Burkert 8136 User Manual [en, de, fr]

Operating Instructions
LEVEL TRANSMITTER
8136
4 20 mA/HART - two-wire

Contents

Contents
1 About this document
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 For your safety
2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . .
2.4 General safety instructions . . . . . . . . . . . . . . . . . . . .
2.5 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 NAMUR recommendations . . . . . . . . . . . . . . . . . . . .
2.7 Radio license for Europe. . . . . . . . . . . . . . . . . . . . . .
2.8 Radio license for USA/Canada . . . . . . . . . . . . . . . . .
3 Product description
3.1 Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Packaging, transport and storage . . . . . . . . . . . . . . .
3.4 Accessories and replacement parts . . . . . . . . . . . . . .
4 Mounting
4.1 General instructions . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Collar or adapter ange . . . . . . . . . . . . . . . . . . . . . .
4.3 Mounting preparations, mounting strap. . . . . . . . . . . .
4.4 Instructions for installation . . . . . . . . . . . . . . . . . . . . .
4 4 4
5 5 5 5 6 6 6 6
7 8 8 9
10 10 11 12
5 Connecting to power supply
5.1 Preparing the connection . . . . . . . . . . . . . . . . . . . . .
5.2 Connect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Wiring plan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Switch-on phase. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Set up with the indicating and adjustment module
6.1 Insert indicating and adjustment module. . . . . . . . . . .
6.2 Adjustment system . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Parameter adjustment. . . . . . . . . . . . . . . . . . . . . . . .
6.4 Saving the parameter adjustment data . . . . . . . . . . . .
7 Setup with PACTware
7.1 Connect the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Parameter adjustment with PACTware . . . . . . . . . . . .
7.3 Saving the parameter adjustment data . . . . . . . . . . . .
8 Set up with other systems
8.1 DD adjustment programs . . . . . . . . . . . . . . . . . . . . .
8.2 Communicator 375, 475 . . . . . . . . . . . . . . . . . . . . . .
2 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
25 26 27 28
29 30 31 44
46 46 46
47 47
41783-EN-120316
9 Diagnosis, Asset Management and service
9.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2 Diagnosis memory . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3 Asset Management function . . . . . . . . . . . . . . . . . . .
9.4 Remove interferences. . . . . . . . . . . . . . . . . . . . . . . .
9.5 Exchanging the electronics module . . . . . . . . . . . . . .
9.6 How to proceed in case of repair. . . . . . . . . . . . . . . .
10 Dismounting
10.1 Dismounting steps . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 Supplement
11.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
48 48 49 53 57 57
58 58
59 67
Safety instructions for Ex areas
Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.
Editing status: 2012-02-29
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 3

1 About this document

1 About this document

1.1 Function

This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectication. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target group

This operating instructions manual is directed to trained qualied personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Act
1 Sequence
4 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
ion
This arrow indicates a single action.
Numbers set in front indicate successive steps in a procedure.
41783-EN-120316

2 For your safety

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.
During work on and with the device the required personal protective equipment must always be worn.

2.2 Appropriate use

LEVEL TRANSMITTER 8136 is a sensor for continuous level measurement.
You can nd detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used according to the specications in the operating instructions manual as well as possible supplementary instructions.
2.3 Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

This is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technically awless and reliable condition. The operator is responsible for the trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regulations.
The safety instructions in this operating instructions manual, the national installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.
For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modications are explicitly forbidden.
The safety approval markings and safety tips on the device must also be observed.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 5
2 For your safety
Depending on the instrument version, the emitting frequencies are in
the C or K band range. The low emitting frequencies are far below the internationally approved limit values. When used correctly, there is no danger to health.

2.5 CE conformity

The device fullls the legal requirements of the applicable EC guidelines. With the CE mark, we provide conrmation of successful testing.

2.6 NAMUR recommendations

NAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are accepted as the standard in eld instrumentation.
The device fullls the requirements of the following NAMUR recommendations:
l NE 21 – Electromagnetic compatibility of equipment l NE 43 – Signal level for malfunction information from measuring
transducers
l NE 53 – Compatibility of eld devices and indicating/adjustment
components
l NE 107 - Self-monitoring and diagnosis of eld devices
For further information see
www.namur.de.

2.7 Radio license for Europe

The instrument is approved according to EN 302372-1/2 (2006-04) for use in closed vessels.

2.8 Radio license for USA/Canada

The instrument is in conformity with part 15 of the FCC regulations. Take note of the following two regulations:
l The device must not generate interfering emissions, and l The device must be non-sensitive to interfering immissions,
including those that may cause undesirable operating conditions.
Modications not expressly approved by the manufacturer will lead to expiry of the operating licence according to FCC/IC.
The instrument is in conformity with RSS-210 of the IC regulations.
The instrument may only be operated in closed vessels made of metal,
concrete, or bre-reinforced plastic.
6 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316

3 Product description

2
1
10
11
12
13
9
8
3
4
5
6
7

3.1 Structure

3 Product description
Type
label
The type label contains the most important data for identication and use of the instrument:
Fig. 1: Structure of the type label (example) 1 Instrument type
2 Product code 3 Approvals 4 Process and ambient temperature, process pressure 5 Signal output electronics, voltage supply 6 Protection rating 7 Order number 8 Serial number of the instrument 9 Symbol of the device protection class 10 ID numbers, instrument documentation 11 Note to observe the instrument documentation 12 Notied authority for CE marking 13 Approval directive
Sco
pe of the operating
instructions manual
Sco
pe of delivery
This operating instructions manual applies to the following instrument versions:
l Hardware from 2.1.1 l Software from 4.4.0
The scope of delivery encompasses:
l Radar sensor l Documentation
- this operating instructions manual
- Operating instructions manual "Indicating and adjustment
module" (optional)
- Ex-specic "Safety instructions" (with Ex versions)
- if necessary, further certicates
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 7
3 Product description

3.2 Principle of operation

cation area
Appli
Func
tional principle
Packag
ing
The LEVEL TRANSMITTER 8136 is a radar sensor for continuous level measurement of liquids under simple process conditions.
Dependent on the application range, dierent versions are used:
l Level measurement of aggressive liquids in small vessels:
encapsulated antenna system
l Flow measurement in open umes or gauge measurement of
bodies of water: Plastic horn antenna
l Products with an ε l Products with an ε
value 1.8: Standard electronics
r
value 1.5, < 1.8; applications with very poor
r
reective properties: Electronics with increased sensitivity
The actual values that can be reached depend on the measurement conditions, the antenna system or the standpipe or bypass.
The antenna of the radar sensor emits short radar pulses with a duration of approx. 1 ns. These pulses are reected by the product and received by the antenna as echoes. The transit time of the radar pulses from emission to reception is proportional to the distance and hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.

3.3 Packaging, transport and storage

Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180.
The packaging of standard instruments consists of environment­friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Tr
ansport
Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.
Tr
ansport inspection
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Stora
ge
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.
Unless otherwise indicated, the packages must be stored only under the following conditions:
l Not in the open l Dry and dust free l Not exposed to corrosive media
8 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
Stora
ge and transport
temperature
3 Product description
l Protected against solar radiation l Avoiding mechanical shock and vibration
l Storage and transport temperature see chapter "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 85 %

3.4 Accessories and replacement parts

Indic
ating and adjust-
ment module
Electro
nics module
The indicating and adjustment module is used for measured value indication, adjustment and diagnosis. It can be inserted into the sensor and removed at any time.
You can nd further information in the operating instructions "Indicating and adjustment module" (Document-ID 41787).
The electronics module is a replacement part of the LEVEL TRANS­MITTER series. An own version is available for each type of signal
output.
You can nd further information in the operating instructions "Electronics module LEVEL TRANSMITTER 813X" (Document-ID
41786).
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 9

4 Mounting

4 Mounting

4.1 General instructions

wing in
Scre
Moisture
Suita
bility for the proc-
ess conditions
With instruments with threaded process tting, suitable tools must be applied for tightening the hexagon.
Warning:
The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing.
Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland.
You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off. This applies mainly to outdoor mounting as well as installation in areas where high humidity is expected (e.g. through cleaning processes) or on cooled or heated vessels.
Make sure that all parts of the instrument exposed to the process, in particular the active measuring component, process seal and process tting, are suitable for the existing process conditions. These include above all the process pressure, process temperature as well as the chemical properties of the medium.
You can nd the specications in chapter "Technical data" and on the type label.
4.2 Collar or adapter ange
For mounting the instrument on a socket, a combi compression ange for DN 80 (ASME 3" or JIS 80) is also available for retro tting. Optionally, the instrument can be also equipped with an adapter ange from DN 100 (ASME 4" or JIS 100).
With the housing versions plastic, aluminium single chamber and stainless steel, the collar ange can be placed directly over the housing. With the aluminium double chamber housing, retroactive mounting in this way is not possible - the mounting type must be specied with the order.
You can nd drawings of these mounting options in chapter
"Dimensions".
10 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
4 Mounting
Fig. 2: Flange mounting of the radar sensor

4.3 Mounting preparations, mounting strap

The mounting strap enables simple mounting on the vessel wall or silo top. It is suitable for wall, ceiling or boom mounting. Especially in open vessels this is a very easy and eective way to align the sensor to the bulk solid surface.
The strap is supplied unassembled and must be screwed to the sensor before setup with three hexagon screws M5 x 10 and spring washers. Max. torque, see chapter "Technical data". Required tools: Allen wrench size 4.
There are two ways to screw the strap onto the sensor. Depending on the selected version, the sensors can be swivelled in the strap as follows:
l Single chamber housing
- Angle of inclination 180°, innitely variable
- Angle of inclination in three steps 0°, 90° and 180°
l Double chamber housing
- Angle of inclination 90°, innitely variable
- Angle of inclination in two steps 0° and 90°
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 11
4 Mounting
Fig. 3: Adjustment of the angle of inclination
Fig. 4: Turning by fastening in the centre

