This document is the intellectual property of Bosch Security Systems, Inc. and is protected by
copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered
trademarks and must be treated accordingly.
Determine Bosch Security Systems, Inc. Product Manufacturing
Dates
Use the serial number located on the product label and refer to the Bosch Security Systems,
Inc. web site at http://www.boschsecurity.com/datecodes/.
The following image shows an example of a product label and highlights where to find the
manufacturing date within the serial number.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 5
Control PanelInstallation | en5
2
2.1
2.2
2.3
Installation
Installation Preparation
This section contains a general installation procedure and refers to other sections of the
document for detailed instructions. Review this document and the D9412GV4/D7412GV4Program Entry Guide (P/N: F01U265459) before beginning the installation to determine the
hardware and wiring requirements for the features used. Have the following documentation
available when reading through this guide:
–D9412GV4/D7412GV4 Installation and System Reference Guide (P/N: F01U265457)
–D9412 GV4/D7412GV4 v2.00 Owner’s Manual (P/N: F01U265452)
Enclosure Options
Mount the control panel assembly in any of the Bosch Security Systems, Inc. enclosures listed:
–D8103 Universal Enclosure (tan)
–D8109 Fire Enclosure (red) for the D9412GV4 and D7412GV4 Control Panels
–D8108A Attack Resistant Enclosure (tan)
Refer to the Approved Applications chapter inside the D9412GV4/D7412GV4 v2.00 Installationand System Reference Guide (P/N: F01U265457) to determine if the application requires a
specific enclosure.
Mounting Enclosure
1.Run the necessary wiring throughout the premises.
2.Mount the enclosure in the desired location. Use all five enclosure mounting holes. Refer
to the diagram for mounting locations and descriptions.
Electromagnetic interference (EMI) can cause problems on long wire runs.
Figure 2.1: Enclosure Mounting
Callout - Description
1 - Point chart label
2 - Mounting skirt hooks (2)
3 - Module mounting holes (12)
4 - Tamper switch mounting holes (5)
5 - Skirt mounting hole (1)
6 - Enclosure mounting holes (5)
7 - Mounting skirt hook holes (2)
8 - Back of the control panel
9 - Lock down tab
2.4
Installing the Control Panel
1.Place the control panel over the inside back of the enclosure, aligning the large
2.Remove the tape from the #6 x 1/4-in. screw in the mounting tab on the control panel.
3.Connect earth ground to the control panel before making any other connections. Refer to
rectangular openings of the mounting skirt with the mounting hooks of the enclosure.
Slide the control panel down so that it hangs on the hooks. Refer to Figure 2.1.
The screw passes through the mounting tab and into the skirt mounting hole in the
enclosure. Tighten the screw to secure the control panel in the enclosure.
Connecting Earth Ground.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 7
!
i
Control PanelInstallation | en7
2.5
2.5.1
2.5.2
Connecting Earth Ground
Terminal 10
To help prevent damage from electrostatic charges or other transient electrical surges,
connect the system to earth ground at Terminal 10 before making other connections.
Recommended earth ground references are a grounding rod or a cold water pipe.
Warning!
Do not use telephone or electrical ground for the earth ground connection. Use 14 AWG (1.8
mm) to 16 AWG (1.5 mm) wire when making the connection. Do not connect other control
panel terminals to earth ground.
Ground Fault Detect Enable
Notice!
To meet UL 864 requirements, enable Ground Fault Detect.
A ground fault is a circuit impedance to earth ground. The control panel has a ground fault
detection circuit that, when enabled, detects ground faults on Terminals 1 to 9 and 11 to 36.
The control panel also detects and annunciates ground faults on any device connected to it.
If a ground fault condition occurs, the keypads display SERVC GND FAULT and the control
panel sends a GROUND FAULT TROUBLE, AREA 1. When the control panel recognizes that the
ground fault condition is corrected, and remains corrected for between 5 to 45 consecutive
seconds, a Restoral Report is sent.
