3500/60 and 3500/61 Temperature
Modules
Datasheet
BentlyNevadaMachineryCondition Monitoring 141540Rev. L
The3500/60& 61modules providesixchannels of temperaturemonitoring and accept both Resistance TemperatureDetector (RTD) and Thermocouple(TC) temperatureinputs. Themodules condition theseinputs and comparethem against user-programmablealarm setpoints. The3500/60and 3500/61provideidenticalfunctionality except that the3500/61provides recorder outputs for each of its sixchannels whilethe3500/60does not.
Theuser programs themodules to perform either RTDor TC temperaturemeasurements using the3500Rack Configuration Software. Different I/Omodules areavailablein RTD/TCnon-isolated or TCisolated versions. Theuser can configuretheRTD/TCnon-isolated version to accept either TC or RTD, or a mixtureofTCand RTDinputs. TheTCisolated version provides 250Vdc ofchannel-to-channelisolation to protect against externalinterference.
When used in a TripleModular Redundant (TMR) configuration, temperaturemonitors must beinstalled adjacent to each other in groups ofthree. When used in this configuration, thesystem employs two types ofvoting to ensureaccurateoperation and to avoid single-point failures.
3500/60and3500/61 TemperatureModules |
|
Datasheet |
141540Rev. L |
Inputs
Signal |
Accepts from 1to 6RTDor TC |
|
transducer signals. |
|
|
Input |
10MΩfor each lead input. |
Impedance |
|
Power Consumption |
|
|
|
3500/60 |
Nominalconsumption of7 |
|
watts. |
3500/61 |
Nominalconsumption of9 |
|
watts. |
Tranducers
TCs |
|
TypeE |
-100°Cto +1000°C, (-148°F to |
|
+1832 °F). |
When using any oftheisolated thermocoupleI/Omodules (-03 or -04 I/Oordering option) with TypeE thermocouples, theavailablefull-scale rangewillbereduced ifthe3500 system is operated in an ambient temperatureabove+35C. Thereduced rangewillbe-60Cto +1000C(-76F to +1832F). Rack configuration software willallow theuser to configurea channeldown to -100Cbut thesystem willnot function properly in this scenario and thereforeshould not be configured to operatewith these settings.
TypeJ |
-18 |
°Cto +760°C, (+0°F to +1400 |
|
°F). |
|
|
|
|
TypeK |
-18 |
°Cto +1370°C, (+0°F to |
|
+2498°F) |
|
.TypeT |
-160°Cto +400°C, (-256°F to |
|
|
+752 °F). |
|
RTDs |
|
|
|
|
|
100Ω3-wire |
-200°Cto +850°C |
|
& 4-wire |
(-328°F to +1562 °F). |
|
platinum |
||
RTD(alpha |
With externalbarriers: |
|
= 0.00385) |
-50°Cto +850°C |
|
|
||
|
(-122 °F to +1562 °F). |
|
|
|
|
100Ω3-wire |
-200°Cto +700°C |
|
& 4-wire |
(-328°F to +1292 °F). |
|
platinum |
||
RTD(alpha |
With externalbarriers: |
|
= 0.00392) |
-50°Cto +260°C |
|
|
||
|
(-122 °F to + 1292 °F). |
|
|
|
|
120Ω3-wire |
-80°Cto +260°C |
|
& 4-wire |
(-112 °F to +500°F). |
|
nickelRTD |
||
With externalbarriers: |
||
|
||
|
-50°Cto +260°C |
|
|
(-122 °F to + 500°F). |
|
|
|
|
10Ω3-wire& |
-100°Cto +260°C, |
|
4-wire |
(-148°F to +500°F). |
|
copper RTD |
||
|
With externalbarriers: |
|
|
-50°Cto +260°C |
|
|
(-122 °F to +500°F). |
|
|
|
|
|
Platinum RTD's with |
|
|
0.00385alphas arethe |
|
|
worldwideindustrial |
|
|
standard and are |
|
|
recommended for all |
|
|
applications |
|
|
|
|
I/OModules |
|
|
|
|
|
|
Isolated I/OModule |
|
|
System Isolation: 500Vdc |
|
|
Channelto ChannelIsolation: |
|
|
250Vdc |
|
|
Isolation is only required for |
|
|
fault scenarios and these |
|
|
voltages willnot bepresent on |
|
|
|
2/13
3500/60and3500/61 TemperatureModules |
|
Datasheet |
141540Rev. L |
theI/Omoduleinputs when a wiring or field fault occurs.
