APC AP7922B Service Manual

5 (1)
User Guide
Rack Power Distribution Unit
Switched AP89XX
990-5569G-001 Publication Date: June 2018
APC by Schneider Electric Legal Disclaimer
The information presented in this manual is not warran ted by the APC by Schn eider Electric to be auth orit ative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, APC by Schneider Electric assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction. This Publication has been compiled in good faith by APC by Schneider Electric. However, no representation is made or warranty given, either express or implied, as to the completeness or accuracy of the information this Publication contains.
IN NO EVENT SHALL APC BY SCHNEIDER ELECTRIC, OR ANY PARENT, AFFILIATE OR SUBSIDIARY COMPANY OF APC BY SCHNEIDER ELECTRIC OR THEIR RESPECTIVE OFFICERS, DIRECTORS, OR EMPLOYEES BE LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IF APC BY SCHNEIDER ELECTRIC HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. APC BY SCHNEIDER ELECTRIC RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary right s in the content (including bu t not limited to soft ware, audio, video, text, and photographs) rests with APC by Schneider Electric or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.
This Publication shall not be for resale in whole or in part.
Content s
Introduction...................................................................................................................... 1
Product Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Types of User Accounts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Watchdog Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Network interface watchdog mechanism . . . . . . . . . . . . . . . . . . . . . . . 2 Resetting the network timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Network Port Sharing (NPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
About the Network Port Sharing Feature . . . . . . . . . . . . . . . . . . . . . . . 3 Display ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Specific assignment of Display IDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Firmware Upgrade with NPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 RF Tag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 EnergyWise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 EnergyWise and NPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Establish Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
IPv4 initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 IPv6 initial setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 .ini file utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 DHCP and BOOTP configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Network Management with Other Applications . . . . . . . . . . . . . . . . . . . 7 Command Line Interface (CLI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Recovering from a Lost Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Rack PDU Front Panel .................................................................................................. 10
Network Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 10/100 LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Load Indicator LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Example 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Example 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Command Line Interface................................................................................................ 17
About the Command Line Interface (CLI) . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Log on to the CLI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Remote access to the Command Line Interface . . . . . . . . . . . . . . . . . 17 Telnet for basic access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 SSH for high-security access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Local access to the Command Line Interface . . . . . . . . . . . . . . . . . . . 18
About the Main Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 Using the CLI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Command Syntax. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 Command Response Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Switched Rack PDU AP89XX User Guide i
Network Management Card Command Descriptions. . . . . . . . . . . . . . . . . . . .23
? or help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 about . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 alarmcount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 boot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 cd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 clrrst . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 dir . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 dns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 email . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 eventlog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 exit, quit, or bye . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 firewall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 ftp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 lang . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 lastrst . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 ledblink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 logzip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 netstat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 ntp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 ping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 portSpeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 prompt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 pwd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 radius . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 resetToDef . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 session . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 smtp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 snmp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 snmpv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 snmptrap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 tcpip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 tcpip6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 userdflt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 whoami . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 xferINI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 xferStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Switched Rack PDU AP89XX User Guideii
Device Command Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Network Port Sharing Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 alarmList . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 bkLowLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 bkNearOver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 bkOverLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 bkPeakCurr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 bkReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 bkRestrictn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 devLowLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 devNearOver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 devOverLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 devPeakLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 devReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 devStartDly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 dispID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 energyWise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 humHyst . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 humLow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 humMin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 humReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 humStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 lcd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 lcdBlink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 logToFlash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 olAssignUsr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 olCancelCmd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 olDlyOff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 olDlyOn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 olDlyReboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 olGroups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 olName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 olOff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 olOffDelay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 olOn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 olOnDelay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 olRbootTime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 olReboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 olStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 olType . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 olUnasgnUsr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 phLowLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 phNearOver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 phOverLoad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 phPeakCurr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 phReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 phRestrictn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 phTophVolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 prodInfo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 sensorName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 tempHigh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 tempHyst . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 tempMax . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 tempReading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 tempStatus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 userAdd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 userDelete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Switched Rack PDU AP89XX User Guide iii
userList . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 userPasswd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Web User Interface........................................................................................................ 88
Supported Web Browsers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 Log On to the Web User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 URL address formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Web Interface Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Device status icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Quick Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Network Port Sharing (NPS) on the Web User Interface (Web UI) . . . . . . . . .91
Group Control using Network Port Sharing . . . . . . . . . . . . . . . . . . . . 91
About Home. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
The Overview view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Status Tab......................................................................................................................93
About the Status Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
View the Load Status and Peak Load . . . . . . . . . . . . . . . . . . . . . . . . . 94 View the Network Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Current IPv4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Current IPv6 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Domain Name System Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Ethernet Port Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Control ........................................................................................................................... 96
Controlling Rack PDU Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
To control the outlets on your Rack PDU . . . . . . . . . . . . . . . . . . . . . . 97 Control actions you can select . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Managing User Sessions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98 Resetting the Network Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99
Configuration................................................................................................................ 100
About the Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Configure Load Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
To configure load thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Configure Rack PDU Name and Location . . . . . . . . . . . . . . . . . . . . . . . . . . .101 Set the Coldstart Delay for the Rack PDU. . . . . . . . . . . . . . . . . . . . . . . . . . .101 Reset Peak Load and kWh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101 Set the Overload Outlet Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102
To set Overload Outlet Restrictions: . . . . . . . . . . . . . . . . . . . . . . . . . 102
Configure and Control Outlet Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102
Outlet group terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Purpose and benefits of outlet groups . . . . . . . . . . . . . . . . . . . . . . . 102 System requirements for outlet groups . . . . . . . . . . . . . . . . . . . . . . . 103 Rules for configuring outlet groups . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Enable outlet groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Create a local outlet group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Create a global outlet group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Edit or delete an outlet group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Typical outlet group configurations . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Verify your setup and configuration for global outlet groups . . . . . . . 107
Outlet Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Configure outlet settings and the outlet name . . . . . . . . . . . . . . . . . 108
Switched Rack PDU AP89XX User Guideiv
Schedule Outlet Actions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Actions you can schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Schedule an outlet event . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Edit, disable, enable, or delete a scheduled outlet event . . . . . . . . . 110
Outlet User Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
Configure an outlet user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Outlet Manager and Network Port Sharing . . . . . . . . . . . . . . . . . . . . 111
Configure Temperature and Humidity Sensors . . . . . . . . . . . . . . . . . . . . . . .112 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
Session Management screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Ping Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Local Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Remote Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Configure the RADIUS Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Supported RADIUS servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 RADIUS and Network Port Sharing . . . . . . . . . . . . . . . . . . . . . . . . . 117 Firewall Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Network Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118
TCP/IP and Communication Settings . . . . . . . . . . . . . . . . . . . . . . . . 118 Port Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120 DNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 SNMPv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 SNMPv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 FTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
Event Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Configure event actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Email notification screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 SNMP trap receiver screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 SNMP traps test screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 Remote Monitoring Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
General Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
Identification screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Date/Time screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 Creating and importing settings with the config file . . . . . . . . . . . . . 136 Configure Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Logs in the Configuration Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
Identifying Syslog servers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 Syslog settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 Syslog test and format example . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Tests Tab............ ......................................................................................................... 139
Setting the Rack PDU LCD or LED Lights to Blink . . . . . . . . . . . . . . . . . . . .139
Logs Tab...................................................................................................................... 140
Event, Data and Firewall Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
Event log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Data log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142 Firewall Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144 Use FTP or SCP to retrieve log files . . . . . . . . . . . . . . . . . . . . . . . . . 144
About Tab . ................................................................................................................... 146
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
About the Rack PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
Support Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Switched Rack PDU AP89XX User Guide v
Device IP Configuration Wizard................................................................................... 148
Capabilities, Requirements, and Installation . . . . . . . . . . . . . . . . . . . . . . . . .148
How to use the Wizard to configure TCP/IP settings . . . . . . . . . . . . 148 System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
How to Export Configuration Settings.......................................................................... 149
Retrieving and Exporting the .ini File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .149
Summary of the procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Contents of the .ini file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 .ini and Network Port Sharing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 Detailed procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
The Upload Event and Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
The event and its error messages . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Messages in config.ini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Errors generated by overridden values . . . . . . . . . . . . . . . . . . . . . . . 152
Related Topics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152
File Transfers............................................................................................................... 153
Upgrading Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153
Benefits of upgrading firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153 Firmware module files (Rack PDU) . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Firmware File Transfer Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
Using the Firmware Upgrade Utility . . . . . . . . . . . . . . . . . . . . . . . . . 154 Use FTP or SCP to upgrade one Rack PDU . . . . . . . . . . . . . . . . . . 155 Use XMODEM to upgrade one Rack PDU . . . . . . . . . . . . . . . . . . . . 156 Use a USB drive to transfer and upgrade the files . . . . . . . . . . . . . . 156 How to upgrade multiple Rack PDUs . . . . . . . . . . . . . . . . . . . . . . . . 157 Using the Firmware Upgrade Utility for multiple upgrades . . . . . . . . 157 Updating firmware for Network Port Sharing (NPS) Groups . . . . . . . 157
Verifying Upgrades and Updates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158
Verify the success or failure of the transfer . . . . . . . . . . . . . . . . . . . 158 Last Transfer Result codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 Verify the version numbers of installed firmware. . . . . . . . . . . . . . . . 158
Download Log files to a USB Flash drive. . . . . . . . . . . . . . . . . . . . . . . . . . . .158
Troubleshooting........................................................................................................... 159
Rack PDU Access Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159 SNMP Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .161 Source Code Copyright Notice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .162
Switched Rack PDU AP89XX User Guidevi

Introduction

Product Features

The APC by Schneider Electric Switched Rack Power Distribution Unit (PDU) may be used as a stand-alone, network-manageable power distribution device or up to four devices can be connected together using one network connection. The Rack PDU provides real-time remote monitoring of connected loads. User-defined alarms warn of potential circuit overloads. The Rack PDU provides full control over outlets through remote commands and user interface settings.
Your Rack PDU comes with a terminator installed in the display In or Out port. In stand-alone operation of Switched Rack PDU models, one terminator must be installed in the display In or Out port. To use Network Port Sharing between up to four units, a terminator must be installed in the In port at one end of the group and another on the Out port at the other end of the group.
You can manage a Rack PDU through its Web User Interface (Web UI), its Command Line Interface (CLI), StruxureWare, or Simple Network Management Protocol (SNMP). (To use the PowerNet MIB with an SNMP browser, see the PowerNet SNMP Management Information Base (MIB) Reference Guide, available at
www.apc.com.) Rack PDUs have these additional features:
• Device power, peak power, apparent power, power factor and energy.
• Phase voltage, current, peak current, power, apparent power and power factor.
• Bank current and peak current (for models that support breaker banks).
• Configurable alarm thresholds that provide network and visual alarms to help avoid overloaded circuits.
• Various levels of access: Super User, Administrator, Device User, Read-Only, Outlet User, and Network-Only User (These are protected by user name and password requirements).
• Multiple user login feature which allows up to four users to be logged in simultaneously.
• Individual outlet control.
• Configurable power delays.
• Event and data logging. The event log is accessible by Telnet, Secure CoPy (SCP), File Transfer Protocol (FTP), serial connection, or web browser (using HTTPS access with SSL, or using HTTP access). The data log is accessible by web browser, SCP, or FTP.
• Email notifications for Rack PDU and Network Management Card (NMC) system events.
• SNMP traps, Syslog messages, and email notifications based on the severity level or category of the Rack PDU and NMC system event.
• Security protocols for authentication and encryption.
• Network Port Sharing (NPS). Up to four Rack PDUs of any model can be connected using the In and Out ports so that only one network connection is necessary.
• NPS guest firmware auto-update feature allows the NPS host to automatically pass a firmware update to its connected guests. This feature will be functional for all guests that have AOS firmware version 6.1.3 or later.
• RF Code wireless monitoring support via serial port connection
• Cisco EnergyWise certified.
NOTE: The Rack PDU does not provide power surge protection. To ensure that the device is protected from
power failure or power surges, connect the Rack PDU to a Schneider Electric Uninterruptible Power Supply (UPS).
1Switched Rack PDU AP89XX User Guide

