These products earned the ENERGY STAR® by meeting strict energy efficiency guidelines set by Natural Resources
Canada and the US EPA. They meet ENERGY STAR requirements only when used in Canada.
REGISTER YOUR PRODUCT ONLINE AT: www.broan.com/register
For additional information - visit www.broan.com
99528512A
ABOUT THIS GUIDE
Please take note that this manual uses the following symbols to emphasize particular information:
!
WARNING
Identies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Identies an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.
ABOUT THESE UNITS
LIMITATION
For residential (domestic) installation only. Installation work and electrical wiring must be done by a qualied person(s) in accordance with
all applicable codes and standards, including re-rated construction codes and standards.
WARNING
!
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or
telephone number listed in the warranty.
2. We recommend that your unit be inspected by a specialized technician once a year.
3. Before servicing or cleaning the unit, disconnect power cord from electrical outlet.
4. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Do not use the units with any solid-state speed control device other than the corresponding ones listed below:
UNITMAIN CONTROLAUXILIARY CONTROL
HRVH100SE ANDW02BV01404SE001HVRE
7. This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged in to a
mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances.
Do not remove the ground prong. Do not use an extension cord.
8. Do not inst
9. Do not use to exhaust hazardous or explosive materials and vapors.
10. When performing installation, servicing or cleaning the unit, it is recommended to wear safety glasses and gloves.
11. Due to the weight of the unit, two installers are recommended to perform installation.
12. When applicable local regulations comprise more restrictive installation and/or certication r equirements, the aforementioned requirements
prevail on those of this document and the installer agrees to conform to these at his own expenses.
all in a cooking area or connect directly to any appliances.
CAUTION
1. To avoid prematurate clogged lters, turn OFF the unit during construction or renovation.
2. Please read specication label on product for further information and requirements.
3. Be sure to duct air outside – Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage.
4. Intended for residential installation only in accordance with the requirements of NFPA 90B.
5. Do not run any air ducts directly above or closer than 2 ft (0.61 m) to any furnace or its supply plenum, boiler, or other heat producing
appliance. If a duct has to be connected to the furnace return plenum, it must be connected not closer than 9’ 10” (3 m) from this plenum
connection to the furnace.
6. The ductwork is intended to be installed in compliance with all applicable codes.
7. When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit
operates adequately.
8. If the ductwork passes through
maintenance and/or repair. Also, the ambient temperature of the house should never drop below 65°F (18°C).
an unconditioned space (e.g.: attic), the unit must operate continuously except when performing
Use the following illustrations as guidelines to help you decide on how the unit will be installed.
All the units should be hung from the joists.
In every case, bathroom fans and a range hood could be used to exhaust stale air. Also, for homes with more than one level, we recommend
one exhaust register at the highest level.
There are 3 installation methods: Fully Ducted System, Central Draw Point and Simplified Installation.
NOTE: An electrical outlet has to be available within 3 feet of the unit.
2.1 FULLY DUCTED SYSTEM (PRIMARILYFORHOMESWITHRADIANTHOTWATERORELECTRICBASEBOARDHEATING)
Stale air coming from the register located at the highest level of the
house is exhausted to the outside. Fresh air from outside is filtered and
supplied by the register located in the lowest liveable level.
Homes with more than one level require at least one exhaust register at
the highest level.
See figure at right.
2.2 CENTRAL DRAW POINT (CONNECTIONTOAFORCEDAIRSYSTEM)
Stale air coming from the register located at the highest level of the
house is exhausted to the outside. Fresh air from outside is filtered and
supplied to the return (plenum) of the forced air unit. See figure at right.
For this type of installation, it is not essential that the forced air system
blower runs when the unit is in operation, but we recommend it.
NOTE: Home with multiple forced air systems should have one unit on
each system.
CAUTION
Do not connect the unit to any forced air system supply
duct.
Stale air is exhausted to the outside. Fresh air from outside is filtered and
supplied to the return (plenum) of the forced air unit.
