Overview
1.0 Overview
The printer installed with your security system records various types of events. You need a D9131A Parallel Printer Interface Module to be able to use the printer. Your security system has been programmed by your security technician to provide you with printed reports of activities such as Openings, Closings, Alarms, etc. This User’s Guide describes the types of reports that can be printed, and explains the information contained in these reports. The manual that comes with your printer explains printer functions such as how to load printer paper.
You can display events from your security system on a monitor; however, you will not retain a permanent record of your system events this way.
1.2 Operation
The security system only remembers a certain number of events. If more than this number of events occur, new events push out older events one by one. Your system has a Print Log command that allows you to print the entire history of events stored in your system or you may select to print only events that have occurred from a specific date forward.
1.3 Printing Format
Your security system prints events with top and bottom margins and form feed between pages with descriptive headers. Each event is printed on two lines. The first line contains the time and date the event occurred. The second line contains the type of event and additional information.
EVENT ACCT AR ID PT# TEXT
01/01 01:21AM Fire Alarm 1111 1 1 Hall Smoke 01/01 01:22AM Fire Cancel 1111 1 002 1 John Smith 01/01 01:23AM Fire Restoral 1111 1 1 Hall Smoke
Line 1:
Date the event occurred at the panel
Time the event occurred at the panel
Line 2:
Event Description
Indicates the current armed status. The descriptions are listed alphabetically under Section 2.0 Event Descriptions and Troubleshooting beginning on page 5.
Account Number
Area Number
ID Number
USER XXX Event reported was initiated by this user ID. USER XXX-0 Event reported was initiated with the Master User (Card/Token). USER XXX-1,2,3 Event reported was initiated with the Sub User Noted (Card/Token).
Point Number
D9131A User's Guide
© 2002 Bosch Security Systems Page 3 34584G
Page 4
D9131A
Overview
Text
Usually this is programmed by your alarm technician, however, the following text is not: SDI XX- Event reported was initiated by the Serial Device Interface indicated. The numbers 1 through 8 indicate the
event is from one of the supervised command centers. The numbers 17, 18 or 19 indicate the event is from a printer. Numbers 33 to 40 indicate the event is from the Access Control Module.
(The following text indicates previous armed status.)
Was Master Armed Was Perim Delay Was Perim Instant Was Disarmed Was Mstr Instnt
User Text
Your alarm technician usually will program this. User text is printed whenever an event with a User ID is noted.
D9131A User's Guide
34584G Page 4 © 2002 Bosch Security Systems
Page 5
D9131A
Event Description and Troubleshooting
2.0 Event Descriptions and Troubleshooting
The following events and their respective descriptions are listed in alphabetical order. Your system may not display all of the events. For detail in the cause of events, see your Security System Owner’s Manual.
Event Description
Access Granted A card access holder has been granted access at the point specified. AC Failure
AC Restoral ALARM-Door Open An access door has been held open beyond the allowed time while the area was armed. Alarm Report Alarm at device in area specified. This event also reports Cross Point Alarms, including
All Points Tested
Bad Call To RAM
Battery Low Security system battery is low. Replace the battery. Battery Missing
Battery Restore Security system battery has recharged. Cancel Alarm User with reported ID canceled an alarm from the area specified. Card Assigned Command Bypass Closing Early Closing Late Closing Report User with reported ID armed area. Comm Failure Security system could not communicate using the phone number reported. Call for service. Date Changed Door Closed-
Restoral Door Cycled Door Left Open Door Locked Door Secured An access door in the area specified was secured, which prohibits access. Door Unlocked An access door in the area specified was unlocked allowing free access. Duress Early to Open
Extra Point Area specified reports an unprogrammed device. Call for service. Extn Close Time User with reported ID extended area’s closing time to that specified. Fail To Close Fail To Open F Close Early F Close Late User with reported ID force armed* specified area later than expected. F Close Pr Dlay User with reported ID force armed* perimeter with entry/exit delay. F Close Pr Inst Fire Alarm Fire Cancel See Cancel Alarm. Fire Restoral The fire trouble or alarm event at the device specified has been restored.
AC power to the security system is interrupted. Check the plug-in transformer and the circuit breaker.
AC power to the security system has been restored.
Cross Group (CG:##) information. All points have been tested while in the Service Walk Test, Fire Walk Test, or Walk Test
mode. System tried to call Remote Account To Ram Manager (RAM) and failed. Call your security
company.
Security system battery is disconnected or has discharged. Reconnect the battery; call for service.
An access card/token was added to the system. Device specified is bypassed.* System will not respond to faults at this point. User armed area earlier than expected. User armed area later than expected.
User with reported ID changed the date in the security system. An access door in the area specified restored to normal after a Door Left Open event
has occurred. An access door in the area specified was cycled. The door specified has been left open past the programmed time. An access door in the area specified was locked for normal operation.
User with reported ID manually initiated a special alarm in the area specified. User disarmed area earlier than expected. If the entire security system is being disarmed,
the previous state of security system is indicated. If just one area is being disarmed, no previous status is indicated.
Area failed to arm within your programmed closing window. Area failed to disarm within your programmed opening window. User with reported ID force armed* specified area later than expected.
User with reported ID force armed* area perimeter with no delay time. Fire Alarm at device specified.
