Carrier 30GTN015-035 User Manual

Page 1
Installation Instructions
Fig. 1 — Model 30GTN (020 Shown)
CONTENTS
Page
SAFETY CONSIDERATIONS INSTALLATION
Step 1 — Rig and Place the Unit
• RIGGING
• PL A C ING UNIT
• MOUNTING UNIT
Step 2 — Check Compressor Mounting Step 3 — Cooler Fluid and Drain Piping
Connections
• PREPARATION FOR YEAR-ROUND OPERATION
• PREPARATION FOR WINTER SHUTDOWN
Step 4 — Make Electrical Connections
• POWER SUPPLY
• POWER WIRING
Step 5 — Install Accessories
• ELECTRICAL
• HOT GAS BYPASS
Step 6 — Refrigerant Circuit
• LEAK TESTING
• DEHYDRATION
• REFRIGERANT CHARGE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical com­ponents, and equipment location (roofs, elevated structures, etc).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be per­formed by trained service personnel.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when
brazing.
Use care in handling, rigging, and setting bulky
equipment.
See Tables 1A and 1B for Physical Data.
. . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . 3
. . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . 11
30GTN015-035
Reciprocating Liquid Chillers
with ComfortLink™ Controls
50/60 Hz
INSTALLATION
Step 1 — Rig and Place the Unit
RIGGING — Preferred method is with spreader bars from above the unit. Use 2-in. (50 mm) OD pipe or hooks in lifting holes. Rig with 4 cables and spreader bars. All panels must be in place when rigging. See rigging label on unit for details con­cerning shipping weights, distance between lifting holes, center of gravity, and spreader bar dimensions. See Fig. 2.
If overhead rigging is not possible, place chiller on skid or pad for rolling or dragging. When rolling, use a minimum of 3 rollers. When dragging, pull the pad. Do not apply force to the unit. When in final position, raise from above to lift unit off pad.
All panels must be in place when rigging.
PLACING UNIT — There must be at least 4 ft (1.2 m) for service and for unrestricted airflow on all sides of unit, and a minimum of 8 ft (2.4 m) clear air space above unit. Provide ample room for servicing cooler. For cooler removal see clear­ance requirements in Fig. 3-5. For multiple units, allow 8 ft (2.4 m) separation between units for airflow and service.
If unit is to be used in an area with high solar radiation, mounted position should be such that control box is not ex­posed to direct solar radiation. Exposure to direct solar radia­tion could affect the temperature switch controlling cooler heaters. See Table 2.
ELECTRIC SHOCK HAZARD Open all remote disconnects before servicing
this equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Ta b 5 c
PC 903 Catalog No. 563-068 Printed in U.S.A. Form 30GTN-10SI Pg 1 1-00 Replaces: New
Page 2
Table 1A — Physical Data — 60 Hz
UNIT 30GTN 015 020 025 030 035 COMPRESSOR Reciprocating, Semi-Hermetic
No. ...Type 1...06DG537 1...06E2250 1...06E7265 1...06E7275 1...06E7299
No. Cyls (ea)...Speed, Rpm (r/s) 6...1750 (29) 4...1750 (29) 6...1750 (29) 6...1750 (29) 6...1750 (29) Capacity Steps 32 3 3 3 Oil Charge*, Pt (L) 8 (3.8) 17 (8.0) 21 (9.9) 21 (9.9) 19 (9.0)
REFRIGERANT CHG, R-22
Total/Over Clear Glass, lb (kg) 25.0 (11.3)/5.0 (2.3) 31.0 (14.1)/7.0 (3.2) 40.0 (18.1)/12.0 (5.4) 47.0 (21.3)/14.0 (6.4) 57.0 (25.9)/8.0 (3.6)
CONDENSER FANS, Type Propeller Type, Direct Drive
No. ...Diameter, in. (mm) 2...30 (762) 2...30 (762) 3...30 (762)
Total Airflow, Cfm (L/s) 10,600 (5000) 15,700 (7400) 23,700 (11 200) Speed, Rpm (r/s) 1140 (19) 1140 (19) 1140 (19)
CONDENSER COIL, Type Horizontal Plate Fin
Rows...Fins/in. (Fin Spacing mm) 2...19 (1.34) 3...17 (1.49) 2...19 (1.34) 3...17 (1.49) 3...17 (1.49) Total Face Area, sq ft (m
COOLER Shell and Tube, Direct Expansion
Net Water Volume, gal. (L) 6.8 (25.7) 9.9 (37.5) 12.8 (48.4) Maximum Design Working Pressure
psig (kPa)
WATER CONNECTIONS, in.