Types of User Accounts

The Rack PDU has various levels of access (Super User, Administrator, Device User, Read-Only User, Outlet User, and Network-Only User), which are protected by user name and password requirements. Up to four users are allowed to login to the same Rack PDU simultaneously (available in AOS version 6.1.3 or later).
• An Administrator or the Super User can use all of the menus in the Web UI and all of the commands in the CLI. Administrator user types can be deleted, but the Super User cannot be deleted. The default user name and password for the Super User are both apc.
–The Super User or Administrator can manage another Administrator's account (enable,
disable, change password, etc).
• A Device User has read and write access to device-related screens. Administrative functions like session management under the Security menu and Firewall under Logs are grayed out.
• A Read-Only User has the following restricted access:
– Access to the same menus as a Device User, but without the capability to change
configurations, control devices, delete data, or use file transfer options. Links to configuration options are visible but disabled. The event and data logs display no button to clear the log.
• An Outlet User has the following restricted access:
– Access through the Web User Interface and Command Line Interface. – Access to the same menus as a Device User, but with limited capability to change
configurations, control devices, delete data, or use file transfer options. Links to configuration options are visible but are disabled. The Outlet User has access to the Outlet Control menu option that allows the user to control only the outlets assigned by the Administrator. Outlet Users cannot clear the event or data logs. The user name and password are defined by the Administrator during the process of adding a new Outlet User.
• A Network-Only User can only log on using the Web UI and CLI (telnet, not serial). A network­only user has read/right access to the network rela te d men us only.

Watchdog Features

Overview

To detect internal problems and recover from unanticipated inputs, the Rack PDU uses internal, system-wide watchdog mechanisms. When it restarts to recover from an internal problem, a Network Interface Restarted event is recorded in the event log.

Network interface watchdog mechanism

The Rack PDU implements internal watchdog mechanisms to protect itself from becoming inaccessible over the network. For example, if the Rack PDU does not receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes that there is a problem with its network interface and restarts. The network interface watchdog mechanism is only enabled on a PDU that discovers an active network inte rf ac e co nn ec tio n at start-up. T his allows guest PDUs in a Network Port Sharing chain to function normally without rebooting every 9.5 minutes.

Resetting the network timer

To ensure that the Rack PDU does not restart if the network is quiet for 9.5 minutes, the Rack PDU attempt s to contact the default gateway every 4.5 minutes. If the gateway is present, it responds to the Rack PDU, and the response restarts the 9.5-minute timer. If your application does not require or have a gateway, specify the IP address of a computer that is running on the network and is on the same subnet. The network traffic of that computer will restart the 9.5-minute time frequently enough to prevent the Rack PDU from restarting.
Switched Rack PDU AP89XX User Guide2

Network Port Sharing (NPS)

About the Network Port Sharing Feature

You can use the Network Port Sharing feature to view the status of and configure and manage up to four Rack PDUs using only one network connection. This is made possible by connecting the Rack PDUs via the In and Out ports on the Rack PDU front panel.
NOTE: All Rack PDUs in the group must be using the same Rack PDU firmware revision, 5.1.5 or later (excluding v6.0.5 EnergyWise), in order to support the Network Port Sharing Feature.

Display ID

The display ID is a number, 1 to 4, used to un iquely identify the Rack PDUs in a group. After two or more Rack PDUs are connected to one another in an NPS group, they can be identified on the various interfaces by the use of this "Display ID". This Display ID is viewable in the top left corner of the display. Alternatively, a larger Display ID “shadow” can be enabled on the LCD by selecting the Display Settings > Display ID > Show option on the LCD keypad.

Installation Instructions

Connect up to four Rack PDUs via the In and Out ports on the Rack PDU. Insert an RJ45 terminator (in cluded) in the unused In/Out ports on each end of the chain.
NOTE: Failure to use terminators may cause a loss of communication on the Rack PDUs. NOTE: To reduce the possibility of communication issues, the maximum total length of cabling connecting
Rack PDUs in a group should not exceed 10 meters. All Rack PDUs in a NPS group should reside in the same rack enclosure.
Connect the "Network" port of one of the grouped Rack PDUs to a network hub or switch. This unit will be the Host for the Rack PDU group. Guest PDU data will be viewable on the Host PDU. Set up network functionality for this Host Rack PDU as specified in the Establish Network Settings section. The Host will automatically discover any Guest PDUs connected via In/Out ports. The Rack PDU group is now available via the Host's IP address.
NOTE: Only one Rack PDU in an NPS group is allowed to be the host. If two host Rack PDUs are connected together, one will automatically be chosen to be the single host for the NPS group. The user also has the option to select a particular guest to be the host as long as that guest has an active network link.
The host Rack PDU supports many features that are not supported b y NPS guest s. These includ e, but are not limited to:
• SNMP rPDU2Group OIDs
• EnergyWise support
• Initiating AOS/App firmware updates for guest Rack PDUs
• Time synchronization for guest Rack PDUs
• Data logging for the guest Rack PDUs

Specific assignment of Display IDs

Follow the instructions below before powering up any of the Rack PDUs in the group. If it is desired to have a specific assignment of Display IDs, this can be achieved by powering up the units for
the first time in the desired order, 1 to 4. For example, before powering up any of the Rack PDUs connected in a group, determine the Display ID order that you wou ld like. Then, first power up the unit that you would like to have Display ID 1. After that unit has initialized and the LCD has started displaying its screens, power on the unit that you would like to have Display ID 2. Continue in the same way for units 3 and 4, if applicable for your setup.
NOTE: The Display ID can be configured from the Web User Interface via the "Configuration > RPDU > Device > Display ID" field. The Display ID can also be configured from the CLI interface via the dispID command.
3Switched Rack PDU AP89XX User Guide

Firmware Upgrade with NPS

At start-up and routinely during operation, the rPDU2g NPS host compares its own AOS and application versions with the versions found on each guest. In the event of a version difference, the host copies its AOS and then its application to the non-complying guests via the NPS chain.
NOTE: Automatic firmware upgrade is only available for Rack PDUs running AOS version v6.1.3 or later as this functionality requires resident firmware support in the NPS host and guest s. This functionality requires that any replacement Rack PDUs also be running AOS version v6.1.3 or later to maintain correct operation of the NPS chain.

