The Agilent E3632A isa high performance 120 watt-dualrange DC powersupply withGPIB and RS-232 interfaces. The combination of bench-top and system features in thispower supply provides versatile solutions for your design and test requirements.
Convenient bench-top features
•Dual range
•Easy-to-use knob controlsettings
•Highly visible vacuum-fluorescent display meters
•High accuracy andhigh resolution
•Remote voltage sensing
•Overvoltage and overcurrent protection
•Output on/off
•Excellent load and line regulation and low ripple and noise
•Operating states storage
•Portable, ruggedized case with non-skid feet
Flexible system features
•GPIB (IEEE-488) and RS-232 interfaces are standard
1 15V/7A range selection key Selects the 15V/7A range and allows the full rated output
to 15V/7A.
2 30V/4A range selection key Selects the 30V/4A range and allows the full rated output
to 30V/4A.
3 Overvoltage protection key Enables or disables the overvoltage protection function,
sets trip voltage level, and clears the overvoltage condition.
4 Overcurrent protection key Enables or disables the overcurrent protection function,
sets trip current level, and clears the overcurrent condition.
5 Display limit key Shows voltage and current limit values on the display and allows
knob adjustment for setting limit values.
6 Recall operating state key Recalls a previously stored operating state from location
‘‘1’’, ‘‘2’’, or ‘‘3’’.
7 Store operating state / Local key1 Stores an operating state in location ‘‘1’’, ‘‘2’’, or
‘‘3’’ / or returns the power supply to local mode from remote interface mode.
8 Error / Calibrate key2 Displays error codes generated during operation, self-test and
calibration / or enables calibration mode (the power supply must be unsecured before
performing calibration). See Service Guide for more details on calibration.
9 I/O Configuration / Secure key3 Configures the power supply for remote interfaces
/ or secure or unsecure the power supply for calibration. See Service Guide for more
details on how to secure or unsecure the power supply.
10 Output On/Off key Enables or disables the power supply output. This key toggles
between on and off.
11 Control knob Increases or decreases the value of the blinking digit by turning
clockwise or counter clockwise.
12 Resolution selection keys Move the blinking digit to the right or left.
13 Voltage/current adjust selection key Selects the knob control function for voltage
or current adjustment.
1
The key can be used as the ‘‘Local’’ key when the power supplyis in the remote
interface mode.
2
You can enable the ‘‘calibration mode’’ by holding down this key when you turnon
the power supply.
3
You can use it as the‘‘Secure’’ or ‘‘Unsecure’’ key when the power supply is in the
calibration mode.
3
Front-Panel Voltage and Current Limit Settings
You can set the voltage and current limit values from the front panel using the
following method.
Use the voltage/current adjust selection key, the resolution selection keys, and
the control knob to change the voltage and current limit values.
1 Select the desired range using the range selection keys after turning on the power
supply.
2 Press the key to show the limit values on the display.
3 Move the blinking digit to the appropriate position using the resolution selection keys
and change the blinking digit value to the desired voltage limit by turning the control
knob. If the display limit times out, press the
4 Set the knob to current control mode using the voltage/current adjust selection key.
5 Move the blinking digit to the appropriate position using the resolution selection keys
and change the blinking digit value to the desired current limit by turning the control
knob.
6 Press the key to enable the output. After about 5 seconds, the
display will go to output monitoring mode automatically to display the voltage and
current at the output or the display will go to output monitoring mode immediately by
pressing the
Display Limit
Output On/Off
Output On/Off
key again.
Display Limit
key again.
Note
All front panelkeys andcontrols canbedisabled withremote interface commands. The Agilent E3632A must be in "Local" mode for the front panelkeys and controls to function.
4
Display Annunciators
AdrsPower supply is addressed to listen or talk over a remote interface.
RmtPower supply is in remote interface mode.
15VShows the 15V/7A range is selected.
30VShows the 30V/4A range is selected.
OVPThe overvoltage protection function is enabled when the annunciator
OCPThe overcurrent protection function is enabled when the annunciator
CALThe power supply is in calibration mode.
LimitThe display shows the limit values of voltage and current.
ERRORHardware or remote interface command errors are detected and the error
OFFThe output of the power supply is disabled (See page 52 for more
UnregThe output of the power supply is unregulated (output is neither CV
CVThe power supply is in constant voltage mode.
CCThe power supply is in constant current mode.
turns on or the overvoltage protection circuit has caused the power
supply to shutdown when the annunciator blinks.
turns on or the overcurrent protection circuit has caused the power
supply to shutdown when the annunciator blinks.
bit has not been cleared.
information).
nor CC).
To review the display annunciators, hold down key as you
Display Limit
turn on the power supply.
5
The Rear Panel at a Glance
1 Power-line voltage setting
2 Power-line fuse-holder assembly
3 AC inlet
Use the front-panel key to:
• Select the GPIB or RS-232 interface (see chapter 3).
• Set the GPIB bus address (see chapter 3).
• Set the RS-232 baud rate and parity (see chapter 3).
supply. This chapter also provides instructions for checkingyour power supply, connecting to ac power, and selecting power-line voltage.
Initial Operation
outputs and properly responds to operation from the front panel.
Front-Panel Operation
keys andhow they are used to operate the power supply from the front panel.This chapter also shows how to configure the power supply for the remote interface and gives a brief introduction to the calibrationfeatures.
Remote Interface Reference
you program the power supply over the remote interface. This chapter also explains how to program for status reporting.
Error Messages
working with thepower supply. Each listing contains information to help you diagnose and solve the problem.
Application Programs
to help you develop programs for your application.
Tut or ia l
gives specific details on the operation and use of the Agilent E3632Apower supply.
Specifications
Chapter 7 describes basicoperation of linear power supplies and
Chapter 1 containsa generaldescription of your power
Chapter 2 ensures that the power supply develops its rated
Chapter 3 describes in detailthe use of front-panel
Chapter 4 contains reference information to help
Chapter 5 lists the error messages that may appear as you are
Chapter 6 contains some remote interface applications
Chapter 8 lists the power supply’s specifications.
If you havequestions relating to the operation of thepowersupply,call
1-800-829-4444
Technologies SalesOffice.
If yourAgilent E3632A fails within one year of purchase,Agilent willrepair or replaceit free of charge. Call1-800-258-5165("ExpressExchange") in theUnited States, or contact yournearest Agilent Technologies SalesOffice.
in the United States, or contact your nearest Agilent
This chapter provides a general description of your powersupply. This chapter alsocontains instructions for initialinspection, location and cooling for bench and rack operation, selectingthe power-line voltage, and connecting your power supply to ac power.
Safety Considerations
Thispower supplyis a Safety Class I instrument, which means that ithas a protective earth terminal. Thatterminal must be connected to earth groundthrough a powersource with a 3-wire ground receptacle.
Before installation or operation, check the powersupply and review thismanual for safety markings and instructions. Safety information for specific procedures islocated at the appropriate places in thismanual. See also‘‘
Safety
’’ at the beginningof thismanual for general safetyinformation.
Safety and EMC Requirements
Thispower supplyis designed to comply with the following safety and EMC(Electromagnetic Compatibility) requirements:
•IEC 1010-1(1990)/EN 61010-1(1993) + A2 (1995):Safety Requirements for
Electrical Equipment for Measurement, Control, and Laboratory Use
•CSA C22.2 No.1010.1-92: Safety Requirements for Electrical Equipmentfor
Measurement, Control,and Laboratory Use
•UL 1244: Electrical and Electric Measuring and Testing Equipment
•EMC Directive 89/336/EEC
•Low Voltage Directive:73/23/EEC
•EN 55011(1991) Group I, Class A/CISPR II(1990): Limits and Methods of
Radio Interface Characteristics of Industrial, Scientific, and Medical(ISM) Radio-Frequency Equipment.
•EN50082-1(1992):
IEC801-2(1991): Electrostatic Discharge RequirementsIEC 801-3(1984):Radiated Electromagnetic Field RequirementsIEC801-4(1988): Electrical Fast Transient/Burst Requirements
•ICES/NMB-001
ThisISM device complies with Canadian ICES-001.Cet appareil ISM est conforme à la norme NMB-001 du Canada.
14
Chapter 1 General Information
Options and Accessories
Options and Accessories
Options
Options 0EM, 0E3, and 0E9 determine which power-linevoltage is selected at the factory.The standard unit isconfigured for 115 Vac ± 10%,47-63 Hz input voltage. Formore information about changing the power-line voltage setting, see ‘‘
Power-Line Voltage Selection
OptionDescription
0EM115
0E3
0E9
1CM
0L2
Vac ± 10%, 47-63Hz input voltage230 Vac ± 10%,47-63 Hz input voltage100 Vac ± 10%,47-63 Hz input voltageRack mount kit (Agilent partnumber 5063-9243)Extra Englishmanual set (local language manual files are includedon the CD-ROM, Agilent part number 5964-8251)
Accessories
’’, starting on page22 in thischapter.
1
The accessories listed below may be ordered from your local Agilent Technologies Sales Office either with the power supplyor separately.