D9131A User's Guide
© 2002 Bosch Security Systems Page 5 34584G
Page 6
D9131A
Event Description and Troubleshooting
Event Description
Fire Supervision
Fire Supervision Restoral
Fire Trouble Fire Walk End Walk test* for fire devices in the area specified is complete. Fire Walk Start A walk test* is in progress for fire devices in the area specified. Forced Close Forced Point Late To Close Late To Open
Log Overflow Log Threshold Missing Alarm Missing Fire Fire device in area specified is not reporting. Call for service. Missing Trouble Trouble Condition at area device specified. Msng
Supervision No Entry -
Level No Entry -
Interlk No Entry -
Secured No Entry -
Unknown Opening Report Params Changed Peri Dlay Armed Peri Inst Armed User with reported ID armed the perimeter of the specified area with no delay time. Phone Line Fail The phone line specified is not working. Call for service. Phone Restoral Point Bypass Point Closing Point Opening User disarmed device in area specified. Point Status Status report for device in area specified. Point Tested Prog Access Ok Pt Bus Trouble Pt Bus Restoral Wiring problem is resolved. Ram Access Fail Technician could not access your security system from the security company. Ram Access Ok Re-Boot Relay Reset Relay Set Request To A Request To Enter device for an access door has been activated.
Supervision condition at the fire point specified.
Supervision condition at the fire point specified has been restored.
Trouble condition at area device specified.
User with reported ID armed area with point(s) faulted. User force armed device in area reported. User with reported ID armed the security system later than expected. User with the reported ID disarmed area later than expected. If the entire security system is
being disarmed, the previous state of the system is indicated. If just one area is being disarmed, no previous state is indicated.
Security system event log is full. Events are being overwritten. Security system event log is at the programmed maximum capacity. Device in area specified is not reporting. Call for service.
Supervision device at area specified is not reporting.
An access card holder attempted access but was denied due to the user’s authority level.
Access was denied due to the interlock door being open.
Access was denied due to the door being secured.
Access was denied because the user was not found in the database.
User with reported ID disarmed area. Security system programming has been changed. User with ID reported armed the perimeter of the specified area with delay time.
The problem with the phone line specified has been restored. Area device specified is bypassed.* System will not respond to faults at this device. User armed device in area specified.
This device has been walk tested.* Account has been accessed locally by the device specified. Wiring problem. Call for service.
Your security company accessed your system from the security company. Your security system was reset. Relay has reset. Relay specified has been turned on.
D9131A User's Guide
34584G Page 6 © 2002 Bosch Security Systems
Page 7
D9131A
Event Description and Troubleshooting
Event Description
Enter Request To Exit Restoral Report RF Low Battery RF Batt Restor The Low Battery condition previously sent from the point specified has restored. RTE Deny
Intrlok RTE Deny
Secured REX Deny
Intrlok REX Deny
Secured S: Alarm S: Closing S: Fire
Supervision S: Opening S: Perim Delay S: Perim
Instant S: Supervision S: Trouble Status report: trouble at area specified. SDI Failure Serial Device Interface specified is not reporting. 1-8 = command centers; 017, 018, 019 =
SDI Restoral Sensor Reset Service End Service Start A Service Walk Test in the specified area has started. Sked Bypass Sked* in area specified is bypassed.* System will not respond to faults at this device. Sked Changed Sked Executed Status report Supervision Swinger Bypass
Test Report Time Changed
A Request To Exit device for an access door has been activated. Restoral at point in area specified. A Low Battery condition at the point specified has been detected.
A Request To Enter device has been activated but was denied due to the interlock door being open.
A Request To Enter device has been activated but was denied due to the door being Secured. See Door Secured.
A Request To Exit device has been activated but was denied due to the interlock door being open.
A Request To Exit device has been activated but was denied due to the door being Secured. See Door Secured.
Status report: alarm at area specified. Status report: closing at area specified. Status report: Fire Supervision at area specified.
Status report: opening at area specified. Status report: area perimeter specified is armed with entry/exit delay. Status report: area perimeter specified is armed (no delay).
Status report: Supervision at area specified.
printers; 33-40 = Access Control Module. 80 = Home Automation; 88 = RAMIV/Netcom. Make sure the device is plugged in. The problem with the device specified is resolved. User with reported ID reset detection devices in area specified. A Service Walk Test in the specified area has ended.
User with reported ID changed the Sked* indicated. Sked* was activated. Status report was sent to the receiver. Supervision condition at point specified. Area specified had four alarm or trouble signals within an hour. It is now bypassed from the
system. Test report was sent. User with reported ID changed the time in the security system.
D9131A User's Guide
© 2002 Bosch Security Systems Page 7 34584G
Page 8
D9131A
Event Description and Troubleshooting
Event Description
Trouble Door Open
Trouble Report Unverified
Event User Alarm Cmd7 User Alarm Cmd9 Usr Code Change Usr Code Delete User ID specified was deleted. User Level Set The authority level of the specified user has been modified. User Tamper Walk End Walk Start Was Force Armed Watch Mode Start The Watch Mode in the specified area has started. Watch Mode End The Watch Mode in the specified area has ended. Watchdog Reset
* For an explanation of terms, see your Security System Owner’s Manual.
Access door was left open beyond the programmed time.
Trouble condition at device specified. The point specified generated an unverified alarm event.
User with reported ID manually initiated special alarm in the area specified. User with reported ID manually initiated special alarm in the area specified. User ID specified was changed.
User with wrong ID tried to access specified area. Walk test in area specified is complete. A walk test is in progress in the area specified. User with the reported ID force armed* account with point(s) faulted.
Panel was internally reset.