Inlet and Outlet 2 FPT 2 Drain
*See Oil Charge section for Carrier-approved oil.
2
) 23.5 (2.18) 23.5 (2.18) 39.2 (3.64) 39.2 (3.64) 58.4 (5.43)
Refrigerant Side — 235 (1620)
Water Side — 150 (1034)
1
3
/4 MPT
/2 FPT
3
/4 MPT
Table 1B — Physical Data — 50 Hz
UNIT 30GTN 015 020 025 030 COMPRESSOR Reciprocating, Semi-Hermetic
No. ...Type 1...06E2250 1...06E7265 1...06E7275 1...06E7299
No. Cyls (ea)...Speed, Rpm (r/s) 4...1450 (24.2) 6...1450 (24.2) 6...1450 (24.2) 6...1450 (24.2) Capacity Steps 2333 Oil Charge*, Pt (L) 17 (8.0) 21 (9.9) 21 (9.9) 19 (9.0)
REFRIGERANT CHG, R-22
Total/Over Clear Glass, lb (kg) 26.0 (11.8)/6.0 (2.7) 35.0 (15.9)/8.0 (3.6) 42.0 (19.0)/12.0 (5.4) 49.0 (22.2)/14.0 (6.4)
CONDENSER FANS, Type Propeller Type, Direct Drive
No. ...Diameter, in. (mm) 2...30 (762) 2...30 (762)
Total Airflow, Cfm (L/s) 10,600 (5000) 15,700 (7400) Speed, Rpm (r/s) 950 (15.8) 950 (15.8)
CONDENSER COIL, Type Horizontal, Plate Fin
Rows...Fins/in. (Fin Spacing mm) 2...19 (1.34) 3...17 (1.49) 2...19 (1.34) 3...17 (1.49) Total Face Area, sq ft (m
COOLER Shell and Tube, Direct Expansion
Net Water Volume, gal. (L) 6.8 (25.7) 9.9 (37.5) Maximum Design Working Pressure
psig (kPa)
WATER CONNECTIONS, in.
Inlet and Outlet 2 FPT Drain
*See Oil Charge section for Carrier-approved oil.
2
) 23.5 (2.18) 23.5 (2.18) 39.2 (3.64) 39.2 (3.64)
Refrigerant Side — 235 (1620)
Water Side — 150 (1034)
3
/4 MPT
1201
2
Page 3
MAXIMUM
UNIT
30GTN
SHIP WT
Lb Kg in. mm in. mm in. mm in. mm 015 1876 851 94.0 2388 48.0 1219 23.0 583 49.5 1256 020 2031 921 94.0 2388 47.5 1207 23.0 583 49.5 1256 025 2415 1095 94.0 2388 51.0 1295 34.5 876 73.5 1867 030 2606 1182 94.0 2388 51.0 1295 34.5 876 73.5 1867 035 3365 1526 127.0 3225 66.5 1689 35.5 901 73.5 1867
LIFTING
HOLES
“A”
CENTER OF GRAVITY
“B” “C”
“D”
Fig. 2 — Rigging with Spreader Bars
(Field Supplied)
Table 2 — Temperature Limits for Standard Units
TEMPERATURE F C Maximum Ambient Temperature 125 52 Minimum Ambient Temperature 0–18 Maximum Cooler EWT* 95 35 Maximum Cooler LWT 70 21 Minimum cooler LWT† 38 3.3
LEGEND
EWT — Entering Fluid (Water) Temperature LW T — Leaving Fluid (Water) Temperature
*For sustained operation, EWT should not exceed 85 F (29.4 C).
†Unit requires modification below this temperature.
MOUNTING UNIT — When unit is in proper location, use of mounting holes in base rails is recommended for securing unit to supporting structure, or for mounting unit on vibration isolators if required. See Fig. 3-5. Fasteners for mounting unit
are field supplied. Be sure unit is level to ensure proper oil return to compressor.