See figure at right.
To avoid cross-contamination and achieve the highest efficiencies, the
forced air system blower must always be ON.
NOTE: Home with multiple forced air systems should have one unit on
each system.
VH0091
VH0092
CAUTION
Do not connect the unit to any forced air system supply
duct.
VH0093
4
3. INSTALLATION
3.1 INSPECTTHE CONTENTOFTHE BOX
NOTE: Before proceeding to the installation, check the content of the box. If items are missing or damaged, contact the
manufacturer. Remove all packaging material from the unit.
• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, ports, power cord, etc.
• Using a Phillips or a Robertson screwdriver, loosen both door screws (A).
NOTE: The screws will stay attached to the door.
A
VD0302
• Open (B) and lift out (C) the door.
CAUTION
In order to prevent damages to the door hooks, do not open completely the
unit door; tilt it about 3” from the unit base and lift it up. See illustration at
right.
• Remove the transport tape over the heat or energy recovery core
of the unit.
• Inspect the inside of the unit for damage. Ensure that blower
assembly, heat or energy recovery core, core filters, insulation,
dampers, prefilter and HEPA filter, etc. are all intact, then reinstall
the door.
NOTE: Write the installation date on the HEPA filter frame for future
reference (see illustration at right).
C
B
VD0303A
TOP
DESSUS
FRONT
AVANT
Instal. date:
Date d’instal. :
__ / __ / ____
±3”
21293
FRONT
AVANT
Instal. date:
Date d’instal. :
__ / __ / ____
VD0322
5
3. INSTALLATION(CONT’D)
3.2 TOOLSAND MATERIAL
Following are the tools and material needed:
• Phillips no. 2 or Robertson no. 2 screwdriver
• Small flat blade screwdriver (for wall control connection)
• Wire stripper (for wall control connection)
• Hammer and flat blade screwdriver (for plenum connection installation only, to make holes in existing metal duct)
• Scissors or utility knife (to cut duct tape)
• Measuring tape
• Duct tape
• Tin snips or metal shear (for plenum connection installation only, to cut ductwork)
• Within an area of the house where the ambient temperature is kept between 50°F (10°C) and 104°F (40°C).
• Away from living areas (dining room, living room, bedroom), if possible.
• So as to provide easy access to the interior of the unit, for maintenance.
• Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.
• Away from hot chimneys and other fire hazards.
• Allow for a power source (standard 3-prong grounding outlet).
• FOR HRV UNITS ONLY: Close to a drain. If no drain is close by, use a pail to collect
run-off.
Hang the unit with the four hooks, chains and springs provided. See illustration at right.
CAUTION
Make sure the unit is level.
3.4 PLANNINGOFTHE DUCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of insulated ducts to a minimum.
• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This
would cause clogging of the filters and recovery module.
• If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
3.5 INSTALLING NON-INSULATED DUCTSAND DIFFUSERS
3.5.1 FULLY DUCTED SYSTEM (ASILLUSTRATEDIN SECTION 2.1)
Never install a stale air exhaust diffuser in a closed room where a combustion device operates, such as a
gas furnace, a gas water heater or a fireplace.
Stale air exhaust ductwork
• Install the stale air exhaust diffuser in the main area where the contaminants are produced: kitchen, living room, etc. Position
the diffuser as far from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.
If desired, you can install another diffuser (sold separately).
• If a diffuser is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.
• Install the diffuser 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install it in the ceiling.
ULLY DUCTED SYSTEM (ASILLUSTRATEDIN SECTION 2.1) (CONT’D)
Fresh air distribution ductwork
• Install the fresh air distribution diffuser in a large, open area in the lowest level to ensure the greatest possible air circulation.
• Keep in mind that the fresh air diffuser must be located as far as possible from the stale air diffuser. If desired, you can install
another diffuser.