2.5.3
Enabling Ground Fault Detection
To enable the Ground Fault Detect Enable feature, lock (close) the S4 Ground Fault Detect Pin
on the control panel.
1 - S4 Locked (Closed). Control panels detects ground faults.
2 - S4 Unlocked (Open). Control panel does not detect ground faults.
2.5.4
2.5.5
Ground Fault Impedance Specifications
The table below provides the impedance specifications for detecting ground faults when any
terminal or field wiring is shorted to ground.
ImpedanceControl Panel Detects Ground Fault
≤ 300 ΩYes
300 Ω to 200 k ΩDetection depends upon the terminal
≥ 200 k ΩNo
Table 2.1: Ground Fault Impedance Specifications
Locking the Reset Pin
Locking the reset pin disables the control panel. When the reset pin is locked, the control
panel is disabled. CALL FOR SERVICE appears in some keypad displays (SDI2 keypads display
enter Installer Passcode) when the pin is locked down.
On-board outputs (Terminals 6 and 7) and off-board outputs deactivate when the control
panel is disabled. Terminal 8 has power when the output is deactivated. Activation interrupts
power at that terminal. The on-board output (Terminal 8) remains deactivated when the reset
pin is locked in the disable position.
Unlocking the reset pin from the locked position resets the control panel. The control panel
resets all its timers, counters, indexes, and buffers. Any points that restore after a reset do not
generate Restoral Reports.
If the reset pin is placed in the Lock position, and all areas are armed, the control panel will
not answer RPS over a phone line unless the Answer Armed program item has a value other
than zero in it. No entry is required for network or RPS Enhanced direct connection
communication. Refer to RPS Parameters in RPS Help.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
For UL Certified accounts, additional power can be obtained using only a UL Listed auxiliary
12.0 VDC regulated, power-limited power supply.
Notice!
All terminals accept for Outputs A, B, and C (Terminals 6, 7 and 8) are supervised.
3.3
D9412GV4/D7412GV4 Input Points and Peripheral Devices
System Wiring Diagram
Figure 3.3: Input Points and Peripheral Devices System Wiring Diagram
Callout - Description
1 - (Optional): For 24 V applications use a UL 1481 Listed regulated, power-limited 24 VDC power supply with a
D130 Relay Module. Refer to the D130 Installation Instructions (P/N: F01U072455) for correct wiring
requirements.
2 - D130 Relay Module
3 - D125B Powered Loop Interface Module
4 - To UL Listed two-wire smoke detectors with a fire rated EOL resistor. Refer to Two-Wire Smoke Detectors
section in the Approved Applications chapter in the D9412GV4/D7412GV4 v2.00 Installation and System ReferenceGuide (P/N: F01U265457) for a listing of compatible two-wire smoke detectors.
D9412GV4 SDI and Zonex Devices System Wiring Diagram
Figure 3.4: D9412GV4 System Wiring Diagram, SDI and Zonex Devices
Callout ᅳ DescriptionCallout ᅳ Description
1 ᅳ Up to 16 supervised D1265, D1255 (all versions),
6 ᅳ Zonex 1: 15 D8128Ds maximum
1
D1255RB, D1256RB Keypads, or D1257RB Fire Annunciators,
or up to 8 supervised D1260 Keypads (all versions) (maximum
16 supervised, maximum 32 unsupervised)
2 ᅳ Up to 8 D9210C Access Control Interface Modules7ᅳ Zonex 2: 15 D8128Ds maximum
3 ᅳ Up to 2 B426/B420/DX4020 or ITS-DX4020-G Network
8 ᅳ Zonex 1: Up to 8 D129s maximum
1
1
Interface Modules
4 ᅳ D8125 POPEX Module9 ᅳ Zonex 2: Up to 8 D8129s maximum
1
5 ᅳ Up to 119 D9127U/T POPITs
1
The number of D8129 OctoRelays that can be connected to each Zonex terminal on the control panel is limited
by the number of D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide
(P/N: F01U070537) or the D8129 Operation and Installation Guide (P/N: F01U036302) for specific information.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 15
i
Control PanelDiagrams | en15
Notice!