4.4 Instructions for installation

Ti
ght installation of the
plastic horn antenna
Polaris
ation plane
12 LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire
For tight installation of the version with plastic horn antenna with
compression or adapter ange, the following conditions must be fullled:
1 Use suitable at seal, e.g. of EPDM with Shore hardness 25 or 50 2 Make sure the number of ange screws corresponds to the
number of ange holes
3 Tighten all screws with the torque stated in the technical data
The emitted radar impulses of the radar sensor are electromagnetic
waves. The polarisation plane is the direction of the electrical wave component. By turning the instrument in the connection ange or mounting boss, the polarisation can be used to reduce the eects of false echoes.
The position of the polarisation plane is marked on the process tting of the instrument.
41783-EN-120316
1
1
4 Mounting
Fig. 5: P osition of the polarisation plane with LEVEL TRANSMITTER 8136 with encapsulated antenna system
1 Marking hole
Fig. 6: P osition of the polarisation plane with LEVEL TRANSMITTER 8136 with
plastic horn antenna 1 Marking bars
Mountin
g position
When mounting the sensor, keep a distance of at least 200 mm (7.874 in) to the vessel wall. If the sensor is installed in the center of
dished or round vessel tops, multiple ec hoes can arise. These can, however, be suppressed by an appropriate adjustment (see chapter
"Setup").
If you cannot keep this distance you should carry out a false echo storage before setup. This applies mainly if buildup on the vessel wall is expected. In this case, w e recommend repeating a false echo storage later with existing buildup.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 13
> 200 mm
(7.87
")
4 Mounting
Fig. 7: Mounting of the radar sensor on round vessel tops
In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom.
Fig. 8: Mounting of the radar sensor on vessels with conical bottom
Inow
ing medium
Do not mount the instruments in or above the lling stream. Make sure that you detect the product surface, not the inowing product.
14 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
Fig. 9: Mounting of the radar sensor with inowing medium
4 Mounting
ket with plastic horn
Soc antenna
A corresponding collar ange for DN 80 (ASME 3" or JIS 80) as well as a suitable adapter ange are available for mounting LEVEL TRANS-
MITTER 8136.
With the housing versions plastic, aluminium single chamber and
stainless steel, the collar ange can be placed directly over the housing. With the aluminium double chamber housing, retroactive mounting in this way is not possible - the mounting type must be specied with the order.
Information:
The socket should be as short as possible and the socket end should be rounded. Interfering reections from the vessel socket are thus minimised.
Fig. 10: Recommended socket mounting
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 15
d
h
4 Mounting
If the medium has good reective properties, LEVEL TRANSMITTER
8136 can also be mounted on a longer socket piece. Recommended values for socket heights are specied in the following illustration. You must carry out a false echo storage afterwards.
The below charts specify the max. socket piece length h depending on the diameter d.
Socket diameter d Socket length h
80 mm 300 mm 100 mm 400 mm 150 mm 500 mm
Socket diameter d Socket length h
3" 11.8 in 4" 15.8 in 6" 19.7 in
Tip:
In new facilities it is useful to incline the vessel socket in the direction of the outlet. False reections from the vessel wall are thus reduced and measurement all the way down to the bottom of the conical outlet is possible.
16 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
Fig. 12: Alignment in silos
ca. 10 mm
4 Mounting
ket with encapsu-
Soc lated antenna system
The socket piece should be dimensioned in such a way that the antenna end protrudes at least 10 mm (0.4 in) out of the socket.
Fig. 13: Recommended socket mounting
If the reective properties of the medium are good, you can mount LEVEL TRANSMITTER 8136 on sockets which are higher than the
length of the antenna. You will nd recommended values for socket heights in the following illustration. The socket end should be smooth and burr-free, if possible also rounded. After installation you must carry out a false echo storage.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 17
d
h
d
h
1½" 50 mm/2" 80 mm/3" 100 mm/4" 150 mm/6"
200 mm 250 mm 300 mm 500 mm 800 mm
4 Mounting
Fig. 14: Deviating socket dimensions
Sen
sor orientation
Vess
el installations
Align the sensor in liquids as vertical as possible to the product surface to achieve optimum measurement results.
Fig. 15: Alignment in liquids
The mounting location of the radar sensor should be a place where no other equipment or xtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spirals, struts, etc., can cause false echoes and impair the useful echo. Make sure when planning your measuring site that the radar sensor has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be carried out during setup.
If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small, inclined sheet metal baes above the installations scatter the radar signals and prevent direct interfering reections.
41783-EN-120316
18 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
Fig. 16: Cover smooth proles with deectors
4 Mounting
Agitato
Foam
rs
generation
If there are agitators in the vessel, a false signal memory should be carried out with the agitators in motion. This ensures that the interfering reections from the agitators are saved with the blades in dierent positions.
Fig. 17: Agitators
Through the action of lling, stirring and other processes in the vessel, compact foams that considerably damp the emitted signals may form on the product surface.
If foams are causing measurement errors, the biggest possible radar antennas, the electronics with increased sensitivity or low frequency radar sensors (C band) should be used.
As an alternative, sensors with guided microwave can be used. These are unaected by foam generation and are best suited for such applications.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 19
1
2
3
100%
4
5
8
6
7
0%
9
4 Mounting
rement in a surge
Measu pipe
When using a surge pipe in a vessel, inuences from vessel installations and turbulences can be excluded. Under these prereq­uisites, the measurement of products with low dielectric values (ε
r
value 1.6) is possible. In very adhesive products, measurement in a surge pipe is not recommended.
Fig. 18: Conguration surge pipe 1 Radar sensor
2 Marking of the polarisation direction 3 Thread or ange on the instrument 4 Vent hole 5 Holes 6 Weld joint
20 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
7 Welding neck ange 8 Ball valve with complete opening 9 Fastening of the surge pipe
Instructions for orientation:
l Note marking of the polarisation plane on the sensor l With threaded tting, the marking is on the hexagon, with ange
connection between the two ange holes
l All holes in the surge pipe must be in one plane with this marking
Instructions for the measurement:
41783-EN-120316
4 Mounting
l The 100 % point must be below the upper vent hole and the
antenna edge
l The 0 % point is the end of the surge pipe l The tube diameter must be at least DN 40 or 1½" with antenna
size 40 mm (1½")
l For the parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate errors due to running time shift
l A false signal suppression with integrated sensor is recommended
but not mandatory
l The measurement through a ball valve with complete run is
possible
Constructional requirements on the surge pipe:
l Material metal, smoother inner tube l Preferably pultruded or straight beaded stainless steel tube l Welded joint should be straight and lie in one axis with the holes l Flanges are welded to the tube according to the orientation of the
polarisation level
l In case of a extension with a welding neck ange or pipe collar as
well as when a ball valve is used, the inner surfaces should be aligned and accurately joined together
l Gap size with junctions 0.1 mm l Do not weld through the pipe wall. The surge pipe must remain
smooth inside. Roughness and beads on the inside caused by unintentional penetration should be removed since they cause strong false echoes and encourage buildup
l Surge pipes must extend all the way down to the requested min.
level, as measurement is only possible within the tube
l Diameter of holes 5 mm, any number OK, on one side or
completely through
l The antenna diameter of the sensor should correspond to the
inner diameter of the tube
l Diameter should be constant over the complete length
Measu
rement in the by-
pass
An alternative to measurement in a surge pipe is measurement in a bypass tube outside of the vessel.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 21
0 %
100 %
1
2
5
4
3
6
4 Mounting
Fig. 19: Conguration bypass 1 Radar sensor
2 Marking of the polarisation direction 3 Instrument ange 4 Distance sensor reference plane to upper tube connection 5 Distance of the tube connections 6 Ball valve with complete opening
Instructions for orientation:
l Note marking of the polarisation plane on the sensor l With threaded tting, the marking is on the hexagon, with ange
connection between the two ange holes
l The pipe connections to the vessel must be in one plane with this
marking
Instructions for the measurement:
l The 100 % point must not be above the upper tube connection to
the vessel
l The 0 % point must not be below the lower tube connection to the
vessel
l Min. distance sensor reference plane to the upper edge upper
tube connection > 300 mm
l The tube diameter must be at least DN 40 or 1½" with antenna
size 40 mm (1½")
l For the parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate errors due to running time shift
41783-EN-120316
22 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
h
max
d
min
≥ 2 mm x h
max
90°
4
3 ... 4 h
max
≥ 50 mm
90
°
2
3
1
4 Mounting
l A false signal suppression with integrated sensor is recommended
but not mandatory
l The measurement through a ball valve with complete run is
possible
Constructional requirements on the bypass pipe:
l Material metal, smoother inner tube l In case of an extremely rough tube inner surface, use an inserted
tube (tube in tube) or a radar sensor with tube antenna
l Flanges are welded to the tube according to the orientation of the
polarisation level
l Gap size with junctions 0.1 mm, for example, when using a ball
valve or intermediate anges with single pipe sections
l The antenna diameter of the sensor should correspond to the
inner diameter of the tube
l Diameter should be constant over the complete length
ow measurement with
Fl rectangular ume
The short examples give you introductory information on the ow measurement. Detailed planning information is available from ume manufacturers and in special literature.
Fig. 20: Flow measurement with rectangular ume: d sensor (see chapter "Technical data"); h ume
= max. lling of the rectangular
max.
1 Overow orice (side view) 2 Headwater 3 Tail water 4 Overfall orice (view from bottom water)
= min. distance of the
min.
In general, the following points must be observed:
l Install the sensor on the headwater side l Installation in the centre of the ume and vertical to the liquid
surface
l Distance to the overfall orice l Distance of orice opening above ground l Min. distance of the orice opening to bottom water
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 23
l Min. distance of the sensor to max. storage level
2
3 ... 4 x h
max
90°
h
max
d
1
B
4 Mounting
Fl
ow measurement with
Khafagi Venturi ume
Fig. 21: Flow measurement with Khafagi-Venturi ume: d = Min. distance to sensor; h
= max. lling of the ume; B = tightest constriction in the ume
max.
1 Position sensor 2 Venturi ume
In general, the following points must be observed:
l Installation of the sensor at the inlet side l Installation in the centre of the ume and vertical to the liquid
surface
l Distance to the Venturi ume l Min. distance of the sensor to max. storage level
41783-EN-120316
24 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire

5 Connecting to power supply

5 Connecting to power supply

5.1 Preparing the connection

Saf
ety instructions
Volta
ge supply
Conne
ction cable
Always keep in mind the following safety instructions:
l Connect only in the complete absence of line voltage l If voltage surges are expected, install overvoltage arresters
Power supply and current signal are carried on the same two-wire cable. The voltage supply range can dier depending on the instrument version.
The data for power supply are specied in chapter "Technical data".
Provide a reliable separation between the supply circuit and the mains circuits according to DIN VDE 0106 part 101.
Keep in mind the following additional factors that inuence the
operating voltage:
l Output voltage of the power supply unit can be lower under
nominal load (with a sensor current of 20.5 mA or 22 mA in case of fault message)
l Inuence of additional instruments in the circuit (see load values in
chapter "Technical data")
The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326-1 for industrial areas, screened cable should be used.
For instruments with housing and cable gland, use cable with round cross-section. A cable outer diameter of 5 … 9 mm (0.2 0.35 in) ensures the seal eect of the cable gland. If you are using cable with a dierent diameter, exchange the seal or use a suitable cable gland.
We generally recommend the use of screened cable for HART multidrop mode.
Cable
gland ½ NPT
Cable
screening and
grounding
With plastic housing, the NPT cable gland or the Conduit steel tube must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data"
If screened cable is necessary, connect the cable screen on both ends
to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the potential equalisation (low impedance).
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 25
5 Connecting to power supply
Cable
screening and
grounding
If potential equalisation currents are expected, the connection on the processing side must be made via a ceramic capacitor (e. g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interfer­ence signals remains.
If screened cable is necessary, connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the potential equalisation (low impedance).
If potential equalisation currents are expected, the connection on the processing side must be made via a ceramic capacitor (e. g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interfer­ence signals remains.

5.2 Connect

Conne
ction technology
Conne
ction procedure
The voltage supply and signal output are connected via the spring­loaded terminals in the housing.
The connection to the indicating and adjustment module or to the interface adapter is carried out via contact pins in the housing.
Proceed as follows:
1 Unscrew the housing cover 2 If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.
3 Loosen compression nut of the cable entry 4 Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
41783-EN-120316
26 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
5 Connecting to power supply
5 Insert the cable into the sensor through the cable entry
Fig. 22: Connection steps 5 and 6
6 Insert the wire ends into the terminals according to the wiring plan
Information:
Solid cores as well as exible cores with cable end sleeves are inserted directly into the terminal openings. In case of exible cores without end sleeves, press the terminal head with a small screwdriver; the terminal opening is freed. When the screwdriver is released, the terminal closes again.
7 Check the hold of the wires in the terminals by lightly pulling on
them
8 Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
9 Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10 Screw the housing cover back on The electrical connection is nished.
Information:
The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When inserting the terminal block again, you should hear it snap in.

5.3 Wiring plan

The following illustration applies to the non-Ex as well as to the Ex-ia version.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 27
5
1
2
+
( )
(-)
6 7 8
4...20mA
2
3
4
1
5 Connecting to power supply
nics compart-
Electro ment
Fig. 23: Electronics and connection compartment, single chamber housing 1 Voltage supply, signal output
2 For indicating and adjustment module or interface adapter 3 For external indicating and adjustment unit 4 Ground terminal for connection of the cable screen
5.4 Switch-on phase
After connecting the instrument to power supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:
l Internal check of the electronics l Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
l Indication of the status message "F 105 Determine measured
value" on the display or PC
l The output signal jumps to the set error current
As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.
28 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316

6 Set up with the indicating and adjustment module

6 Set up with the indicating and adjustment
module

6.1 Insert indicating and adjustment module

The indicating and adjustment module can be inserted into the sensor and removed any time. Four positions displaced by 90° can be selected. It is not necessary to interrupt the power supply.
Proceed as follows:
1 Unscrew the housing cover 2 Place the indicating and adjustment module in the requested
position onto the electronics and turn to the right until it snaps in
3 Screw housing cover with inspection window tightly back on Removal is carried out in reverse order.
The indicating and adjustment module is powered by the sensor, an
additional connection is not necessary.
Fig. 24: Insertion of the indicating and adjustment module with single chamber housing
Note:
If you intend to retrot the instrument with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 29
1
2
6 Set up with the indicating and adjustment module

6.2 Adjustment system

Fig. 25: Indicating and adjustment elements 1 LC display
2 Adjustment keys
Key
functions
l [OK] key:
- Move to the menu overview
- Conrm selected menu
- Edit parameter
- Save value
l [->] key:
- Presentation change measured value
- Select list entry
- Select editing position
l [+] key:
- Change value of the parameter
l [ESC] key:
- interrupt input
- Return to higher-ranking menu
Adjus
tment system
The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not conrmed with [OK] will not be sa ved.
30 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
Main
menu
6 Set up with the indicating and adjustment module

6.3 Parameter adjustment

Through the parameter adjustment the instrument is adapted to the application conditions. The parameter adjustment is carried out via an adjustment menu.
The main menu is divided into ve sections with the following functions:
Setup: Settings, e.g., for measurement loop name, medium, applica- tion, vessel, adjustment, signal output
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, e.g. on the instrument status, pointer,
reliability, simulation, echo curve
Further settings: Instrument unit, false signal suppression, linear- isation curve, reset, date/time, reset, copy function
Info: Instrument name, hardware and software version, calibration date, instrument features
Information:
In this operating instructions manual, the instrument-specic param­eters in the menu sections "Setup", "Diagnosis" and "Additional settings" are described. The general parameters in these menu section are described in the operating instructions manual "Indicating
and adjustment module".
You can nd in the operating instructions manual "Indicating and adjustment module" also the description of the menu sections "Display" and "Info".
In the main menu point "Setup", the individual submenu points should be selected subsequently and provided with the correct parameters to ensure the optimum adjustment of the measurement. The procedure is described in the following.
Set
up/Medium
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 31
Each medium has dierent reection properties. With liquids, further
interfering factors are uctuation pr oduct surface and foam generation. With bulk solids, these are dust generation, material cone and additional echoes from the vessel wall.
To adapt the sensor to these dierent measuring conditions, the selection "Liquid" or "Bulk solid" should be made in this menu item.
6 Set up with the indicating and adjustment module
Through this selection, the sensor is adapted perfectly to the product
and measurement reliability, particularly in products with poor reective properties, is considerably increased.
Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.
up/Application
Set
In addition to the medium, also the application, i.e. the measuring site, can inuence the measurement.
With this menu item, the sensor can be adapted to the applications. The adjustment possibilities depend on the selection "Liquid" or "Bulk
solid" under "Medium".
The following options are available when "Liquid" is selected:
The selection "Standpipe" opens a new window in which the inner
diameter of the applied standpipe is entered.
41783-EN-120316
The following features form the basis of the applications:
Storage tank:
l Setup: large-volumed, upright cylindrical, spherical
32 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
6 Set up with the indicating and adjustment module
l Product speed: slow lling and emptying l Process/measurement conditions:
- Condensation
- Smooth product surface
- Max. requirement to the measurement accuracy
Storage tanke with product circulation:
l Setup: large-volumed, upright cylindrical, spherical l Product speed: slow lling and emptying l Vessel: small laterally mounted or large top mounted stirrer l Process/measurement conditions:
- Relatively smooth product surface
- Max. requirement to the measurement accuracy
- Condensation
- Slight foam generation
- Overlling possible
Storage tank on ships (Cargo Tank):
l Product speed: slow lling and emptying l Vessel:
- Installations in the bottom section (bracers, heating spirals)
- High sockets 200 500 mm, also with large diameters
l Process/measurement conditions:
- Condensation, buildup by movement
- Max. requirement on measurement accuracy from 95 %
Stirrer vessel (reactor):
l Setup: all vessel sizes possible l Product speed:
- Fast to slow lling possible
- Vessel is very often lled and emptied
l Vessel:
- Socket available
- Large agitator blades of metal
- Vortex breakers, heating spirals
l Process/measurement conditions:
- Condensation, buildup by movement
- Strong spout generation
- Very agitated surface, foam generation
Dosing vessel:
l Setup: all vessel sizes possible l Product speed:
- Fast lling and emptying
- Vessel is very often lled and emptied
l Vessel: narrow installation situation l Process/measurement conditions:
- Condensation, buildup on the antenna
- Foam generation
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 33
6 Set up with the indicating and adjustment module
Standpipe:
l Product speed: very fast lling and emptying l Vessel:
- Vent hole
- Joins like anges, weld joints
- Shifting of the running time in the tube
l Process/measurement conditions:
- Condensation
- Buildup
Bypass:
l Product speed:
- Fast up to slow lling with short up to long bypass tube
possible
- Often the level is hold via a control facility
l Vessel:
- Lateral outlets and inlets
- Joins like anges, weld joints
- Shifting of the running time in the tube
l Process/measurement conditions:
- Condensation
- Buildup
- Separation of oil and water possible
- Overlling into the antenna possible
Plastic tank:
l Vessel:
- Measurement x mounted or integrated
- Measurement depending on the application through the vessel
top
- With empty vessel, the measurement can be carried out
through the bottom
l Process/measurement conditions:
- Condensation on the plastic ceiling
- In outside facilities water and snow on the vessel top possible
Transportable plastic tank:
l Vessel:
- Material and thickness dierent
- Measurement through the vessel top
l Process/measurement conditions:
- Measured value jump with vessel change
Open water (gauge measurement):
l Gauge rate of change: slow gauge change l Process/measurement conditions:
- Distance sensor to water surface to big
- Extreme damping of output signal due to wave generation
41783-EN-120316
34 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
6 Set up with the indicating and adjustment module
- Ice and condensation on the antenna possible
- Spiders and insect nestle in the antennas
- Floating material and animals sporadically on the water
surface
Open ume (ow measurement):
l Gauge rate of change: slow gauge change l Process/measurement conditions:
- Ice and condensation on the antenna possible
- Spiders and insect nestle in the antennas
- Smooth water surface
- Exact measurement result required
- Distance to the water surface normally relatively high
Rain water overfall (weir):
l Gauge rate of change: slow gauge change l Process/measurement conditions:
- Ice and condensation on the antenna possible
- Spiders and insect nestle in the antennas
- Turbulent water surface
- Sensor ooding possible
Demonstration:
l Adjustment for all applications which are not typically level
measurement
l Sensor accepts all measured value changes within the measuring
range immediately
l Typical applications:
- Instrument demonstration
- Object recognition/monitoring (additional settings required)
Caution:
If a separation of liquids with dierent dielectric gure occurs in the vessel, for example through condensation, the radar sensor can detect under certain circumstances only the medium with the higher dielectric gure. Keep in mind that layer interfaces can cause faulty measure­ments.
If you want to measure the total height of both liquids reliably, please contact our service department or use an instrument specially designed for interface measurement.
The following options are available when "Bulk solid" is selected:
The following features form the basis of the applications:
Silo (slim and high):
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 35
6 Set up with the indicating and adjustment module
l Vessel of metal: weld joints l Process/measurement conditions:
- Filling too close to the sensor
- System noise with completely empty silo increased
- Automatic false signal suppression with partly lled vessel
Bunker (large-volumed):
l Vessel of concrete or metal:
- Structured vessel walls
- Installations present
l Process/measurement conditions:
- Large distance to the medium
- Large angles of repose
Bunker with fast lling:
l Vessel of concrete or metal, also multiple chamber silo:
- Structured vessel walls
- Installations present
l Process/measurement conditions:
- Measured value jumps, e.g. by truck loading
- Large distance to the medium
- Large angles of repose
Heap:
l Sensor mounting on movable conveyor belts l Detection of the heap prole l Height detection during lling l Process/measurement conditions:
- Measured value jumps, e.g. by the prole of the heap or
traverses
- Large angles of repose
- Measurement near the lling stream
Crusher:
l Vessel: installations, wear and protective facilities available l Process/measurement conditions:
- Measured value jumps, e.g. by truck loading
- Fast reaction time
- Large distance to the medium
Demonstration:
l Adjustment for all applications which are not typically level
measurement
l Sensor accepts all measured value changes within the measuring
range immediately
l Typical applications:
- Instrument demonstration
- Object recognition/monitoring (additional settings required)
41783-EN-120316
36 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
6 Set up with the indicating and adjustment module
Through this selection, the sensor is adapted optimally to the application or the location and measurement reliability under the various basic conditions is increased considerably.
Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.
up/Vessel height,
Set
measuring range
Set
up/Vessel form
With this selection, the operating range of the sensor is adapted to the vessel height and the reliability with dierent frame conditions is increased considerably.
Independent from this, the min. adjustment must be carried out.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.
Also the vessel form can inuence the measurement apart from the medium and the application. To adapt the sensor to these measure­ment conditions, this menu item oers you dierent options for vessel bottom and ceiling in case of certain applications.
Enter the requested parameters via the appropriate keys, save your settings with [OK] and jump to the next menu item with the [ESC] and the [->] key.
Set
up/Adjustment
Because a radar sensor is a distance measuring instrument, the distance from the sensor to the product surface is measured. To have the real product level displayed, an allocation of the measured distance to the percentage height must be made. To carry out this adjustment, the distance is entered with full and empty vessel. If these values are not known, an adjustment with the distance values, e.g. 10 % and 90 % is also possible. Starting point for these distance specications is always the seal surface of the thread or ange. By means of these settings, the real level is calculated.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 37
6 Set up with the indicating and adjustment module
The real product level during this adjustment is not important, because
the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time without the instrument having to be installed.
Setup/Min. adjustment
Set
up/Max. adjustment
Proceed as follows:
1 Select the menu item "Setup" with [->] and conrm with [OK]. Now
select with [->] the menu item "Min. adjustment" and conrm with
[OK].
2 Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3 Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to the percentage value.
5 Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Proceed as follows:
1 Select with [->] the menu item max. adjustment and conrm with
[OK].
2 Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
38 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
6 Set up with the indicating and adjustment module
3 Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4 Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max. level must lie below the min. distance to the antenna edge.
5 Save settings with [OK]
sis/Peak value
Diagno
Diagno
sis/Measurement
reliability
Diagno
ses/Curve indica-
tion
Min. and max. measured values are saved in the sensor. The values are displayed in the menu item "Peak values".
When non-contact level sensors are used, the measurement can be inuenced by the respective process conditions. In this menu item, the measurement reliability of the level echo is displayed as dB value. The measurement reliability equals signal strength minus noise. The higher the value, the more reliable the measurement. With a functioning measurement, the values are > 10 dB.
The "Echo curve" shows the signal strength of the echoes over the measuring range in dB. The signal strength enables an evaluation of the quality of the measurement.
The "False signal suppression" displays the saved false echoes (see menu "Additional settings") of the empty vessel with signal strength in "dB" over the measuring range.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 39
6 Set up with the indicating and adjustment module
A comparison of echo curve and false signal suppression allows a
more accurate conclusion on measurement reliability. The selected curve is continuously updated. With the [OK] key, a submenu with zoom functions is opened:
l "X-Zoom": Zoom function for the meas. distance l "Y-Zoom": 1, 2, 5 and 10x signal magnication in "dB" l "Unzoom": Reset the presentation to the nominal measuring range
with single magnication
sis/Echo curve
Diagno
memory
Fur
ther settings/False
signal suppression
With the function "Echo curve memory" the echo curve can be saved at the time of setup. This is generally recommended; for using the Asset Management functions it is absolutely necessary. If possible, the curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolution echo curve can be displayed and used to recognize signal changes over the operating time. In addition, the echo curve of the setup can be also displayed in the echo curve window and compared with the actual echo curve.
The following circumstances cause interfering reections and can inuence the measurement:
l High sockets l Vessel installations such as struts l Agitators l Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account for level measurement.
This should be done with a low level so that possible interfering reections can be detected.
Proceed as follows:
41783-EN-120316
40 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
6 Set up with the indicating and adjustment module
1 Select the menu item "Additional settins" with [->] and conrm with
[OK]. With [->] you have to select the menu item "False signal suppression" and conrm with [OK].
2 Conrm again with [OK].
3 Conrm again with [OK].
4 Conrm again with [OK] and enter the actual distance from the
sensor to the product surface.
5 All interfering signals in this section are detected by the sensor
and stored after conrming with [OK].
Note:
Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as false signal.
The lling level would then no longer be detectable in this area.
If a false signal suppression is already created in the sensor, then the
following menu window appears when selecting "False signal suppression":
The menu item "Delete" is used to completely delete an already created false signal suppression. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 41
6 Set up with the indicating and adjustment module
The menu item "Extend" is used to extend an already created false
signal suppression. This is useful if a false signal suppression was carried out with a too high level and not all false signals could be detected. When selecting "Extend", the distance to the product surface of the created false signal suppression is displayed. This value can now be changed and the false signal suppression can be extended to this range.
ther settings/Lineari-
Fur
zation curve
A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level - e.g. in a horizontal cylindrical or spherical tank - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item
"Display".
Enter the requested parameters via the appropriate keys, save your settings and jump to the next menu item with the [ESC] and [->] key.
Caution:
Note the following if the instrument with corresponding approval is used as part of an overll protection system according to WHG:
If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level. This must be taken into consideration by the user, particularly when adjusting the switching point on the level switch.
Addition set
42 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
al settings - Re-
With a reset, certain parameter adjustments carried out by the user are reset.
The following reset functions are available:
41783-EN-120316
6 Set up with the indicating and adjustment module
Delivery status: Restoring the parameter settings at the time of shipment from the factory incl. the order-specic settings. A created false signal suppression, user-programmable linearization curve as well as the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special and laboratory parameters to the default values of the respective instru­ment. A created false signal suppression, user programmable linearization curve as well as the measured value memory will be deleted.
Setup: Resetting of the parameter settings to the default values of the respective instrument in the menu item Setup. Order-related settings remain but are not taken over into the current parameters. User­generated false signal suppression, user-programmed linearization curve, measured value memory as well as event memory remain untouched. The linearization is set to linear.
False signal suppression: Deleting a previously created false signal suppression. The false signal suppression created in the factory remains active.
Peak values measured value: Resetting of the measured min. and max. distances to the actual measured value.
The following table shows the default values of the instrument. Depending on the instrument version, not all menu items are available
or dierently assigned:
Menu Menu
Setup Measurement
item Default value
loop name
Medium Liquid/Water
Application Storage tank
Vessel form Vessel bottom, dished boiler end
Vesell height/ Measuring range
Min. adjustment Recommended measuring range, see
Max. adjustment 0,000 m(d)
Damping 0.0 s
Current output
mode
Current output Min./Max.
Sensor
Bulk solids/Crushed stones, gravel
Silo
Vessel top, dished boiler end
Recommended measuring range, see
"Technical data" in the supplement
"Technical data" in the supplement
4 20 mA, < 3.6 mA
Min. current 3.8 mA, max. current
20.5 mA
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 43
6 Set up with the indicating and adjustment module
Menu Menu item Default value
Lock operation Released
Display Language Like order
Displayed value Distance
Display unit m
Scaling size Volume
Scaling 0.00 lin %, 0 l
Lighting Switched o
Further settings Distance unit m
Temperature unit °C
Probe length Length of the standpipe Ex factory
Linearisation
curve
HART mode Standard
l
100.00 lin %, 100 l
linear
Address 0
6.4 Saving
the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating instructions manual, and archiving them afterwards. They are thus available for multiple use or service purposes.
If the instrument is equipped with an indicating and adjustment module, the data in the sensor can be saved in the indicating and adjustment module. The procedure is described in the operating instructions manual "Indicating and adjustment module" in the menu item "Copy sensor data". The data remain there permanently even if the sensor power supply fails.
The following data or settings for adjustment of the indicating and adjustment module are saved:
l All data of the menu "Setup" and "Display" l In the menu "Additional settings" the items "Sensor-specic units,
temperature unit and linearization"
l The values of the user programmable linearisation curve
The function can also be used to transfer settings from one instrument to another instrument of the same type. If it is necessary to exchange a sensor, the indicating and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy sensor data".
44 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
6 Set up with the indicating and adjustment module
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 45
1
3
2
5
4

7 Setup with PACTware

the interface adapter
Via and HART
7 Setup with PACTware

7.1 Connect the PC

Fig. 26: Connecting the PC via HART to the signal cable 1 Sensor
2 HART resistance 250 Ω (optional depending on processing) 3 Connection cable with 2 mm pins and terminals 4 Processing system/PLC/Voltage supply

7.2 Parameter adjustment with PACTware

Prereq
uisites
46 LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire
For parameter adjustment of the sensor via a Windows PC, the conguration software PACTware and a suitable instrument driver (DTM) according to FDT standard are required. The up-to-date PACTware version as well as all available DTMs are compiled in a DTM Collection. The DTMs can also be integrated into other frame applications according to FDT standard.
Note:
To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore, not all described functions are included in older rmware versions. You can download the latest instrument software from our homepage. A description of the update procedure is also available in the Internet.

7.3 Saving the parameter adjustment data

We recommend documenting or saving the parameter adjustment data via PACTware. That way the data are available for multiple use or service purposes.
41783-EN-120316

8 Set up with other systems

8 Set up with other systems

8.1 DD adjustment programs

Device descriptions as Enhanced Device Description (EDD) are available for DD adjustment programs such as, for example, AMS and PDM.

8.2 Communicator 375, 475

Device descriptions for the instrument are available as DD or EDD for parameter adjustment with the Field Communicator 375 or 475.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 47

9 Diagnosis, Asset Management and service

9 Diagnosis, Asset Management and service

9.1 Maintenance

If the device is used correctly, no maintenance is required in normal operation.

9.2 Diagnosis memory

The instrument has several memories which are available for diagnosis purposes. The data remain even with voltage interruption.
Measu
red value memory
Event
memory
Echo
curve memory
Up to 70,000 measured values can be stored in the sensor in a ring memory. Each entry contains date/time as well as the respective measured value.
Stored values are for example:
l Original sensor value l Filling height l Measured value l Meas. reliability l Electronics temperature
The requested values and recording conditions are set via a PC with PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Up to 500 events are automatically stored with a time stamp in the sensor (non-deletable). Each entry contains date/time, event type, event description and value.
Event types are for example:
l Modication of a parameter l Switching on and otimes l Status messages l Error messages
The data are read out via a PC with PACTware/DTM or the control system with EDD.
The echo curves are stored with date and time and the corresponding echo data. The memory is divided into two sections:
Echo curve of the setup: This is used as reference echo curve for the measurement conditions during setup. Changes in the measurement conditions during operation or buildup on the antenna can thus be recognized.
The echo curve of setup is stored via:
l PC with PACTware/DTM l Control system with EDD l Indicating and adjustment module
41783-EN-120316
48 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
4
1
2
3
9 Diagnosis, Asset Management and service
Further echo curves: Up to 10 echo curves can be stored in a ring buer in this memory section.
Additional echo curves are stored via:
l PC with PACTware/DTM l Control system with EDD

9.3 Asset Management function

The instrument features self-monitoring and diagnosis according to NE
107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item "Diagnosis" via the indicating and adjustment module, PACTware/DTM and EDD.
Statu
s messages
The status messages are classied in the following categories:
l Failure l Function check l Out of specication l Maintenance requirement
and explained by pictographs:
Fig. 27: Pictograms of the status messages 1 Failure - red
2 Function check - orange 3 Out of specication - yellow 4 Maintenance - blue
Failure: Due to a malfunction in the instrument, a failure message is outputted.
This status message is always active. It cannot be deactivated by the user.
Function check: The instrument is in operation, the measured value is temporarily invalid (for example during simulation).
This status message is always active. It cannot be deactivated by the user.
Out of specication: The measured value is unstable because the instrument specication is exceeded (e.g. electronics temperature).
This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 49
9 Diagnosis, Asset Management and service
Maintenance: Due to external inuences, the instrument function is limited. The measurement is aected, but the measured value is still valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD.
Fa
ilure
The following table shows the error codes in the status message
"Failure" and gives information on the reason and rectication. Keep in mind that some information is only valid with four-wire instruments.
Code
mes-
Text sage
F013
no measured value avail­able
F017 Adjustment
span too small
F025 Error in the
linearization table
F036 No operable
software
F040 Error in the
electronics
F080 l General software error l Separate operating voltage
F105 Determine
measured val­ue
F113 Communica-
tion error
Cause Rectication
l Sensor does not detect an
echo during operation
l Antenna system contami-
nated or defective
l Adjustment not within
specication
l Index markers are not
continuously rising, for ex­amle unlogical value pairs
l Failed or interrupted soft-
ware update
l Hardware defect l Exchange of the elec-
l The instrument is still in the
start phase, the measured value could not yet be determined
l EMC interferences l Transmission error with the
external communication with 4-wire power supply unit
l Check or correct installa-
tion and/or parameter ad­justment
l Clean or exchange process
component or antenna
l Change adjustment ac-
cording to the limit values (dierence between min. and max. 10 mm)
l Check linearization table l Delete table/Create new
l Repeat software update l Check electronics version l Exchange of the elec-
tronics
l Send instrument for repair
tronics
l Send instrument for repair
briey
l Wait for the warm-up phase l Duration depending on the
version and parameter ad­justment up to approxi­mately 3 min.
l Remove EMC inuences l Exchange 4-wire power
supply unit or electronics
41783-EN-120316
50 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
9 Diagnosis, Asset Management and service
Func
tion check
Code Text mes-
sage
F125 Unpermissible
electronics temperature
F260 Error in the
calibration
F261 Error in the
conguration
F264 Installation/S-
etup error
F265 Measurement
function dis­turbed
e following table shows the error codes and text messages in the
Th
Cause Rectication
l Temperature of the elec-
tronics in the non-specied section
l Error in the calibration car-
ried out in the factory
l Error in the EEPROM
l Error during setup l False signal suppression
faulty
l Error when carrying out a
reset
l Adjustment not within the
vessel height/measuring range
l Max. measuring range of
the instrument not suffi- cient
l Sensor does no longer
carry out a measurement
l Operating voltage too low
l Check ambient tempera-
ture
l Isolate electronics l Use instrument with higher
temperature range
l Exchange of the elec-
tronics
l Send instrument for repair
l Repeat setup l Repeat reset
l Check or correct installa-
tion and/or parameter ad­justment
l Use an instrument with
bigger measuring range
l Check operating voltage l Carry out a reset l Separate operating voltage
briey
status message "Function check" and provides information on causes as well as corrective measures.
Out
of specication
Code Text
mes-
sage
C700 Simulation
e following table shows the error codes and text messages in the
Th
Cause Rectication
l Simulation active l Finish simulation
l Wait for the automatic end
after 60 mins.
status message "Out of specication" and provides information on causes as well as corrective measures.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 51
9 Diagnosis, Asset Management and service
Maint
enance
Code Text mes-
sage
S600 Unpermissible
electronics temperature
S601 Overlling
e following table shows the error codes and text messages in the
Th
Cause Rectication
l Temperature of the elec-
tronics in the non-specied section
l Danger of vessel overlling l Make sure that there is no
l Check ambient tempera-
ture
l Isolate electronics l Use instrument with higher
temperature range
further lling
l Check level in the vessel
status message "Maintenance" and provides information on causes as well as corrective measures.
Code Text
mes-
sage
M500 Error with the
reset delivery status
M501 Error in the
non-active lin­earization ta­ble
M502 Error in the
diagnosis memory
M503 Reliability too
low
M504 Error on an
device inter­face
Cause Rectication
l With the reset to delivery
status, the data could not be restored
l Hardware error EEPROM l Exchange of the elec-
l Hardware error EEPROM l Exchange of the elec-
l The echot/noise ratio is the
small for a reliable meas­urement
l Hardware defect l Check connections
l Repeat reset l Load XML le with sensor
data into the sensor
tronics
l Send instrument for repair
tronics
l Send instrument for repair
l Check installation and
process conditions
l Clean the antenna l Change polarisation direc-
tion
l Use instrument with higher
sensitivity
l Exchange of the elec-
tronics
l Send instrument for repair
41783-EN-120316
52 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
9 Diagnosis, Asset Management and service
Procedu tication
Check signal
re for fault rec-
the 4 20 mA
Code Text mes-
sage
M505 No echo
available
9.4 Remo
Cause Rectication
l Level echo can no longer
be detected
l Clean the antenna l Use a more suitable an-
tenna/sensor
l Remove possible false
echoes
l Optimize sensor position
and orientation
ve interferences
The rst measures are:
l Evaluation of fault messages via the indicating and adjustment
module
l Checking the 4 20 mA signal l Treatment of measurement errors
Further comprehensive diagnosis possibilities are oered by a PC with the software PACTware and suitable DTM.
In many case, the failure reasons can thus be determined and faults rectied.
Connect a handmultimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to remove them:
Error Cause Rectication
4 20 mA signal not
stable
4 20 mA signal missing
Current signal greaterthan22 mA or less than
3.6 mA
l Level uctua-
tions
l Electrical con-
nection faulty
l Voltage supply
missing
l Operating volt-
age too low or load resist­ance too high
l Electronics
module in the sensor defec­tive
l Set damping according to the in-
strument via the indicating and adjustment module or PACTware/
DTM
l Check connection according to
chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan".
l Check cables for breaks; repair if
necessary
l Check, adapt if necessary
l Exchange the instrument or send it
in for repair
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 53
1
2
Level
time
0
Level
time
0
Level
time
0
9 Diagnosis, Asset Management and service
eatment of measure-
Tr ment errors with liquids
The below tables show typical examples of application-relevant measurement errors with liquids. The measurement errors are dierentiated according to the following:
l Constant level l Filling l Emptying
The images in column "Error pattern" show the actual level with a broken line and the level displayed by the sensor as a continuous line.
1 Real level 2 Level displayed by the sensor
Instructions:
l Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"
l In case of a too low level indication, the reason could be a line
resistance that is too high
Measurement error with constant level
Fault
description Error pattern Cause Rectication
1. Measured value shows a too low or too high level
2. Measured value jumps towards 0 %
l Min./max. adjustment not cor-
rect
l Linearization curve incorrect l Adapt linearization curve
l Installation in a bypass tube or
standpipe, hence running time error (small measurement er­ror close to 100 %/large error close to 0 %)
l Multiple echo (vessel top,
product surface) with ampli­tude higher than the level echo
l Adapt min./max. adjustment
l Check parameter "Application"
with respect to vessel form, adapt if necessary (bypass, standpipe, diameter)
l Check parameter "Application",
in particular Vessel top, Prod­uct type, Dished bottom, High dielectric value and adapt if necessary
41783-EN-120316
54 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
Level
time
0
Level
time
0
Level
time
0
Level
time
0
Level
time
0
9 Diagnosis, Asset Management and service
Fault description Error pattern Cause Rectication
3. Measured value jumps towards 100 %
rement error during lling
Measu
Fault description Error pattern Cause Rectication
4. Measured value re­mains unchanged dur­ing lling
5. Measured value re­mains in the bottom section during lling
l Due to the process, the am-
plitude of the product echo sinks
l A false signal suppression was
not carried out
l Amplitude or position of a false
echo has changed (e.g. con­densation, buildup); false sig­nal suppression no longer matches
l False echoes in the close
range too big or product echo too small
l Strong foam or spout genera-
tion
l Max. adjustment not correct
l The tank oor echo is larger
than the product echo, e.g. with products with ε based, solvents
< 2.5 oil-
r
l Carry out false signal suppres-
sion
l Determine the reason for the
changed false echoes, carry out false signal suppression, e. g. with condensation
l Remove false echoes in the
close range
l Check measurement situation:
Antenna must protrude out of
the socket, installations
l Remove pollution on the an-
tenna
l Minimize interfering installa-
tions in the close range by changing the polarization di­rection
l Create a new false signal sup-
pression
l Adapt max. adjustment
l Application parameter "Me-
dium", check Vessel height and Floor form, adapt if necessary
6. Measured value re­mains momentarily un­changed during lling
l Turbulence on the product
surface, quick lling
l Check application parameters,
change if necessary, e.g. in
dosing vessel, reactor and then jumps to the correct level
7. Measured value jumps towards 0 % during lling
l Amplitude of a multiple echo
(vessel top - product surface) is larger than the level echo
l Check application, especially
Vessel top, Product type,
Dished bottom, High dielectric
value, and adapt if necessary
l The level echo cannot be
distinguished from the false echo at a false echo position (jumps to multiple echo)
l Remove/reduce false echo:
minimize interfering installa-
tions by changing the polar-
ization direction
l Chose a more suitable instal-
lation position
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 55
Level
time
0
Level
time
0
Level
time
0
Level
time
0
Level
time
0
Level
time
0
9 Diagnosis, Asset Management and service
Fault description Error pattern Cause Rectication
8. Measured value jumps towards 100 % during lling
l Due to strong turbulence and
foam generation during lling, the amplitude of the product echo sinks. Measured value jumps to the false echo
l Carry out false signal suppres-
sion
9. Measured value jumps sporadically to 100 % during lling
l Varying condensation or con-
tamination on the antenna
l Carry out a false signal sup-
pression or increase false sig­nal suppression with condensation/contamination in the close range by editing
10. Measured value jumps to 100 % or0 m distance
l Level echo is no longer de-
tected in the close range due to foam generation or false echoes in the close range. The sensor goes into overll pro­tection mode. The max. level (0 m distance) as well as the
l Check measuring site: Antenna
must protrude out of the socket
l Remove pollution on the an-
tenna
l Use a sensor with a more
suitable antenna
status message "Overll pro­tection" are outputted.
rement error during emptying
Measu
Fault description Error pattern Cause Rectication
11. Measured value remains unchanged in the close range during emptying
l False echo larger than the
level echo
l Level echo too small
l Remove false echoes in the
close range. Check: Antenna must protrude out of the socket
l Remove pollution on the an-
tenna
l Minimize interfering installa-
tions in the close range by changing the polarization di­rection
l After removing the false ech-
oes, the false signal suppres­sion must be deleted. Carry out a new false signal suppression
12. Measured value jumps towards 0 % during emptying
l The tank oor echo is larger
than the product echo, e.g. with products with ε based, solvents
< 2.5 oil-
r
l Application parameter "Me-
dium type", check Vessel height and Floor form, adapt if necessary
13. Measured value jumps sporadically to­wards 100 % during emptying
l Varying condensation or con-
tamination on the antenna
l Carry out false signal suppres-
sion or increase false signal suppression in the close range by editing
l With bulk solids use radar
sensor with purging air con­nection
56 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
9 Diagnosis, Asset Management and service
ction after fault rec-
Rea tication
Depending on the reason for the fault and the measures taken, the steps described in chapter "Setup" must be carried out again or must be checked for plausibility and completeness.

9.5 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module with respective Ex approval may be used.
If there is no electronics module available on site, one can be ordered
from the agency serving you.

9.6 How to proceed in case of repair

If it is necessary to repair the instrument, please contact the agency serving you.
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 57

10 Dismounting

10 Dismounting

10.1 Dismounting steps

Warning:
Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

10.2 Disposal

The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable.
Correct disposal avoids negative eects on humans and the environ­ment and ensures recycling of useful raw materials.
Materials: see chapter "Technical data"
If you have no way to dispose of the old instrument properly, please
contact us concerning return and disposal.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.
58 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316

11 Supplement

11 Supplement

11.1 Technical data

General data
316L corresponds to 1.4404 or 1.4435 Materials, wetted parts with encapsulated antenna system
- Process tting PVDF, 316L
- Process seal FKM (IDG FKM 13-75)
- Antenna PVDF
Materials, wetted parts with plastic horn antenna
- Adapter ange PP
- Seal, adapter ange FKM (COG VI500), EPDM (COG AP310)
- Antenna PBT-GF 30
- Focussing lense PP
Materials, non-wetted parts
- Compression ange PP
- Mounting strap 316L
- Fixing screws, mounting strap 316L
- Fixing screws, adapter ange 304
- Housing plastic PBT (Polyester), 316L
- Seal between housing and housing
cover
- Inspection window in housing cover
(optional)
- Ground terminal 316L
Process ttings
- Pipe thread, cylindrical (ISO 228 T1) G1½ A
- American pipe thread, tapered 1½ NPT
- Flanges DIN from DN 80, ANSI from 3", JIS from DN 100
- Hygienic ttings Clamp, bolting according to DIN 11851, Tuchen-
Weight depending on process tting and housing material
Max. torque, mounting screws - strap on the sensor housing
Max. torque ange screws
- Compression ange DN 80 5 Nm (3.689 lbf ft)
- Adapter ange DN 100 7 Nm (5.163 lbf ft)
Max. torque for NPT cable glands and Conduit tubes
- Plastic housing 10 Nm (7.376 lbf ft)
Silicone
Polycarbonate
10K
hagen Varivent
0.7 … 3.4 kg (1.543 … 7.496 lbs)
4 Nm
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 59
3
4
2
1
11 Supplement
- Aluminium/Stainless steel housing 50 Nm (36.88 lbf ft)
Input variable
Measured variable The measured quantity is the distance between
process tting of the sensor and product surface. The reference plane is the seal surface on the hexagon or the lower side of the ange.
Fig. 41: Data of the input variable 1 Reference plane
2 Measured variable, max. measuring range 3 Antenna length 4 Useful measuring range
Standard electronics
Max. measuring range 35 m (114.8 ft) Recommended measuring range
- Encapsulated antenna system up to 10 m (32.81 ft)
- Plastic horn antenna up to 20 m (65.62 ft)
Electronics with increased sensitivity
Max. measuring range 35 m (114.8 ft) Recommended measuring range
- Encapsulated antenna system up to 10 m (32.81 ft)
- Plastic horn antenna up to 20 m (65.62 ft)
Output variable
Output signal 4 20 mA/HART Fullled HART specication 7.0
60 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
11 Supplement
Signal resolution 0.3 µA Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA Max. output current 22 mA Starting current 3.6 mA; 10 mA for 5 ms after switching on Load see load diagram under Power supply Damping (63 % of the input variable),
0 999 s
adjustable
HART output values according to HART 7.0
1)
- PV (Primary Value) Distance to the level
- SV (Secondary Value) Level as percentage value
- TV (Third Value) Linearised percentage value
- QV (Fourth Value) Scaled measured value
Resolution, digital < 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
- Temperature +18 … +30 °C (+64 +86 °F)
- Relative humidity 45 75 %
- Air pressure 860 … 1060 mbar/86 106 kPa (12.5 15.4 psig)
Installation reference conditions
- Min. distance to installations > 200 mm (7.874 in)
- Reector Corner reector
- False reections Largest false echo 20 dB smaller than the useful
echo
Deviation with liquids See following diagrams
1)
values, can be assigned individually
Default
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 61
0,5 m (1.6 ft)
10 mm (0.394 in)
- 10 mm (- 0.394 in)
2 mm (0.079 in)
- 2 mm (- 0.079 in)
0
1
2
3
0,5 m (1.6 ft)
10 mm (0.394 in)
- 10 mm (- 0.394 in)
2 mm (0.079 in)
- 2 mm (- 0.079 in)
0
1
2
3
11 Supplement
Fig. 42: Deviation under reference conditions - encapsulated antenna system 1 Reference plane
2 Antenna edge 3 Recommended measuring range
Fig. 43: Deviation under reference conditions - plastic horn antenna 1 Reference plane
2 Antenna edge 3 Recommended measuring range
Reproducibility ≤ ±1 mm Deviation with bulk solids The values depend to a great extent on the
application. Binding specications are thus not possible.
Variables inuencing measurement accuracy Specications apply to the HART signal and the current output
Temperature drift - Digital output ±3 mm/10 K relating to the max. measuring range
or max. 10 mm
62 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
11 Supplement
Additional deviation through strong, high
50 mm
frequency electromagnetic elds acc. to EN
61326
Specications apply also to the current output
Temperature drift - Current output ±0.03 %/10 K relating to the 16 mA span max.
±0.3 %
Deviation on the current output by analogue/
15 µA
digital conversion Deviation on the current output by strong,
150 µA
high frequency electromagnetic elds within
EN 61326
Characteristics and performance data
Frequency K-band (26 GHz technology) Measuring cycle time
- Standard electronics approx. 450 ms
- Electronics with increased sensitivity
700 ms
approx.
Step response time Tracking speed of the measuring window
2)
3 s 1 m/min
max. Beam angle
3)
- Encapsulated antenna system 22°
- Plastic horn antenna 10°
Emitted HF power (depending on the parameter adjustment)
- Average spectral transmission power
-14 dBm/MHz EIRP
4)
density
- Max. spectral transmission power den-
+43 dBm/50 MHz EIRP
sity
- Max. power density in a distance of 1 m < 1 µW/cm²
Ambient conditions
Ambient, storage and transport temperature -40 +80 °C (-40 +176 °F)
Process conditions
For the process conditions, please also note the specications on the type label. The lower value always applies.
2)
3)
4)
span after a sudden measuring distance change by max. 0.5 m in
Time liquid applications, max 2 m with bulk solids applications, until the output signal has taken for the rst time 90 % of the nal value (IEC 61298-2). Outside
the specied beam angle, the energy of the radar signal has a level
which is reduced by 50 % (-3 dB) EIRP: Equivalent Isotropic Radiated Power
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 63
11 Supplement
Vessel pressure
- Encapsulated antenna system -1 3 bar (-100 300 kPa/ -14.5 43.5 psi)
- Plastic horn antenna -1 2 bar (-100 200 kPa/-14.5 29 .0 psig)
- Version with adapter ange from DN 150PP-1 1 bar (-100 100 kPa/-14.5 14 .5 psig)
Process temperature (measured on the
-40 +80 °C (-40 +176 °F)
process tting)
Vibration resistance
- With adapter ange 2 g at 5 … 200 Hz according to EN60068-2-6
(vibration with resonance)
- with mounting strap 1 g at 5 … 200 Hz according to EN60068-2-6
(vibration with resonance)
Shock resistance 100 g, 6 ms according to EN60068-2-27 (mechan-
ical shock)
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry/plug
5)
- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 9 mm), 1 x blind stopper M20 x 1.5
or:
l 1 x closing cap M20 x 1.5; 1 x blind stopper
M20 x 1.5
or:
l 1 x closing cap ½ NP T, 1 x blind plug ½ NPT
or:
l 1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5
- Double chamber housing l 1 x cable entry M20 x 1.5 (cable: ø 5 9 mm), 1 x blind stopper M20 x 1.5; 1 x blind stopper
M16 x 1.5 or optional6)1 x plug M12 x 1 for external indicating and adjustment unit
or:
l 1 x closing cap ½ NP T, 1 x blind stopper
½ NPT, 1 x blind stopper M16 x 1.5 or
optionally7)1 x plug M12 x 1 for external indicating and adjustment unit
or:
l 1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5; 1 x blind stopper M16 x 1.5 or optionally8)1 x plug M12 x 1 for external indicating and adjustment unit
41783-EN-120316
5)
Depending
6)
Only with Ex d version
7)
Only with Ex d version
8)
Only
on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.
with Ex d version
64 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
11 Supplement
Spring-loaded terminals for wire cross-section
- Massive wire, cord 0.2 … 2.5 mm² (AWG 24 … 14)
- Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)
Indicating and adjustment module
Voltage supply and data transmission through the sensor Indication LC display in dot matrix Measured value indication
- Number of digits 5
- Size of digits W x H = 7 x 13 mm (sensors with software 4.0.0,
hardware 2.0.0) W x H = 5 x 8 mm (sensors with software 3.99, hardware < 2.0.0)
Adjustment elements 4 keys Protection rating
- unassembled IP 20
- mounted into the sensor without cover IP 40
Materials
- Housing ABS
- Inspection window Polyester foil
Integrated clock
Date format Day.Month.Year Time format 12 h/24 h Time zone Ex factory CET
Measurement electronics temerature
Resolution 1 °C (1.8 °F) Accuracy ±1 °C (1.8 °F)
Voltage supply
Operating voltage
- Non-Ex instrument 9.6 … 36 V DC
- Ex-ia instrument 9.6 … 30 V DC
Operating voltage with illuminated indicating and adjustment module
- Non-Ex instrument 16 36 V DC
- Ex-ia instrument 16 30 V DC
Interpolation protection Available Permissible residual ripple - Non-Ex, Ex-ia instrument
- for 9.6 V
- for 18 V
< 14 V 0.7 Ve(16 400 Hz)
< U
N
< 36 V 1.0 Ve(16 400 Hz)
< U
N
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 65
1200
927
500
750
250
12 18
16
9,6
14 2015,1 22 24 26 28 30 32 34 36
V
1
4
2
3
11 Supplement
Load see diagram
Fig. 44: Voltage diagram 1 HART load
2 Voltage limit Ex-ia instrument 3 Voltage limit non-Ex instrument 4 Operating voltage
Electrical protective measures
Protection rating IP 66/IP 67 Overvoltage category III Protection class II
Approvals
Instruments with approvals can have deviating technical data (depending on the version). For such instruments, the corresponding approval documents must be noted.
66 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
127 mm
(5")
~ 76 mm
(2 63/64")
ø 91 mm (3 37/64")
M20x1,5/ ½ NPT
~ 76 mm (2 63/64")
123 mm
(4
27
/
32
")
ø 91 mm (3 37/64")
M20x1,5/ ½ NPT
1
2
SW 50 mm
(1.97")
43 mm
(1.69")
20 mm
(0.79")
78 mm (3.07")
ø 39 mm
(1.54")
G1½A / 1½ NPT
11 Supplement

