Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures,
etc).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.
•Follow all safety codes.
•Wear safety glasses and work gloves.
•Keep quenching cloth and fire extinguisher nearby when
brazing.
•Use care in handling, rigging, and setting bulky
equipment.
•See Tables 1A and 1B for Physical Data.
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . 3
. . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . 11
30GTN015-035
Reciprocating Liquid Chillers
with ComfortLink™ Controls
50/60 Hz
INSTALLATION
Step 1 — Rig and Place the Unit
RIGGING — Preferred method is with spreader bars from
above the unit. Use 2-in. (50 mm) OD pipe or hooks in lifting
holes. Rig with 4 cables and spreader bars. All panels must be
in place when rigging. See rigging label on unit for details concerning shipping weights, distance between lifting holes, center
of gravity, and spreader bar dimensions. See Fig. 2.
If overhead rigging is not possible, place chiller on skid or
pad for rolling or dragging. When rolling, use a minimum of
3 rollers. When dragging, pull the pad. Do not apply force tothe unit. When in final position, raise from above to lift unit off
pad.
All panels must be in place when rigging.
PLACING UNIT — There must be at least 4 ft (1.2 m) for
service and for unrestricted airflow on all sides of unit, and a
minimum of 8 ft (2.4 m) clear air space above unit. Provide
ample room for servicing cooler. For cooler removal see clearance requirements in Fig. 3-5. For multiple units, allow 8 ft
(2.4 m) separation between units for airflow and service.
If unit is to be used in an area with high solar radiation,
mounted position should be such that control box is not exposed to direct solar radiation. Exposure to direct solar radiation could affect the temperature switch controlling cooler
heaters. See Table 2.
ELECTRIC SHOCK HAZARD
Open all remote disconnects before servicing
this equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Ta b 5 c
PC 903Catalog No. 563-068Printed in U.S.A.Form 30GTN-10SIPg 11-00Replaces: New
Table 1A — Physical Data — 60 Hz
UNIT 30GTN 015020025030035
COMPRESSORReciprocating, Semi-Hermetic
TEMPERATUREFC
Maximum Ambient Temperature12552
Minimum Ambient Temperature0–18
Maximum Cooler EWT*9535
Maximum Cooler LWT7021
Minimum cooler LWT†383.3
LEGEND
EWT — Entering Fluid (Water) Temperature
LW T — Leaving Fluid (Water) Temperature
*For sustained operation, EWT should not exceed 85 F (29.4 C).
†Unit requires modification below this temperature.
MOUNTING UNIT — When unit is in proper location, use
of mounting holes in base rails is recommended for securing
unit to supporting structure, or for mounting unit on vibration
isolators if required. See Fig. 3-5. Fasteners for mounting unit
are field supplied. Be sure unit is level to ensure proper oil
return to compressor.
Step 2 — Check Compressor Mounting —
As
shipped, compressor is held down by 4 bolts. After unit is installed, loosen each bolt using nut indicated in Fig. 6 until the
flat washer (
3
/8 in.) can be moved with finger pressure.
Step 3 — Cooler Fluid and Drain Piping Connections —
turn water connection is on the left and the leaving water connection is on the right. See Fig. 3-5 and 7. Install a minimum
40-mesh strainer in the cooler fluid inlet line just ahead of and
as close as possible to the cooler. Provide a means of venting
air from the high point of the field-installed piping.
After field piping is complete, freeze-up protect ion is recommended using inhibited ethylene glycol or other suitable inhibited antifreeze solution and electric heat tapes in area where
piping is exposed to low ambient temperatures (34 F [1 C] or
below). Heat tapes should possess a rating for area ambients
and be covered with a suitable thickness of closed-cell
insulation. Route power for heating tapes from a separatelyfused disconnect. Identify disconnect as heat tape power source
with a warning that power must not be turned off except when
unit is being serviced.
The cooler drain connection is at the opposite end from th e
compressor (See Fig. 3-5). Insulate the drain piping (in the
same manner as the chilled water piping) for at least one ft
(305 mm) from cooler.
PREPARATION FOR YEAR-ROUND OPERATION — If
unit is on year-round operation, add sufficient inhibited ethylene glycol or other suitable inhibited antifreeze solution to
chilled water to prevent freezing under low-ambient operating
conditions. Consult local water authority on characteristics of
area water and add a recommended inhibitor to the chilled
water.
PREPARATION FOR WINTER SHUTDOWN — Do not
shut off control power disconnect during off-season shutdown.
At end of cooling season:
1. Drain water from system.
2. Replace drain plug and put 2 gall ons (8 liters) of inhibited ethylene glycol (or other suitable inhibited antifreeze) in cooler to prevent freezing of residual water.
(Remove plug on top of leaving chilled water noz zle to
add liquid.)
3. At the beginning of the next cooling season, refill cooler
and add recommended inhibitor.
When facing the cooler side of the unit, the re-
3
NOTES:
1. There must be minimum 8 ft (2.4 m) clear air space above unit.
2. Dimensions in [ ] are in millimeters.
3. The approximate operating weight of the unit is: