Bently Nevada 3500/60 Data sheet

5 (1)
Bently Nevada 3500/60 Data sheet

3500/60 and 3500/61 Temperature

Modules

Datasheet

BentlyNevadaMachineryCondition Monitoring 141540Rev. L

Description

The3500/60& 61modules providesixchannels of temperaturemonitoring and accept both Resistance TemperatureDetector (RTD) and Thermocouple(TC) temperatureinputs. Themodules condition theseinputs and comparethem against user-programmablealarm setpoints. The3500/60and 3500/61provideidenticalfunctionality except that the3500/61provides recorder outputs for each of its sixchannels whilethe3500/60does not.

Theuser programs themodules to perform either RTDor TC temperaturemeasurements using the3500Rack Configuration Software. Different I/Omodules areavailablein RTD/TCnon-isolated or TCisolated versions. Theuser can configuretheRTD/TCnon-isolated version to accept either TC or RTD, or a mixtureofTCand RTDinputs. TheTCisolated version provides 250Vdc ofchannel-to-channelisolation to protect against externalinterference.

When used in a TripleModular Redundant (TMR) configuration, temperaturemonitors must beinstalled adjacent to each other in groups ofthree. When used in this configuration, thesystem employs two types ofvoting to ensureaccurateoperation and to avoid single-point failures.

3500/60and3500/61 TemperatureModules

 

Datasheet

141540Rev. L

Specifications

Inputs

Signal

Accepts from 1to 6RTDor TC

 

transducer signals.

 

 

Input

10MΩfor each lead input.

Impedance

 

Power Consumption

 

 

3500/60

Nominalconsumption of7

 

watts.

3500/61

Nominalconsumption of9

 

watts.

Tranducers

TCs

 

TypeE

-100°Cto +1000°C, (-148°F to

 

+1832 °F).

When using any oftheisolated thermocoupleI/Omodules (-03 or -04 I/Oordering option) with TypeE thermocouples, theavailablefull-scale rangewillbereduced ifthe3500 system is operated in an ambient temperatureabove+35C. Thereduced rangewillbe-60Cto +1000C(-76F to +1832F). Rack configuration software willallow theuser to configurea channeldown to -100Cbut thesystem willnot function properly in this scenario and thereforeshould not be configured to operatewith these settings.

TypeJ

-18

°Cto +760°C, (+0°F to +1400

 

°F).

 

 

 

 

TypeK

-18

°Cto +1370°C, (+0°F to

 

+2498°F)

.TypeT

-160°Cto +400°C, (-256°F to

 

+752 °F).

RTDs

 

 

 

 

 

100Ω3-wire

-200°Cto +850°C

& 4-wire

(-328°F to +1562 °F).

platinum

RTD(alpha

With externalbarriers:

= 0.00385)

-50°Cto +850°C

 

 

(-122 °F to +1562 °F).

 

 

100Ω3-wire

-200°Cto +700°C

& 4-wire

(-328°F to +1292 °F).

platinum

RTD(alpha

With externalbarriers:

= 0.00392)

-50°Cto +260°C

 

 

(-122 °F to + 1292 °F).

 

 

120Ω3-wire

-80°Cto +260°C

& 4-wire

(-112 °F to +500°F).

nickelRTD

With externalbarriers:

 

 

-50°Cto +260°C

 

(-122 °F to + 500°F).

 

 

10Ω3-wire&

-100°Cto +260°C,

4-wire

(-148°F to +500°F).

copper RTD

 

With externalbarriers:

 

-50°Cto +260°C

 

(-122 °F to +500°F).

 

 

 

Platinum RTD's with

 

0.00385alphas arethe

 

worldwideindustrial

 

standard and are

 

recommended for all

 

applications

 

 

I/OModules

 

 

 

 

Isolated I/OModule

 

System Isolation: 500Vdc

 

Channelto ChannelIsolation:

 

250Vdc

 

Isolation is only required for

 

fault scenarios and these

 

voltages willnot bepresent on

 

 

2/13

3500/60and3500/61 TemperatureModules

 

Datasheet

141540Rev. L

theI/Omoduleinputs when a wiring or field fault occurs.

Outputs

Front PanelLEDs

OK LED

Indicates when the

 

TemperatureMonitor is

 

operating properly.

TX/RXLED

Indicates then theTemperature

 

Monitor is communicating with

 

other modules in the3500rack.

Bypass LED

Indicates when the

 

TemperatureMonitor is in

 

Bypass Mode.

RTDCurrent SourceValue

925±15µA @ 25°Cper transducer (single supply for the4-wireRTDand two supplies for the3-wire).

Recorder

+4to +20mA. Values areproportionalto monitor full-scale. Individualrecorder values areprovided for each channel. Monitor operation is unaffected by short circuits on recorder outputs.

VoltageCompliance(current output)

0to +12 Vdc rangeacross load. Load resistanceis 0to 600Ω.

Resolution

0.3662 µA per bit ±0.15% error at room temperature±0.4% error over temperature range.

SignalConditioning

Specified at +25°C(+77°F) unless otherwisenoted.

Full-scalerangefor each channelis set in thefield via 3500Configuration Software. No calibration is required.

RTDs and TCs (except for 10ΩCopper RTDs)

Resolution

1°Cor 1°F

 

 

Accuracy

 

 

 

Internal

 

Termination

 

Non-

 

Isolated

 

Bulkhead

±3 °Cat 25°C

Rack

(±5.4°F at 77°F).

 

 

 

Standard

±3 °Cat 25°C

Rack

(±5.4°F at 77°F).

 

 

 

ExternalTermination Non-Isolated

Bulkhead

±3 °Cat 25°C

Rack

(±5.4°F at 77°F).

 

 

 

Standard

±1°Cat 25°C

Rack

(±1.8°F at 77°F).

 

 

 

InternalTermination Isolated

Bulkhead

±2 °Cat 25°C

Rack

(±3.6°F at 77°F).

 

 

±3 °Cat 25°C

 

±5.4°F at 77°F).

 

 

Standard

±3 °Cat 25°C

Rack

±5.4°F at 77°F).

 

 

 

ExternalTermination Isolated

Bulkhead

±1°Cat 25°C

Rack

(±1.8°F at 77°F).

 

 

 

Standard

°Cat 25°C

Rack

(±1.8°F at 77°F)

 

 

 

10ΩCopper RTDs

 

 

Resolution

1°Cor 1°F

 

 

Accuracy

±3 °Cat 25°C

 

 

3/13

3500/60and3500/61 TemperatureModules

 

Datasheet

141540Rev. L

(±5.4°F at 77°F).

Cold Junction Compensation Sensor(used forTC measurements)

Accuracy

±1°Cat 25°C

 

(±1.8°F at 77°F).

 

 

Alarms

Alarm

Theuser can set Alert and

Setpoints

Danger setpoints for thevalue

 

measured by themonitor using

 

softwareconfiguration. Alarms

 

areadjustablefrom 0to 100% of

 

full-scalefor each measured

 

value. Theexception is when the

 

full-scalerangeexceeds the

 

rangeofthesensor. In this case,

 

therangeofthesensor willlimit

 

thesetpoint. Accuracy ofalarms

 

areto within 0.13% ofthedesired

 

value. TheTemperature

 

Monitors haveboth under and

 

over alarm setpoints.

Alarm Time Delays

Theuser can program alarm delays using softwareas follows:

Alert

From 1to 60seconds in 1second

 

intervals.

 

 

Danger

From 1to 60seconds in 0.5

 

second intervals

Measured Values

Measured values aretemperature measurements used to monitor themachine. TheTemperatureMonitors return temperaturemeasured values.