11.2 Dimensions

Plastic housing
Fig. 45: Housing versions in protection IP 66/IP 68 (0.2 bar) - with integrated indicating and adjustment module the housing is 9 mm/0.35 in higher
1 Single chamber version 2 Double chamber version
LEVEL TRANSMITTER 8136, threaded version
Fig. 46: LEVEL TRANSMITTER 8136, threaded version G1½ A and 1½ NPT
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 67
2
3
1
2
3
SW 50 mm
(1.97")
SW 50 mm
(1.97")
SW 50 mm
(1.97")
121 mm (4.76")121 mm (4.76")
121 mm (4.76")
ø 64 mm (2.52") ø 91 mm (3.58")
ø 78 mm (3.07") ø 95 mm (3.74")
ø 39 mm
(1.54")
ø 68 mm
(2.68")
ø 84 mm
(3.31")
ø 39 mm
(1.54")
11 Supplement
LEVEL TRANSMITTER 8136, hygienic tting
Fig. 47: LEVEL TRANSMITTER 8136, hygienic tting 1 Clamp 2" (ø 64 mm) and 3" (ø 91 mm) PN 16 DIN 32676, ISO 2852/316L
2 Bolting according to DIN 11851 DN 50 and DN 80 3 Tuchenhagen Varivent DN 32
68 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
LEVEL TRANSMITTER 8136, version with mounting strap
125 mm
(4.92")
2,5 mm
(0.10")
75 mm (2.95")
107 mm
(4.21")
115 mm
(4.53")
300 mm
(11.81")
19 mm
(0.75")
98 mm
(3.86")
15 mm
(0.59")
8,5 mm
(0.34")
9 mm
(0.35")
85 mm
(3.35")
12 mm
(0.47")
9 mm
(0.35")
12 mm (0.47")
170 mm
(6.69")
11 Supplement
Fig. 48: LEVEL TRANSMITTER 8136, version with mounting bracket 170 or 300 mm in length
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 69
115,5 mm (4.55")
218 mm (8.58")
45°
71 mm
(2.8")
17,5 mm
(0.69")
ø 9 mm
(0.35")
107,5 mm
(4.23")
117,5 mm
(4.63")
110 mm
(4.33")
160 mm
(6.30")
60 mm (2.36")
11 Supplement
LEVEL TRANSMITTER 8136, version with mounting strap and reector
Fig. 49: LEVEL TRANSMITTER 8136, version with mounting strap and reector
70 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
LEVEL TRANSMITTER 8136, version with compression ange
126 mm
(4.96")
10,5 mm
(0.41")
19 mm
(0.75")
ø 75 mm (2.95")
ø 115 mm (4.53")
ø 156 mm (6.14")
ø 200 mm (7.87")
ø 21 mm
(0.83")
ø 107 mm
(4.21")
11 Supplement
Fig. 50: LEVEL TRANSMITTER 8136, compression ange suitable for DN 80 PN 16/ASME 3" 150lbs/JIS80 10K
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 71
2
1
138 mm (5.43")
31 mm
(1.22")
20 mm
(0.79")
8 mm
(0.32")
ø 75 mm (2.95")
ø 98 mm (3.86")
11 Supplement
LEVEL TRANSMITTER 8136, version with adapter ange
Fig. 51: LEVEL TRANSMITTER 8136, adapter ange 1 Adapter ange
2 Seal
72 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
INDEX
Index
A
Acc
essory
- Indicating and adjustment module 9
Adjustment 37
- Max. adjustment 38
- Min. adjustment 38
Adjustment system 30 Agitators 19 Application
- Bulk solid 35
- Liquid 32
- Standpipe 32
B
Bypass 21
C
Cable entry 25 Check signal 53 Connection cable 25 Connection procedure 26 Connection technology 26 Curve indication
- Echo curve 39
- False signal suppression 39
D
DD (Device Description) 47 Default values 43
G
Grounding 25-26
I
Inowing medium 14
K
Key function 30
L
Linearisation curve 42
M
Main menu 31 Meas. reliability 39 Measured value memory 48 Measurement error 54 Medium
- Bulk solid 31 Moisture 10 Mounting position 13
N
NAMUR NE 107
- Failure 50
- Function check 51
- Maintenance 52
- Out of specication 51
E
Echo curve memory 48 Echo curve of the setup 40 EDD (Enhanced Device Description) 47 Electronics and connection compartment, single
chamber housing 28
Error messages 49 Event memory 48
F
False signal suppression 40 Fault rectication 53 Flow measurement
- Khafagi-Venturi ume 24
- Rectangular ume 23
Foam generation 19 Functional principle 8
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 73
O
Overll protection according to WHG 42
P
Packaging 8 Peak value 39 Polarisation plane 12 Potential equalisation 26
R
Reection properties 32 Replacement parts
- Electronics module 9 Reset 42
S
Sensor orientation 18 Shielding 25-26
Index
Socket 17 Status messages 49 Storage 8 Surge pipe 20
T
Type label 7
V
Vessel form 37 Vessel height 37 Vessel installations 18 Voltage supply 25
74 LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
41783-EN-120316
Index
41783-EN-120316
LEVEL TRANSMITTER 8136 4 20 mA/HART - two-wire 75
The smart choice of Fluid Control Systems www.burkert.com
41783-EN-120316
Bedienungsanleitung
LEVEL TRANSMITTER
8136
4 20 mA/HART - Zweileiter

Inhaltsverzeichnis

Inhaltsverzeichnis
diesem Dokument
1 Zu
1.1 Funktion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Zielgruppe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Verwendete Symbolik . . . . . . . . . . . . . . . . . . . . . . . .
2 Zu Ihrer Sicherheit
2.1 Autorisiertes Personal. . . . . . . . . . . . . . . . . . . . . . . .
2.2 Bestimmungsgemäße Verwendung . . . . . . . . . . . . . .
2.3 Warnung vor Fehlgebrauch . . . . . . . . . . . . . . . . . . . .
2.4 Allgemeine Sicherheitshinweise . . . . . . . . . . . . . . . . .
2.5 CE-Konformität. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 NAMUR-Empfehlungen. . . . . . . . . . . . . . . . . . . . . . .
2.7 Funktechnische Zulassung für Europa . . . . . . . . . . . .
2.8 Funktechnische Zulassung für USA/Kanada . . . . . . . .
3 Produktbeschreibung
3.1 Aufbau. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Arbeitsweise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Verpackung, Transport und Lagerung . . . . . . . . . . . .
3.4 Zubehör und Ersatzteile . . . . . . . . . . . . . . . . . . . . . .
4 Montieren
4.1 Allgemeine Hinweise . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Überwurf- oder Adapteransch . . . . . . . . . . . . . . . . .
4.3 Montagevorbereitungen Montagebügel. . . . . . . . . . . .
4.4 Montagehinweise . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 4 4
5 5 5 5 6 6 6 6
7 8 8 9
10 10 11 12
5 An die Spannungsversorgung anschließen
5.1 Anschluss vorbereiten. . . . . . . . . . . . . . . . . . . . . . . .
5.2 Anschließen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Anschlussplan . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Einschaltphase. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 In Betrieb nehmen mit dem Anzeige- und Bedienmodul
6.1 Anzeige- und Bedienmodul einsetzen . . . . . . . . . . . .
6.2 Bediensystem . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Parametrierung. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Sicherung der Parametrierdaten . . . . . . . . . . . . . . . .
7 In Betrieb nehmen mit PACTware
7.1 Den PC anschließen. . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Parametrierung mit PACTware . . . . . . . . . . . . . . . . .
7.3 Sicherung der Parametrierdaten . . . . . . . . . . . . . . . .
8 In Betrieb nehmen mit anderen Systemen
8.1 DD-Bedienprogramme . . . . . . . . . . . . . . . . . . . . . . .
8.2 Communicator 375, 475 . . . . . . . . . . . . . . . . . . . . . .
2 LEVEL
25 26 27 28
29 30 31 45
46 46 46
41783-DE-120229
47 47
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
Inhaltsverzeichnis
9 Diagnose
9.1 Wartung. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2 Diagnosespeicher. . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3 Asset-Management-Funktion. . . . . . . . . . . . . . . . . . .
9.4 Störungen beseitigen . . . . . . . . . . . . . . . . . . . . . . . .
9.5 Elektronikeinsatz tauschen . . . . . . . . . . . . . . . . . . . .
9.6 Vorgehen im Reparaturfall. . . . . . . . . . . . . . . . . . . . .
10 Ausbauen
10.1 Ausbauschritte . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2 Entsorgen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 Anhang
11.1 Technische Daten . . . . . . . . . . . . . . . . . . . . . . . . . .
11.2 Maße. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
, Asset Management und Service
48 48 49 53 57 58
59 59
60 68
Sicherheitshinweise für Ex-Bereiche
Beachten Sie hinweise. Diese sind Bestandteil der Betriebsanleitung und liegen jedem Gerät mit Ex-Zulassung bei.
Redaktionsstand: 2012-02-29
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
bei Ex-Anwendungen die Ex-spezischen Sicherheits-
T - Zweileiter 3
diesem Dokument
1 Zu
1 Zu diesem Dokum
ent

1.1 Funktion

Die vorliegende Betriebsanleitung liefert Ihnen die erforderlichen Informationen für Montage, Anschluss und Inbetriebnahme sowie
wichtige Hinweise für Wartung und Störungsbeseitigung. Lesen Sie diese deshalb vor der Inbetriebnahme und bewahren Sie sie als Produktbestandteil in unmittelbarer Nähe des Gerätes jederzeit zugänglich auf.

1.2 Zielgruppe

Diese Betriebsanleitung richtet sich an ausgebildetes Fachpersonal. Der Inhalt dieser Anleitung muss dem Fachpersonal zugänglich
gemacht und umgesetzt werden.

1.3 Verwendete Symbolik

Information, Tip
Dieses Symbol kennzeichnet hilfreiche Zusatzinformationen.
Vorsicht: Bei Nich Störungen oder Fehlfunktionen die Folge sein.
Warnung: Bei Nichtbeachten dieses Warnhinweises kann ein Perso- nenschaden und/oder ein schwerer Geräteschaden die Folge sein. Gefahr: Bei Nichtbeachten dieses Warnhinweises kann eine ernst- hafte Verletzung von Personen und/oder eine Zerstörung des Gerätes die Folge sein.
p, Hinweis
tbeachten dieses Warnhinweises können
endungen
Ex-Anw
Dieses Sym dungen.
l Liste
Der vorangestellte Punkt kennzeichnet eine Liste ohne zwingende Reihenfolge.
à Handlungsschritt
Dieser Pfeil kenn
1 Handlungsfolge
Vorangestellte Zahlen kennzeichnen aufeinander folgende Hand­lungsschritte.
4 LEVEL
bol kennzeichnet besondere Hinweise für Ex-Anwen-
zeichnet einen einzelnen Handlungsschritt.
41783-DE-120229
TRANSMITTER 8136 4 20 mA /HART - Zweileiter

2 Zu Ihrer Sicherheit

2 Zu Ihrer Sicherhe
it
2.1 Auto
Sämtliche in dieser Betriebsanleitung beschriebenen Handhabungen dürfen nur durch ausgebildetes und vom Anlagenbetreiber autorisier­tes Fachpersonal durchgeführt werden.
Bei Arbeiten am und mit dem Gerät ist immer die erforderliche persönliche Schutzausrüstung zu tragen.
risiertes Personal

2.2 Bestimmungsgemäße Verwendung

Der LEVEL TRANSMITTER 8136 ist ein Sensor zur kontinuierlichen Füllstandmessung.
Detaillierte Angaben zum Einsatzbereich nden Sie im Kapitel
"Produktbeschreibung".
Die Betriebssicherheit des Gerätes ist nur bei bestimmungsgemäßer Verwendung entsprechend den Angaben in der Betriebsanleitung sowie in den evtl. ergänzenden Anleitungen gegeben.

2.3 Warnung vor Fehlgebrauch

Bei nicht sachgerechter oder nicht bestimmungsgemäßer Verwen­dung können von diesem Gerät anwendungsspezische Gefahren ausgehen, so z. B. ein Überlauf des Behälters oder Schäden an Anlagenteilen durch falsche Montage oder Einstellung.

2.4 Allgemeine Sicherheitshinweise

Das Gerät entspricht dem Stand der Technik unter Beachtung der
üblichen Vorschriften und Richtlinien. Es darf nur in technisch einwandfreiem und betriebssicherem Zustand betrieben werden. Der
Betreiber ist für den störungsfreien Betrieb des Gerätes verantwortlich.
Der Betreiber ist ferner verpichtet, während der gesamten Einsatz-
dauer die Übereinstimmung der erforderlichen Arbeitssicherheits­maßnahmen mit dem aktuellen Stand der jeweils geltenden Regel­werke festzustellen und neue Vorschriften zu beachten.
Durch den Anwender sind die Sicherheitshinweise in dieser Be­triebsanleitung, die landesspezischen Installationsstandards sowie die geltenden Sicherheitsbestimmungen und Unfallverhütungsvor­schriften zu beachten.
Eingrie über die in der Betriebsanleitung beschriebenen Hand­habungen hinaus dürfen aus Sicherheits- und Gewährleistungsgrün­den nur durch vom Hersteller autorisiertes Personal vorgenommen werden. Eigenmächtige Umbauten oder Veränderungen sind aus­drücklich untersagt.
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 5
2 Zu Ihrer Sich
erheit
Weiterhin sind die auf dem G zeichen und -hinweise zu beachten.
Die Sendefrequenzen der Radarsensoren liegen je nach Geräteaus­führung im C- oder K-Bandbereich. Die geringen Sendeleistungen liegen weit unter den international zugelassenen Grenzwerten. Bei bestimmungsgemäßem Gebrauch sind keinerlei gesundheitliche Be­einträchtigungen zu erwarten.
erät angebrachten Sicherheitskenn-
2.5 CE-Konformität
Das Gerät erfüllt die gesetzlichen Anforderungen der zutreenden EG- Richtlinien. Mit dem CE-Zeichen bestätigen wir die erfolgreiche Prüfung.
2.6 NAMUR-Empfehlungen
Die NAMUR ist die Interessengemeinschaft Automatisierungstechnik in der Prozessindustrie in Deutschland. Die herausgegebenen NAMUR-Empfehlungen gelten als Standards in der Feldinstrumentie­rung.
Das Gerät erfüllt die Anforderungen folgender NAMUR-Empfehlun­gen:
l NE 21 – Elektromagnetische Verträglichkeit von Betriebsmitteln l NE 43 – Signalpegel für die Ausfallinformation von Messumfor-
mern
l NE 53 – Kompatibilität von Feldgeräten und Anzeige-/Bedien-
komponenten
l NE 107 - Selbstüberwachung und Diagnose von Feldgeräten
Weitere Informationen siehe
www.nam
ur.de.
2.7 Funkt
Das Gerät ist gemäß EN 302372-1/2 (2006-04) für den Einsatz in geschlossenen Behältern zugelassen.

