity.
2. Denotes accessory or factory-installed option.
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
14.44 (367)
14.82 (376)
15.82 (402)
46.50
(1181)
47.50
(1207)
54.50
(1384)
100,200,
600,800,900
500 500,800 800 200,800
500 500 500,800
100,200,
600,900
100,200,
600,900
100,600,900
MODEL VOLT-Hz
100 575-60 200 380-60 500 208/230-60 600 460-60 800 230-50 900 400-50
100,200,
600,900
Fig. 6 — 30HWA018-040 (Condenserless)
6
LEFT SIDE VIEW
REAR VIEW
UNIT
30HWB
018
025
028
035
040
DISCONNECT
COND — Condenser DISC. — Disconnect K.O. Knockout
ABCDEFGHJ
13.14
18.72
(334)
(475)
13.22
18.25
(336)
(464)
13.18
17.71
(335)
(450)
13.45
17.98
(342)
(457)
13.27
17.75
(337)
(451)
(Amps)
80
100
200
LEGEND
DIMENSIONS — in. (mm)
22.02
33.85
11.72
5.75
12.29
17.95
(559)
22.10 (561)
22.39 (569)
22.68 (576)
23.44 (595)
(860)
33.85 (860)
33.85 (860)
33.85 (860)
34.15 (867)
(298)
11.72 (298)
11.72 (298)
11.72 (298)
11.34 (288)
(146)
5.75
(146)
5.75
(146)
5.75
(146)
8.22
(209)
(312)
12.29 (312)
12.29 (312)
12.29 (312)
12.38 (314)
(456)
17.95 (456)
17.95 (456)
17.95 (456)
17.36 (441)
9.28
(236)
9.28
(236)
9.28
(236)
9.28
(236)
8.22
(209)
RIGHT SIDE VIEW
LOCATION — in. (mm) MODEL 30HWB (See Table Below)
K L M N 018--- 025--- 028--- 035--- 040---
3.33 (85)
4.33
(110)
7.46
(189)
2.98 (76)
4.98
(126)
11.19 (284)
14.44 (367)
14.82 (376)
15.82 (402)
46.50
(1181)
47.50
(1207)
54.50
(1384)
100,200,300,
600,800,900
500 500,800 500,800 800
500 500,800
100,200,
600,900
NOTES:
1. Denotes center of gravity.
2. Denotes accessory or factory-installed option.
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
100,200,
600,900
MODEL VOLT-Hz
100,200,
600,900
100 575-60 200 380-60 500 208/230-60 600 460-60 800 230-50 900 400-50
600,900
Fig. 7 — 30HWB018-040 (Fluid Cooled)
100
200,
7
LEFT SIDE VIEW FRONT VIEW
UNIT
30HWC,S
018
025
028
035
040
DISCONNECT
(Amps)
LEGEND
D. Diameter Disc. Disconnect K.O. Knockout SCH.40 — Schedule 40 Pipe
ABCDEFG
80
100
200
47.50
(1206)
48.30
(1227)
48.00
(1219)
48.20
(1224)
47.80
(1214)
9.90
(251)
9.90
(251)
10.00 (254)
10.00 (254)
10.00 (254)
(1971) (2022) (2127)
DIMENSIONS — in. (mm)
14.00 (356)
15.50 (394)
15.80 (401)
15.90 (404)
15.90 (404)
LOCATION — in. (mm) MODEL 30HWC,S (See Table Below)
J K L 018--- 025--- 028--- 035--- 040---
77.61
79.61
83.74
NOTES:
1. Denotes center of gravity.
2. Denotes accessory or factory-installed option.
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
4.38
(111)
5.00
(127)
10.00 (254)
18.15 (461)
18.15 (461)
18.15 (461)
18.15 (461)
18.45 (469)
17.95 (456)
17.95 (456)
17.95 (456)
17.95 (456)
17.36 (441)
3.33 (85)
4.33
(110)
7.46
(189)
6.69
(170)
6.69
(170)
6.69
(170)
6.69
(170)
6.40
(163)
34.20 (869)
34.20 (869)
34.20 (869)
34.20 (869)
32.94 (837)
100,200,
600,800,900
500 500,800 500,800 800
500 500,800
100,200,
600,900
RIGHT SIDE VIEW
100,200,
600,900
100,200,
600,900
MODEL VOLT-Hz
100 575-60 200 380-60 500 208/230-60 600 460-60 800 230-50 900 400-50
Fig. 8 — 30HWC,S018-040 (Fluid Cooled)
100
200,
600,900
8
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE, 60 HZ UNITS
MOUNTING HOLES
UNIT SIZE
040 710322712323705320703319———————— 050 787 357 789 358 782 355 780 354 519 235 521 236 516 234 514 233 060 838 380 840 381 832 377 830 376 534 242 536 243 531 241 529 240
NOTE: See Fig. 4 and 5 for specific mounting hole location dimensions.