Agilent No. Description
10833A
10833B
34398A
34399A
GPIB cable, 1 m (3.3 ft.)GPIB cable, 2 m (6.6 ft.)RS-232, 9 pin (f) to 9 pin (f),2.5 m(8.2ft.) cable; plus 9 pin (m) to 25 pin (f) adapter
RS-232 adapter kit (contains 4 adapters):
9 pin (m) to 25 pin (m) for use with PCor printer9 pin (m) to 25 pin (f) for usewith PCor printer9 pin (m) to 25 pin (m) for use with modem9 pin (m) to 9 pin (m) for usewith modem
15
Chapter 1 General Information
Description
Description
The Agilent E3632A DCpower supply feature a combination of programming capabilities and linear power supply performance that makes it ideal for power systems applications. The power supply is programmable locally from the front panel or remotely over the GPIB and RS-232 interfaces. This power supply hastwo ranges,allowing more voltage at a lower current. The desired output range is selected from the front panel or over the remoteinterfaces.
Operational features include:
•Dual range of 15V/7A or 30V/4A
•Constant voltage(CV) or constant current (CC) operation
•Overvoltage protection (OVP) and overcurrent protection (OCP)
•Threestorage locations (1 to 3) for user-defined operating states
•Automatic turn-on self-test
•Remote sensing for load voltage
•User calibration from the front panel or over the remote interfaces
The front panel operation permits:
•Easy-to-useof knob control
•Output range selection
•Enabling or disablingOVP and OCP features
•Setting the OVP and OCP triplevels
•Clearing OVP and OCP conditions
•Setting and displaying thevoltage and current limit values
•Saving and recalling operating states
•Returning the power supplyto local mode from remote interface mode
•Displaying remote interface error message
•Calibrating the powersupply,including changing the calibration secure code
•Configuring the power supply for remote interfaces
•Enabling or disablingthe output
16
Chapter 1 General Information
Description
When operated over the remote interface, the power supply can be both a listener and a talker.Using an external controller, you caninstruct the power supply toset the output and to send the statusdata back over the GPIB or RS-
232. Capabilities include the following features:
•Voltage and current programming
•Voltage and current readback
•Present and stored status readback
•Programmingsyntax error detection
•Complete self-test
The front-panelVFD (Vacuum-Fluorescent Display) includes:
1
•Displaying actual values of output voltage and current (
•Or displaying the limit values of voltageand current (
•Checking the operating status fromthe annunciators
•Checking the type of error from the error codes (messages)
Connections to thepower supply’s output and to chassis ground are made tobindingposts on the front panel
Warning Floating the power supply output more than ±60 Vdc from the chassis presents an
electric shock hazard to the operator. Do not float the outputs more than ±60 Vdc
when metal shorting bars without insulation are used to connect the (+) output to the
(+) sense and the (-) output to the (-) sense terminals.
meter mode
limit mode
)
)
17
Chapter 1 General Information
Description
Warning Outputs can be floated to maximum of ±240 Vdc provided that the metal shorting bars
without insulation are either replaced with insulated conductors or they are removed
from the terminals so there is no operator access to the output conductors without
insulation. All field wiring insulation must be adequate for the voltage present.
The powersupply isshipped with a detachable, 3-wire grounding type power cord.The ac line fuse isan extractortype onthe rear panel. The power supply can be calibrated from the frontpanel directly or with a controller over the GPIB or RS-232 interface using calibration commands. Correction factors are stored inCalibration from the front panel or a controller eliminate the need to remove the top cover or even the need to remove the power supply from your systemcabinet. You canguard against unauthorizedcalibrationby using the “Secured” calibration protection function.
non-volatile
memory and are used during output programming.
18
Chapter 1 General Information
Installation
Installation
Initial Inspection
When you receive your power supply, inspect it for any obvious damagethatmay have occurred during shipment. If any damage isfound, notify thecarrier and the nearest Agilent Sales Officeimmediately.Warranty information isshown in the front of this manual.
Keep theoriginal packingmaterials in case the power supply has to be returnedto Agilent Technologies inthe future. If you return the power supply for service,attach atag identifying theowner and model number. Also include a brief description of the problem.
Mechanical Check
This checkconfirmsthat there are no broken keys or knob,that the cabinet and panel surfaces are free of dents and scratches,andthat the display is not scratched or cracked.
1
Electrical Check
Chapter 2 describes an initial operation procedure which, when successfully completed, verifies to a high level of confidence that the power supply isoperating in accordance with its specifications. Detailed electrical verification procedures are included in the
Service Guide
.
Cooling and Location
Cooling
The power supply can operate without loss of performance withinthe temperature range of 0 °Cto 40 °C,and with derated output current from40 °C to 55 °C. A fan cools the power supply by drawing air through the rear panel and exhausting it out the sides. Using an Agilent rack mount willnot impede the flow of air.
Bench Operation
Your power supply must be installed in a location that allows sufficient spaceatthe sides and rear of thepower supply for adequate air circulation. The rubber bumpers must be removed for rack mounting.
19
Chapter 1 General Information
Installation
Rack Mounting
The power supply can be mounted in a standard 19-inch rackcabinet using one of three optionalkits available. A rack-mounting kit for a singleinstrument isavailable as Option 1CM (P/N 5063-9243). Installation instructions and hardwareare included with each rack-mountingkit. Any Agilent System II instrument of thesame sizecan be rack-mounted beside the Agilent E3632Apower supply.
Remove the front and rear bumpers before rack-mounting the power supply.
To remove the rubber bumper, stretch a corner and then slide it off.
To rack mount a single instrument, order adapter kit 5063-9243.
20
Chapter 1 General Information
Installation
To rack mount two instrument of the same depth side-by-side, order
lock-link kit 5061-9694 and flange kit 5063-9214.
1
To install two instruments in a sliding support shelf, order support shelf
5063-9256, and slide kit 1494-0015.
21
Chapter 1 General Information
Input Power Requirements
Input Power Requirements
You canoperate yourpower supply from a nominal 100 V, 115 V, or 230 V single phase acpower sourceat 47 to 63 Hz. An indication on the rear panel showsthe nominal input voltage set for the power supply at the factory.If necessary, you can change the power-line voltage setting according to the instructions on the next page.
Power-Line Cord
The power supply is shipped from the factory with a power-line cord that has a plug appropriate for your location. Contact the nearest Agilent TechnologiesSalesand Service Office if the wrong power-line cord isincluded with yourpowersupply. Your power supply isequipped with a 3-wire grounding type power cord; the third conductor being theground. The power supply isgrounded only when the power-line cord is plugged into an appropriate receptacle. Donot operate your power supply without adequate cabinet ground connection.
Power-Line VoltageSelection
Power-line voltage selection is accomplished by adjusting two components:power-line voltage selector and power-line fuse on the power-line module of the rear panel.To change the power-line voltage, proceed as follows:
22
Chapter 1 General Information
Input Power Requirements
1
1Remove the power cord. Remove the
fuse-holder assembly with a flat-blad
screwdriver from the rear panel.
3 Rotate the power-line voltage selector
until the correct voltage appears.
2Install the correct line fuse. Remove
the power-line voltage selector from the
power-line module.
100 or 115 Vac, 4 AT fuse
230 Vac, 2.5 AT fuse
4 Replace the power-line voltage selector
and the fuse-holder assembly in the rear
panel.
100, 115, or 230 Vac
23
Chapter 1 General Information
Input Power Requirements
24
Chapter 1 General Information
Input Power Requirements
1
25
2
Initial Operation
Initial Operation
There arethree basic tests inthis chapter. The automatic power-on testincludes a self-test that checks the internal microprocessors and allows the user visuallyto check the display.The output check ensuresthat the power supply develops its rated outputsand properly respondsto operation fromthe front panel.For complete performance and/or verification tests, refer to the
Service Guide
Thischapter is intended for both the experienced and the inexperienced userbecause it callsattention to certain checks that should be madeprior tooperation.
Throughout this chapter the key to be pressed is shown in the left margin.
.
26
Chapter 2 Initial Operation
Preliminary Checkout
Preliminary Checkout
The following steps help you verify that the power supply is ready for use.
1
Verify the power-line voltage setting on the rear panel.
The power-line voltage isset to the proper value for your country when the power supply is shipped from the factory. Change the voltage setting ifit isnot correct. The settings are: 100, 115,or 230 Vac.
2
Verify that the correct power-line fuse is installed.
The correct fuseis installed for yourcountry when the power supply is shipped from the factory.For 100 or 115Vac operation, you must use a 4 AT fuse. For230 Vac operation, you must use a 2.5 ATfuse.
3
Connect the power-line cord and turn onyour power supply.
The front-panel display will light up and apower-on self-test occurs automaticallywhen you turn on the power supply.
See "Power-Line Voltage Selection", starting on page 22 in chapter1 ifyou need to changethepower-line voltage or the power-linefuse.
To replacethe 4 ATfuse, order Agilent part number 2110-0996.Toreplace the 2.5ATfuse, order Agilent part number2110-0999.
2
27
Chapter 2 Initial Operation
Power-On Checkout
Power-On Checkout
The power-on testincludesan automatic self-test that checksthe internalmicroprocessors and allows the uservisuallyto check the display.You willobservethe following sequence on the display after pressing the front panel power switch to on.
1 All segments of the display including all annunciators will turn on for about one
second.
To review the annunciators, hold down key as you turn onthe power supply
.
2 The GPIB address or RS-232 message will then be displayed for about one
second.
ADDR 05 (or RS-232)
The GPIB address is setto ‘‘5’’ when the power supply is shipped from the factory for remote interface configuration. If this is not the first time the power supply isturned on, a different interface(RS-232) or a different GPIB addressmay appear.
See "Remote Interface Configuration"in chapter 3 starting on page 56 if you needto change the remote interface configuration.
Display Limit
Output On/Off
Note
3The “15V”, “OVP”, “OCP” and “OFF” annunciators are on. All others are off.