RF Tag

The Rack PDU supports the RF Code sensor tag for Schneider Electric Rack PDUs. The tag enables data center managers to wirelessly monitor power consumption and utilization with the enterprise-class Asset RF Code Zone Manager. The Zone Manager middleware consumes information about power attribute values as reported by the Rack PDU. The RF Code sensor tag for Schneider Electric works in concert with the Rack PDUs with firmware v6.1.0 or later. To implement an RF Code sensor tag solution, plug the tag into the RJ-12 socket labeled Serial Port. Scroll the LCD menu to highlight the RF Code Control entry, press the Select button. Press the select button again to enable. The Rack PDU will immediately reboot and start serial communication with the tag. When an NPS guest RF tag is removed, the NPS host will signal an alarm. In order to clear this alarm, one must replace the tag and disable the tag in the LCD menu. Then the error will be cleared and the NPS guest will auto reboot.
The RF Tag reports per-phase load voltage/amperage/power readings every 10 minutes and device power/ energy use, per-outlet watt-hour/switch state/RMS current, and phase outlet voltages/bank overload state readings every hour. Outlet an d bank readings are Rack PDU model dependent as all models do not support monitoring. The complete RF solution requires an RF Code reader, an RF Code Zone Manager, or RF Code Asset Manager. For more information see: www.rfcode.com.

EnergyWise

The Rack PDU has the capability of becoming a Cisco EnergyWise Entity. This entity reports power usage and alarms in the EnergyWise Domain.
To exercise this capability, plug the Rack PDU network port into a Cisco switch/router that supports the EnergyWise Domain. Log into the Web User Interface of the Rack PDU and navigate to the Configuration/ RPDU/EnergyWise web page. Click on the enable radio button to initiate the task. The task will generate unique parent and children names, default roles, keywords and importance values that comply with EnergyWise requirements. Customization of the aforementioned is supported by clicking on any of the underlined entities to navigate to a configuration web page.
The EnergyWise port, domain name and shared secret may also be modified, but must be coord inated with the same parameters in the Cisco gear.
The Rack PDU implementation supports a single p arent, multiple children h ierarchy. The parent may exist as a standalone Rack PDU or as the host Rack PDU for an NPS chain of Rack PDUs. The parent usage reports the power consumed by the Rack PDUs themselves, including any NPS guest Rack PDUs. The children report either inlet power or, in the case of monitored outlets, the power consumed at the outlet. Both parent and children report a usage level (0-10 scale). The parent and inlet usage are always reported as 10 or “ On”. In the case of switched outlets the actual state of the switch is reported and m ay also be altered by the Cisco device.
When the parent is the host Rack PDU of an NPS chain, the reported parent power is the sum of the parent and each of the NPS guests. The parent also reports an inlet entity for itself and for each guest as well as an outlet entity for each host outlet and each outlet of every guest.
The remaining configurable items are string variables that ma y be modified as needed and are ret ained acro ss power cycles or reboots.
Switched Rack PDU AP89XX User Guide4

EnergyWise and NPS

RPDUs support Cisco EnergyWise with Rack PDU v6.0.9 firmware or later. The Rack PDU EnergyWise application generates a family tree at startup. This tree is reported to Cisco hardware during the discovery process.
For an initial installation, either establish the NPS chain and enable EnergyWise on the host or enable EnergyWise on the host and then disable and re-enable EnergyWise after the NPS communication is established. Clearly, the first option is simpler.
For Rack PDU replacement, the following procedure should be followed. Power down the Rack PDU – any children associated with this Rack PDU will report EW levels and usage as zero. On the Status/Rack PDU/ Group web page, there should be a check box to allow the user to remove the now non-functio ning Rack PDU from the NPS chain. Once removed from the chain, any children associated with that Rack PDU will report “.0.” in the display identifier portion of the EW name field. At this time, one can replace the Rack PDU with another of the same model and expect the EnergyWise to function properly again once communication is established. If for some reason the replacement model is different, EnergyWise will have to be disabled and re-enabled after NPS communication is established, to upda te the family tree and the order of data reported. For more information see: www.cisco.com/en/us/products/ps10195/index.html.

Getting Started

To start using the Rack PDU:
1. Install the Rack PDU using the Rack Power Distribution Unit Installation Instructions that were shipped with your Rack PDU.
2. Apply power and connect to your network. Follow the directions in the Rack Power Distribution Unit Installation Instructions.
3. Establish network settings
4. Begin using the Rack PDU by way of one of the following:
– “Web User Interface” on page 88 – “Command Line Interface” on page 17 – “Rack PDU Front Panel” on page 10
5Switched Rack PDU AP89XX User Guide

Establish Network Settings

IPv4 initial setup

You must define three TCP/IP settings for the Rack PDU before it can operate on the network:
• The IP address of the Rack PDU
• The subnet mask of the Rack PDU
• The IP address of the default gateway (only needed if you are going off segment) NOTE: If a default gateway is unavailable, use the IP address of a computer tha t is located on the
same subnet as the Rack PDU and is usually running. The Rack PDU used the default ga teway to test the network when traffic is very light.
NOTE: Do NOT use the loopback address (127.0.0.1) as the default gateway. Doing so disables the card. To enable again, you must log on using a serial connection and reset the TCP/IP settings to their defaults.
For detailed information on how to use a DHCP server to configure the TCP/IP settings at an Rack PDU, see.“DHCP response options” on page 119

IPv6 initial setup

IPv6 network configuration provides flexibility to accommodate your requirements. IPv6 can be used anywhere an IP address is entered on this interface. You can configure manually, automatically, or using DHCP.

TCP/IP configuration methods

Use one of the following methods to define the TCP/IP settings needed by the Rack PDU:
• “Device IP Configuration Wizard” on page 148
• “DHCP and BOOTP configuration”
• “Command Line Interface” on page 17

.ini file utility

You can use the .ini file export utility to export .ini file settings from configured Rack PDUs to one or more unconfigured Rack PDUs. For more information, see “Creating and importing settings with the config file” on page 136.