• Install the diffuser either in the ceiling OR 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall. (The cooler air
will then cross the upper part of the room and mix with room air, before descending to occupant’s level.)
• If a register must be floor installed, direct the airflow up the wall.
HOWTOCONNECTTHEFLEXIBLEDUCTSTOTHEDIFFUSERS
Once the diffusers location is determined, cut out 5¼” diameter hole.
Run one end of the flexible duct through the hole and fix it to the diffuser base (1),
using a tie wrap and duct tape. Assemble the diffuser base to the wall (or ceiling)
using its 4 no. 8 x 3/4” screws. Then, slide in the diffuser (2).
See illustration at right.
Ø 5¼”
VJ0094A
1
2
UNITPORTSIDENTIFICATION
Aire de salida hacia el exterior
Each unit port has an identification label
beside it to avoid wrong duct connections to
the unit. Always refer to these labels before
Aire fresco hacia el interior
DOOR
performing any duct and port connection.
VJ0106
HOWTOCONNECTTHEFLEXIBLEDUCTSTOTHEUNITPORTS
Both flexible ducts attached to the diffusers must be connected to the bottom ports of
the unit. When facing the unit door, the fresh air to building port is located on left side
and the exhaust air from building port is on the right side. Refer to the identification
labels affixed beside each unit ports. Using tie wrap, attach the fresh air to building
duct to its corresponding port, then do the same for the exhaust air to building duct
and port. See illustration at right.
NOTE: Use an insulated duct if the duct will have to go through a space where it is
possible to experience extreme temperature conditions (eg: in northern area,
unheated attic in winter or uncooled attic in southern area). Also, if you plan
to stop the unit for more than 12 hours, we recommend to cover the duct with
R12 insulation.
Same as for Fully Ducted System, described in step 3.5.1
Fresh air distribution ductwork
When performing duct connections, always use approved tools and materials. Respect all corresponding
laws and safety regulations. Please refer to your local building code.
• Locate the opening for fresh air ductwork on the forced air unit return duct
at a minimum linear distance of 9’ 10” (3 m) upstream (from forced air unit drop:
A+B+C). Cut out a 5” Ø hole in this location, using metal shear.
• Use a metal transition (not included, available in hardware store) to connect the
unit duct to the forced air unit return duct.
• Attach the other end of the flexible duct to the Fresh air to building port (see
icon on the left side of the unit). Use tie wrap and duct tape to seal the connection.
See illustration at right.
Fresh air distribution ductwork (return side connection)
Same as for Central Draw Point, described in step 3.5.2
!
WARNING
U
VJ0099
NITDOOR
TRANSITION
A + B + C = NOTLESS
THAN 9’ 10” (3 M)
METAL
Stale air exhaust ductwork (return side connection)
!
WARNING
When performing duct connections, always use approved tools and materials. Respect all corresponding
laws and safety regulations. Please refer to your local building code.
• Locate the opening for stale air ductwork on the forced air unit at least 3’ (0.9 m)
from fresh air ductwork connection. Cut out a 5” Ø hole in this location, using
metal shear.
• Use a steel transition (not included, available in hardware store) to connect the
unit duct to the forced air unit return duct.
• Attach the other end of the flexible duct to the Exhaust air from building port
(see icon on the right side of the unit). Use tie wrap and duct tape to seal the
connection. See illustration at right.
VJ0109
UNITDOOR
3’ (0.9 M)
MINIMUM
A + B + C = NOTLESS
THAN 9’ 10” (3 M)
CAUTION
The furnace blower must be running when the ventilation unit is in operation.
8
3. INSTALLATION(CONT’D)
3.6 INSTALLING INSULATED FLEXIBLE DUCTS
Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation
within the ducts.
3.6.1 C
ONNECTIONTOTHEUNITPORTS
Use the following procedure for connecting the insulated flexible ducts to the unit ports (exhaust air to outside and fresh air from
outside). Refer to identification labels beside ports before performing any duct and port connection.
