3500/92 Communication Gateway
Datasheet
Bently Nevada Machinery Condition Monitoring
The 3500/92 Communication Gateway module provides extensive communication capabilities of all rack monitored values and statuses for integration with process control and other automation systems using both Ethernet TCP/IP and serial (RS232/RS422/RS485) communications capabilities. It also permits Ethernet communications with 3500 Rack Configuration Software and Data Acquisition Software.
Supported protocols include:
•Modicon Modbus protocol (via serial communications)
•Modbus/TCP protocol (a variant of serial Modbus used for TCP/IP Ethernet communications)
•Proprietary Bently Nevada protocol (for communication with 3500 Rack Configuration and Data Acquisition Software packages)
The Ethernet connection to the 3500/92 is an RJ45 connection for 10BASE-T star configuration Ethernet networks.
The 3500/92 supports the communication interfaces, communication protocols, and other features from the original 3500/90 with the exception of the primary value Modbus registers. The 3500/92 now has a Configurable Modbus Register Utility, which can provide the same functionality originally addressed by the primary value Modbus registers.
Document: 141542
Rev. J
3500/92 Communication Gateway
Datasheet
Inputs
Power Consumption |
5.0 watts typical with |
|
ModbusRS232/ RS422 I/O |
|
Module |
|
5.6 watts typical with Modbus |
|
RS485 I/O Module |
Data Types |
Collects data from other |
|
modules in the rack, such as |
|
current measured values with |
|
time stamp, module statuses, |
|
and current alarm statuses, via |
|
a high speed internal network. |
|
Exact data types returned |
|
depend on module type and |
|
channel configuration. |
|
Update Time: The data |
|
collection rate depends on |
|
rack configuration but will not |
|
exceed 1 second for all |
|
modules in the 3500 rack. |
Outputs |
|
|
|
OK LED: |
Indicates when the 3500/92 is |
|
operating properly. |
TX/RX LED: |
Indicates when the 3500/92 is |
|
communicating with other |
|
modules in the 3500 rack. |
Protocols |
|
|
|
BNC Host Protocol |
Communication with 3500 |
|
Configuration Software and |
|
3500 Data Acquisition and |
|
Display Software over Ethernet |
|
TCP/IP. |
Modbus |
Based on AEG Modicon PI- |
|
MBUS-300 Reference Manual. |
|
Uses Remote Terminal Unit |
|
(RTU) transmission mode. |
Ethernet |
|
Communication Link |
Ethernet, 10Mbps, and |
|
conforms to IEEE802.3 |
Protocol |
Ethernet TCP/IP frame and |
|
Modbus/TCP |
Connection |
RJ-45 (telephone jack style) |
|
for 10BASE-T Ethernet cabling |
Environmental Limits
Main and I/O Module
Operating Temperature: |
-30 °C to +65 °C |
|
(-22 °F to +149 °F) |
||
|
||
Storage Temperature: |
-40 °C to +85 °C |
|
(-40 °F to +185 °F) |
||
|
||
Humidity: |
95%, non-condensing |
|
Physical |
|
|
|
|
|
Main Board |
|
|
Dimensions |
241 mm x 24.4 mm x 242 mm |
|
(Height x Width x Depth): |
(9.50 in x 0.96 in x 9.52 in) |
|
|
|
|
Weight: |
0.82 kg (1.8 lb.) |
|
I/O Modules |
|
|
Dimensions |
241 mm x 24.4 mm x 99.1 mm |
|
(Height x Width x Depth): |
(9.50 in x 0.96 in x 3.90 in) |
|
|
|
|
Weight |
0.44 kg (0.96 lb.) |
|
Rack Space Requirements |
||
|
|
|
Monitor Module |
1 full-height front slot |
|
I/O Modules |
1 full-height rear slot |
2/8 |
141542 Rev. J |
3500/92 Communication Gateway
Datasheet
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
•This device may not cause harmful interference.
•This device must accept any interference received, including interference that may cause undesired operation.
EMC
European Community Directive:
EMC Directive 2014/30/EU
Standards:
EN 61000-6-2 Immunity for Industrial Environments
EN 61000-6-4 Emissions for Industrial Environments
Electrical Safety
European Community Directive:
LV Directive 2014/35/EU
Standards:
EN 61010-1
RoHS
European Community Directive:
RoHS Directive 2011/65/EU
Maritime
ABS - Marine and Offshore Applications
DNV GL Rules for Classification – Ships, Offshore Units, and High Speed and Light Craft
For the detailed listing of country and product specific approvals, refer to the Approvals Quick Reference Guide (108M1756) available from www.Bently.com.
CSA/NRTL/C
Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc;
Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc;
Class I, Division 2, Groups A, B, C, and D;
T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F)
When installed per drawing 149243 or 149244.
ATEX/IECEx
II 3 G
Ex nA nC ic IIC T4 Gc
Ex ec nC ic IIC T4/T5 Gc
T4 @ Ta= -20˚C to +65˚C (-4˚F to +149˚F)
When installed per drawing 149243 or 149244.
3/8 |
141542 Rev. J |