The power supply will go into the (the
OFF
annunciator turnson); the 15V/7Arange isselected (the
annunciator turns on); and theknob is selected for
OVP
and
OCP
the
annunciator also turn on.
power-on / reset
state; the output is disabled
15V
voltage
control. Notice that
4Enable the outputs.
Press the key to enable the output. Theoff and the
Output On/Off
15V, OVP, OCP
OFF
, and CV annunciatorsare lit. The
annunciatorturns
blinking
digit can be adjusted by turning the knob. Notice that the display isin the meter mode. ‘‘Meter mode’’ means that the display shows the actual output voltage andcurrent.
If the power supplydetects anerrorduring power-on self-test, the annunciator willturn on.
See "ErrorMessages" for more information
ERROR
starting on page 121 in chapter5
28
Power
Output On/Off
Chapter 2 Initial Operation
Output Checkout
Output Checkout
The following procedures check to ensure thatthe power supply develops its rated outputs and properly responds to operation from the front panel.Forcomplete performance and verification tests, refer to the
For eachstep, use the keys shownontheleft margins.
Voltage OutputCheckout
The following steps verify basic voltage functions with no load.
1 Turn on the power supply.
The power supply will go into the
OFF
(the annunciator turns on); and the knob is selected for
2 Enable the outputs.
The lit. The displayis inthe meter mode. ‘‘Meter mode’’ means thatthe display shows the actual output voltage and current.
annunciator turnson); the 15V/7Arange isselected (the
OFF
annunciator turns off and the
blinking
digit can be adjusted by turning the knob. Noticethat the
power-on / reset
15V, OVP, OCP
state; the output is disabled
Service Guide
15V
voltage
control.
, and CV annunciators are
.
2
3
Check that the front-panel voltmeterproperlyresponds to knobcontrol for the 15V/7A range.
Turn the knob clockwiseor counter clockwise to check that the voltmeter responds to knob control and the ammeter indicates nearly zero.
4
Ensure that the voltage can beadjusted from zero to the full ratedvalue.
Adjustthe knob untilthe voltmeter indicates 0 voltsand thenadjust the knob until the voltmeterindicates ‘‘
1
You can use the resolution selection keys to move the blinking digitto the
right or left whensetting thevoltage.
1
15.0
volts’’.
29
Power
Chapter 2 Initial Operation
Output Checkout
Current OutputCheckout
The following steps check basic current functionswith a short across thepower supply’s output.
1
Turn on the power supply.
The power supply will go into the
OFF
(the
annunciator turnson); the 15V/7Arange isselected (the
annunciator turns on); and the knob is selected for
2
Connect a short across (+) and (-) output terminals with an insulatedtest lead.
power-on / reset
state; the output is disabled
15V
voltage
control.
Output On/Off
Display Limit
Volt/Curr
3
Enable the output.
The
OFF
The
CV
or CCannunciator turns on depending on the resistance of the test
lead. The
annunciator turns off and the
blinking
digit can be adjusted by turningthe knob. Notice that the
15V, OVP
, and
OCP
annunciators are lit.
displayis inthe meter mode. ‘‘Meter mode’’ means thatthe display shows the actual output voltage and current.
4
Adjust the voltage limit value to 1.0 volt.
Set the display to the Adjust the voltage limit to 1.0 voltto assure CC operation. The
limit
mode (the
Limit
annunciator will be
blinking
CC
annunciator
will turn on.
5
Check that the front-panel ammeter properlyresponds toknob control for the15V/7A range.
Set the knob to the clockwise when the display isin the meter mode (the
current
control, and turn the knob clockwiseor counter
Limit
annunciator is off). Check that the ammeter responds to knob control and the voltmeter indicatesnearly zero (the voltmeter will show the voltage drop caused bythetest lead).
).
30
Chapter 2 Initial Operation
Output Checkout
6
Ensure that the current canbe adjusted from zero to the full ratedvalue.
Note
Adjust the knob until the ammeter indicates 0 amps and thenuntil the ammeter indicates 7.0 amps.
If an error hasbeendetected during the outputcheckoutprocedures, the
ERROR
starting on page 121 in chapter5.
annunciator will turn on. See "ErrorMessages" for more information
1
2
1
You can use the resolution selection keys to move the blinkingdigit the right
or left whensetting the current.
31
Chapter 2 Initial Operation
Output Checkout
32
3
Front-Panel Operation
Front-Panel Operation
So far you have learned how to install your power supply and perform initial operation. During the initial operation, youwere briefly introduced tooperatingfrom the front panel as you learned how to check basic voltage andcurrent functions. Thischapter will describein detail the use of these front-panel keys and show how theyare used to accomplish power supplyoperation.
•Front-Panel Operation Overview, page 35
•Constant Voltage Operation, page 36
•Constant Current Operation, page38
•Storing and Recalling Operating States, page40
•Programming Overvoltage Protection, page 42
•ProgrammingOvercurrent Protection, page 45
•Remote Voltage Sensing, page 48
•Disabling the Output, page 50
•Disabling the Output Usingan External Relay, page51
•Knob Locking, page 51
•System-Related Operations, page 52
•Remote Interface Configuration, page 56
•GPIB Interface Configuration, page 61
•RS-232 InterfaceConfiguration, page 62
•Calibration Overview, page 66
Note
Throughout this chapter the key to be pressed is shown in the left margin.
See "Error Messages", startingon page 121 in chapter 5 if you encounter anyerrors during front-panel operation.
34
Chapter 3 Front-Panel Operation
Front-Panel Operation Overview
Front-Panel Operation Overview
The following section describes an overview of the front-panel keys beforeoperating your power supply.
•The power supply is shipped from the factoryconfigured in the operationmode. At power-on,the power supply is automatically set tooperate in the front-panel operation mode. When in this mode, the front-panel keys can be used. When the power supply is in
remote
you can return to front-panel operation mode at any timeby pressing the
Local
key ifyoudid not previously sendthe front-panel lockout command. A changebetween front-panel and remote operation modes willin a change in the output parameters.
•The power supply has two output ranges of 15V/7A or 30V/4A. This featureallows more voltage ata lower current or more current at a lower voltage.The desired output range isselected from the frontpanel or over the remote
15V
or
30V
interfaces. The
annunciator indicates the presently selected
range.
•When you press key(thedisplayof the power supply goes to the
Display Limit
Limit
annunciator blinks), the
limit
mode and the present limit values will bedisplayed. In this mode, you can also observethe change of the limit values when adjusting the knob. If you press the key again or let thedisplay time-out after several seconds, the power supply
Limit
will return the display to the
meter
mode (the
annunciator turns off).
In thismode, the actual outputvoltage and current willbe displayed.
•The output ofthe power supply can be enabled or disabled from the front panel using the
Output On/Off
key. When the output is off, the
annunciator turns on and theoutput is disabled.
•The display providesthe present operating status of the power supply with annunciatorsand also informs the user oferror codes. For example, the power supply is operating in CV mode in the 15V/7A range and controlled
CV
and
15V
from the front panel, then the however, the power supply is remotely controlled, the
annunciators willturnon.If,
Rmt
also turn on, and when thepower supplyis being addressed over GPIB interface, the
Adrs
annunciator willturnon.See "
Display Annunciators
on page 5 for more information.
front-panel
operation mode,
not
result
Display Limit
OFF
annunciator will
"
3
35
Power
Chapter 3 Front-Panel Operation
Constant Voltage Operation
Constant Voltage Operation
Toset up the power supply for constant voltage (CV) operation, proceed asfollows.
•Front-panel operation:
1
Connect a load to the output terminals.
With power-off, connect a load to the (+) and (-) output terminals.
2
Turn on the power supply.
Display Limit
Volt/Curr
The power supply will go into the
OFF
(the
annunciator turnson); the 15V/7Arange isselected (the
annunciator turns on); and the knob is selected for To operate the powersupply in the 30V/4Arange, pressthe keybefore
proceedingto the next step. The
3
Set the display to the limit mode.
Notice that the
Limit
annunciator blinks, indicating that the display isin the
limit mode. Whenthedisplayis in the
power-on / reset
30V
annunciator turns on.
limit
state; the output is disabled
mode, you can seethe voltage and
voltage
control.
30V,4A
15V
current limit values of thepower supply.
Inconstant voltage mode, the voltage values betweenthe meter and limit modes are the same, but the current values arenot. Moreover, if the display is inthe meter mode,youcannot see the change of current limit value whenadjusting the knob. Werecommendthat you should setthe display to “limit” mode to seethechange of current limit value in the constant voltage mode wheneveradjustingthe knob.
4
Adjust the knob for the desired current limit.
Check that the The second digit of the ammeterwill be
Limit
annunciatorstill blinks. Set the knob for
blinking
1
current
control.
. The blinking digit can be changed using theresolution selection keys and the blinking digit can be adjusted by turning the knob. Adjust the knob to the desired current limit.
1
You can use the resolution selection keys to move the blinking digitto the
right or left whensetting current.
36
Chapter 3 Front-Panel Operation
Constant Voltage Operation
Volt/Curr
Display Limit
Output On/Off
5
Adjust the knob for the desired output voltage.
Check that the The second digit of the voltmeterwill be
Limit
annunciator still blinks. Set the knob for
blinking
1
voltage
control.
. Change the blinkingdigit using the resolution selection keys and adjust the knob to the desired output voltage.
6
Return to the meter mode.
Display Limit
Press key or let the display time-out after several seconds to return to the meter mode. Notice that the
Limit
annunciator turns off and the
display shows “OUTPUTOFF” message.
7
Enable the output.