DHCP and BOOTP configuration

The default TCP/IP configuration setting, DHCP, assumes that a properly configured DHCP server is available to provide TCP/IP settings to Rack PDU. You can also configure the setting for BOOTP.
A user configuration (INI) file can function as a BOOTP or DHCP boot file. For more information, see “Creating and importing settings with the config file” on page 136.
If neither of these servers is available, see “Device IP Configuration Wizard” on page 148 or “Device IP Configuration Wizard” on page 148.
BOOTP: For the Rack PDU to use a BOOTP server to configure its TCP/IP settings, it must find a properly
configured RFC951-compliant BOOTP server. In the BOOTPTAB file of the BOOTP server, enter the Rack PDU’s MAC address, IP address, subnet mask,
and default gateway, and, optionally, a bootup file name. Look for the MAC address on the bottom of the Rack PDU or on the Quality Assurance slip included in the package.
When the Rack PDU reboots, the BOOTP server provides it with the TCP/IP settings.
• If you specified a bootup file name, the Rack PDU attempts to transfer that file from the BOOTP server using TFTP or FTP. The Rack PDU assumes all settings specified in the bootup file.
• If you did not specify a bootup file name, you can configure the other settings of the Rack PDU remotely through its “Web User Interface” on page 88 or “Command Line Interface” on page 17; the user name and password are both apc, by default. To create a bootup file, see your BOOTP server documentation.
Switched Rack PDU AP89XX User Guide6
DHCP: You can use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the
Rack PDU. This section summarizes the Rack PDU’s communication with a DHCP server. For more detail about how a
DHCP server can configure the network settings for a Rack PDU, see “DHCP response options” on page 119.
1. The Rack PDU sends out a DHCP request that uses the following to identify itself: – A Vendor Class Id entifier (APC by default) – A Client Identifier (by default, the MAC address of the Rack PDU) – A User Class Identifier (by default, the identification of the app lication firmware inst alled on the
Rack PDU)
– A Host Name (by default, apcXXYYZZ with XXYYZZ being the last six digits of the PDU). This
is known as DHCP Option 12.
2. A properly configured DHCP server responds with a DHCP offer that includes a ll the settings that
the Rack PDU needs for network communication. The DHCP offer also includes the Vendor Specific Information option (DHCP option 43). The Rack PDU can be configured to ignore DHCP offers that do not encapsulate the APC cookie in DHCP option 43 using the following hexadecimal format. (The Rack PDU does not requ ire this co ok ie by de fa u lt.)
Option 43 = 01 04 31 41 50 43
Where:
– The first byte (01) is the code. – The second byte (04) is the length. – The remaining bytes (31 41 50 43) are the APC cookie.
See your DHCP server documentation to add code to the Vendor Specific Information option. NOTE: By selecting the Require vendor specific cookie to accept DHCP Address check box in the Web User Interface, you can require the DHCP server to provide an “APC” cookie, which supplies information to the Rack PDU.

Network Management with Other Applications

These applications and utilities work with a Rack PDU which is connected to the network.
• PowerNet
SETs and GETs and use SNMP traps
• StruxureWare — Provide enterprise-level power management and management of agents, Rack
PDUs, and environmental monitors.
• Device IP Configuration Utility — Configure the basic settings of one or more Rack PDU over the
network, see “Device IP Configuration Utility”
• Security Wizard — Create components neede d to help with security for the Rack PDUs wh en you
are using Secure Sockets Layer (SSL) and related protocols and encryption routines.
®
Management Information Base (MIB) with a standard MIB bro wser — Pe rform SNMP
7Switched Rack PDU AP89XX User Guide

Command Line Interface (CLI)

1. Log on to the CLI. See “Log on to the CLI” on page 17.
2. Contact your network administrator to obtain the IP address, subnet mask, and default gateway for the Rack PDU.
3. Use these three commands to configure network settings. (Text in italics indicates a variable.)
tcpip -i yourIPaddress tcpip -s yourSubnetMask tcpip -g yourDefaultGateway
For each variable, type a numeric value that has the format xxx.xxx.xxx.xxx. For example, to set a system IP address of 156.205.14.141, type the following command and press E
tcpip -i 156.205.14.141
4. Type exit. The Rack PDU restarts to apply the changes.
NTER:
Switched Rack PDU AP89XX User Guide8

Recovering from a Lost Password

You can use a local computer (a computer that connects to the Rack PDU or other device through the serial port) to access the Command Line Interface.
1. Select a serial port at the local computer, and disable any service that uses that port. NOTE: If your computer does not have a serial port, you will need to acquire a machine that has one or purchase an adapter to fit your machine.
2. Connect the serial cable (Schneider Electric part number 940-0144A) to the selected port on the computer and to the Serial port at the Rack PDU.
3. Run a terminal program (such as Tera Term for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
4. Press
5. Press the Reset button. The Status LED will flash alternately orange and green within 5 to 7
6. Press
7. At the Command Line Interface, use the following commands to change the Password setting,
ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to
display the
– The serial port is not in use by another application. – The terminal settings are correct as specified in step 3. – The correct cable is being used as specified in step 2.
seconds of pressing the Reset button. Press the Reset button a second time immediately when the LED begins flashing to reset the user name and password to their defaults temporarily.
default, apc the
User Name prompt is re-displayed, you must repeat step 5 and log on again.)
which is apc at this stage:
User Name prompt, verify the following:
ENTER, repeatedly if necessary, to display the User Name prompt again, then use the
, for the user name and passwo rd. (If you t ake lo nger tha n 30 second s to log on af te r
®
or HyperTerminal®) and configure the selected port
user -n <user name> -pw <user password>
For example, to change the Super User password to XYZ type:
user -n apc -cp apc -pw XYZ
8. Type quit or exit to log off, reconnect any serial cable you disconnected, and restart any service you disabled.
9Switched Rack PDU AP89XX User Guide

