Bosch D9069B Installation Manual

D9069A Fire System Annunciator
Installation Guide
1.0 Notice
These instructions cover the installation of the D9069A Fire System Annunciator in an analog system controlled by a Radionics D8024 or D10024 Series Analog Fire Alarm Control Panel (FACP).
Install, test and maintain the D9069A according to these instructions, NFPA 72, Local Codes and the Authority Having Jurisdiction. Failure to follow these instructions may result in failure of the device to operate properly. Radionics is not responsible for improperly installed, tested or maintained devices.
NFPA 72 requires a complete system-wide functional test be performed following any modifications, repair, upgrades or adjustments made to the system’s components, hardware, wiring, programming and software/ firmware.
2.0 Device Description
Radionics’ D9069A Fire System Annunciator is a remote annunciator designed for use in public places in an analog system controlled by Radionics’ D8024 and D10024 Series Analog FACPs. It annunciates system events only and has no provision for system control. The FACP sends system status information to the D9069A over a two-wire Class A or Class B RS-485 circuit.
An 80-character back-lit liquid crystal display shows system events in English text. Forty of these characters are programmable to display individual device locations (20 for the zone and 20 for the device). System-wide text displays include Alarm, Trouble, Service, Missing Point and custom polling circuit and address text.
Six front panel display LEDs report system conditions. See Table 1 for a description of these LEDs. There are also four on-board LEDs that indicate system activity. See Table 2 for a description of these LEDs.
An internal sounder signals the annunciator’s location in alarm conditions. Each analog control panel can support up to 31 D9069A Fire System Annunciators.
Power System Trouble Trouble Silenced
Sounders Silenced Point Bypassed ALARM
Figure 1: D9069A Front Panel Display
Fire System Repeater
een
)
minal Block
g
Mounting the D9069A
Holes for surface mountin
LED 2 (Green)
Sounder
+24V +24V
OV
OV EARTH EARTH
D9069A
LED 1 (Gr
Te r
LED 3 (Yellow)
DIP switches
LED 4 (Red)
Figure 2: Internal View of D9069A
Note: Although the D9069A has a DIP switch block, it cannot be learned into a system. Leave all DIP switches in the OFF
(down) position.
3.0 Mounting the D9069A
Inform the operator before installing this device in an existing system. Remove all power (AC and battery) to the FACP before installing this device. Failure to do so may result in personal injury and/or damage to the equipment.
3.1 Semi-flush Mounting the D9069A
1) Prepare an opening in the wall 9 1/8 in. x 6 5/16 in. (23.2 cm x 16.0 cm)
2) Remove the knockouts from the D9069A as necessary for wiring conduit fittings.
3) Mount the D9069A enclosure in the wall.
4) Run the necessary wiring throughout the premises and pull the wires into the enclosure. Knockouts are provided at the top and bottom of the enclosure.
5) Mount the D9081 Flush Mount Trim Ring to the enclosure.
3.2 Surface Mounting the D9069A
1) Remove the necessary knockouts and install conduit fittings.
2) Mount the enclosure in the desired location. Use all four mounting holes (see Figure 2 for mounting hole locations).
3) Run the necessary wiring throughout the premises and pull the wires into the enclosure. Knockouts are provided at the top and bottom of the enclosure.
D9069A Installation Guide
Copyright © 2002 Radionics Page 2 50992B
Loading...
+ 2 hidden pages