The
OFF
annunciator turns offand the
15V
or
30V, OVP, OCP
and CVannunciators are lit. Notice that the display is in the meter mode. In the mode, the display shows the actual output voltage and current.
Refer to “Programming Overvoltage Protection” and “Programming OvercurrentProtection” sections, starting on information on
8
Verify that the power supply is in the constant voltage mode.
OVP
and
OCP
annunciators.
page 42 andpage 45 for more
If you operate the power supply in the constant voltage (CV) mode, verify thatthe
CV
annunciator is lit. If the CC annunciator is lit, choose a
higher
current
limit.
meter
3
Note
During actual CV operation, if a load change causes the current limit to beexceeded, the power supplywill automatically crossover tothe constantcurrent modeat the presetcurrent limit and the output voltage willdrop proportionately.
•Remote interface operation:
CURRent {<current>|MIN|MAX}Set the current
VOLTage {<voltage>|MIN|MAXSet the voltage
OUTPut ONEnable the output
1
You can use the resolution selection keys to move the blinking digitto the
right or left whensetting voltage.
37
Power
Chapter 3 Front-Panel Operation
Constant Current Operation
Constant Current Operation
Toset up the power supply for constant current (CC)operation, proceed as follows.
•Front-panel operation:
1
Connect a load to the output terminals.
With power-off, connect a load to the (+) and (-) output terminals.
2
Turn on the power supply.
Display Limit
The power supply will go into the
OFF
(the
annunciator turnson); the 15V/7Arange isselected (the
annunciator turns on); and the knob is selected for Tooperate the power supply in the 30V/4A range, press key before
proceedingto the next step. The
3
Set the display to the limit mode.
Notice that the
Limit
annunciator blinks, indicating that the display isin the
limit mode. Whenthedisplayis in the
power-on / reset
30V
annunciator turns on.
limit
state; the output is disabled
mode, you can seethe voltage and
voltage
30V,4A
control.
15V
current limit values oftheselectedsupply.
Inconstant current mode, the current values between the meter mode andlimit mode are the same, butthe voltagevalues are not. Moreover, if thedisplay is in the meter mode, you cannot see the change of voltage limitvalue whenadjusting the knob. Werecommendthat you should setthe display to“limit” mode tosee the change of voltage limitvalue in theconstant current mode wheneveradjustingthe knob.
4
Adjust the knob for the desired voltage limit.
Check thatthe
blinks
to indicate the knob is selected for voltage control. The blinkingdigit
Limit
annunciator still blinks and the second digit of voltmeter
1
can be changed using the resolution keysand the blinking digit can be adjusted by turning the knob.Adjust the knobfor the desired voltage limit.
1
You can use the resolution selection keys to move the blinking digitto the
right or left whensetting thevoltage.
38
Chapter 3 Front-Panel Operation
Constant Current Operation
Volt/Curr
Display Limit
Output On/Off
5
Adjust the knob for the desired output current.
Check that the The second digit of the ammeterwill be
Limit
annunciatorstill blinks. Set the knob for
blinking
. Change the blinking digit
1
current
control.
using the resolution selection keys and adjust the knob to the desired output current.
6
Return to the meter mode.
Display Limit
Press key or let the display time-out after several seconds to return the meter mode.Notice that the
Limit
annunciator turns off and the
display shows “OUTPUTOFF” message.
7
Enable the output.
The
OFF
annunciator turns offand the
15V
or
30V, OVP, OCP
and CCannunciators are lit. Notice that the display is in the meter mode. In the mode, the display shows the actual output voltage and current.
Refer to “Programming Overvoltage Protection” and “Programming OvercurrentProtection” sections, starting on information on
8
Verify that the power supply is in the constant current mode.
OVP
and
OCP
annunciators.
page 42 andpage 45 for more
If you operate the power supply in the constantcurrent (CC) mode, verify that the
CC
annunciator is lit. If the CV annunciator is lit, choose a
higher
voltage
limit.
meter
3
Note
During actualCCoperation, if aload change causes the voltage limit to be exceeded,the power supply will automatically crossover to constant voltagemode atthe presetvoltagelimit and the outputcurrent will dropproportionately.
•Remote interface operation:
VOLTage {<voltage>|MIN|MAX}Set the voltage
CURRent {<current>|MIN|MAX}Set the current
OUTPut ONEnable the output
1
You can use the resolution selection keys to move the blinking digitto the
right or left whensetting thecurrent.
39
Chapter 3 Front-Panel Operation
Storing and Recalling Operating States
Storing and Recalling Operating States
Store
You can storeup to three different operating states in This also enablesyou to recall the entire instrumentconfiguration with justa few key presses fromthe front panel.
The memory locationsare supplied with the reset statesfrom the factory for front-panel operation. Refer to the description of page 94 in chapter 4 for more information. The following steps show you howto store and recall an operating state.
•Front-panel operation:
1
Set up the power supply for the desired operating state.
The storage feature “remembers” output rangeselection, the limit value settings of voltage and current, output on/off state,OVP and OCPon/off state, and OVP and OCP trip levels.
2
Turn on the storage mode.
Three memory locations (numbered 1, 2 and 3) are availableto store the operating states. The operating states are stored in are remembered when being recalled.
non-volatile
*RST
command, starting on
non-volatile
memory and
memory.
STORE 1
This messageappears on the display for approximately 3 seconds.
3
Store the operating state in memory location “3”.
Turn the knob to the right to specifythememory location 3.
STORE 3
To cancel the store operation, letthe display time-out after about 3 seconds
Store
or press any other function key except the returns to the normaloperating modeand to the function pressed.
40
key. Thepowersupply
Chapter 3 Front-Panel Operation
Storing and Recalling Operating States
Store
Recall
4
Save the operating state.
The operating state is now stored. To recall the stored state, go to the following steps.
DONE
This messageappears on the display for approximately 1 second.
5
Turn on the recall mode.
Memory location “1” willbe displayed in the recallmode.
RECALL 1
This messageappears on the display for approximately 3 seconds.
6
Recall the stored operating state.
Turn the knob to the right to changethe displayed storage location to 3.
RECALL 3
3
Recall
If thissetting is not followed within 3 seconds with key stroke, thepower supply returns to normal operating mode and will not recall the instrument state3 from memory.
7
Restore the operating state.
The power supply should now be configured inthe samestate aswhen you stored the state on the previous steps.
Recall
DONE
This messageappears on the display for approximately 1 second.
•Remote interface operation:
*SAV {1|2|3}Store an operating state to a specified location
*RCL {1|2|3}Recall a previously stored state from a specified location
41
Chapter 3 Front-Panel Operation
Programming Overvoltage Protection
Programming Overvoltage Protection
Overvoltage protection guards the load against output voltages that reach aspecified value greater than theprogrammed protection level. It isaccomplished by shorting the output via an internal SCR whenthe trip levelisset to equal or greater than 3volts,or byprogamming the output to 1 voltwhen the trip level isset tolessthan 3 volts.
The following steps show how to set the OVP trip level,how to check OVP operation, and how to clear overvoltage condition.
•Front-panel operation:
Setting the OVP Level and Enable the OVP Circuit
Power
Output On/Off
Over Voltage
Note
Over Voltage
1
Turn on the power supply.
The powersupply will go into the
OFF
(the annunciator turns on); and the knob is selected for
2
Enable the output.
The
3
Enter the OVP menu and set the trip level.
annunciator turnson); the 15V/7Arange isselected (the
OFF
annunciator turns offand the display will go to the meter mode.
power-on / reset
state; the output is disabled
15V
voltage
control.
LEVEL 32.0 V
You willsee the abovemessage on the display when you enter the OVP menu.Adjust the control knob for thedesired OVP trip level.
Note that youcannot set the trip levels to lowerthan 1.0volt.
4
Enable the OVP circuit.
OVP ON
You willsee the above message after pressing key.
Over Voltage
42
Chapter 3 Front-Panel Operation
Programming Overvoltage Protection
Over Voltage
5
Exit the OVP menu.
CHANGED
The “CHANGED”message is highlightedfor a second to show that the newOVP trip level isnow in effect. If the OVP settings are not changed, “NO CHANGE”will be displayed.The power supply will exit the OVP menu andthe
OVP
display willreturnto the meter mode.Check that theon.
annunciator turns
Checking OVP Operation
Tocheck OVP operation, raise the outputvoltageto near the trip point. Then verygradually increase the output byturning the knob until the OVP circuit trips. This willcause the power supply output to drop to near zero, the
CC
annunciator to message also appears on the display.
blink
, and the
annunciator to turn on. The “OVPTRIPPED”
Clearing the Overvoltage Condition
When the OVP condition occurs (the “OVP TRIPPED” messageis shown on the display), the voltage source such as a battery, disconnectit first. The following steps showhow to clear the overvoltage conditions and get backto normal mode operation. In the following steps, the display willgo back to "OVP TRIPPED" if you letthe display time out after about several seconds.
OVP
annunciator
blinks
. When it was caused by external
OVP
3
Over Voltage
Display Limit
Over Voltage
or
1
Readjustthe OVP trip level or the output voltage level.
Lower the output voltage level below the OVP trippoint after pressing the
Display Limit
Over Voltage
the key.
2
Move to the clear mode.
ovp on
You willsee the above message after pressing the key. If you changed the output voltage level, press the key twice. Turn theknob to the right until the "OVPCLEAR" appears on the display.
or raise the OVP trip level by using the knob after pressing
Over Voltage
Over Voltage
43
Chapter 3 Front-Panel Operation
Programming Overvoltage Protection
Over Voltage
Note
3
Clear the overvoltage condition and exit this menu.