2.8 Funktechnische Zulassung für USA/Kanada

Dieses Gerät ist konform zu Teil 15 der FCC-Vorschriften. Für den Betrieb sind die folgenden beiden Bestimmungen zu beachten:
l Das Gerät darf keine Störemissionen verursachen, und l Das Gerät muss unempndlich gegen Störimmissionen sein, auch
gegen solche, die unerwünschte Betriebszustände verursachen.
Vom Hersteller nicht ausdrücklich genehmigte Änderungen führen zum Erlöschen der Betriebserlaubnis nach FCC/IC.
Das Gerät ist konform zu RSS-210 der IC-Vorschriften.
Das Gerät darf nur in geschlossenen Behältern aus Metall, Beton oder glasfaserverstärktem Kunststobetrieben werden.
6 LEVEL
echnische Zulassung für Europa
41783-DE-120229
TRANSMITTER 8136 4 20 mA /HART - Zweileiter

3 Produktbeschreibung

2
1
10
11
12
13
9
8
3
4
5
6
7
3 Produktbeschreibung
au
Typs
child
3.1 Aufb
Das Typschild enthält die wichtigsten Daten zur Identikation und zum Einsatz des Gerätes:
Abb. 1: Aufbau 1 Gerätetyp
2 Produktcode 3 Zulassungen 4 Prozess- und Umgebungstemperatur, Prozessdruck 5 Signalausgang Elektronik, Spannungsversorgung 6 Schutzart 7 Auftragsnummer 8 Seriennummer des Gerätes 9 Symbol für Geräteschutzklasse 10 ID-Nummern Gerätedokumentation 11 Hinweis zur Beachtung der Gerätedokumentation 12 Notizierte Stelle für die CE-Kennzeichnung 13 Zulassungsrichtlinie
Gelt
ungsbereich dieser
bsan
Betrie
leitung
Lieferumfang
Die vorliegende Betriebsanleitung gilt für folgende Geräteausfüh­rungen:
l Hardware ab 2.1.1 l Software ab 4.4.0
Der Lieferumfang besteht aus:
l Radarsensor l Dokumentation
- Dieser Betriebsanleitung
- Betriebsanleitung "Anzeige- und Bedienmodul" (optional)
- Ex-spezischen "Sicherheitshinweisen" (bei Ex-Ausführun-
- Ggf. weiteren Bescheinigungen
des Typschildes (Beispiel)
gen)
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 7
3 Produktbeschreibung

3.2 Arbeitsweise

Einsatz
bereich
Funktionsprinzip
Verpackung
VEL TRANSMITTER 8136 ist ein Radarsensor zur kontinuier-
Der LE
lichen Füllstandmessung von Flüssigkeiten unter einfachen Prozess­bedingungen.
Je nach Einsatzbereich werden unterschiedliche Ausführungen ver­wendet:
l Füllstandmessung von aggressiven Flüssigkeiten in kleinen
Behältern: gekapseltes Antennensystem
l Durchussmessung in oenen Gerinnen oder die Pegelmessung
in Gewässern: Kunststohornantenne
l Füllgüter mit einem ε l Füllgüter mit mit einem ε
-Wert 1,8: Standardelektronik
r
-Wert 1,5, < 1,8; Anwendungen mit sehr
r
schlechten Reexionseigenschaften: Elektronik mit erhöhter
Empndlichkeit
Die tatsächlich erreichbaren Werte hängen von den Messbedingun­gen, dem Antennensystem bzw. dem Standrohr oder Bypass ab.
Von der Antenne des Radarsensors werden kurze Radarimpulse mit einer Dauer von ca. 1 ns ausgesendet. Diese werden vom Füllgut reektiert und von der Antenne als Echos empfangen. Die Laufzeit der Radarimpulse vom Aussenden bis zum Empfangen ist der Distanz und damit der Füllhöhe proportional. Die so ermittelte Füllhöhe wird in ein entsprechendes Ausgangssignal umgewandelt und als Messwert ausgegeben.

3.3 Verpackung, Transport und Lagerung

Ihr Gerät wurde auf dem Weg zum Einsatzort durch eine Verpackung geschützt. Dabei sind die üblichen Transportbeanspruchungen durch eine Prüfung nach DIN EN 24180 abgesichert.
Bei Standardgeräten besteht die Verpackung aus Karton, ist umwelt­verträglich und wieder verwertbar. Bei Sonderausführungen wird zusätzlich PE-Schaum oder PE-Folie verwendet. Entsorgen Sie das anfallende Verpackungsmaterial über spezialisierte Recyclingbetrie­be.
Transport
Der Transport muss unter Berücksichtigung der Hinweise auf der Transportverpackung erfolgen. Nichtbeachtung kann Schäden am Gerät zur Folge haben.
Transportinspektion
Die Lieferung ist bei Erhalt unverzüglich auf Vollständigkeit und eventuelle Transportschäden zu untersuchen. Festgestellte Trans­portschäden oder verdeckte Mängel sind entsprechend zu behandeln.
Lagerung
Die Packstücke sind bis zur Montage verschlossen und unter Beachtung der außen angebrachten Aufstell- und Lagermarkierungen
aufzubewahren.
8 LEVEL
41783-DE-120229
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
3 Produktbeschreibung
Lager- und Transport­temp
eratur
Anzeige- und Bedien­modul
Elektronikeinsatz
Packstücke, sofer
n nicht anders angegeben, nur unter folgenden
Bedingungen lagern:
l Nicht im Freien aufbewahren l Trocken und staubfrei lagern l Keinen aggressiven Medien aussetzen l Vor Sonneneinstrahlung schützen l Mechanische Erschütterungen vermeiden
l Lager- und Transporttemperatur siehe Kapitel "Anhang - Techni-
sche Daten - Umgebungsbedingungen"
l Relative Luftfeuchte 20 85 %

3.4 Zubehör und Ersatzteile

Das Anzeige- und Bedienmodul dient zur Messwertanzeige, Bedie­nung und Diagnose. Es kann jederzeit in den Sensor eingesetzt und wieder entfernt werden.
Weitere Informationen nden Sie in der Betriebsanleitung "Anzeige- und Bedienmodul" (Document-ID 41787).
Der Elektronikeinsatz ist ein Austauschteil für Radarsensoren der LEVEL TRANSMITTER Serie. Für die unterschiedlichen Signalaus- gänge steht jeweils eine eigene Ausführung zur Verfügung.
Weitere Informationen nden Sie in der Betriebsanleitung "Elektro-
nikeinsatz LEVEL TRANSMITTER 813X" (Document-ID 41786).
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 9
4 Montie
ren

4 Montieren

Einschrauben
Feuchtigkeit
Eignung für die Pro-
zess
bedingungen
4.1 Allge
Bei Geräten mit Prozessanschluss Gewinde muss am Sechskant mit geeignetem Werkzeug angezogen werden.
Warnung:
Das G Festziehen kann Schäden an der Drehmechanik des Gehäuses
verursachen.
Verwenden Sie die empfohlenen Kabel (siehe Kapitel "An die Spannungsversorgung anschließen") und ziehen Sie die Kabelver-
schraubung fest an.
Sie schützen Ihr Gerät zusätzlich gegen das Eindringen von Feuchtigkeit, indem Sie das Anschlusskabel vor der Kabelverschrau-
bung nach unten führen. Regen- und Kondenswasser können so abtropfen. Dies gilt vor allem bei Montage im Freien, in Räumen, in denen mit Feuchtigkeit zu rechnen ist (z. B. durch Reinigungs­prozesse) oder an gekühlten bzw. beheizten Behältern.
Stellen Sie sicher, dass sämtliche, im Prozess bendlichen Teile des Gerätes, insbesondere messaktiver Teil, Prozessdichtung und Pro-
zessanschluss für die auftretenden Prozessbedingungen geeignet sind. Dazu zählen insbesondere Prozessdruck, Prozesstemperatur sowie die chemischen Eigenschaften der Medien.
Die Angaben dazu nden Sie im Kapitel "Technische Daten" und auf dem Typschild.
meine Hinweise
ehäuse darf nicht zum Einschrauben verwendet werden! Das
4.2 Überwurf- oder Adapteransch
Für die Montage des Gerätes auf einem Stutzen steht ein loser Kombi­Überwuransch für DN 80 (ASME 3" oder JIS 80) auch zur Nachrüstung zur Verfügung. Optional kann das Gerät auch ab Werk mit einem Adapteransch ab DN 100 (ASME 4" oder JIS 100) ausgerüstet werden.
Bei den Gehäusevarianten Kunststoff, Aluminium-Einkammer und Edelstahl kann der Überwuransch direkt über das Gehäuse geführt werden. Beim Aluminium-Zweikammergehäuse ist eine nachträgliche Montage nicht möglich, die Montageart ist bei der Bestellung festzu-
legen.
Zeichnungen zu diesen Montageoptionen nden Sie im Kapitel
"Maße".
10 LEVEL
41783-DE-120229
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
4 Montieren
Abb. 2: Flanschmontage
des Radarsensors

4.3 Montagevorbereitungen Montagebügel

Der Montagebügel ermöglicht die einfache Befestigung an der Behälterwand oder der Silodecke. Er ist geeignet zur Montage an Wand, Decke oder am Ausleger. Vor allem bei oenen Behältern ist dies eine sehr einfache und eektive Möglichkeit, den Sensor auf die Schüttgutoberäche auszurichten.
Der Bügel wird lose mitgeliefert und muss vor der Inbetriebnahme mit
den drei Inbusschrauben M5 x 10 und Federscheiben am Sensor angeschraubt werden. Max. Anzugsmoment siehe Kapitel "Techni-
sche Daten". Erforderliches Werkzeug: Innensechskantschlüssel Größe 4.
Zum Anschrauben des Bügels am Sensor sind zwei Varianten möglich. Je nach gewählter Variante kann der Sensor wie folgt im Bügel geschwenkt werden:
l Einkammergehäuse
- Neigungswinkel 180° stufenlos
- Neigungswinkel in drei Stufen 0°, 90° und 180°
l Zweikammergehäuse
- Neigungswinkel 90° stufenlos
- Neigungswinkel in zwei Stufen 0° und 90°
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 11
4 Montie
ren
r Einbau der
Dichte Kuns
tstohornantenne
Polarisationsebene
Abb. 3: Verstellung
Abb. 4: Drehen
des Neigungswinkels
bei Befestigung in der Mitte

