APC AP7922B User Manual

Switched Rack PDU AP7922B
Overview
The APC by Schneider Electric Switched Rack Power Distribution Unit (PDU) distributes power to devices in the rack. It has a sensor that measures the current used by the PDU and its attached devices. It can be monitored through Web, Telnet, SNMP, SSH, or StruxureWare Data Center Expert
Digital display: A digital display shows aggregate current being used per bank. Power cord: The 12 ft (3.65 m) power cord terminates with a IEC 309 connector.
®
interfaces.
Specifications
Electrical
Nominal input voltage 230 V Acceptable input voltage ± 10% Nominal input voltage Maximum total current draw 32 A Input frequency 47–63 Hz Cord length 12 ft (144 in) Input connectors IEC 309, 32A, 230V, 1~ plug Output connectors Sixteen IEC 320 C13 outlets Overload protection Two (2) 16 A
Physical
Size (H × W × D) 3.5×17.5×4.5 in (88.9×444.5×114.3 mm) Weight 9.9 lb ( 4.49 kg) Shipping weight 14.4 lb (6.53 kg)
Environmental
Elevation (above MSL)
Operating Storage
Temperature
Operating Storage
Humidity
Operating Storage
Compliance
Safety VDE, CE, EAC EMC EN 55022, AS/NZS, EN55024, CISPR22
0–15 000 ft (0–4500 m) 0–50 000 ft (0–15 000 m)
–5 to 45° C (23 to 115° F) –25 to 65° C (–13 to 149° F)
5–95% RH, Non-condensing 5–95% RH, Non-condensing
Customer support and warranty information are available on the website, www.apc.com. © 2016 APC by Schneider Electric. All rights reserved.