ABCDABCD
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
30HK 30HL
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE, 50 HZ UNITS
MOUNTING HOLES
UNIT SIZE
040 721327723328716325715325———————— 050 838 380 840 381 832 377 830 376 534 242 526 238 531 241 529 240 060 853 387 855 388 847 384 845 383 550 249 551 250 545 247 544 247
NOTE: See Fig. 4 and 5 for specific mounting hole location dimensions.
ABCDABCD
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
30HK 30HL
LOCATION OF MOUNTING HOLES
Fig.9—Weight Distribution and Mounting Hole Location; 30HK,HL Units
30HWA,B 30HWC,S
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE — Lb (kg)
UNIT
30HW
A018 185 (83.9) A025 220 (99.8) A028 240 (108.9) A035 244 (110.7) A040 270 (122.5) B018 199 (90.3) B025 238 (108.0) B028 266 (120.7) B035 271 (122.9)
B040 328 (148.8) C,S018 171 (77.6) 136 (61.7) C,S025 196 (88.9) 144 (65.3) C,S028 211 (95.7) 160 (72.6) C,S035 216 (98.0) 161 (73.0) C,S040 240 (108.9) 185 (83.9)
12345678
MOUNTING HOLE NO.
Fig. 10 — Mounting Hole Weight Distribution; 30HW Units
9
Table 1A — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — English
UNIT 30 HW-018* HW-025* HW-028* HW-035* HW-040* HK040 HK050 HK060 OPERATING WT (Approximate) − lb
HWB 795 950 1065 1085 1310 HWC,S 1231 1358 1484 1508 1702
HK —————
REFRIGERANT — lb R-22
HWB 12.5 15.0 17.5 18.5 23.2 HWC,S 35.0 37.0 42.0 42.0 47.0 HK — Ckt 1 —————35/40† 45/45† 45/45† HK − Ckt 2 —————35/35† 35/45† 45/45†
COMPRESSOR Model No. 06DG537 06E2150** 06E7265 06E7175** 06E7299 06E2150 Nominal Hp 15 20 25 30 35 20 (ea) 20,30 30 (ea)
Quantity 11111 21(ea) 2 Cylinders Per Compressor 646664(ea) 6,4 6 (ea) Capacity Control — Standard No. of Steps 32333 4 4 4 Minimum Step Capacity (%) 33 50 33 33 33 25 20†† 33 Capacity Control — With Optional
Hot Gas Bypass
No. of Steps 43444 5 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10 10
Relief Valve Flow Rate — lb air/min 15.1 15.1 15.1 15.1 15.1 15.1 15.1
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664 Dry Weight — lb 69 81 105 105 145 657 726 726 Fluid Side — psig 300 300 300 300 300 150 150 150 Refrigerant Side — psig 430 430 430 430 430 235 235 235 Net Fluid Volume — Gal. 1.4 1.6 2.1 2.1 3.3 13.1 15.2 15.2
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 1
CONDENSER
30HWB (Water Cooled)
Part No. LL01S- D001 D002 D003 D004 E004 Dry Weight — lb 48 62 79 87 153 Water Side — psig 300 300 300 300 300 Refrigerant Side — psig 430 430 430 430 430 Net Water Volume — Gal. 0.9 1.2 1.6 1.8 3.3
(includes nozzles)
Water Connections — in. Grooved End
Inlet 1 Outlet 11⁄
30HWC (Water Cooled)
Part No. 09RW- 400007 400007 400011 400011 400009 Dry Weight — lb 532 532 560 560 624 Water Side — psig 300 300 300 300 300 Refrigerant Side — psig 365 365 365 365 365 Net Water Volume — Gal. 2.6 2.6 4.0 4.0 7.3 Relief Valve Flow Rate — lb air/min 24.6 24.6 24.6 24.6 24.6 Water Connections — in. Weld
Inlet 2 Outlet 21⁄
30HWS (Water Cooled)
Part No. 09RW- 400017 400017 400019 400019 400018 Dry Weight — lb 532 532 560 560 624 Water Side — psig 300 300 300 300 300 Refrigerant Side — psig 335 335 335 335 335 Net Water Volume — Gal. 2.6 2.6 4.0 4.0 7.3 Relief Valve Flow Rate — lb air/min 22.6 22.6 22.6 22.6 22.6 Water Connections — in. Weld
Inlet 2 Outlet 21⁄
30HK (Water Cooled)
