Additional features ensure smooth,
trouble-free operation. Compressors are mounted on heavy-duty spring
vibration isolators to minimize potentially damaging vibration transmission to the building structure. Sounddeadening mufflers dampen hot gas
pulsations. Servicing is made easy by
bolted, readily-accessible semi-hermetic
compressors that can be removed
with minimal field labor when adjustments or repairs are needed.
Flotronic™ Plus control system regulates the refrigerant cycle for optimum
efficiency
The 30HR,HS Flotronic Plus chillers
feature an electronic expansion valve
(EXV) operated by a microprocessorbased control system. The system
monitors safety functions and controls
unit capacity to maintain leaving
chilled fluid temperature. The microprocessor controls loading and unloading of compressors to match
changing cooling load requirements.
The control system consists of a
control box with a keypad and display
module, an EXV for each refrigeration circuit, and thermistors (temperature sensors) which provide analog
inputs to the microprocessor. The
control also operates a quick test program to check input and output signals to and from the microprocessor.
The 30HR,HS control system is self
contained and can operate on a
stand-alone basis if desired.
Components
The control box — All the
microprocessor-based controls required to optimize chiller operation
and protect it against unsafe conditions are contained in the control
box. This includes the processor module, relay module, EXV driver module, keypad and display module, relays,
and transformers. The box has a
hinged door for ready access.
The EXV driver — The driver positions the EXVs (based on commands
from the microprocessor) and
monitors the status of the oil and
refrigerant pressure switches.
The keypad and display module
— This module consists of a key-
pad with 11 function keys and 12 numeric keys (0 to 9,.,-)andan
alphanumeric 8-character liquid crystal
display. The module allows the operator to perform the following
functions:
• read and change set point
• configure unit
• run quick test unit checkout
• observe diagnostic information
• schedule chiller operation
Control features
Leaving fluid temperature control
with return compensation —
The rate at which the compressors
are turned on will depend on the difference between the actual leaving
fluid temperature and the set point,
the rate of change of leaving fluid
temperature, the return fluid temperature, and the number of compressor
stages on. The control is primarily
from leaving fluid temperature, and
the other factors are used as compensation. Because the control operates
from leaving fluid, the chiller is independent of cooling gpm (L/s). It is a
true droopless control.
Return temperature reset — The
control system is capable of handling leaving fluid temperature reset
based on return cooler temperature.
Because the change in temperature
through the cooler is a measure of the
building load, the return temperature
reset is in effect an average building load reset method. All sensors required to activate return reset are
standard with the unit.
Space and outdoor-air temperature reset — Space temperature
reset and outdoor-air temperature
reset allow for the reset of the leaving
fluid temperature based on an external temperature sensor. (Accessory
thermistor required.)
Energy management system reset
— Many energy management sys-
tems have the capability to transmit a
4 to 20 mA signal in proportion to
the desired leaving chilled-fluid set
point. The Flotronic Plus chillers have
the ability to recognize a proportioned signal to establish the reset
condition (field-installed components
are required).
Remote alarm — Upon initialization
of an alarm condition, an internal
contact will close to activate a signal
suitable for remote alarm activation.
Load shed (demand limit) — A
2-step demand limit can be programmed through the Flotronic Plus
controls. The control limits total power
draw of the unit by controlling the
number of steps of capacity operating
during the demand limiting period.
Pulldown control — Pulldown control is used to minimize compressor
usage and reduce the peak kW that
occurs at start-up, when the cooler
fluid temperature is very warm but the
load is small. When activated, this
feature limits the pulldown rate to
1° F (.56° C) per minute.
Unit checkout (quick test) — The
quick test feature allows determination
of the status (on or off) of various
Flotronic Plus control components (i.e.,
solenoid valves, compressors, and
unloaders). When the unit is in standby
mode, these steps will energize these
components and indicate whether
or not the components are operational.
Diagnostics — The Flotronic Plus
control system features extensive selfdiagnostics as standard. The display
will show a 2-digit diagnostic code,
and will scroll an explanation of the
code for failures that cause the unit to
shut down, terminate a reset option,
or use a default value as set point.
Time schedule — The Flotronic Plus
control system has an integral function that allows scheduling of the circulating pump and chiller operation
for up to 8 occupied/unoccupied periods per schedule, with 7 different
schedule days.
Table of contents
Page
Features/Benefits ........................................ 1-4
Model Number Nomenclature ............................... 4
Physical Data ........................................... 5-8
Accessories (Field Installed) ................................. 9
Base Unit Dimensions .................................... 10-12
Application Data ........................................13-16
Selection Procedure ....................................... 17
Performance Data .......................................18-28
Electrical Data ............................................29
Typical Field Control Wiring ..................................30
Controls ............................................... 31
Typical Piping and Wiring ................................... 32
Guide Specifications ......................................33-36
2