Fire Alarm Systems | FMC‑120‑DKM Manual Call Points
FMC‑120‑DKM Manual Call Points
www.boschsecurity.com
u Adjustment of the manual call point after alarm trig-
gering
u Indicator LED for alarm or for inspection evaluation
u Second contact with connections for panel control
u Variants for indoor and outdoor use
The FMC-120-DKM Manual Call Points handle manual
alarm triggering and are used with conventional technology.
Functions
In the event of an alarm, the glass pane (2) is broken
first, then the manual call point (3) is pressed hard.
This activates the micro switch for alarm triggering
and the indicator LED (4) blinks.
A locking mechanism holds the pressed manual call
point.
The manual call point can be reset with the reset lever
(5). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
Variants
The design of the manual call points for indoor
(form G) and outdoor use (form H) are identical. Three
color variants, red, blue, and yellow are available.
Detectors for outdoor use (form H) have a cover
equipped with a seal.
Certifications and Approvals
Type NumberComplies with
FMC‑120‑DKM‑G‑REN54-11:2001/A1:2005
FMC‑120‑DKM‑H‑REN54-11:2001/A1:2005
FMC‑120‑DKM‑G‑YEN12094-3:2003
FMC‑120‑EST‑G‑BEN12094-3:2003
RegionCertification
GermanyVdSG 298061 FMC-120-DKM-G-R/-H-
R_G298061
VdSG 206079 FMC-120-DKM-G-
Y_G206079
VdSG 206080 FMC-120-EST-G-B/-H-
HE_G206080
Page 2
ø 3,4
135°
140°
2,5
2
139
1
2
3
10
147
2 | FMC‑120‑DKM Manual Call Points
RegionCertification
PTB01 ATEX 2163 X OTC/OC 310/410,
OT/O/T 300/400, DKM/SKM 120, DM/
SM 210, MPA_01 ATEX 2163 X
PTB01 ATEX 2163 X FMC-120-DKM
EuropeCEFMC-120-EST-G-B / -DKM-G-Y
CEFMC-120-DKM-G-R/-H-R
CEFMC-120-DKM-G-B/ -H-B
CPD0786-CPD-20294 FMC-120-DKM-G/H-
R
CPD0786-CPD-20231 FMC-120-DKM-G-Y
CPD0786-CPD-20232 FMC-120-EST-G-B/-
H-HE
Installation/Configuration Notes
• Manual call points have to be mounted visibly along
escape and rescue routes (e.g. exits, passageways,
stairwells) and be easily accessible.
• An installation height of 1400 mm ±200 mm, measured from the middle of the manual call point to the
floor, must be maintained.
• Manual call points must be illuminated sufficiently
with daylight or another light source (including emergency lighting, if present).
• Max. one test detector may be used for primary lines
together with automatic detectors. The test detector
is connected at the end of the primary line.
• Further standards, guidelines and planning recommendations regarding the installation location etc.,
should also be taken into consideration (see Fire Detection manual).
• Regulations of local fire departments must be observed.
Installation
• Cables can be inserted surface-mounted or flushmounted.
Pos.Description
1Installation depth version 1: 36 mm
2Installation depth version 2: 14 mm
3Installation depth version 3: approx. 30 mm
Technical Specifications
Electrical
Operating voltage24 V DC (16.2 V DC . . . 30 V DC)
Current consumptionSpecified by the respective se-
curity system
Mechanics
Dimensions (W x H x D)135 x 135 x 37 mm /
• Installation in fire hose cabinets is possible in three
ways:
Housing materialPlastic (ASA)
5.31 x 5.31 x 1.4 in.
ColorsRed, RAL 3001
Blue, RAL 5005
Yellow, RAL 1003
WeightApprox. 224 g
Page 3
3 | FMC‑120‑DKM Manual Call Points
Environmental conditions
Protection class as per EN 60529
Form G (indoor area)IP 52
Form H (outdoor area)IP 54
Norm
FMC-120-DKM-G-R,
FMC‑120‑DKM‑H‑R
FMC-120-DKM-G-Y,
FMC‑120‑EST‑G‑B
Permissible operating temperature
Form G (indoor area)-10 °C . . . +55 °C /
Form H (outdoor area)-25 °C . . . +70 °C /
EN 54-11
EN 12094-3
14 °F … 131 °F
-13 °F … 158 °F
Ordering Information
FMC‑120‑DKM‑G‑R Form G, Red
Manual Call Point for indoor use, indirect alarm triggering (type B), conventional technology
Order number FMC-120-DKM-G-R
FMC‑FST‑DE Printed Labeling Foils for the Upper Label
Field
For yellow and blue manual call points of Series
FMC‑120 and FMC‑210, 1 unit = 5 sheets
Order number FMC-FST-DE
FMC‑SPGL‑DEIL Spare Glasses
For manual call points of Series DM, DKM, SKM,
FMC‑120 and FMC‑210.
1 unit = 5 spare glasses
Order number FMC-SPGL-DEIL
Key for Fire Detectors Types G and H
made of red plastic (ASA)
Order number FMM-KEY-Form G/H
FMC‑120‑DKM‑H‑R Form H, Red
Manual Call Point for outdoor use, indirect alarm triggering (type B), conventional technology
Order number FMC-120-DKM-H-R
FMC‑120‑DKM‑G‑B Form G, Blue
Manual Call Point for indoor use, indirect triggering
(type B), conventional technology
Order number FMC-120-DKM-G-B
FMC‑120‑DKM‑H‑B Form H, Blue
Manual Call Point for outdoor use, indirect triggering
(type B), conventional technology
Order number FMC-120-DKM-H-B
FMC‑120‑DKM‑G‑Y Form G, Yellow
Manual Call Point for indoor use, indirect triggering
(type B), conventional technology