Part No. 09RP- —————022/022† 022/027† 027/027† Dry Weight — lb —————1000 1095 1190 Water Side — psig —————250250250 Refrigerant Side — psig —————385385385 Net Water Volume — Gal. —————4.4/4.4† 4.4/5.2† 5.2/5.2†
(includes nozzles)
Relief Valve Flow Rate — lb air/min —————25.9 25.9 25.9 Water Connections — in. Weld
Inlet —————2 Outlet —————2
LEGEND
ODS — Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units. †60 Hz/50 Hz units.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2
1
2
1
2 2
1
2 2
1
2 2
11⁄ 11⁄
11⁄ 11⁄
21⁄ 21⁄
21⁄ 21⁄
2 2
2 2
2 2
2 2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
21⁄ 21⁄
21⁄ 21⁄
21⁄ 21⁄
21⁄ 21⁄
2 2
2 2
2 2
2 2
2830/ 2875†
333 333
——— ———
——— ———
——— ———
1
2
1
2
3138/ 3340†
06E6175,
06E2150
1
2
2
1
2
2
3340/
3400†
06E6175
1
2
2
1
2
2
10
Table 1B — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — SI
OPERATING WT (Approximate) − kg
UNIT 30 HW-018* HW-025* HW-028* HW-035* HW-040* HK040 HK050 HK060
HWB 360 431 483 492 594 HWC,S 554 611 668 679 766
HK —————
REFRIGERANT — kg R-22
HWB 5.7 6.8 7.9 8.4 10.5 HWC,S 15.9 16.8 19.1 19.1 21.3 HK — Ckt 1 —————15.9/18.1† 20.4/20.4† 20.4/20.4† HK — Ckt 2 —————15.9/15.9† 15.9/20.4† 20.4/20.4†
COMPRESSOR Model No. 06DG537 06E2150** 06E7265 06E7175** 06E7299 06E2150 Nominal kW 11.1 14.9 18.7 22.4 26.1 14.9 (ea) 14.9,22.4 22.4 (ea)
Quantity 11111 21(ea) 2 Cylinders Per Compressor 646664(ea) 6,4 6 (ea) Capacity Control — Standard No. of Steps 32333 4 4 4 Minimum Step Capacity (%) 33 50 33 33 33 25 20†† 33 Capacity Control — With Hot Gas Bypass
No. of Steps 43444 5 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10 10
Relief Valve Flow Rate — kg air/min 6.8 6.8 6.8 6.8 6.8 6.8 6.8
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664 Dry Weight — kg 31.3 36.7 47.6 47.6 65.7 297 330 330 Fluid Side — kPa 2069 2069 2069 2069 2069 1034 1034 1034 Refrigerant Side — kPa 2965 2965 2965 2965 2965 1620 1620 1620 Net Fluid Volume — L 5.3 6.1 8.0 8.0 12.5 49.9 57.5 57.5
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 11⁄
CONDENSER
30HWB (Water Cooled)
Part No. LL01S- D001 D002 D003 D004 E004 Dry Weight — kg 21.8 28.1 35.8 39.5 69.4 Water Side — kPa 2069 2069 2069 2069 2069 Refrigerant Side — kPa 2965 2965 2965 2965 2965 Net Water Volume — L 3.4 4.5 6.1 6.8 12.5
(includes nozzles)
Water Connections — in. Grooved End
Inlet 1 Outlet 1
30HWC (Water Cooled)
Part No. 09RW- 400007 400007 400011 400011 400009 Dry Weight — kg 241 241 254 254 283 Water Side — kPa 2069 2069 2069 2069 2069 Refrigerant Side — kPa 2517 2517 2517 2517 2517 Net Water Volume — L 9.8 9.8 15.4 15.4 27.6 Relief Valve Flow Rate — kg air/min 11.2 11.2 11.2 11.2 11.2 Water Connections — in. Weld
Inlet 2 Outlet 2
30HWS (Water Cooled)
Part No. 09RW- 400017 400017 400019 400019 400018 Dry Weight — kg 241 241 254 254 283 Water Side — kPa 2069 2069 2069 2069 2069 Refrigerant Side — kPa 2310 2310 2310 2310 2310 Net Water Volume — L 9.8 9.8 15.4 15.4 27.6 Relief Valve Flow Rate — kg air/min 10.3 10.3 10.3 10.3 10.3 Water Connections — in. Weld
Inlet 2 Outlet 2
30HK (Water Cooled)
Part No. 09RP- —————022/022† 022/027† 027/027† Dry Weight — kg —————454497540 Water Side — kPa —————1724 1724 1724 Refrigerant Side — kPa —————2655 2655 2655 Net Water Volume — L —————17/17† 17/20† 20/20†
(includes nozzles)
Relief Valve Flow Rate — kg air/min —————11.711.711.7 Water Connections — in. Weld
Inlet —————2 Outlet —————2
LEGEND
ODS — Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units.