Terminals 24 through 36 are power limited, supervised. Fire and Intrusion devices must be on
separate circuits. Refer to ICP-SDI-9114 Installation Instructions (P/N: F01U030068)
3.4.2
D7412GV4 SDI and Zonex Devices System Wiring Diagram
Figure 3.5: D7412GV4 SDI and Zonex Devices System Wiring Diagram
Callout - Description
1 - Up to 16 supervised D1265, D1255 (all versions), D1255RB, D1256RB Keypads, or D1257RB Fire
Annunciators, or up to 8 supervised D1260 Keypads (all versions) (maximum 16 supervised, maximum 32
unsupervised)
2 - Up to 2 D9210C Access Control Interface Modules
3 - Up to 2 B426/B420/DX4020 or ITS-DX4020-G Network Interface Modules
4 - D8125 POPEX Module
5 - Up to 67 D9127U/T POPITs
6 - Zonex 1: Up to 9 D8128Ds maximum
7 - Zonex 1: Up to 8 D8129s maximum
1
The number of D8129 OctoRelays that can be connected to each Zonex terminal on the control panel is limited
by the number of D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide
(P/N: F01U070537) or the D8129 Operation and Installation Guide (P/N: F01U036302) for specific information.
Use the following SDI2 bus wiring recommendations for SDI2 installation. The SDI2 bus is
used by the GV4 Control Panel and corresponding modules to communicate with one another.
Modules can be connected via home run, daisy chain, or single level T-tapped anywhere on the
SDI2 bus. Please reference Figure 2.7 below.
Figure 3.7: SDI2 Bus Wiring
Callout ᅳ Description
1 ᅳ Control panel
2 ᅳ SDI2 module
3 ᅳ Daisy chained wiring
4 ᅳ Single-level T-tapped wiring
5 ᅳ Home run wiring
If the voltage at any device is below the minimum, you must add an auxiliary power supply to
the system to power these devices.
Notice!
The absolute lowest voltage for the SDI2 devices is 10 VDC at the device terminals when in
normal operation, with a fully charged battery on the system.
Maximum cable lengths
The following rules must be followed when wiring the SDI2 bus.
–The SDI2 bus requires the use of non-shielded cable from 12 AWG to 22 AWG.
–Maximum overall cable length based on the table listed below:
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 19
i
i
Control PanelDiagrams | en19
Cable
capacitance
pF/ftftpF/ftftpF/ftftpFf/ftft
< 177500226363275185324400
187500236086285000334242
197350245800294828344100
207000255600304700354000
216666265385314516363800
Table 3.1: Maximum cable length
Overall
cable
length
Cable
capacitance
Notice!
Use Non-shielded cable only.
Notice!
Maximum capacitance of 140nF (140,000 pf) per system. Contact the wire manufacturer for
the capacitance ratings of the wire being used.
Overall
cable
length
Cable
capacitance
Overall
cable
length
Cable
capacitance
Overall
cable
length
3.6
Keyswitch Wiring
Figure 3.8: Keyswitch Wiring
Callout - Description
1 - Maintained keyswitch
2 - Momentary keyswitch
3 - Common
4 - Point Input
5 – End of Line (EOL) resistor*
6 - Open on a circuit arms the area
7 - Short on a circuit toggles the arming state
*Use proper EOL for the specific device you are using.
20en | Power Supply and Power OutputsControl Panel
4
4.1
4.1.1
Modem4 Events
Power Supply and Power Outputs
Power Supply - Primary
Primary (AC) Power Circuit
The primary source is a 16.5 VAC, 40 VA, internally-fused transformer (Bosch Security
Systems, Inc. Model D1640). The control panel draws 225 mA when idle and 300 mA when in
an alarm state. The total available auxiliary current is 1.4 A. Transient suppressors and spark
gaps protect the circuit from power surges. This protection relies on the ground connection at
Terminal 10. Ensure that you connect Terminal 10 to a proper ground. Refer to ConnectingEarth Ground, page 7.