Now, when you press key again, the “DONE” messageisdisplayed for a second and the
Over Voltage
OVP
annunciator will not blink any more. The
output will return to meter mode.
•Remote interface operation:
VOLT:PROT {<voltage>|MIN|MAX}Set the OVP level
VOLT:PROT:STAT {OFF|ON)Disable or enable the OVP circuit
VOLT:PROT:CLEClear the tripped OVP circuit
The power supply’sOVP circuitcontains a crowbar SCR, which effectively shortstheoutputof the power supplywhenever the overvoltageconditionoccurs. Ifexternalvoltage sourcesuch as a batteryisconnected acrosstheoutput, and the overvoltage condition inadvertently occurs, the SCRwillcontinuously sinka large current from thesource; possibly damaging thepower supply. To avoid this a diode mustbeconnected in series withtheoutput asshown below.
Figure 3-1. Recommended Protection Circuit for Battery Charging
44
Chapter 3 Front-Panel Operation
Programming Overcurrent Protection
Programming Overcurrent Protection
Overcurrent protection guards the loadagainstoutput currents that reach a specified value greater than the programmed protection level. It isaccomplished by programming the output current to zero.
The following steps show how to set the overcurrent protection trip level,how to check OCP operation and how to clear overcurrentcondition.
•Front-panel operation:
Power
Output On/Off
Over Current
Over Current
Setting the OCP Level and Enable the OCP Circuit
1
Turn on the power supply.
The power supply will go into the
OFF
(the annunciator turns on); and the knob is selected for
2
Enable the output.
The
3
Enter the OCP menu and set the trip level.
You will see the above message on the display when you enter the OCP menu.Adjust the knob for the desired OCP trip level.
4
Enable the OCP circuit.
annunciator turnson); the 15V/7Arange isselected (the
OFF
annunciator turns offand the display will go to the meter mode.
LEVEL 7.5 A
power-on / reset
state; the output is disabled
15V
voltage
control.
OCP ON
You willsee the above message after pressing the key.
Over Current
3
45
Chapter 3 Front-Panel Operation
Programming Overcurrent Protection
Over Current
5
Exit the OCP menu.
CHANGED
The “CHANGED” message isdisplayed for a second to showthat the new OCP trip level is now in effect. If the OCP settings are not changed, “NO CHANGE” will be displayed. The power supplywill exit the OCP menu and the display
OCP
will return to themeter mode. Check that the
annunciator turns on.
Checking OCP Operation
To check OCP operation, raise the output current tonear the trippoint.Then verygradually increase the output byturning the knob until the OCP circuit trips. This will cause the power supply’s output current to drop tozero and the
OCP
annunciator to
blink
. The “OCP TRIPPED” message alsoappears on the
display.
Clearing the OvercurrentCondition
When the OCP condition occurs (the“OCPTRIPPED” message is shown on the display), the voltage source such as a battery, disconnectit first. The following steps showhow to clear the overcurrentconditions and getback to normal mode operation. In the following steps, the display will go back to "OCP TRIPPED" if you letthe display time out after about several seconds.
OCP
annunciator blinks. When it was caused by external
Over Current
Display Limit
or
1
Readjust the OCP trip levelor the output current level.
Lower the output current level below the OCP trip point after pressingthe
Display Limit
Over Current
the key.
2
Move to the clear mode.
orraise the OCPtriplevel by using the knob after pressing
ocp on
You willsee the above message after pressing the key. If you changed the output current level, press the key twice. Turn the
Over Current
Over Current
knob to the right untilthe "OCPCLEAR" appears on the display.
46
Chapter 3 Front-Panel Operation
Programming Overcurrent Protection
Over Current
3
Clear the overcurrent condition and exit this menu.
Now, when you press key again, the “DONE’’ message isdisplayed for a second and the output will return to meter mode.
•Remote interface operation:
CURR:PROT {<current>|MIN|MAX}Set the OCP level
CURR:PROT:STAT {OFF|ON}Disable or enable the OCP circuit
CURR:PROT:CLEClear the tripped OCP circuit
Over Current
OCP
annunciator willnot blink any more. The
3
47
Chapter 3 Front-Panel Operation
Remote Voltage Sensing
Remote Voltage Sensing
Remote voltage sensing is used to maintain regulation at the load and reduce the degradation of regulation that would occur due to the voltage drop in the leads between thepower supply and the load.
By connecting the power supply for remote voltage sensing, voltage is sensed at the load rather thanat the power supply’soutput terminals. This will allow the power supply to automatically compensate for the voltagedrop inapplicationswith long lead lengthsas well asto accurately read back thevoltage directly across the load.
When the power supply is connected forremote sensing, the OVP circuit senses the voltage at the
CV Regulation
The voltage load regulation specification in chapter 8 applies at theoutput terminals ofthe power supply.When remote sensing, add 5 mV to thisspecification for each 1 V drop between the positive sensing point and (+)output terminal due to the change in load current. Because the sense leads are part of thepower supply’s feedback path, keep the resistance of the sense leadsat or below0.5
sensing
Ω
per lead to maintain the above specified performance.
points (load) and not the output terminals.
Output Rating
The rated output voltage and current specifications in chapter 8 apply at the output terminalsof the powersupply. With remote sensing,any voltage dropped in the load leads must beadded to the load voltage to calculate maximum output voltage. The performance specifications are not guaranteed when the maximum output voltage isexceeded. If the excessivedemand on
Unreg
the power supply forces the power supplyto loseregulation, the annunciator willturn on to indicatethatthe output is unregulated.
Output Noise
Any noise picked up on the sense leads alsoappearsat the output of the power supply and may adversely affect the voltage loadregulation.Twist the senseleads to minimizeexternal noise pickup and run them parallel and close to the load leads.In noisy environments it may be necessary to shield the sense leads.Ground the shield at the power supply end only.
ofthe sense conductors
48
.
Do not use the shield as one
Chapter 3 Front-Panel Operation
Remote Voltage Sensing
Stability
Using remote sensing under certain combinations of load lead lengths andlarge load capacitances may cause your application to form a filter, which becomes part of the voltage feedback loop. The extra phase shiftcreated by this filter can degrade the power supply’sstability,resulting inpoor transient response or loop instability.In severe cases, it may causeoscillations. Tominimizethis possibility, keepthe load leads as short as possible andtwistthem together. Asthe sense leads are partof thepower supply’s programming feedback loop, accidental open-connectionsof sense or load leads during remote sensing operation have various unwanted effects.Provide secure and permanent connections.
Remote Voltage Sensing Connections
Remote voltage sensing requires connectingthe load leads from output terminals to the load and connecting the sense leads from sense terminals to the load as shown below. Observe polarity when connecting the sensing leads to the load.
Noticethat the metal shorting barsshouldberemovedfrom the outputand sense terminalsfor remote voltage sensing connections.
3
Note
Note
For local voltage sensing connections,the sense leads must be connected tothe output terminals.
Duringremote sensing setup,it is strongly recommendedto poweroff(by
presssing powerON/OFF button) the power supply to avoid
damageto the load or the power supply.
Figure 3-2. Remote Voltage Sensing Connections
undesirable
49
Chapter 3 Front-Panel Operation
Disabling the Output
Disabling the Output
The output of thepower supply can be disabled or enabled from the front panel.
•When the power supply isin the “Off” state, the
OFF
the output isdisabled. The returns to the“On” state. When the output isdisabled, the voltage value is0 voltsand the current value is 0.02 amps.
•The output state is stored inwhen power has been off or after a remote interfacereset.
While theoutputis disabled, the range selectionkeys, the control knob, resolution selectionkeys,andadjust selection key are still working. Ifthedisplay isinthemetermode, you cannot see the changes of outputvoltage and current settings on thedisplay whenturning the knob.Toseeor check the changes when the outputs are disabled, the display should bein the limitmode.
•Front-panel operation:
You can disable the output by pressing key. This key toggles between output “Off” and “On” states.
•Remote interface operation:
OUTP {OFF|ON}Disable or enable the output
annunciator turnsoff when the power supply
volatile
memory; the output isalwaysdisabled
Output On/Off
OFF
annunciator turns on and
50
Chapter 3 Front-Panel Operation
Disabling the Output Using an External Relay
Disabling the Output Using an External Relay
When the output of the E3632A is turned off, itis implemented by settingthe output to 0 volts and 0.02 amps. This gives a zero output voltagewithout actually disconnecting the output. Todisconnect the output an external relay must be connected between the output and the load. A TTL signal of either lowtrue or high true isprovided to control an external relay. Thissignal can only be controlled with the remote command output is available on the RS-232connection pin 1 and pin 0.
When the (4.5 V)and pin 9 is low (0.5 V). The levels are reversed when the
OUTPut:RELay
OUTPut:RELay
state is“OFF”.
state is “ON”, theTTL output of pin 1 is high
OUTPut:RELay {OFF|ON}
. The TTL
3
Note
Note
TTL output of pin 1 or pin 9 of the RS-232 connector is available only afterinstallingtwo jumpersinside the power supply. See the Service Guide formore information.
Do not use the RS-232 interface if you have configured the power supply to output relaycontrol signals. Internalcomponents on the RS-232circuitrymay be damaged.
Knob Locking
The knob locking function can be used to disable the knob, thereby preventingany unwanted changes during an experiment, or when you leave the power supply unattended. To disablethe knob, press the resolution selection key untilthe blinking digit disappears.
Notice thattheknob and front panel keys are disabled when intheremoteinterface mode.