†60 Hz/50 Hz units.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2 2
1
2
1
2
1
2
1
2
1
2
1
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
1284/ 1305†
333 333
——— ———
——— ———
——— ———
1
2
1
2
1424/ 1514†
06E6175,
06E2150
1
2
2
1
2
2
1514/ 1542†
06E6175
1
2
2
1
2
2
11
Table 2A — Physical Data; 30HL, HWA Condenserless Units — English
UNIT 30 HWA018 HWA025 HWA028 HWA035 HWA040 HL050 HL060 OPERATING WT (Approximate) − lb 740 880 960 975 1080 REFRIGERANT† — lb R-22
1.6 2.0 2.4 2.4 3.0 6.3/4.2** 5.3/5.3**
COMPRESSOR
Model No. 06DG537 06E2250 06E7265 06E7275 06E7299 Nominal Hp 15 20 25 30 35 25,20 30 (ea)
Quantity 111111(ea) 2 Cylinders Per Compressor 646666,4 6 Capacity Control — Standard No. of Steps 32333 4 4 Minimum Step Capacity (%) 33 50 33 33 33 20†† 33 Capacity Control — With Optional
Hot Gas Bypass
No. of Steps 43444 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10
Relief Valve Flow Rate — lb air/min 15.1 15.1 15.1 15.1 15.1 15.1
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 Dry Weight — lb 69 81 105 105 145 726 726 Fluid Side — psig 300 300 300 300 300 150 150 Refrigerant Side — psig 430 430 430 430 430 235 235 Net Fluid Volume — Gal. 1.4 1.6 2.1 2.1 3.3 13.1 15.2
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 11⁄
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS Discharge Line ODS 11⁄
LEGEND
ODS — Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown. **Ckt 1/Ckt 2. ††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2 2
7
8
8
11⁄ 11⁄
11⁄
2 2
7
8
8
11⁄
2
11⁄
2
7
8
13⁄
8
NOTE: Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
11⁄
2
11⁄
2
7
8
13⁄
8
21⁄
2
21⁄
2
7
8
15⁄
8
2070/ 2120*
06E6275,
06E2250
33 33
7
8
13⁄
8
2130/
2190*
06E6275
7
8
13⁄
8
Table 2B — Physical Data; 30HL, HWA Condenserless Units — SI
UNIT 30 HWA018 HWA025 HWA028 HWA035 HWA040 HL050 HL060
OPERATING WT (Approximate) − kg 335 399 435 442 490
REFRIGERANT† — kg R-22
0.7 0.9 1.1 1.1 1.4 2.9/1.9** 2.4/2.4**
COMPRESSOR
Model No. 06DG537 06E2250 06E7265 06E7275 06E7299 Nominal kW 11.2 14.9 18.7 22.4 26.1 18.7,14.9 22.4 (ea)
Quantity 111111(ea) 2 Cylinders Per Compressor 646666,4 6 Capacity Control — Standard No. of Steps 32333 4 4 Minimum Step Capacity (%) 33 50 33 33 33 20†† 33 Capacity Control — With Optional Hot Gas Bypass
No. of Steps 43444 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10
Relief Valve Flow Rate — kg air/min 6.8 6.8 6.8 6.8 6.8 6.8
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 Dry Weight — kg 31.3 36.7 47.6 47.6 65.7 330 330 Fluid Side — kPa 2069 2069 2069 2069 2069 1034 1034 Refrigerant Side — kPa 2965 2965 2965 2965 2965 1620 1620 Net Fluid Volume — L 5.3 6.1 8.0 8.0 12.5 49.9 57.5
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 1
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS Discharge Line ODS 11⁄
LEGEND
ODS — Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown. **Ckt 1/Ckt 2. ††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2
1
2
11⁄
2
11⁄
2
7
8
8
11⁄
2
11⁄
2
NOTE: Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
11⁄
2
11⁄
2
7
8
13⁄
8
21⁄ 21⁄
15⁄
2 2
7
8
8
938/ 961†
06E6275,
06E2250
33 33
7
8
13⁄
8
966/
993†
06E6175
7
8
13⁄
8
12
THUMB-SCREW BRAKE
Fig. 11 — Factory-Installed Unit Wheels (4)
Fig. 12 — Compressor Mounting
Step 5 — Make Piping Connections — See
Fig. 13 and 14 for typical piping applications. 30HK, HWC, HWS CONDENSER DESCRIPTION — All
30HWC and HWS units use a shell-and-tube condenser with removable heads for easy tube servicing. Refrigerant is con­tained within the shell, and water flows through the tubes. The 30HK and HWC units use a steel shell condenser(s) with steel tube sheets and copper tubes. The 30HWS units are designed for sea coast applications and use a steel shell con­denser with cupronickel tube sheets and tubes. In addition, the 30HWS water heads utilize ‘‘sacrificial’’ zinc anodes for condenser corrosion protection.