AC Power Fail
The system indicates an AC power failure when Terminals 1 and 2 do not have power. The AC
Fail Time parameter sets the number of minutes or seconds without AC power before the
control panel acknowledges the failure and the number of minutes or seconds after the power
returns before the control panel acknowledges restored power.
Refer to the D9412GV4/D7412GV4 v2.00 Program Entry Guide (P/N: F01U265459) for
additional information about AC Fail Time and UL 864 requirements.
Reference the table below to view the Modem4 communication format signals.
Modem4 code
D6500 Mode
Modem4 Code
Bosch SIA Mode
Contact ID
Events
Contact ID Codes
AC Fail - mains power supplyPssssNATAC Loss1 301 00 000
AC Restore - mains power supplyRsss0NARAC Loss3 301 00 000
Table 4.1: AC Power Fail
4.1.2
Installing the Transformer
Notice!
Do not short-circuit the terminals of the transformer. Shorting the terminals opens the inter-
nal fuse, causing permanent failure. Connect the transformer to Terminals 1 and 2 of the con-
trol panel before plugging it into the power source.
1.Use 18 AWG (1.22 mm) wire (minimum) to connect the transformer to the control panel.
The wire length should be as short as possible. The maximum length is 50 ft (15 m).
Connect the battery and plug in the transformer.
2.Route telephone and sensor loop wiring away from any AC conductors, including the
transformer wire.
AC wiring can induce noise and low level voltage into adjacent wiring. Route data wiring
away from AC and telephone wiring.
Notice!
Always connect the battery first and then plug in the transformer.
3.Connect the battery. Refer to Installing the Battery, page 21
4.Plug the transformer into an unswitched, 120 VAC 60 Hz power outlet only.
5.Secure the transformer to the outlet with the screw provided.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 21
i
!
!
i
Control PanelPower Supply and Power Outputs | en21
D8004 Transformer Enclosure Required for Fire Systems
Use the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fire
and burglary applications.
Notice!
Check with the Authority Having Jurisdiction (AHJ) about mounting transformers on specific
circuits.
4.2
4.2.1
Power Terminals - Secondary
Secondary (DC) Power
A 12 V, 7 Ah (up to 18 Ah) sealed lead-acid rechargeable battery supplies secondary power for
auxiliary and alarm outputs, and powers the system during interruptions in primary (AC)
power.
Warning!
Use Lead Acid Batteries Only: The charging circuit is calibrated for lead-acid batteries. Do not
use gel-cell or nicad batteries.
Extra Batteries Increase Back-up Time
To increase battery back-up time, connect a second 12 V battery in parallel to the first battery.
Use a D122/D122L Dual Battery Harness to ensure proper and safe connection. Refer to the
Standby Battery and Current Rating Chart in the Approved Applications section of the
D9412GV4/D7412GV4 v2.00 Installation and System Reference Guide (P/N: F01U265457) for
battery standby time calculations.
D1218 Battery
The D1218 is a 12 V, 18 Ah battery for use in applications requiring extended battery standby
time. Up to two D1218 batteries can be connected when used with a D122 Dual Battery
Harness.
Warning!
When connecting two D1218 Batteries to the control panel, the control panel can charge up
to 36 Ah of battery.
Notice!
When using two D1218 batteries, use a separate enclosure, a D122L Dual Battery Harness,
1.Place the battery upright in the base of the enclosure.
2.Locate the red and black leads supplied in the literature pack.
3.Connect the black battery lead to Terminal 4, and then to the negative (-) side of the
battery.
4.Connect the red battery lead to Terminal 5, and then to the positive (+) side of the
battery.
Page 22
!
!
22en | Power Supply and Power OutputsControl Panel
Warning!
High current arcs are possible. The positive (red) battery lead and Terminal 5 can create high
current arcs if shorted to other terminals or the enclosure. Use caution when working with
the positive lead and Terminal 5. Always disconnect the positive (red) lead from the battery
before removing it from Terminal 5.