Step 2 — Check Compressor Mounting —
As shipped, compressor is held down by 4 bolts. After unit is in­stalled, loosen each bolt using nut indicated in Fig. 6 until the flat washer (
3
/8 in.) can be moved with finger pressure.
Step 3 — Cooler Fluid and Drain Piping Con­nections —
turn water connection is on the left and the leaving water con­nection is on the right. See Fig. 3-5 and 7. Install a minimum 40-mesh strainer in the cooler fluid inlet line just ahead of and as close as possible to the cooler. Provide a means of venting air from the high point of the field-installed piping.
After field piping is complete, freeze-up protect ion is rec­ommended using inhibited ethylene glycol or other suitable in­hibited antifreeze solution and electric heat tapes in area where piping is exposed to low ambient temperatures (34 F [1 C] or below). Heat tapes should possess a rating for area ambients and be covered with a suitable thickness of closed-cell insulation. Route power for heating tapes from a separately­fused disconnect. Identify disconnect as heat tape power source with a warning that power must not be turned off except when unit is being serviced.
The cooler drain connection is at the opposite end from th e compressor (See Fig. 3-5). Insulate the drain piping (in the same manner as the chilled water piping) for at least one ft (305 mm) from cooler.
PREPARATION FOR YEAR-ROUND OPERATION — If unit is on year-round operation, add sufficient inhibited ethyl­ene glycol or other suitable inhibited antifreeze solution to chilled water to prevent freezing under low-ambient operating conditions. Consult local water authority on characteristics of area water and add a recommended inhibitor to the chilled water.
PREPARATION FOR WINTER SHUTDOWN — Do not
shut off control power disconnect during off-season shutdown.
At end of cooling season:
1. Drain water from system.
2. Replace drain plug and put 2 gall ons (8 liters) of inhib­ited ethylene glycol (or other suitable inhibited anti­freeze) in cooler to prevent freezing of residual water. (Remove plug on top of leaving chilled water noz zle to add liquid.)
3. At the beginning of the next cooling season, refill cooler and add recommended inhibitor.
When facing the cooler side of the unit, the re-
3
Page 4
NOTES:
1. There must be minimum 8 ft (2.4 m) clear air space above unit.
2. Dimensions in [ ] are in millimeters.
3. The approximate operating weight of the unit is:
60 Hz
UNIT Lb Kg 30GTN015 1640 744 30GTN015C 1732 786 30GTN020 1821 826 30GTN020C 1945 882
UNIT A
30GTN015
30GTN020
(1219)
4
(1207)
′′′′
3
-11
′′′′-0″″″″
1
″″″″
/
2
50 Hz
UNIT Lb Kg 30GTN015 1741 790 30GTN015C 1833 831 30GTN020 1864 846 30GTN020C 1988 902
LEGEND
C—Copper Coils COMPR — Compressor MTG Mounting NEC National Electrical Code (U.S.A.) VAV Variable-Air Volume
Fig. 3 — Dimensional Drawing, 30GTN015,020
4
Page 5
NOTES:
1. There must be minimum 8 ft (2.4 m) clear air space above unit.
2. Dimensions in [ ] are in millimeters.
3. The approximate operating weight of the unit is:
60 Hz
UNIT Lb Kg 30GTN025 2170 984 30GTN025C 2324 1054 30GTN030 2268 1029 30GTN030C 2474 1122
LEGEND
C—Copper Coils COMPR — Compressor MTG Mounting NEC National Electrical Code (U.S.A.) VAV Variable-Air Volume
50 Hz
UNIT Lb Kg 30GTN025 2193 995 30GTN025C 2347 1065 30GTN030 2332 1058 30GTN030C 2538 1151
Fig. 4 — Dimensional Drawing, 30GTN025,030
5
Page 6
NOTES:
1. There must be minimum 8 ft (2.4 m) clear air space above unit.
2. Dimensions in [ ] are in millimeters.
3. The approximate operating weight of the unit is:
60 Hz
UNIT Lb Kg 30GTN035 2965 1345 30GTN035C 3273 1485
LEGEND
C—Copper Coils COMPR — Compressor MTG Mounting NEC National Electrical Code (U.S.A.)