51
Chapter 3 Front-Panel Operation
System-Related Operations
System-Related Operations
This section gives information on topics such as self-test, error conditions, and front-panel display control. This information isnot directly related to setting up thepower supply but isan important part of operatingthe power supply.
Self-Test
A
power-on
Thistest assures you that thepower supply is operational. This test does notperformthe extensive set of tests that are includedas part of the complete self-test described below. If the power-on self-test fails,theturns on.
•A
complete
seconds to execute. If all tests pass, you can have a high confidence that the power supply is operational.
self-test occurs automatically when you turn on the power supply.
ERROR
self-test performs a series of tests and takes approximately2
annunciator
•If the
•Front-panel operation:
•Remote interface operation:
complete
If the self-test fails,“FAIL” is displayed and the See the Technologies for service.
The panel keys except the key) and the power-line switch simultaneouslyand then continuing to press the key for 5 seconds. The complete self-test willbe finished in2seconds.
Service Guide
complete
self-test issuccessful, “PASS” is displayed on the front panel.
ERROR
for instructions on returning thepower supply to Agilent
self-test is enabled by pressing the the(actually any front
Error
Recall
annunciator turnson.
Recall
*TST?
Returns “0” if the complete self-test passes or “1” if it fails.
52
Chapter 3 Front-Panel Operation
System-Related Operations
Error Conditions
When the front-panelsyntax or hardware errorshave been detected.A record of up to 20 errorscan be stored in the power supply’s error queue.
starting on
•Errors are retrieved in first-in-first-out (FIFO) order. The first error returned is the firsterror that was stored. When you haveread all errors from the queue,
ERROR
the error isgenerated.
•If morethan 20 errors have occurred when you operatethe power supply over the remote interface, the last error stored in the queue(the most recent error) is replaced with -350, “you remove errors from the queue.If no errors have occurred when you read the error queue, the power supply responds with +0, “interface or “NO ERRORS” from the frontpanel.
•The error queue iscleared when powerhas been off or after a status) command has been executed. The clear the error queue.
•Front-panel operation:
If the errors stored inthequeue. All errors are cleared when you read all errors.
page 121 for acomplete listing ofthe errors.
annunciator turns off. The power supply beeps once each timean
ERROR
annunciator is on, pressthe key repeatedly to read the
ERROR
annunciator turns on, one or more command
Too many errors
See chapter 5 “Error Messages”,
”. No additional errors are stored until
No error
*RST
(reset) command does not
Error
” over the remote
*CLS
(clear
ERR -113
3
•Remote interface operation:
SYST:ERR?Reads and error from the error queue
Errors have the following format (the error string may contain up to 80 characters).
-113, "Undefined header"
53
Chapter 3 Front-Panel Operation
System-Related Operations
Display Control
For security reasons, you may want to turn off thefront-panel display.Fromthe remote interface, you can display a12-character message on the front panel.
Thedisplay can be enabled/disabled from the remote interface only.
•When the display isturned off, outputs are not sent to the display and allannunciators are disabledexcept the operation isotherwise unaffected by turning off the display.
ERROR
annunciator. Front-panel
•The display state isstored inwhen power has been off, after a remote interface reset, or after returning tolocal from remote.
•Youcan display a message on the front panel by sending a commandfrom the remote interface. The power supply can display up to 12 charactersof themessage on the front panel; any additional characters are truncated. Commas, periods, and semicolons share a display space with the preceding character, and
are not
outputs are notsent to the display.
•Sending a message to the display fromthe remoteinterface overrides the display state; this means that you can display a message even if the display isturned off.
The display state is automatically turned on when you return to the local (front panel) operation. Pressinterface.
•Remote interface operation:
DISP {OFF|ON}Disable / enable the display
DISP:TEXT <quoted string>Display the string enclosed in quotes
DISP:TEXT:CLEClear the displayed message
The following statement shows how to displaya message on the front panelfrom a Agilent Technologies controller.
"DISP:TEXT ‘HELLO’ "
considered individual characters. When a message isdisplayed,
volatile
Local
memory; the display is always enabled
key to return to the local state from the remote
54
Chapter 3 Front-Panel Operation
System-Related Operations
Firmware Revision Query
The power supply has three microprocessors for control ofvarious internalsystems.You can querythe power supply to determine which revision of firmwareis installed for each microprocessor.
Youcan query the firmware revisionfrom the remote interface only.
•The power supply returns four fields separated by commas and the fourth field is a revision code which contains three numbers. The first number is the firmware revision number for the main processor; the second is for the input/output processor; and the third isfor the front-panel processor.
Be sure to dimension a string variable with at least 40 characters.
SCPI Language Version
The power supply complieswith the rules and regulationsof the present version ofSCPI (Standard Commands for Programmable Instruments). You can determine the SCPI version with which the power supply is in compliance by sendinga command from the remote interface.
You can query the SCPI version fromthe remote interface only.
•Remote interface operation:
SYST:VERS?Query the SCPI version
Returns a string in theform “YYYY.V” where the “Y’s” represent the year of the version, and the “V” representsa version number for that year (for example,
1995.0).
3
55
Chapter 3 Front-Panel Operation
Remote Interface Configuration
Remote Interface Configuration
Before you can operate the power supply over the remote interface, you must configure the power supply for the remote interface. This sectiongivesinformation on configuringthe remote interface. For additional informationon programming the power supply over the remote interface, Interface Reference", starting on page 71 in chapter 4.
Remote InterfaceSelection
The power supply is shipped with both an GPIB (IEEE-488) interface and an RS-232 interface on the rear panel. Only oneinterface can beenabled ata time. The
GPIB interface
factory.
The remote interface can be selected from the front-panel only.
•The interface selection is stored inchangewhen power has been off or after a remote interfacereset.
•If you select the GPIB interface, you must selecta unique address for the power supply. The current address isdisplayed momentarily on the front panel when you turn on the power supply.
•Your GPIB bus controller has its own address. Be sure to avoid using the bus controller’s address for any instrument on the interfacebus. Agilent Technologiescontrollers generally use address“21”.
•If you enablethe RS-232 interface, you must select the baudrate and parity to be used. “RS-232” is displayed momentarily on the front panel when youturn on the power supply ifyou have selected thisinterface.
is selected when the power supply is shipped fromthe
non-volatile
memory, and
1
See "Remote
does not
2
1
Refer to "GPIB Interface Configuration" starting on page 61 for more information
on connecting the power supply to a computer over the GPIB interface.
2
Refer to "RS-232 Interface Configuration" starting on page 62 for more information
on connecting the power supply to a computer over the RS-232 interface.
56
Chapter 3 Front-Panel Operation
Remote Interface Configuration
GPIB Address
Each device on the GPIB (IEEE-488) interface musthavea unique address.You can set the power supply’s addressto any value between0 and 30.The current address is displayed momentarily on thefront panel when you turn onthe power supply.The address isset to “05” when the power supply isshipped from the factory.
The GPIB address can be set from the front-panel only.
•The addressis stored in power has been off or after a remote interfacereset.
•Your GPIB bus controller has its own address. Be sure to avoid thebuscontroller’s address for anyinstrument on the interface bus. Agilent Technologiescontrollers generally use address“21”.
non-volatile
memory,and
does not
change when
Baud Rate Selection (RS-232)
You can selectone of six baud rates for RS-232operation. The rate isset to
9600 baud
The baud rate can be set from the front-panel only.
•Select one of the following: 300, 600, 1200, 2400, 4800,
setting is 9600 baud.
•The baud rate selection isstored in changewhen power has been off or after a remote interfacereset.
whenthe power supply isshipped from the factory.
9600
baud.
non-volatile
memory,and
The factory
does not
3
Parity Selection (RS-232)
You canselect the parity for RS-232 operation.The power supply isconfigured for
noparity and8 data bits
The parity can be set from the front-panel only.
•Select one of the following: (
7 data bits
of data bits.
•The parity selection is stored in when power has been off or after a remote interfacereset.
). When you set the parity,youare indirectly setting the number
when shipped from the factory.
None
(
8 data bits
non-volatile
), Even (
memory, and
7 data bits
does not
), or Odd
change
57
I/O Config
I/O Config
Chapter 3 Front-Panel Operation
Remote Interface Configuration
To Set the GPIB Address
Toconfigurethe power supply for the GPIB interface, proceed as follows:
1
Turn on the remote configuration mode.
GPIB / 488
You willsee the above message on thefront-panel display if the power supply has not been changed fromthe factory setting. If “RS-232” appears,choose “GPIB / 488” by turning the knob to the right.
2
Move to the GPIB address setting mode.
ADDR 05
The address isset to “05” when the power supply isshipped fromthe factory.Notice thata different GPIB address may appear if the power supply has been changed from the factory setting.
I/O Config
Note
3
Turn the knob to change the GPIB address.
The displayed addressis changed when turning the knob to the right or left.
4
Save the change and turn off theI/O configuration mode.
CHANGE SAVED
The addressis stored in power has been off or after a remote interfacereset. The power supply displaysa message to show that the change isnow in effect. Ifthe GPIB address is notchanged, “NO CHANGE” willbe displayed for one second.
ToexittheI/O configuration mode without anyfurther changes, press the “I/O Config” key until the “NO CHANGE” message isdisplayed.
58
non-volatile
memory,and
does not
change when
I/O Config
I/O Config
Chapter 3 Front-Panel Operation
Remote Interface Configuration
To Set the Baud Rateand Parity (RS-232)
Toconfigurethe power supply for the RS-232 interface, proceed as follows:
1
Turn on the remote configuration mode.