Rack PDU Front Panel

Serial
In
Out
USB
Reset
Main
Menu
Select
Scroll
- Warning
- OK
- Overload
pdu0713a
MA
apc
MA
apc12345678
MA
pdu0714a
MA
Pha
Ne
MA
Temp/ Hum idi ty
SELECT
0
0
0
4.37 kW
MAIN
NOTE: Your Rack PDU is configured so the display backlight turns off after 10 minutes of inactivity. The backlight can be turned on by depressing any button below the display.
Item Function
Network
x
pdu0711a
Display
Main Menu button
Scroll button
Select button
Shows information about the Rack PDU. In normal operation, input voltage, current, and power refreshes every five seconds. To reverse the text, select Display settings, scroll to Orientation and press Select.
Device N
37.8%RH
24.5ºC
12345678
ame
SELECT
0
IN
0
24.5ºC
SELECT
37.8%RH
IN
Device Name
Press to view the Rack PDU electrical input.
SELECT
0
0
IN
1.23 kW
Press once to display the menu. Press additional times to highlight the desired menu option.
se Info
Outlet Current
SELECT
twork
IN
T em p/Humidity
With a menu option highlighted, press the Select button to display Rack PDU information. (Network information is shown
SELECT
at right.)
IPv4 Address
IN
10.234.576.89
pdu0712a
pdu0724a
pdu0715a
Switched Rack PDU AP89XX User Guide10
Serial
In
Out
Temp/ Hum idi ty
USB
Reset
Main
Menu
Select
Scroll
- Warning
- OK
- Overload
SELECT
0
0
0
4.37 kW
MAIN
Network
x
Item Function
Load Indicator LEDs Indicates the status of the Rack PDU load. See “Load Indicator
LED” on page 12.
Temp/Humidity port Port for connecting an optional Schneider Electric Temperature
Sensor (AP9335T) or an optional Schneider Electric Temperature/Humidity Sensor (AP9335TH).
pdu0740a
In and Out ports
USB port
Outlet status LED Illuminates green when the outlet is energized. (Eac h outlet has
For use with the Network Port Sharing feature. For use with a flash drive for firmware upgrades - 5V @ 100ma.
an outlet LED.)
RJ-12 Serial Port Port for connecting the Rack PDU to a terminal emulator
program for local access to the Command Line Interface. Use the supplied serial cable (Schneider Electric part number 940-0144A).
10/100 Base-T Connector
Network status LED
10/100 LED
Reset button
Connects the Rack PDU to the network. See “Network Status LED” on page 12. See “10/100 LED” on page 12. Resets the Rack PDU without affecting the outlet status.
11Switched Rack PDU AP89XX User Guide

Network Status LED

Condition Description
One of the following situations exists:
Off
Solid Green The Rack PDU has valid TCP/IP settings.
•The Rack PDU is not receiving input power.
•The Rack PDU is not operating properly. It may need to be repaired or replaced. Contact Customer Support.
Solid Orange Flashing Green The Rack PDU does not have valid
A hardware failure has been detected in the Rack PDU. Contact Customer Support.
TCP/IP settings.
Flashing Orange The Rack PDU is making BOOTP requests. Alternately flashing Green
and Orange
1. If you do not use a BOOTP or DHCP server, see “Establish Network Settings” on page 6 to configure the TCP/IP settings of the Rack PDU.
2. To use a DHCP server, see “TCP/IP and Communication Settings” on page 118.
If the LED is flashing slowly, the Rack PDU is making DHCP If the LED is flashing rapidly, the Rack PDU is starting up.
2
requests1.

10/100 LED

Condition Description
One or more of the following situations exists:
•The Rack PDU is not receiving input power.
•The cable that connects the Rack PDU to the network is disconnected or
Off
defective
•The device that connects the Rack PDU to the network is turned off.
•The Rack PDU itself is not o perating pr operly. It may need to be repaired or replaced. Contact Customer Support.
Solid Green
The Rack PDU is connected to a network operating at 10 Me gabits per second
(Mbps). Solid Orange The Rack PDU is connected to a network operating at 100 Mbps. Flashing Green The Rack PDU is receiving or transmitting data packets at 10 Mbps. Flashing Orange The Rack PDU is receiving or transmitting data packets at 100 Mbps.

Load Indicator LED

The load indicator LED identifies near-overload (warning) and overload (critical) conditions for the Rack PDU.
Condition Description
Solid Green OK. No near-overload (warning) or overload (critical) alarms are present. Solid Yellow Flashing Red Overload. At least one overload (critical) alarm is present.
Warning. At least one near-overloa d (warning) alarm is present, but no
overload (critical) alarms are present.
Switched Rack PDU AP89XX User Guide12

Example 1

1. 14.1 A
2. 14.2 A
3. 14.3 A
SELECTMAIN
pdu0719a
Phase 2
208.0 V
14.2 A
1.23 kW
SELECTMAIN
Phase 3
208.0 V
14.3 A
1.23 kW
SELECTMAIN
SELECTMAIN
1
phase
Phase Info
Phase
Outlets?
Y e s
No
Y e s
SELECTMAIN
Phase 1
208.0 V
14.1 A
1.23 kW
Input
208.0 V
14.1 A
SELECTMAIN
1.23 kW
pdu0780a
Temp/Humidity
Software Info
SKU/Serial #
SELECTMAIN
Phase Info
Display Settin gs
Network
SKU/SN
RF Code Control
RF Code
Log to Fla sh
NOTE: If there are more selections available than can be shown on the display, they will appear on multiple pages. Multiple pages are indicated by the arrow in the corner of the screen.
NOTE: “T emp/Humidity” only appears when an AP9335T or AP9335TH sensor is attached.
Display Tree
Main
Menu
Phase
Info
T/H
Network
SW Info
Disp
Settings
USB
Phase Current
Phase to
No
Voltage
L1 - 2: 208V L2 - 3: 208V L3 -1: 208 V
13Switched Rack PDU AP89XX User Guide