Fig. 5 — Dimensional Drawing, 30GTN035
6
Page 7
NOTE: All dimensions are in inches.
Fig. 6 — Compressor Mounting
WATER INLET (RETURN WATER)
Liquid Chiller
IN
WATER OUTLET (LEAVING WATER)
OUT
REFRIGERATING
MACHINE U.N.2857
WATER DRAIN
Fig. 7 Water Connection Locations
Step 4 — Make Electrical Connections
POWER SUPPLY — Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in Tables 3A and 3B.
IMPORTANT: Operating unit on improper supply volt­age or with excessive phase imbalance constitutes abuse and may affect Carrier warranty.
POWER WIRING — All power wiring must comply with ap­plicable local and national codes. Install field-supplied branch circuit fused disconnect(s) per NEC (N ational Electrical Code, U.S.A.) of a type that can be locked OFF or ON. Disconnect(s) must be within sight from and readily accessible from unit in compliance with NEC Article 440-14.
General Wiring Notes
1. The control circuit power must be from a separate source and must be brought through a field-supplied fused dis­connect rated at 15 amps for 230-v and 30 amps for 115-v control power. Two terminal blocks are provided for field-wired control devices.
2. Crankcase and cooler heaters are wired in the control cir­cuit so they are always operable as long as the control power disconnect is on and safety de vice is open or the Enable-Off-Remote contact switch is in t he Off position. Heaters are wired so that they ar e energized even when
power to the Main Base Board (MBB) is off. They are protected by a 7-amp fuse in field-supplied control power supply disconnect.
3. The control circuit field-supplied disconnect should never
be off except when unit is being serviced or is to be down for a prolonged period, in which case cooler should be drained. When operation is resumed, crankcase heater should be energized for 24 hours before start-up.
4. Power entry is at one end only.
5. Maximum field wire sizes allowed by lugs on terminal block are:
350 kcmil for 30GTN030,035 (208/230-3-60) and 30GTN030 (230-3-50) units.
2/0 A WG for all other units.
6. Termina ls for field power supply are suitable for copper, copper-clad aluminum, or aluminum conductors. Insula­tion must be rated 167 F (75 C) minimum.
Field Connections Main Power — Bring wires from the fused disconnect switch
through hole in bottom rail of unit to control box (Fig. 3-5) and connect to terminals on terminal block TB1 (See Fig. 8).
Control Power — Bring separate source power (see Fig. 8, note 2) into unit as shown in Fig. 3-5. This supplies power for control circuit, compressor crankcase heater, and cooler heater.
Connect incoming wires to TB4 in unit control box (L1 to and L2 to ). Neutral side must be connec ted to the neutral
terminal block (by C-A1) for 380-3-60 and 400-3-50 V units only. In the auxiliary power supply a field-supplied disconnect with 15-amp circuit protection must be provided to accommo­date crankcase heater and cooler heater cable.
To co mply with NEC Article 440-14, the disconnect must
be located within sight from and readily accessible from unit.
IMPORTANT: To ensure power to the heaters, make sure auxiliary power to unit is always on (except for servicing or prolonged shutdown).
A toggle switch (marked Emergency On-Off on the unit label diagram and by the switch) allows the control circuit to be manually disconnected when necessary. This switch does not affect the crankcase heater and cooler heater cable.
7
Page 8
Table 3A Electrical Data Standard Unit
UNIT SIZE
30GTN
015
020
025
030
035
See Legend and Notes on page 9.