Warning!
The battery terminals and wire are not power limited. A 0.250 in (6.4 mm) space must be
maintained between the battery terminals, battery wiring, and all other wiring. Battery wiring
cannot share the same conduit, conduit fittings, or conduit knock-outs with other wiring. Re-
fer to the Battery Terminals illustration.
Figure 4.1: Battery Terminals
Callout - Description
1 - Battery terminals. Terminal 5 is non-power limiting.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 23
Control PanelPower Supply and Power Outputs | en23
Figure 4.2: Non-PowerLimited Wiring
Callout ᅳ Description
1 ᅳ Conduit required for use with external batteries.
2 ᅳ Battery wires
3 ᅳ 0.25 in (6.4 mm) minimum. To ensure proper spacing, use tie-wraps or similar devices to
secure wires.
4 ᅳ Relay output wires
5 ᅳ Input or Zone wires
6 ᅳ Standby battery
4.3
Power Outputs - Circuit Protection
5 PTC’s protect the control panel from short circuits on the continuous and programmable
power outputs. The PTC assignments are listed below.
PTC CB2 protects:
–Terminal 3: Auxiliary Power
PTC CB4 protects:
–Terminal 6: Output A (Alarm Power Output)
–Terminal 7: Output B (Alternate Alarm Power Output)
24en | Power Supply and Power OutputsControl Panel
–Terminal 8: Output C (Switched Auxiliary Power)
PTC CB5 protects Terminal 24: Zonex Power.
PTC CB1 protects Terminal 32: SDI Power +.
PTC CB3 protects Terminal 36: SDI2 Power +.
Required by UL:
–All devices powered from a power output are to be supervised.
–Power outputs are not shared between fire and non-fire devices unless all devices are in
conduit within 20 ft, and in the same room.
4.4
4.5
Power Outputs - Total Available Power
The system produces up to 1.4 A of combined power at 12.0 VDC Nominal for all powered
devices. The outputs listed below share the available power. These outputs are shown as red
circles on the faceplate.
–Terminal 3 - Auxiliary Power. Use this terminal to power devices requiring continuous
power.
–Terminal 6 (Output A) - Alarm Power Output. Programmable relay normally open, power
on alarm.
–Terminal 7 (Output B) - Alternate Alarm Power Output. Programmable relay normally
switches power off when the Sensor Reset command is executed.
–Terminal 24 - Zonex Power. Use this terminal to power Zonex modules such as the
D8125, D8128D, and D8129 Modules.
–Terminal 32 - SDI Power +. Use this terminal to power serial device interface (SDI)
devices such as keypads, the D9210C Wiegand Control Interface Module, the ICPSDI-9114 module, and other compatible SDI devices.
–Terminal 36 - SDI2 Power +. Use this terminal to power serial device interface 2 (SDI2)
devices such as B208, B308, B426, B810, B920, B930, and other compatible SDI2
devices.
Power Outputs - Continuous Power Output Terminals 3, 8, 24,
32, and 36
The continuous current draw for powered devices connected to Terminals 3, 8, 24, 32, and 36,
and the accessory connector must not exceed 1.4 A. Devices powered from these outputs
must operate at 12.0 VDC Nominal.
Power Restricted for Fire and Combined Fire and Burglary Systems
Use the Fire System Power Formula to calculate the current available for fire and combined
fire and burglary systems (refer to Power Outputs - Programmable Power Output Terminals 6, 7,and 8, page 24).