Example 2

pdu0710c
IPv4 Address
255.255.255.255
SELECTMAIN
Network
Sensor
Temp: 45.6ºC
Hum: 37.8%
SELECTMAIN SELECTMAIN
Model
AP8XXX Serial Nu m ber ZAxxxxxxxxxx
SELECTMAIN
APP
Enabled
SELECTMAIN
Press “Select”
WILL REBOOT
IPv6 Address 1234:5678:9012 3456:7890:1234
5678:9012
SELECTMAIN
00 00 00 00 00 00
SELECTMAIN
LCD Contrast
5 / 9
Press “Select”
SELECTMAIN
MAIN
LCD Backlight
Auto-On
to switch
MAIN
Normal
to switch
Hide
SELECTMAIN
to switchto adjust
No
Yes
each IPv6 addr)
SELECTMAIN
Disp. Settings
SKU/SN
SW Info
T/H
SELECTMAIN
XX previous records
Display Tree
RF Code
Log to Flash
AOS
RF Code - Console
6.5.6
6.5.6
IPv6 Address
MAC Address
(scrolls through
LCD Orientation
Press “Select”
SELECT
Press “Select”
SELECT
Network Port
Sharing Group
Display ID
Press “Select”
Log to Fla sh
Press <select> to start export
Switched Rack PDU AP89XX User Guide14

Example 3

Main
Menu
pdu072 0a
2 bank
Yes
N o
S
E
L
E
C
T
M
A
I
N
1
.
2
3
k
W
2
1
Sensor
N o
S
E
L
E
C
T
M
A
I
N
1
.
2
3
k
W
2
1
3
3 bank
Yes
N o
4 bank
Yes
N o
5 bank
Yes
N o
S
E
L
E
C
T
M
A
I
N
1
.
2
3
k
W
2
1
4
3
S
E
L
E
C
T
M
A
I
N
1
.
2
3
k
W
1
3
5
4
2
S
E
L
E
C
T
M
A
I
N
1
.
2
3
k
W
1
3
5
4
2
6
6 bank
Yes
S
E
L
E
C
T
M
A
I
N
0
0
1
.
2
3
k
W
MAIN
Monitor Status
Yes
0
.
2
4
5
º
C
.
7
3
8
%
H
R
c
e
a
m
v
i
N
e
D
c
1
a
p
M
A
N
I
e 8
7
6
4
5
2
3
T
C
E
L
E
S
15Switched Rack PDU AP89XX User Guide

Example 4

S
E
L
E
C
T
M
A
I
N
0
2
4
.
5
º
C
3
7
.
8
%
R
H
D
e
v
i
c
e
N
a
m
e
a
p
c
1
2
3
4
5
6
7
8
S
E
L
E
C
T
M
A
I
N
1
.
2
3
k
W
1
3
5
4
2
6
S
E
L
E
C
T
M
A
I
N
0
0
1
.
2
3
k
W
S
E
L
E
C
T
M
A
I
N
5
.
6
7
k
W
1
3
5
4
2
6
S
E
L
E
C
T
M
A
I
N
5
9
.
0
º
C
3
0
.
0
%
R
H
D
e
v
i
c
e
N
a
m
e
a
p
c
1
2
3
4
5
6
7
8
Normal Status Indicator
Reading
Warning (Near O verload) Indicator
Critical (Overload) Indicator
Normal Status Indicator
Threshold Violation Indicator
V
Monitor Status Indicators
NOTE: Both warning and critical temperature threshold violations will display as “High Temp”. Both warning
and critical humidity threshold violations will display as “Low Humidity”. The icon in the upper left corner of the display interface is the indicator of either a warning or critical event. You must have installed an optional APC by Schneider Electric Temperature/Humidity Sensor (AP9335TH) to your Rack PDU in order to use the Humidity related status screens.
Device Load
Bank Load Graphs (No Indicator = No rmal Status)
Warning
7
.
8
9
k
W
1 2 3
4 5 6
M
N
A
I
S
E
L
E
C
T
Most Critical Sensor Status
p
e
h
T
g
m
i
H
Critical Threshold
iolation
Indicator
D a
p
A
M
m
i
u
d
y
i
H
t
L
w
o
.
C
2
5
4
º
H
0
.
1
0
R
%
N
a
e
m
e
c
v
i
e
6
7
8
4
5
3
2
c
1
N
I
C
L
T
E
E
S
pdu072 1a
Switched Rack PDU AP89XX User Guide16

Command Line Interface

About the Command Line Interface (CLI)

You can use the Command Line In terface to view the status of and configure a nd manag e the Rack PDU ( and any connected Rack PDUs, if using the Network Port Sharing Feature). In addition, the Command Line Interface enables you to create scripts for automated operation. You can configure all parameters of a Rack PDU (including those for which there are not specific CLI commands) by using the CLI to transfer an INI file to the Rack PDU. The CLI uses XMODEM to perform the transfer, however, you cannot read the current INI file through XMODEM.

Log on to the CLI

To access the Command Line Interface, you can use either a local (serial) connection or a remote (Telnet or SSH) connection with a computer on the same network as the Rack PDU.

Remote access to the Command Line Interface

You can choose to access the Command Line Interface through Telnet and/or SSH. Telnet is enabled by default. You do not have to enable either.
To enable or disable these access methods, use the Web User Interface. On the Configuration tab, select
Network from the menu to open the Console Access page. Click to check the desired Enable box. Click
Apply to save your changes or Cancel to leave the page.
17Switched Rack PDU AP89XX User Guide

Telnet for basic access

Telnet provides the basic security of authentication by user name and password, but not the high-security benefits of encryption.
To use Telnet to access the Command Line Interface:
1. From a computer that has access to the network on which the Rack PDU is installed, at a command prompt, type telnet and the IP address for the Rack PDU (for example, telnet
139.225.6.133, when the Rack PDU uses the default Telnet port of 23), and press If the Rack PDU uses a non-default port number (from 5000 to 327 68 ), you must in clu de a colon
or a space, depending on your Telnet client, between the IP address (or DNS name) and the port number. (These are commands for general usage: Some clients do not allow you to specify the port as an argument and some types of Linux might want extra commands).
2. Enter the user name and password (by default, apc and apc for the Super User). If you cannot remember your user name or p assword, see “Recover ing from a Lost Password” on
page 9.
ENTER.

