Basler Electric BE3-37 User Manual

www.basler.com
+1 618.654.2341 (USA)
info@basler.com
INTRODUCTION
SPECIFICATIONS
Inputs
Operating Power
All units require external operating power. Nominal Voltage: 120 Vac, 240 Vac, 380 Vac, 480 Vac,
or 24 Vdc
Current Sensing
Nominal: 5 Aac Range: 0.2 to 10 Aac Overload Withstand: 50 Aac for 3 s Frequency: 50, 60, or 400 Hz Burden: <0.5 VA per phase
Setpoint
Undercurrent Range: Adjustable 0 to 80% (±3%) of
nominal
Overcurrent Range: Adjustable 40 to 120% (±3%) of
nominal Repeatability: Better than 0.5% of full span Time Delay: Adjustable 1 to 10 sec Operating Time: 200 ms typical Differential: Fixed at 5% of nominal
Outputs
Relay Type: D.P.D.T. AC Rating: 250 V, 5 A, non-resistive,
1200 VA DC Rating: 125 V, 1 A, resistive, 120 W Mechanical Life: 5 million operations
Temperature
Operating Temperature: 0°C (32°F) to 60°C (140°F) Functional Temperature: –25°C (–13°F) to 70°C (158°F) Storage Temperature: –40°C (–40°F) to 70°C (158°F) Temperature Coefficient: 0.03% per °C (300 ppm/°C)
Humidity
Relative Humidity: 95% non-condensing
Physical
Mounting: DIN rail 1.38” by 0.29” (35 mm by 7.5
mm)
Model
Case: Complies with IEC 529, DIN 40050,
Case Material: Complies with UL 94VO
BE3-37, BE3-51, and BE3-37/51
BS 5490
Weight
Single Unit: 0.88 lb (0.4 kg) Combined Unit: 1.32 lb (0.6 kg)
Size
Single Unit: 2.17” wide (55 mm) Combined Unit: 3.93” wide (100 mm)
Agency
cULus Listed to UL 508 and CSA C22.2 No. 14 CE compliant GOST-R certified per the relevant standards of Gosstandart of
Russia
OPERATION
BE3-37 and BE3-51 ac current relays have two external, user­adjustable controls marked SET and DELAY . The BE3-37/51 has four controls: UNDER SET, UNDER DELAY, OVER SET, and OVER DELAY. The SET control adjusts the relay trip point. An overcurrent trip causes the relay output to energize when the current rises above the SET threshold. The overcurrent SET level is adjustable from 40 to 120% (±3%) of nominal input. An undercurrent trip causes the relay output to de-energize when the current decreases below the SET threshold. The undercurrent SET level is adjustable from 0 to 80% (±3%) of nominal input. Time delay is the amount of time that elapses after the trip point is reached and when the output relay operates.
Setting Example
A BE3-51 relay has the following settings: SET - 120% DELAY - 4 seconds A trip occurs when the sensing c urrent rises above six am peres for
four seconds. Reset occurs when the current decreases below 5.75 amperes (5% of nominal below trip setting).
INSTALLATION
BE3 ac current sensing relays are designed for mounting on standard DIN rails that c omply t o DIN-EN 50022. Mounting involves hooking the top edge of the cutout on the base of the case over one edge of the DIN rail. The opposite side of the cutout contai ning the release clip is then pushed over t he opposite side of the DIN rail. To remove or reposition the relay, lever the release clip and move the relay as required. BE3 relays should be installed in a dry, vibration­free location where the ambient temperature does not exceed the operating temperature range. Connections to the relay should be made using wire that meets applicable codes and is properly sized for the application. Figure 1 shows the t erminal connections for the BE3-37, BE3-51, and BE3-37/51 ac current relays.
CALIBRATION
The calibration marks on the faceplate have a maximum error of 10% and are provided only as guides. Proper cali bration requires using an accurate ammeter in series wit h the current source. Use the following procedure to calibrate your relay.
Overcurrent
1. Adjust the SET control fully clockwise (CW) and the DELAY
control fully counterclockwise (CCW).
2. Apply the desired trip current to the relay.
Publication
9319900990
Revision
D
Instructions
Date
03/14
Copyright
2014
3. Slowly adjust the SET control CCW until the relay trips. (allow
for the 200 ms operating time).
4. Remove the applied current (do not change the current level)
and set the DELAY control to the desired time delay.
5. Apply the trip current to the relay and measure the time to trip.
6. Adjust the DELAY and repeat Steps 4 and 5 until the desired
time delay is achieved.
Undercurrent
1. Adjust the SET and DELAY controls fully CCW.
2. Decrease the applied sensing current f rom the nominal value
until the desired tripping current is reached.
3. Slowly adjust the SET control CW until the relay trips (allow for
the 200 ms operating time).
FIGURES
4. Set the DELAY control to the desired time delay and apply
nominal current to the relay.
5. Step down the applied current from nominal to a level just
below the trip level set in Step 3.
6. Adjust the DELAY and repeat Steps 4 and 5 until the desired
time delay is achieved.
MAINTENANCE
BE3 relays are solid-state devices that require no maintenance. In the event that your relay requires repair, contact Basler Electric, Highland, IL, USA for return authorization.
ORDERING INFORMATION
Figure 2 shows the BE3 ac current relay style numbers.
Publication
9319900990
Figure 1. BE3-37, BE3-51, BE3-37/51 AC Current Connections
Figure 2. BE3-37, BE3-51, BE3-37/51 Style Number Identification Chart
Revision
D
Instructions
Date
03/14
Page
2 of 2
Loading...