4.6
Power Outputs - Programmable Power Output Terminals 6, 7,
and 8
4.6.1
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Programming
The power outputs at Terminals 6, 7, and 8 are programmed as Outputs A, B, and C. All
outputs are programmed in the Outputs section. Outputs are assigned a output type, (Fire
Bell, for example) when they are assigned to an area. Outputs can be assigned to one or more
areas. The Bosch defaults set Output A (Terminal 6) as a Steady Alarm Bell output, Output B
(Terminal 7) as a Pulsed Fire Bell output, and Output C (Terminal 8) as a Verification or Reset
output for smoke detectors. The D9412GV4/D7412GV4 v2.00 Program Entry Guide (P/N:
Page 25
Control PanelPower Supply and Power Outputs | en25
F01U265459) contains complete instructions for programming outputs. Refer to Terminals 6and 7, page 25, Fire System Power Formula, page 25, and Terminal 8, page 26 for
descriptions of the functions of each terminal. Refer to the Bell Parameters section of the
program to set the Fire Bell, Alarm Bell, and Gas Bell output responses for outputs. Four
annunciation patterns are available: Steady, Pulsed, California Standard, Temporal Code 3,
and Temporal Code 4.
Voltage Output at Terminals 6, 7, and 8
If Terminals 6, 7, and 8 do not provide the expected output, check:
–Programming for Outputs A, B, and C in the outputs section of the program. For proper
operation, do not program a Panel Wide Output the same as an Area Wide Output.
–Bell Parameters section of the program to confirm that the Alarm, Fire, and Gas Bell
responses are programmed for the expected duration and pattern.
–Point Assignments section to confirm that each point is programmed for the expected
local response.
4.6.2
4.6.3
Terminals 6 and 7
When activated, Terminals 6 (Output A) and 7 (Output B), provide positive (+) 12.0 VDC
Nominal power output. Use the power at Terminals 6 and 7 to power bells, siren drivers,
piezoelectric fire sounders, electronic horns, or other devices.
Programming determines the format of the output and the conditions that activate it. One selfresetting circuit breaker protects Terminals 6, 7, and 8 against shorts. When using Output A or
Output B to activate notification appliance circuits in UL Listed fire alarm applications, install
a D192G Indicating Circuit Module.
Available Power
The system combines the 1.4 A of primary power produced by the power supply with the
secondary power source (the battery) to produce a total of 2.0 A of alarm power at 12.0 VDC
Nominal. Terminals 6 and 7 share the available alarm power.
Power Restricted for Fire and Combined Fire and Burglary Systems
Fire systems are prohibited from using the battery for determining alarm power. Use the fire
system power formula described in Fire System Power Formula, page 25 to calculate the
current available for fire and combined fire and burglary systems.
Fire System Power Formula
To calculate the current available at Terminals 6 and 7 for fire and combined fire and burglary
systems:
1.Add together the current draws for all devices connected to Terminals 3, 8, 24, and 32,
and the accessory connector. This is the total current required for the normal standby
condition (NSC).
2.The current available for NSC is 1.4 A. Subtract the NSC current required calculated in
Step 1 from the NSC current available, 1.4 A. The difference is the alarm current available
for Terminals 6 and 7.
In formula format:
1.4 A - NSC current required (Step 1) = Alarm current available
Refer to the Approved Applications chapter inside the D9412GV4/D7412GV4 v2.00 Installationand System Reference Guide (P/N: F01U265457) for module or accessory current requirements.
26en | Power Supply and Power OutputsControl Panel
4.6.4
Terminal 8
Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts the
power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other
devices that are reset by interrupting power. One self-resetting circuit breaker protects
Terminals 6, 7, and 8 against shorts.
Verification/Reset Output
The default program sets Output C (Terminal 8) as a verification and reset output. Refer to
Output Parameters and Point Assignments in the D9412GV4/D7412GV4 v2.00 Program Entry
Guide (P/N: F01U265459) for instructions on programming verification/reset outputs and
points.
Performing a sensor reset at a keypad produces a five-second output activation of verification/
reset outputs. The control panel ignores verification and reset points during the five-second
output activation.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 27
Control PanelSpecifications | en27
5
Specifications
Voltage Input
(Power Supply)
Current
Requirement
Power Outputs2All external connections are power-limited except battery terminals
Primary:Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-in
1
transformer (D1640)
Secondary: Terminals 4 and 5 Sealed lead-acid rechargeable battery
(12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18
Ah). The control panel supports up to two
12.0 VDC, 7 Ah batteries using the D122/
D122L Dual Battery Harness or two
D1218 (12.0 VDC, 17.2 or 18 Ah)
batteries using a D122/D122L.