Avoid compressing the insulation pulling the tape tightly around the joint. Compressed insulation loses its
insulation properties and causes water dripping due to condensation on the exterior surface of the duct.
For both remaining ducts, pull back the insulation to expose
the interior flexible duct.
Connect the interior flexible duct to the smaller part of the
inner ring of the port using a tie wrap.
Pull the insulation over the joint and tuck it between the
inner and outer rings of the port. Pull the vapor barrier over
the insulation and over the outer ring of the port.
Apply duct tape gently to the joint in order to make an airtight
seal. See figures at right.
CAUTION
CAUTION
VJ0102
9
3. INSTALLATION(CONT’D)
3.6 INSTALLING INSULATED FLEXIBLE DUCTS(CONT’D)
OCATING EXTERIOR PORTS
3.6.2 L
Choose an appropriate location for installing the exterior ports:
• There must be a minimum distance of 6’ (1.8 m) between the hoods to avoid cross-contamination
• There must be a minimum distance of 18” (457 mm) from the ground
Make sure the fresh air intake port is located at least 6 feet (1.8 m) away (or more, as per applicable building
codes or standards) from sources of contamination such as:
• Dryer exhaust, high efficiency furnace vent, central vacuum vent
• Gas meter exhaust, gas barbecue grill
• Garbage bin
• Any exhaust from a combustion source
!
WARNING
STALEAIR
EXHAUSTPORT
FRESHAIR
INTAKEPORT
18’’
(457 MM)
6’
(1.8 M)
VD0203
3.7 CONNECTING INSULATED DUCTSTO EXTERIORPORTS
• For each exterior port, using a jig saw, cut a 5’’ diameter hole in the
exterior wall.
• From the outside, slide the exterior port in place and attach it to the
exterior wall, using 2 no. 8 x 1½” provided screws. Seal the outline with
silicone.
• From the inside, pull back the insulation to expose the flexible duct and,
using a tie wrap, attach it to the exterior port rigid duct. Carefully seal
with duct tape. Pull the insulation over the joint. Pull the vapor barrier
over the insulation and over the joint. Apply gently duct tape to the joint
making an airtight seal. See illustration at right.
5’’ Ø
(127 MM)
5’’ Ø
(127 MM)
OPTIONAL
LOCATION
6’
(1.8 M)
18’’ (457 MM)
VR0028
10
3. INSTALLATION(CONT’D)
3.8 INSTALLING TANDEM® TRANSITION KIT
If desired, it is possible to perform insulated ducts connection with the outside
using the Tandem transition kit (purchase separately, part number TYIK1). The
joist opening needed to install the Tandem transition must be 9¾” minimum.
The maximum height of the Tandem transition is 8¾”. To connect the insulated
flexible ducts to the Tandem transition (Exhaust air to outside and Fresh air
from outside), follow the instructions included with the kit.
*Patented.
VR0003
Tandem transition kit
3.9 CONNECTINGTHE DRAIN
A drain tubing (included) must be installed for all HRV units. For ERV units, it is not required, however, it
is recommended for climates where the outside temperature typically remains below -13°F (-25°C), (over a
24-hour period) for several days in a row, combined with an indoor humidity of 40% or higher.
VD0311A
Cut two sections of plastic tubing, approximately
12” long, and connect each one to both inner drain
fittings located under the unit as shown.
Join these both sections to the “T” junction and
main tube as shown, to prevent the unit from
drawing unpleasant odors from the drain source.
VD0323
NOTES: 1. For ERV unit, remove both drain plugs
inside the unit prior to install tubing.
2. ERV core and blower assembly removed
from illustration to ease understanding.
± 12”± 12”
TIEWRAP
CAUTION
± 1”
VD0308A
Run the tube to the floor
drain or to an alternative
drain pipe or pail.
IMPORTANT
If using a pail to collect
water, locate the tube end
approximately 1” from the
top of the pail in order to
prevent water from being
drawn back up into the unit.
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.