GPIB / 488
You willsee the above message on the display if the powersupply has not been changed from the factory setting.
Noticethat if you changed the remote interface selectionto RS-232before,“RS-232” message will be displayed.
2
Choose the RS-232 interface.
RS-232
You can choose the RS-232 interface by turning the knob to the left.
3
Move to the RS-232 interface setting mode and select the baud rate.
3
I/O Config
9600 BAUD
The rate isset to Choosefrom oneof thefollowing by turning the knob to the right or left: 300, 600, 1200, 2400, 4800, or
4
Save the change and choose the parity.
9600
baud when the power supply is shipped from the factory.
9600
baud.
NONE 8 BITS
The power supply isconfigured for 8data bits with no parity when shipped from the factory.Choose from one of the following byturning the knob to the right or left: are indirectly setting the number of the databits.
None 8 Bits
, Odd 7 Bits, or Even 7Bits. When you set parity, you
59
Chapter 3 Front-Panel Operation
Remote Interface Configuration
I/O Config
Note
5
Save the change and turn off theI/O configuration mode.
CHANGE SAVED
The RS-232baud rate and parity selections are stored in and
does not
The power supply displays a message to show that the change is now in effect.If the baudrate and the parity are not changed, “NO CHANGE” will be displayed for one second.
ToexittheI/O configuration mode without anyfurther changes, press the “I/O Config” key until the “NO CHANGE” message isdisplayed.
change when power has been off or after a remote interface reset.
non-volatile
memory,
60
Chapter 3 Front-Panel Operation
GPIB Interface Configuration
GPIB Interface Configuration
The GPIBconnector on the rear panelconnects your power supply tothe computer and other GPIB devices. Chapter 1lists the cables that are availablefrom Agilent Technologies. An GPIB system can be connected together in any configuration (star, linear, or both) as long as the following rules are observed:
•The total number of devices including the computer isno more than 15.
•Thetotal length ofall the cables used isnomorethan 2 meter times thenumber ofdevices connected together, up to amaximum of 20 meters.
Note
IEEE-488statesthat you should exercise caution if your individual cable lengthsexceed 4 meters.
Do not stack morethan three connector blocks together on any GPIBconnector. Make sure thatall connectors are fully seated and thatthe lock screwsare firmly finger tightened.
3
61
Chapter 3 Front-Panel Operation
RS-232 Interface Configuration
RS-232 Interface Configuration
You connectthe power supply to the RS-232 interface using the 9-pin (DB-9)serial connector on the rear panel. Thepower supplyis configured as a DTE(Data Terminal Equipment) device. For all communications over the RS-232interface, thepower supply uses two handshake lines:DTR (Data Terminal Ready, on pin 4) and DSR (
The following sectionscontain information to help you use the power supply over the RS-232interface. The programming commands for RS-232areexplained on
page 99.
RS-232 ConfigurationOverview
Configure the RS-232 interfaceusing the parameters shown below. Usethe front-panel bits (see page 59 for more information to configure from the front panel).
I/O Config
Data Set Ready
key to select the baud rate, parity, and number of data
, on pin 6).
•Baud Rate: 300, 600, 1200, 2400, 4800, or
•Parity and Data Bits:
•Number of Start Bits:
•Number of Stop Bits:
None / 8 data bits (factory setting
Even / 7 data bits, orOdd / 7 data bits
1 bit (fixed2 bits (fixed
9600
baud (
)
)
factory setting
)
)
RS-232 Data Frame Format
A charactercharacter. The frame is defined as the charactersfromthe
stop bit
databits, and parity type. Thepower supply uses the following frame formatsfor seven and eight data bits.
frame
consists of all thetransmitted bits that make up a single
start bit
, inclusively. Within the frame, you can select the baud rate, number of
to thelast
62
Chapter 3 Front-Panel Operation
RS-232 Interface Configuration
Connectionto a Computer or Terminal
Toconnect the power supply to a computer or terminal, you must havethe proper interface cable. Most computers and terminals are DTE(
Equipment
) devices. Sincethe power supply isalso a DTE device, you must
use aDTE-to-DTE interface cable. These cables are also called
modem-eliminator
, or
crossover cables
.
The interface cable must also havethe proper connector on each end and theinternal wiring must be correct. Connectors typically have9 pins (DB-9 connector) or 25 pins (DB-25connector) with a “male” or “female” pin configuration. A male connector has pins insidethe connector shell and a femaleconnector has holes inside the connector shell.
If you cannotfind the correct cable for your configuration, you may have to use a
wiring adapter
. If you are using aDTE-to-DTE cable, make sure the adapter is a “straight-through” type. Typical adapters includegender changers,null-modem adapters, and DB-9to DB-25 adapters.
. If your configuration isdifferent than those described, order the Agilent 34399Acontains adapters for connection to other computers,terminals, and modems. Instructionsand pin diagrams are includedwith the adapter kit.
Data Terminal
null-modem,
Adapter Kit
. This kit
3
DB-9 Serial Connection
If your computer or terminal has a9-pin serial port
with a maleconnector, use the null-modemcable included with the
34398A CableKit.
cable pin diagram isshown below
Instrument
This cable has a 9-pin female connector on each end. The
.
5182-4794
DCD
RX
TX
DTR
GND
DSR
RTS
CTS
RI
DB9
Male
1
2
3
4
5
6
7
8
9
DB9
Female
Cable
DB9
Female
PC
1
2
3
4
5
6
7
8
9
DCD
RX
TX
DTR
GND
DSR
RTS
CTS
RI
DB9
Male
Agilent
63
Chapter 3 Front-Panel Operation
RS-232 Interface Configuration
DB-25 Serial Connection
If your computer or terminal has a 25-pin serialport with a male connector, use the null-modem cable and 25-pin adapter included withthe
Agilent 34398A Cable Kit.
Thecable and adapter pin
diagram are shown below.
5182-4794
InstrumentPC
DCD
1
RX
2
TX
3
DTR
4
5
GND
6
DSR
7
RTS
8
CTS
9
RI
DB9
DB9
Female
Male
Cable
1
2
3
4
5
6
7
8
9
DB9
Femal e
1
2
3
4
5
6
7
8
9
DB9
Male
5181-6641
Adapter
2
3
4
5
6
7
8
20
DB25
Female
TX
RX
RTS
CTS
DSR
GND
DCD
DTR
DB25
Male
DTR / DSR Handshake Protocol
The power supply is configuredas a DTE(and usesthe DTR (
Data Terminal Ready
the RS-232 interface to handshake.The power supply usesthe DTR line to send a hold-off signal. The DTR line mustbe TRUE before the power supply willaccept data from the interface.When the powersupply sets the DTR line FALSE, the data must cease within 10 characters.
To disable the DTR/DSRhandshake,DSR line to logic TRUE. If you disable the DTR/DSR handshake, also select a slower baud rate to ensure that the data istransmittedcorrectly.
Thepowersupply sets the DTR lineFALSE in the following cases:
1
When the power supply’s input buffer isfull (when approximately 100charactershave been received), it sets the DTR line FALSE (pin4 on the RS-232 connector). When enough characters have been removed to make spaceinthe input buffer,the power supply sets the DTR line TRUE,unless thesecond case(see next) preventsthis.
Data Terminal Equipment
) and DSR (
do not
connect the DTR lineand tie the
Data Set Ready
) device
) lines of
64
Chapter 3 Front-Panel Operation
RS-232 Interface Configuration
2
When the power supply wants to “talk” over the interface (which means thatit hasprocesseda query) and has received a it will set the DTR line FALSE. This implies that once a query has been sent to the power supply, the bus controller should read the response before attempting to send more data. It also meansthat a the commandstring.After the response has been output, the power supply sets the DTR line TRUE again, unless the first case(see above)prevents this.
The powersupply monitorsthe DSRline to determine when the bus controller is ready to accept data over the interface. Thepower supply monitors the DSRline (pin 6 onthe RS-232 connector) before each character is sent.The output is suspended if the DSRline isFALSE. When the DSR line goes TRUE, transmission willresume.
The power supplyholds the DTR line FALSE while output issuspended. A formof interface to allow the power supply to complete the transmission. You can break the interface deadlock by sending the operation in progress and discards pending output (this isequivalent to the IEEE-488 device clear action).
deadlock
exists until the bus controller asserts the DSR line TRUE
<Ctrl-C>
<new line>
character, which clears the
message terminator,
<new line>
must terminate
3
For the <Ctrl-C> character toberecognized reliably bythe powersupplywhileit holds DTRFALSE,the bus controller must first set DSRFALSE.
RS-232 Troubleshooting
Here are a few things to check if you are having problems communicating over the RS-232 interface. If you need additional help, refer to the documentation that came with your computer.
•Verify that the power supply and yourcomputer are configuredforthe samebaud rate,parity, and numberof data bits.Make sure that your computerisset up for supply).
•Make sure to execute the supply in the remote mode.
•Verify that you haveconnected the correct interfacecable and adapters.Even if the cable hasthe proper connectors for yoursystem,the internalwiring may be incorrect. The be used to connectthe power supply to most computers or terminals.
•Verify thatyou have connected the interface cable to the correct serial port on yourcomputer (COM1, COM2,etc).
1 start
bit and
2 stop bits
SYSTem:REMote
(these values are fixed on the power
command toplace the power
Agilent Technologies 34398A CableKit
can
65
Chapter 3 Front-Panel Operation
Calibration Overview
Calibration Overview
Thissection gives an overview of the calibration features of the power supply.For more detailed discussion of the calibration procedures, see the
Guide
.
