Fire Alarm Systems | D9069B Fire System Annunciator
D9069B Fire System Annunciator
The D9069B Fire System Annunciator is a remote annunciator designed for use in public places in an analog system controlled by a D8024 or D10024A Fire Alarm Control Panel (FACP). It annunciates system events only and provides no system control.
System Status
The FACP sends system status information to the D9069B over a four-wire RS-485 circuit. Two of the four wires are reserved for 24 VDC power, and the remaining two wires are reserved for RS-485 data. A D9051 RS-485 Bus Module must be mounted inside the FACP for the D9069B to communicate.
Seven LEDs report system conditions:
Fire system annunciator
Displays system status in 80-character LCD English text format
Identifies individual devices, zones, and points of alarm in text
Seven LED system status indicators
Annunciates both alarm and trouble conditions
Internal piezo sounder
Control panel connects up to 31 annunciators per system
Text Display
An 80-character back-lit liquid crystal display (LCD) repeats the status, trouble, and alarm messages displayed at the FACP in English text. Forty of these characters are programmable to display individual device location: 20 for the zone and 20 for the device address.
System-wide text displays include:
•Alarm
•Trouble
•Service
•Missing point
•Custom polling circuit and address text
In the analog FACP systems, depending on programming, the D9069B Annunciators can display information for the entire system, for a specific master panel, or for a group of sub-panels.
•
•
•
•
•
•
Power Status
Trouble Silenced
Point Bypassed
System Trouble
Alarm Silenced
Alarm
Region |
Certification |
|
USA |
UL |
UOXX: Control Unit Accessories, System |
|
|
(UL864, 9th edition) |
|
CSFM |
7120-1615: 187 July 2008 |
www.boschsecurity.com
2 | D9069B Fire System Annunciator
Compatibility Information
The D9069B is compatible with the following products:
Category |
Product ID |
Product Description |
Control Panels |
D10024A |
Analog FACP |
|
D8024 |
Analog FACP |
Modules |
D9051 |
RS-485 bus module |
|
D9073 |
High integrity RS-485 bus module |
Mounting Considerations
The D9069B Fire System Annunciator can be surfacemounted or semi-flush mounted.
Wiring Considerations
The maximum length of the four-wire circuit is 4920 ft (1500 m). Use D9073 High-integrity RS-485 Bus Modules to increase circuit length (refer to the D9073 Installation Instructions [P/N: 34847] for details).
Quant. |
Component |
1 |
Annunciator in enclosure |
1 |
Literature pack |
Environmental Considerations
Relative Humidity: |
5 to 85%, non-condensing at 86°F (30°C) |
Temperature (operating): |
+32°F to +120°F (0°C to +49°C) |
Mechanical Properties |
|
Dimensions (H x W x D): |
6.25 in. x 9 in. x 3 in. (15.9 cm x 23 cm x 3 cm) |
Power Requirements |
|
Current Draw: |
35 mA inactive, 125 mA with display active |
Supply Voltage: |
24 VDC nominal |
Voltage (operating range): |
20 VDC to 28 VDC |
D9069B Fire System Annunciator |
D9069B |
Designed for use in public places in an analog system controlled by a D8024 or D10024A Fire Alarm Control Panel
Americas: |
Europe, Middle East, Africa: |
Asia-Pacific: |
Represented by |
Bosch Security Systems, Inc. |
Bosch Security Systems B.V. |
Robert Bosch (SEA) Pte Ltd, Security Systems |
|
130 Perinton Parkway |
P.O. Box 80002 |
11 Bishan Street 21 |
|
Fairport, New York, 14450, USA |
5600 JB Eindhoven, The Netherlands |
Singapore 573943 |
|
Phone: +1 800 289 0096 |
Phone: + 31 40 2577 284 |
Phone: +65 6258 5511 |
|
Fax: +1 585 223 9180 |
Fax: +31 40 2577 330 |
Fax: +65 6571 2698 |
|
security.sales@us.bosch.com |
emea.securitysystems@bosch.com |
apr.securitysystems@bosch.com |
|
www.boschsecurity.us |
www.boschsecurity.com |
www.boschsecurity.com |
|
© Bosch Security Systems Inc. 2010 | Data subject to change without notice T1119553035 | Cur: en-US, V7, 4 Jul 2010