Voltag e
V-Hz (3 Ph )
208/230-60 187 253 82.2 125 278.4 100 115-60 104 127 30
460-60 414 506 38.3 60 126.2 45 115-60 104 127 30 575-60 518 633 31.7 50 102.8 40 115-60 104 127 30
380-60 418 342 43.9 70 152.8 60 230-60 198 254 15 380/415-50 342 440 49.4 80 179.0 60 230-50 198 254 15 208/230-60 187 253 97.4 150 357.4 125 115-60 104 127 30
460-60 414 506 49.6 80 179.2 60 115-60 104 127 30
575-60 518 633 42.9 70 126.8 60 115-60 104 127 30
380-60 418 342 51.1 80 198.8 60 230-60 198 254 15 380/415-50 342 440 60.5 100 229.0 80 230-50 198 254 15 208/230-60 187 253 124.7 200 458.4 150 115-60 104 127 30
460-60 414 506 60.7 100 229.2 80 115-60 104 127 30
575-60 518 633 52.4 80 170.8 70 115-60 104 127 30
380-60 418 342 64.7 110 254.8 80 230-60 198 254 15 380/415-50 342 440 68.5 110 259.0 90 230-50 198 254 15 208/230-60 187 253 145.5 250 518.4 175 115-60 104 127 30
460-60 414 506 68.7 110 259.2 90 115-60 104 127 30
575-60 518 633 54.9 90 182.8 70 115-60 104 127 30
380-60 418 342 73.6 125 287.8 90 230-60 198 254 15 380/415-50 342 440 87.8 150 351.0 110 230-50 198 254 15 208/230-60 187 253 203.0 350 708.6 250 115-60 104 127 30
460-60 414 506 91.1 150 354.3 110 115-60 104 127 30
575-60 518 633 81.6 125 286.2 100 115-60 104 127 30
380-60 418 342 111.1 175 393.7 150 230-60 198 254 15
UNIT CONTROL CIRCUIT
Supplied*
Min Max Min Max
MCA MOCP ICF
Rec Fuse
Size
V-Hz
(Single Ph)
Supplied
MCA and
MOCP
8
Page 9
Table 3B Electrical Data Unit with Factory-Installed Motormaster® I Control
UNIT
SIZE
30GTN
015
020
025
030
035
ICF
MCA
MOCP
*Units are suitable for use on electrical systems where voltage sup-
plied to unit terminals is not below or above listed minimum and maximum limits.
NOTE: Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.
Percent Voltage Imbalance
= 100 x
Example: Supply voltage is 240-3-60.
Vo lt a ge
V-Hz (3 Ph )
208/230-60 187 253 82.2 125 278.4 100 115-60 104 127 30
460-60 414 506 38.3 60 129.3 45 115-60 104 127 30 575-60 518 633 30.8 50 105.6 40 115-60 104 127 30
380-60 418 342 43.9 70 152.8 60 230-60 198 254 15 380/415-50 342 440 51.9 80 181.5 70 230-50 198 254 15 208/230-60 187 253 97.4 150 357.4 125 115-60 104 127 30
460-60 414 506 49.6 80 182.3 60 115-60 104 127 30
575-60 518 633 42.0 70 129.6 50 115-60 104 127 30
380-60 418 342 51.1 80 198.8 60 230-60 198 254 15 380/415-50 342 440 63.0 100 231.5 80 230-50 198 254 15 208/230-60 187 253 124.7 200 458.4 150 115-60 104 127 30
460-60 414 506 60.7 100 232.3 80 115-60 104 127 30
575-60 518 633 51.5 80 173.6 70 115-60 104 127 30
380-60 418 342 64.7 110 254.8 80 230-60 198 254 15 380/415-50 342 440 71.0 110 261.5 90 230-50 198 254 15 208/230-60 187 253 145.5 250 518.4 175 115-60 104 127 30
460-60 414 506 68.7 110 262.3 90 115-60 104 127 30
575-60 518 633 54.0 90 185.6 70 115-60 104 127 30
380-60 418 342 73.6 125 287.8 90 230-60 198 254 15 380/415-50 342 440 90.3 150 353.5 110 230-50 198 254 15 208/230-60 187 253 203.0 350 708.6 250 115-60 104 127 30
460-60 414 506 91.1 150 357.4 110 115-60 104 127 30
575-60 518 633 80.7 125 289.0 100 115-60 104 127 30
380-60 418 342 111.1 175 393.7 150 230-60 198 254 15
Maximum Instantaneous Current Flow during starting (the point in the starting sequence where the sum of the LRA for the starting compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan motors is maximum). Minimum Circuit Amps (complies with National Elec­trical Code [NEC, U.S.A.], Section 430-24) Maximum Overcurrent Protection
max voltage deviation from average voltage
average voltage
Supplied*
Min Max Min Max
LEGEND
UNIT CONTROL CIRCUIT
MCA MOCP ICF
4
239
Supplied
MCA and
MOCP
Rec Fuse
Size
Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply voltage phase imbalance is more than 2%.