Control Panel: Idle 225 mA; Alarm 300 mA. Refer to the Current RatingChart for Standby Battery Calculations section in the D9412GV4/D7412GV4
v2.00 Installation and System Reference Guide (P/N: F01U265457) for the
current draw requirements of other system components.
Continuous
Power
Outputs
Terminals 3,
24, 32, 36
1.4 A maximum at 12.0 VDC Nominal
(continuous supply) total for all devices
and outputs supplied at Terminals 3, 24,
32, and 36.
Alarm Power
Output
Terminals 6
and 7
2.0 A maximum at 12.0 VDC Nominal
output. Output can be steady or one of
four pulsed patterns depending on
programming. Refer to Outputs in RPS
Help.
Switched
Aux Power
Terminal 81.4 A maximum at 12.0 VDC Nominal
output. Continuous output is interrupted
by Sensor Reset, or alarm verification
depending on programming. Refer to
Outputs in RPS Help.
Fire and Fire/
Burglary
Systems
To comply with UL 985 and 864 listing standards for fire
alarm systems, the total combined continuous and alarm
current draw for the system during alarm conditions must
be limited to 1.4 A provided by the primary power supply
(rectified AC). If current draw for the system exceeds 1.4
A, use a UL Listed 12 VDC regulated, power limited
auxiliary power supply module such as the B520 (refer to
the Keyswitch Wiring section).
1
Requires a UL Listed power supply.
2
For UL 864 applications, refer to 6.0 Compatibilities for compatible devices.
2012.12 | 02 | F.01U.265.462UL Installation InstructionsBosch Security Systens, Inc.
Page 29
Control PanelSpecifications | en29
5.1
B520 Specifications
Voltage Input (Power
Supply)
Current
Requirements
Power Outputs*All external connections are power-limited except battery terminals
Primary:18 VAC terminal 18.0 VAC, 50 VA class 2 plug-in
transformer -TR1850
(18.0 VAC, 50 VA class 2 plug-in
transformer – TR1850-CA for Canada)
Secondary: Batt 1, Batt 2
terminals
Refer to the B520 Auxiliary Power Supply Module Battery Standby Chart
section in the B520 Auxiliary Power Supply Module Installation andOperation Guide (P/B: F01U265445) for the current draw
requirements of other system components.
Continuous
Power
Outputs
SDI2 Out, AUX
PWR terminals
(rated range)
The B520 Auxiliary Power Supply
Module supports the connection of
two independantly monitored sealed
lead-acid rechargeable batteries (12.0
VDC, 7 Ah through 12.0 VDC, 36 Ah).
2.0 A maximum at 11.5 to 12.2 VDC
(special application) (continuous
supply) total for all devices and
outputs supplied at Terminals 1-4,
6-36.
Fire and
Fire/
Burglary
Systems
*For UL 864 applications, refer to the Compatible Accessories section.
Minimum Operating
Voltage
SDI2 BusSDI2 Bus A:
Battery Discharge/
Recharge Schedule
10.2 VDC
SDI2 Bus B:
Discharge
Cycle
To comply with UL 985 and 864 listing standards for fire
alarm systems, the total combined continuous and
alarm current draw for the system during alarm
conditions must be limited to 2.0 A provided by the
primary power supply (rectified AC). If current draw for
the system exceeds 2.0 A, remove connected devices
until the current draw falls below 2.0 A. Then connect
the removed devices to an additional B520 Auxiliary
Power Supply Module or to an external power supply
8 VDC-2000 ft (610 m) maximum
8 VDC-2000 ft (610 m) maximum
13.2 VDC – Charging float level.
12.0 VDC – Low Battery and AC Fail Reports if
programmed. Low Battery LED on.
10.2 VDC – Minimum operational voltage.
9.8 VDC – Battery load (operation continue if AC is
present).