SSH for high-security access

If you use the high security of SSL for the Web interface, use SSH for access to the Command Line Interface. SSH encrypts user names, passwords, and transmitted data. The interface, user accounts, and user access rights are the same whether you access the Command Line Interface through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client program installed on your computer.

Local access to the Command Line Interface

For local access, use a computer that connects to the Rack PDU through the serial port to access the Command Line Interface:
1. Select a serial port at the computer and disable any service that uses that port.
2. Connect the serial cable (Schneider Electric part number 940-0144A) from the selected serial port on the computer to the Serial port on the Rack PDU.
3. Run a terminal program (e.g., Tera Term or HyperTerminal) and configure the selected port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
4. Press
ENTER. It may take mu ltiple (up to thr ee) attempt s to get a prompt to a ppear. At the prompt,
enter your user name and password.
Switched Rack PDU AP89XX User Guide18

About the Main Screen

Schneider Electric Network Management Card AOS vx.x.x (c) Copyright 2018 All Rights Reserved RPDU 2g vx.x.x
-------------------------------------------------------------------------­Name : Test Lab Date : 5/30/2018 Contact : Don Adams Time : 5:58:30 Location : Building 3 User : Administrator Up Time : 0 Days, 21 Hours, 21 Minutes Stat : P+ N4+ N6+ A+
Type ? For command listing Use tcpip for IP address (-i), subnet (-s), and gateway (-g) APC>
Following is an example of the main screen, which is disp lay ed when you log on to the Com m a nd Line Interface of a Rack PDU.
• Two fields identify the operating system (AOS) and application (APP) firmware versions. The application firmware name identifies the type of device that connects to the network. In the example above, the application firmware for the Rack PDU is displayed.
Network Management Card AOS vx.x.x RPDU 2g vx.x.x
• Three fields identify the system name, contact person, and location of the Rack PDU.
Name : Test Lab Contact : Don Adams Location : Building 3
• An Up Time field reports how long the Rack PDU Management Interface has been running since it was last turned on or reset.
Up Time: 0 Days, 21 Hours, 21 Minutes
• Two fields identify when you logged in, by date and time.
Date: 05/30/2018 Time: 5:58:30
• The
• A
User field identifies whether you logged in through th e Super User , Administrator or Device
Manager account.
User: Administrator
Stat field reports the Rack PDU status.
Stat:P+ N4+ N6+ A+
P+ The APC operating system (AOS) is functioning properly.
IPv4 only
N+ N+ N4+ N6+ The network is functioning properly. N? N6? N4? N6? A BOOTP request cycle is in progress. N– N6- N4- N6- The Rack PDU failed to connect to the network.
IPv6 only
IPv4 and IPv6*
Description
N! N6! N4! N6! Another device is using the Rack PDU IP address. * The N4 and N6 values can be different from one another: you could, for
example, have N4- N6+.
19Switched Rack PDU AP89XX User Guide
A+ The application is functioning properly. A– The application has a bad checksum. A? The application is initializing. A! The application is not compatible with the AOS.
NOTE: If P+ is not displayed, contact the Schneider Electric Customer Care Center.

Using the CLI

At the Command Line Interface, you can use comma nds to configure the Rack PDU. To use a command, type the command and press Options are case-sensitive.
While using the Command Line Interface, you can also do the following:
• Type ? and press
• To obtain information about the purpose and syntax of a specified command, type the command, a space, and ? or the word help. For example, to view RADIUS configuration options, type:
radius ?
or
radius help
• Press the the
UP and DOWN arrow keys to scroll through a list of up to ten previous c omm an d s.
• Type at least on e letter of a command and press the commands that match the text you typed in the command line.
• Type exit or quit to close the connection to the Command Line Interface.
ENTER. Commands and arguments are valid in lowercase, upperca se, or mixed case.
ENTER to view a list of available commands, based on your account type.
UP arrow key to view the command that was entered most recently in th e session. Use
TAB key to scroll through a list of valid
Switched Rack PDU AP89XX User Guide20

Command Syntax

Item Description
- Options are preceded by a hyphen. < >
[ ]
|
Example of a command that supports multiple options:
ftp [-p <port number>] [-S <enable | disable>]
In this example, the ftp command accepts the option -p, which defines the port number, and the option -S, which enables or disables the FTP feature.
To change the FTP port number to 5010, and enable FTP:
Definitions of options are enclosed in angle brackets. For example:
-dp <device password> If a command accepts multiple options or an option accepts mutually
exclusive arguments, the values may be enclosed in brackets. A vertical line between items enclosed in brackets or angle bracket s indicates
that the items are mutually exclusive. You must use one of the items.
1. Type the ftp command, the port option, and the argument 5010:
ftp -p 5010
2. After the first command succeeds, type the ftp command, the enable/disable option, and the
enable selection: ftp -S enable
Example of a command that accepts mutually exclusive arguments for an option:
alarmcount -p [all | warning | critical]
In this example, the option -p accepts only three arguments: all, warning, or critical. For example, to view the number of active critical alarms, type:
alarmcount -p critical
The command will fail if you type an argument that is not specified.
21Switched Rack PDU AP89XX User Guide

Command Response Codes

The command response codes enable scripted operations to detect error conditions reliably without having to match error message text:
The CLI reports all command operations with the following format:
E [0-9] [0-9] [0-9] : Error message
Code Message Code Message
E000 Success E200 Input Error E001 Successfully Issued E201 No Response E002 Reboot required for change to take effect E202 User already exists E100 Command failed E203 User does not exist E101 Command not found E204 User does not have access to this
command
E102 Parameter Error E205 Exceeds Maximum Users E103 Command Line Error E206 Invalid value E104 User Level Denial E207 Outlet Command Error: Device not
initialized.
E105 Command Prefill E208 Outlet Command Error: Previous command
is pending.
E106 Data Not Available E209 Outlet Command Error: Database rejected
request.
E107 Serial communication with the
has been lost
Rack PDU
E210 Outlet Command Error: Outlet restricted.
Switched Rack PDU AP89XX User Guide22
Loading...
+ 142 hidden pages