IMPORTANT:Inspect the zinc anodes every 3 months for deterioration and replace as needed. Galvanic pro­tection of the condenser is lost if the anodes are not replaced prior to complete deterioration.
The number of tubes in the condenser(s) varies depending on the unit size.The condensers have internal subcoolers which provide approximately 8 F (4.4 C) for 30HK, HL units or 13 F (7.2 C) for 30HW units subcooling at ARI (Air Condition­ing and Refrigeration Institute, U.S.A.) rating conditions.
30HL, HWA SYSTEM CONDENSER — For detailed con­denser piping installation instructions for 30HL and HWA systems, refer to separate instructions packaged with the re­mote condenser unit(s).
Condenser refrigerant piping for 30HLandHWAunitsshould be sized to minimize the amount of refrigerant required.
The 30HL and HWA units that use an air-cooled evapo­rative condenser(s) must have adequate means for head pres­sure control when operating below 60 F (15.6 C).
Carrier recommends that a field-supplied pressure relief device be installed after the muffler in each discharge line. Most local codes require the relief valve to be vented di­rectly to the outdoors. The vent must not be smaller than the relief valve outlet.
30HWB CONDENSER DESCRIPTION —All 30HWB units use a brazed-plate heat-exchanger-type condenser. These heat exchangers are made of embossed plates of acid-resistant stain­less steel. Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates, forming a lattice of contact points. These plates are vacuum­brazed together to form a compact and pressure-resistant heat exchanger.
After brazing, the impressions in the plates form 2 sepa­rate systems of channels where the refrigerant and water flows are counter-current. The number of plates varies depending on unit tonnage. The condensers provide approximately 14° to 18° F (8° to 10° C) liquid subcooling at the standard Air Conditioning and Refrigeration Institute (ARI) rating condition.
30HK, HWC, HWS CONDENSER(S) — When facing the front of the unit, the condenser(s) is in the uninsulated shell(s) located across the bottom of the unit. The water connections are such that the water inlet is located on the left-hand side (30HK) or right-hand side (30HW) of the unit. The water inlet mustALWAYS be on the bottom of the condenser(s) to provide the proper subcooling. The water outlet is located on the right-hand side (30HK) or left-hand side (30HW) of the unit. The water connections can be reversed by rotating the heads and gaskets 180 degrees ON BOTH ENDS OF THE CONDENSER(S).
IMPORTANT: THE WATER INLET MUST AL­WAYS BE ON THE CONDENSER HEAD(S) THAT HAS THE NOZZLE CONNECTION AT THE BOT­TOM OF THE HEAD. Incorrect inlet connection will result in poor system performance due to incorrect subcooling.
The LIQUID-IN and LIQUID-OUT labels indicate water connections AS SUPPLIED FROM THE FACTORY.
It is recommended that strainer with a minimum of 20 mesh be installed ahead of the condenser water inlet(s) to prevent debris from clogging or damaging the heat exchanger(s).
There is a pressure-relief device on the condenser(s) of all 30HK, HWC, and HWS units. Most local codes require that this relief be vented directly to the outdoors.
NOTE: The relief line must not be smaller than the relief valve outlet. Be sure to provide a way of draining and ser­vicing the unit.
13
LEGEND
Airflow Through Condenser
Airflow Through Air
Handling Unit
Power Wiring
Control Wiring
Chilled Water Piping
ST — Field-Supplied Starter
Flow Switch
FD — Field-Supplied Disconnect
FS — Field-Supplied Differential
*Field Supplied.
14
to maintain proper compressor oil return.
levelly
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping
NOTES:
1. Chiller must be installed
shown are for a quick overview of system and are not in accordance with recognized standards.
of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society
Fig. 13 — Typical Piping with Fluid-Cooled 30HWB Unit Shown
volume.
5. See Table 3 on page 17 for minimum system fluid volume. This system may require the addition of a holding tank to ensure adequate
Loading...
+ 30 hidden pages