V-Hz
(Single Ph)
= 1.7%
Average voltage =
AB = 243 v BC = 236 v AC = 238 v
243 + 236 + 238
= 239 v
3
9
Page 10
C Compressor Contactor CB Circuit Breaker CCN Carrier Comfort Network CWFS Chilled Water Flow Switch CWP Chilled Water Pump CWPI Chilled Water Pump Interlock FC Fan Contactor GCS Ground Current Sensor LEN Local Equipment Network MBB Main Base Board NEC National Electrical Code
TB Te rm in al Bl oc k TDR Time Delay Relay TRAN Transformer
LEGEND
(U.S.A. Standard)
Field Power Wiring
Field Control Power Wiring
Field Control Wiring
Factory-Installed Wiring
Field-Installed Device
TB4
REMOTE
ON-OFF
NOTES:
1. Factory wiring is in accordance with the National Electrical Code. Any field mod­ifications or additions must be in compliance with all applicable codes.
2. Connect separate source of control power from field supplied fused disconnect to terminal 1 of TB4. Neutral side must be connected to terminal 2. This provides power for the unit control circuit, cooler heater and compressor crankcase heater.
3. All field interlock contacts must have minimum rating of 360 va pilot duty plus capacity required for field-installed equipment.
4. For internal unit wiring reference wiring book or unit wiring label diagram.
5. For GCS accessory, remove jumper wire between terminals 5 and 8 on terminal block TB2.
6. For part wind start accessory, remove gray jumper wire between C-A1-C1 and C-A1A-C1. Time delay relay shown in suggested mounting position.
7. Voltage requirements:
MAIN POWER CONTROL POWER
208/230-3-60 115-1-60
460-3-60 115-1-60 575-3-60 115-1-60 380-3-60 220-1-60
380/415-3-50 230-1-50
Fig. 8 Field Wiring Schematic
10
Page 11
Step 5 Install Accessories
ELECTRICAL — A number of electrical accessories are available to provide the following optional features (for details, refer to the Controls, Start-Up, Operation, Service, and Troubleshooting book):
Energy Management Module (used for any of the fol­lowing types of temperature reset, demand limit and ice features):
— 4 to 20 mA leaving fluid temperature reset (requires
field-supplied 4 to 20 mA generator)
— 4 to 20 mA cooling set point reset (requires field-
supplied 4 to 20 mA generator)
— Discrete inputs for 2-step demand limit (requires field-
supplied dry contacts)
— 4 to 20 mA demand limit (requires field-supplied 4 to
20 mA generator)
— Discrete input for Ice Done switch (requires field-
supplied dry contacts)
Chilled fluid flow switch/interlock
Navigator display: Provides hand-held, mobile capability using easy to read
4-line display . Keypad function is the same as the Scrolling Marquee module. Features magnet for ‘hands free’ service of components.
HOT GAS BYPASS — Hot gas bypass usually is not rec­ommended because it results in application of equipment out of its normal design application range. However, if its use is required, the appropriate hot gas bypass package may be used. For installation details, refer to separate instructions supplied with the accessory package.
Step 6 Refrigerant Circuit
LEAK TESTING — Units are shipped with complete op­erating charge of R-22 (see Tables 1A-1B) and should be under sufficient pressure to conduct a leak test. If there is no pressure in the system, use standard refrigeration practices to search for the leak. Repair the leak using good refrigeration practices. After leaks a re repaired, system must be evacuated and dehydrated prior to recharging with refrigerant.
DEHYDRATION — Refer to Carrier Standard Service Tech­niques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for details. Do not use compressor to evacuate system.
REFRIGERANT CHARGE (Refer to Table 1A or 1B) — Immediately ahead of filter drier in each circ uit is a factory­installed liquid line service valve. Each valve has a Schrader connection for charging liquid refrigerant.
1
/4-in.
11
Page 12
Copyright 2000 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Ta b 5 c
PC 903 Catalog No. 563-068 Printed in U.S.A. Form 30GTN-10SI Pg 12 1201 1-00 Replaces: New
Loading...