Outputs
Front PanelLEDs
OK LED |
Indicates when the |
|
TemperatureMonitor is |
|
operating properly. |
TX/RXLED |
Indicates then theTemperature |
|
Monitor is communicating with |
|
other modules in the3500rack. |
Bypass LED |
Indicates when the |
|
TemperatureMonitor is in |
|
Bypass Mode. |
RTDCurrent SourceValue
925±15µA @ 25°Cper transducer (single supply for the4-wireRTDand two supplies for the3-wire).
Recorder
+4to +20mA. Values areproportionalto monitor full-scale. Individualrecorder values areprovided for each channel. Monitor operation is unaffected by short circuits on recorder outputs.
VoltageCompliance(current output)
0to +12 Vdc rangeacross load. Load resistanceis 0to 600Ω.
Resolution
0.3662 µA per bit ±0.15% error at room temperature±0.4% error over temperature range.
SignalConditioning
Specified at +25°C(+77°F) unless otherwisenoted.
Full-scalerangefor each channelis set in thefield via 3500Configuration Software. No calibration is required.
RTDs and TCs (except for 10ΩCopper RTDs)
Resolution |
1°Cor 1°F |
|
|
Accuracy |
|
|
|
Internal |
|
Termination |
|
Non- |
|
Isolated |
|
Bulkhead |
±3 °Cat 25°C |
Rack |
(±5.4°F at 77°F). |
|
|
|
|
Standard |
±3 °Cat 25°C |
Rack |
(±5.4°F at 77°F). |
|
|
|
|
ExternalTermination Non-Isolated |
|
Bulkhead |
±3 °Cat 25°C |
Rack |
(±5.4°F at 77°F). |
|
|
|
|
Standard |
±1°Cat 25°C |
Rack |
(±1.8°F at 77°F). |
|
|
|
|
InternalTermination Isolated |
|
Bulkhead |
±2 °Cat 25°C |
Rack |
(±3.6°F at 77°F). |
|
|
|
±3 °Cat 25°C |
|
±5.4°F at 77°F). |
|
|
Standard |
±3 °Cat 25°C |
Rack |
±5.4°F at 77°F). |
|
|
|
|
ExternalTermination Isolated |
|
Bulkhead |
±1°Cat 25°C |
Rack |
(±1.8°F at 77°F). |
|
|
|
|
Standard |
°Cat 25°C |
Rack |
(±1.8°F at 77°F) |
|
|
|
|
10ΩCopper RTDs |
|
|
|
Resolution |
1°Cor 1°F |
|
|
Accuracy |
±3 °Cat 25°C |
|
|
3/13
3500/60and3500/61 TemperatureModules |
|
Datasheet |
141540Rev. L |
(±5.4°F at 77°F).
Cold Junction Compensation Sensor(used forTC measurements)
Accuracy |
±1°Cat 25°C |
|
(±1.8°F at 77°F). |
|
|
Alarms
Alarm |
Theuser can set Alert and |
Setpoints |
Danger setpoints for thevalue |
|
measured by themonitor using |
|
softwareconfiguration. Alarms |
|
areadjustablefrom 0to 100% of |
|
full-scalefor each measured |
|
value. Theexception is when the |
|
full-scalerangeexceeds the |
|
rangeofthesensor. In this case, |
|
therangeofthesensor willlimit |
|
thesetpoint. Accuracy ofalarms |
|
areto within 0.13% ofthedesired |
|
value. TheTemperature |
|
Monitors haveboth under and |
|
over alarm setpoints. |
Alarm Time Delays
Theuser can program alarm delays using softwareas follows:
Alert |
From 1to 60seconds in 1second |
|
intervals. |
|
|
Danger |
From 1to 60seconds in 0.5 |
|
second intervals |
Measured Values
Measured values aretemperature measurements used to monitor themachine. TheTemperatureMonitors return temperaturemeasured values.
4/13