4.4 Montagehinweise

Zum dichten Einbau der Ausführung mit Kunststohornantenne mit dem Überwurf- oder Adapteransch muss folgendes erfüllt sein:
1 Passende Flachdichtung z. B. aus EPDM mit Shore-Härte 25 oder
50 verwenden
2 Anzahl der Flanschschrauben entsprechend der Anzahl der
Flanschbohrungen
3 Alle Schrauben mit dem in den technischen Daten angegebenen
Anzugsmoment anziehen
Die ausgesandten Radarimpulse des Radarsensors sind elektromag-
netische Wellen. Die Polarisationsebene ist die Richtung des elektrischen Anteils. Durch Drehen des Gerätes im Verbindungs­ansch oder Einschraubstutzen kann die Polarisation genutzt werden, um die Auswirkung von Störechos zu reduzieren.
Die Lage der Polarisationsebene ist durch eine Markierung am Prozessanschluss des Gerätes gekennzeichnet.
41783-DE-120229
12 LEVEL
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
1
1
4 Montieren
Montag
eposition
Abb. 5: Lage gekapseltem Antennensystem
1 Markierungsbohrung
Abb. 6: Lage Kunststohornantenne
1 Markierungsstege
der Polarisationsebene beim LEVEL TRANSMITTER 8136 mit
der Polarisationsebene beim LEVEL TRANSMITTER 8136 mit
Montieren Sie den Sensor an einer Position, die mindestens 200 mm (7.874 in) von der Behälterwand entfernt ist. Wenn der Sensor in
Behältern mit Klöpper- oder Runddecken mittig montiert wird, können Vielfachechos entstehen, die durch einen entsprechenden Abgleich ausgeblendet werden können (siehe Kapitel "Inbetriebnahme").
Wenn Sie diesen Abstand nicht einhalten können, sollten Sie bei der Inbetriebnahme eine Störsignalspeicherung durchführen. Dies gilt vor
allem, wenn Anhaftungen an der Behälterwand zu erwarten sind. In diesem Fall empehlt es sich, die Störsignalspeicherung zu einem späteren Zeitpunkt mit vorhandenen Anhaftungen zu wiederholen.
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 13
> 200 mm
(7.87
")
4 Montie
ren
Einströmendes Füllgut
Abb. 7: Montage
des Radarsensors an runden Behälterdecken
Bei Behältern mit konischem Boden kann es vorteilhaft sein, den Sensor in Behältermitte zu montieren, da die Messung dann bis zum Boden möglich ist.
Abb. 8: Montage
des Radarsensors an Behältern mit konischem Boden
Montieren Sie die Geräte nicht über oder in den Befüllstrom. Stellen Sie sicher, dass Sie die Füllgutoberäche erfassen und nicht das einströmende Füllgut.
41783-DE-120229
14 LEVEL
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
4 Montieren
zen bei Kunststoff-
Stut
horna
ntenne
Abb. 9: Montage
des Radarsensors bei einströmendem Füllgut
Für die Montage des LEVEL TRANSMITTER 8136 auf einem Stutzen steht ein entsprechender Überwuransch für DN 80 (ASME 3" oder
JIS 80) sowie ein geeigneter Adapteransch zur Verfügung.
Bei den Gehäusevarianten Kunststoff, Aluminium-Einkammer und Edelstahl kann der Überwuransch direkt über das Gehäuse geführt werden. Beim Aluminium-Zweikammergehäuse ist eine nachträgliche Montage nicht möglich, die Montageart ist bei der Bestellung festzu-
legen.
tion:
Informa
Der Stutzen
sollte möglichst kurz gehalten werden und das Stutz­enende sollte abgerundet sein. Damit werden Störreexionen durch den Behälterstutzen gering gehalten.
Abb. 10: E
mpfehlenswerte Rohrstutzenmontage
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 15
d
h
4 Montie
ren
Bei guten Reexi
onseigenschaften des Füllgutes können Sie den LEVEL TRANSMITTER 8136 auch auf längeren Rohrstutzen montie­ren. Richtwerte der Stutzenhöhen nden Sie in der nachfolgenden Abbildung. Sie müssen danach eine Störsignalspeicherung durch­führen.
Die Tabe
llen unten geben die max. Rohrstutzenlänge h in Abhängig-
keit vom Durchmesser d an.
Stutzendurchmesser d Stutzenlänge h
80 mm 300 mm 100 mm 400 mm 150 mm 500 mm
Stutzendurchmesser d Stutzenlänge h
3" 11.8 in 4" 15.8 in 6" 19.7 in
Tipp:
Bei Neua
nlagen ist es sinnvoll, die Behälterstutzen in Richtung der Entleerung zu neigen. Dadurch entstehen weniger Störreexionen von der Behälterwand und eine Messung bis in den konischen Auslauf ist möglich.
16 LEVEL
41783-DE-120229
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
ca. 10 mm
4 Montieren
Stutzen bei gekapseltem Antennensy
stem
Abb. 12: Ausrichtung
in Silos
Bevorzugt sollten Sie den Rohrstutzen so dimensionieren, dass der Antennenrand mindestens 10 mm (0.4 in) aus dem Stutzen heraus-
ragt.
Abb. 13: E
mpfehlenswerte Rohrstutzenmontage
Bei guten Reexionseigenschaften des Füllguts können Sie den LEVEL TRANSMITTER 8136 auch auf Rohrstutzen montieren, die höher als die A ntennenlänge sind. Richtwerte der Stutzenhöhen nden Sie in der nachfolgenden Abbildung. Das Stutzenende sollte in diesem Fall glatt und gratfrei, wenn möglich sogar abgerundet sein. Sie müssen danach eine Störsignalspeicherung durchführen.
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 17
d
h
d
h
1½" 50 mm/2" 80 mm/3" 100 mm/4" 150 mm/6"
200 mm 250 mm 300 mm 500 mm 800 mm
4 Montie
ren
Abb. 14: Abweichende Rohrstutzenmaße
Sen
sorausrichtung
Rich
ten Sie den Sensor in Flüssigkeiten möglichst senkrecht auf die
Füllgutoberäche, um optimale Messergebnisse zu erzielen.
. 15: Ausrichtung
Abb
Behältereinbauten
Der Einbauort des Radarsensors sollte so gewählt werden, dass keine Einbauten die Mikrowellensignale kreuzen.
Behältereinbauten, wie z. B. Leitern, Grenzschalter, Heizschlangen, Behälterverstrebungen etc. können Störechos verursachen und das Nutzecho beeinträchtigen. Achten Sie bei der Projektierung Ihrer Messstelle auf eine möglichst "freie Sicht" der Radarsignale zum Füllgut.
Bei vorhandenen Behältereinbauten sollten Sie bei der Inbetrieb- nahme eine Störsignalspeicherung durchführen.
Wenn große Behältereinbauten wie Streben und Träger zu Störechos
führen, können diese durch zusätzliche Maßnahmen abgeschwächt werden. Kleine, schräg angebaute Blenden aus Blech über den Einbauten "streuen" die Radarsignale und verhindern so wirkungsvoll eine direkte Störechoreexion.
18 LEVEL
in Flüssigkeiten
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
41783-DE-120229
4 Montieren
Rührw
Sch
aumbildung
erke
Abb. 16: Glatte Prole
mit Streublenden abdecken
Bei Rührwerken im Behälter sollten Sie eine Störsignalspeicherung bei laufendem Rührwerk durchführen. Somit ist sichergestellt, dass die Störreektionen des Rührwerks in unterschiedlichen Positionen ab­gespeichert werden.
Abb. 17: Rührwerke
Durch Befüllun
g, Rührwerke oder andere Prozesse im Behälter,
können sich zum Teil sehr kompakte Schäume auf der Füllgutober-
äche bilden, die das Sendesignal sehr stark dämpfen.
Wenn Schäume zu Messfehlern führen, sollten Sie größtmögliche Radarantennen, die Elektronik mit erhöhter Empndlichkeit oder niederfrequente Radarsensoren (C-Band) einsetzen.
Als Alternativekommen Sensoren mit geführter Mikrowelle in Betracht. Diese sind unbeeinusst von Schaumbildung und eignen sich für diese Anwendungen besonders gut.
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 19
1
2
3
100%
4
5
8
6
7
0%
9
4 Montie
ren
Messun
g im Schwallrohr
Durch den E
insatz in einem Schwallrohr im Behälter sind Einflüsse von
Behältereinbauten und Turbulenzen ausgeschlossen. Unter diesen Voraussetzungen ist die Messung von Füllgütern mit niedrigen Dielektrizitätswerten
-Wert 1,6) möglich. In Füllgütern, die zu
r
starken Anhaftungen neigen, ist die Messung im Schwallrohr nicht sinnvoll.
Abb. 18: Aufbau Schwallrohr 1 Radarsensor
2 Markierung 3 Gewinde bzw. Flansch am Gerät 4 Entlüftungsbohrung
20 LEVEL
5 Bohrungen 6 Schweißnaht 7 Vorschweißflansch 8 Kugelhahn mit vollem Durchgang 9 Befestigung des Schwallrohres
Hinweise zur Ausrichtung:
l Markierung der P olarisationsebene am Sensor beachten l Beim Gewindeanschluss bendet sich die Markierung auf dem
Sechskant, beim Flanschanschluss zwischen zwei Flanschboh­rungen
der Polarisationsrichtung
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
41783-DE-120229
4 Montieren
l Sämtliche Bohru
ngen im Schwallrohr müssen in einer Ebene mit
dieser Markierung liegen
Hinweise zur Messung:
l Der 100 %-Punkt muss unterhalb der obersten Entlüftungs-
bohrung und des Antennenrandes liegen
l Der 0 %-Punkt ist das Ende des Schwallrohres l Der Rohrdurchmesser muss bei der Antennengröße 40 mm (1½")
mindestens DN 40 bzw. 1½" betragen
l Bei d er Parametrierung muss "Anwendung Standrohr" gewählt
und der Rohrdurchmesser eingegeben werden, um Fehler durch Laufzeitverschiebung zu kompensieren
l Eine Störsignalausblendung bei eingebautem Sensor ist empfeh-
lenswert, jedoch nicht zwingend erforderlich
l Die Messung durch einen Kugelhahn mit Volldurchgang ist
möglich
Konstruktive Anforderungen an das Schwallrohr:
l Werkstometallisch, Rohr innen glatt l Vorzugsweise gezogenes oder längsnahtgeschweißtes Edel-
stahlrohr
l Schweißnaht soll möglichst eben sein und in einer Achse mit den
Bohrungen liegen
l Flansche sind entsprechend der Ausrichtung der Polarisations-
ebene auf das Rohr geschweißt
l Bei Verlängerung mit Vorschweißflanschen oder Rohrmuen
sowie bei Verwendung eines Kugelhahnes, Übergänge an den Innenseiten uchten und passgenau xieren
l Spaltgröße bei Übergängen 0,1 mm l Nicht durch die Rohrwand schweißen. Das Schwallrohr muss
innen glattwandig bleiben. Bei unbeabsichtigen Durchschweißun­gen an der Innenseite entstehende Unebenheiten und Schweiß- raupen sauber entfernen, da diese sonst starke Störechos verursachen und Füllgutanhaftungen begünstigen
l Schwallrohre müssen bis zur gewünschten minimalen Füllhöhe
reichen, da eine Messung nur innerhalb des Rohres möglich ist
l Durchmesser Bohrungen 5 mm, Anzahl beliebig, einseitig oder
durchgängig
l Der Antennendurchmesser des Sensors sollte möglichst dem
Innendurchmesser des Rohres entsprechen
l Durchmesser soll konstant über die gesamte Länge sein
Messun
g im Bypass
Eine Alternative zur Messung im Schwallrohr ist die Messung in einem Bypass außerhalb des Behälters.
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
T - Zweileiter 21
0 %
100 %
1
2
5
4
3
6
4 Montie
ren
Abb. 19: Aufbau Bypass 1 Radarsensor
2 Markierung 3 Geräteansch 4 Abstand Sensorbezugsebene zur oberen Rohrverbindung 5 Abstand der Rohrverbindungen 6 Kugelhahn mit vollem Durchgang
der Polarisationsrichtung
Hinweise zur Ausrichtung:
l Markierung der P olarisationsebene am Sensor beachten l Beim Gewindeanschluss bendet sich die Markierung auf dem
Sechskant, beim Flanschanschluss zwischen zwei Flanschboh­rungen
l Die Rohrverbindungen zum Behälter müssen in einer Ebene mit
dieser Markierung liegen
Hinweise zur Messung:
l Der 100 %-Punkt darf nicht oberhalb der oberen Rohrverbindung
zum Behälter liegen
l Der 0 %-Punkt darf nicht unterhalb der unteren Rohrverbindung
zum Behälter liegen
l Mindestabstand Sensorbezugsebene zur Oberkante obere Rohr-
verbindung > 300 mm
l Der Rohrdurchmesser muss bei der Antennengröße 40 mm (1½")
mindestens DN 40 bzw. 1½" betragen
41783-DE-120229
22 LEVEL
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
h
max
d
min
≥ 2 mm x h
max
90°
4
3 ... 4 h
max
≥ 50 mm
90°
2
3
1
4 Montieren
Durchussmessung bei Rechtecküberfall
l Bei d er Para
metrierung muss "Anwendung Standrohr" gewählt und der Rohrdurchmesser eingegeben werden, um Fehler durch Laufzeitverschiebung zu kompensieren
l Eine Störsignalausblendung bei eingebautem Sensor ist empfeh-
lenswert, jedoch nicht zwingend erforderlich
l Die Messung durch einen Kugelhahn mit Volldurchgang ist
möglich
Konstruktive Anforderungen an das Bypassrohr:
l Werkstometallisch, Rohr innen glatt l Bei extrem rauer Innenseite des Rohres ein eingeschobenes Rohr
(Rohr im Rohr) oder einen Radarsensor mit Rohrantenne ver­wenden
l Flansche sind entsprechend der Ausrichtung der Polarisations-
ebene auf das Rohr geschweißt
l Spaltgröße bei Übergängen 0,1 mm, z. B. bei Verwendung eines
Kugelhahnes oder von Zwischenanschen bei einzelnen Rohr­stücken
l Der Antennendurchmesser des Sensors sollte möglichst dem
Innendurchmesser des Rohres entsprechen
l Durchmesser soll konstant über die gesamte Länge sein
Die Kurzbeispiele geben Ihnen einführende Hinweise für die Durch-ussmessung. Detaillierte Projektierungsdaten nden Sie bei Ge-
rinneherstellern und in der Fachliteratur.
Abb. 20: Durchussmessung Sensors (siehe Kapitel "Technische Daten"); h Rechtecküberfalls
1 Überfallblende (Seitenansicht) 2 Oberwasser 3 Unterwasser 4 Überfallblende (Ansicht vom Unterwasser)
Grundsätzlich sind folgende Gesichtspunkte zu beachten:
l Einbau des Sensors auf der Oberwasserseite
41783-DE-120229
LEVEL TRANSMITTER 8136 4 20 mA/HAR
l Einbau mittig zum Gerinne und senkrecht zur Oberäche der
Flüssigkeit
l Abstand zur Überfallblende l Abstand Blendenöffnung über Grund
mit Rechtecküberfall: d
max.
= Mindestabstand des
min.
= max. Befüllung des
T - Zweileiter 23
2
3 ... 4 x h
max
90°
h
max
d
1
B
4 Montie
ren
Durchussmessung bei Khafagi-Ven
turirinne
l Mindestabstand der Blende l Mindestabstand des Sensors zur max. Stauhöhe
Abb. 21: Durchussmessung Sensors; h
1 Position Sensor 2 Venturirinne
= max. Befüllung der Rinne; B = größte Einschnürung der Rinne
max.
nöffnung zum Unterwasser
mit Khafagi-Venturirinne: d = Mindestabstand des
Grundsätzlich sind folgende Gesichtspunkte zu beachten:
l Einbau des Sensors auf der Einlaufseite l Einbau mittig zum Gerinne und senkrecht zur Oberäche der
Flüssigkeit
l Abstand zur Venturirinne l Mindestabstand des Sensors zur max. Stauhöhe
24 LEVEL
41783-DE-120229
TRANSMITTER 8136 4 20 mA /HART - Zweileiter
Loading...