Calibration Security
This feature allowsyou to enter a security code to prevent accidental or unauthorizedcalibrations of the power supply. When you first receiveyour power supply, itis secured. Before you can calibrate thepower supply, you must unsecure it by entering thecorrect security code.
•
Thesecurity codefrom the factorydoes not
•To secure the powersupply fromthe may contain up to 12alphanumeric characters as shown below. Thefirst character numbers. You do not haveto use all 12 characters but thefirst character must always be a
change when power has been off or after a remoteinterface reset.
mustbe a letter
isset to“HP003632”
. The security code is stored in
, but the remaining characters can be lettersor
letter
.
when the power supply isshipped
remote interface
non-volatile
, the security code
Service
memory, and
A _ _ _ _ _ _ _ _ _ _ _ (
•To secure the powersupply fromthe unsecured from the front panel,use the eight-character format shown below. The first twocharacters mustbe “H P” and the remaining characters must be numbers. Onlythe lastsix characters are recognized fromthe front panel, but alleight charactersare required.
from the front panel, omit the “HP” and enterthe remaining numbers as shown on the following pages.
H P _ _ _ _ _ _ (
If you forget your securitycode,you can disable the security featureby adding a jumper insidethepower supply,and thenentering a new code.See theService Guide for more information.
66
8 characters
12 characters
remote interface
Tounsecure the power supply
)
)
so that it can be
Chapter 3 Front-Panel Operation
Calibration Overview
To Unsecure for Calibration
calibration either from the front panel or over theremote interface.
supply is secured when shipped from the factory, and the security code is set to “HP003632”.
•Front-Panel Operation:
You can unsecure the power supply for
The power
SECURED
If the power supply is secured, you will seethe above message for one second by holding the supply. To unsecure the powersupply,press the key after the “CALMODE” message is displayed inthe calibration mode, enter thesecurity code using the knob and resolution selection keys, and then press the
Calibrate
key for 5 seconds when you turn on the power
Secure
Secure
000000 CODE
When you press the key to save the change, you will see the messagebelow for one second ifthe security code iscorrect. The unsecuredsetting isstored inor after a remote interface reset.
off and on.Noticethat if the security isincorrect, thepowersupply displays an
"INVALID" message for a second andreturns to the codeenteringmodefor youtoenter the correct code.
non-volatile
Secure
memory,and
does not
To exitthe calibration mode, turn the power
change when powerhas been off
3
key.
UNSECURED
•Remote Interface Operation:
CAL:SEC:STAT {OFF|ON},<code> Secure or unsecure the power supply
Tounsecure the power supply, send the above command with the same code usedto secure. Forexample,
"CAL:SEC:STAT OFF, HP003632"
67
Chapter 3 Front-Panel Operation
Calibration Overview
To Secure Against Calibration
calibration either fromthe frontpanel or over the remote interface.
supply is secured when shipped from the factory, and the security code is set to“HP003632
Be suretoread the security coderuleson page 66before attempting tosecurethe power supply.
•Front-Panel Operation:
”.
You can secure the powersupply against
The power
UNSECURED
If the power supply isunsecured, you will seethe above message for onesecond by holding the powersupply. To secure the power supply,press the key after the “CAL MODE” message is displayed in the calibration mode, enter the security code using the key.
Notice that you should omitthe “H P” and enterthe remaining numbers asshown below.
knob
Calibrate
and
resolution selection keys
key for 5 seconds when you turn on the
Secure
, and then press the
Secure
000000 CODE
When you press key to save the change, you will see the messagebelow.The secured setting isstored inchangewhen power has been off or after a remote interface reset. To exit the calibrationmode, turn the power off and on.
Secure
non-volatile
memory, and
does not
SECURED
•Remote Interface Operation:
CAL:SEC:STAT {OFF|ON},<code> Secure or unsecure the power supply
Tosecure the power supply, send the above command with the same code asused to unsecure. For example,
"CAL:SEC:STAT ON, HP003632"
68
Chapter 3 Front-Panel Operation
Calibration Overview
To Changethe Security Code
unsecure the power supply,and then enter a new code.
Be suretoread the security coderuleson page 66before attempting tosecurethe power supply.
•Front-Panel Operation:
Tochangethe security code, first make sure thatthepower supplyis
unsecured
the calibration mode, enter the new security code using the knob and resolution selection keys, thenpress
Changing the code from the front panel alsochanges the code required fromthe remote interface.
•Remote Interface Operation:
CAL:SEC:CODE <new code>Change the security code
To change the security code,first unsecure the powersupply using the old security code. Then, enter the new code. For example,
"CAL:SEC:STAT OFF, HP003632*"Unsecure with old code
"CAL:SEC:CODE ZZ001443"Enter new code
"CAL:SEC:STAT ON, ZZ00143"Secure with new code
. Press
Secure
Tochange the security code, you must first
key afterthe “CAL MODE” message is displayed in
Secure
key.
3
69
Chapter 3 Front-Panel Operation
Calibration Overview
Calibration Count
You can determine the number of times that your power supply hasbeen calibrated. Your power supply was calibrated before it left thefactory.When you receiveyour power supply,read the countto determineits initial value.
The calibration countfeature canbeperformed from the remoteinterface only.
•The calibration count isstored inwhen power has been off or after a remote interfacereset.
•The calibration count increments upto a maximum of 32,767 after which it wraps-around to 0. Since the value increments by one for each calibration point, a complete calibrationwill increase the value by 5 counts.
•Remote Interface Operation:
CAL:COUN?Query the number of times of calibration
non-volatile
memory, and
does not
change
Calibration Message
You can use the calibration message feature torecordcalibration information about your power supply. For example, you can store such information as the last calibration date, thenext calibration due date, the power supply’sserial number,or even the name and phonenumber of the person to contact for anew calibration.
Youcan recordand read informationin the calibration messagefrom the remote interface only.
•The power supply should be unsecured before sending a calibration message.
•The calibration message may contain up to40 characters.
•The calibration message is stored in changewhen power has been off or after a remote interfacereset.
non-volatile
memory,and
does not
•Remote Interface Operation:
CAL:STR <quoted string> Store the cal message
The following command stringshows how to store a calibration message.
"CAL:STR ‘CAL 05-1-97’ "
70
Chapter 3 Front-Panel Operation
Calibration Overview
3
71
4
Remote Interface Reference
SCPI
SCPI
Remote Interface Reference
•SCPI Command Summary, page73
•Simplified Programming Overview, page78
•Using the APPLy Command, page 81
•Output Setting and Operation Commands, page82
•Triggering Commands, page 89
•System-Related Commands, page 92
•Calibration Commands, page 96
•RS-232 Interface Commands, page 99
•The SCPI StatusRegisters, page 100
•StatusReporting Commands, page 108
•An Introduction to the SCPI Language, page 111
•Halting an Output in Progress, page116
•SCPI Conformance Information, page117
•IEEE-488 Conformance Information, page120
SCPI
If youarea first-time userof the SCPI language, you may wantto refer to these sections to become familiar withthelanguage beforeattempting toprogram the power supply.
72
Chapter 4 Remote Interface Reference
SCPI Command Summary
SCPI Command Summary
SCPI
This section summarizes the SCPI (
Instruments
remote interface. Refer to the latersectionsin thischapter for more complete detailson each command.
Throughout this manual, the following conventions areused for SCPIcommand syntax.
•Square brackets ([ ]) indicate optional keywords or parameters.
•Braces ({ }) enclose parameters within a command string.
•Triangle brackets (<>)indicate that you must substitute a value or a code for the enclosed parameter.
•A vertical bar ( | ) separates oneof two or more alternativeparameters.
First-time SCPI users,see page111.
) commandsavailable to programthe power supply overthe
Thissection gives an overview of the basic techniques used to programthepowersupply over the remote interface. Thissection is only an overview and does not give allof the details you will need to write your own application programs. Refer to the remainder of thischapter and also chapter 6, “ApplicationPrograms”, for more details and examples. Also refer to theprogramming reference manual that camewith your computer for details on outputting command strings and entering data.
Using the APPLyCommand
The
APPLy
the power supply over the remote interface. For example, the following statement executed from your computer will set the power supply to an output of 3 V rated at1 A:
‘‘APPL 3.0, 1.0’’
command provides the most straightforward method to program
Using the Low-LevelCommands
Although the program the power supply, the low-level commands give you more flexibility to change individual parameters. For example, the following statementsexecuted from your computer willset the power supply to an output of 3 V rated at 1 A:
‘‘VOLT 3.0’’Set output voltage to 3.0 V‘‘CURR 1.0’’Set output current to 1.0 A
78
APPLy
command provides the most straightforward method to
Chapter 4 Remote Interface Reference
Simplified Programming Overview
Reading a Query Response
Onlythe query commands (commands that end with “ ? ” ) willinstruct the powersupply tosend a response message. Queries return either output values or internalinstrument settings.For example, the following statements executed from your computer willread the power supply’s error queue and print the most recent error:
bus enter statementEnter error string into computer
print statementPrint error string
Selecting a Trigger Source
The power supply willaccept a ‘‘bus’’(software) trigger oran immediate internal trigger as a trigger source. By default, the ‘‘BUS’’ trigger sourceisselected. If you want the power supply to usean immediate internal trigger,you must select ‘‘IMMediate’’. For example, the following statements executed fromyour computer will set to an output of 3 V/1 Aimmediately:
‘‘VOLT:TRIG 3.0’’Set the triggered voltage level to 3.0 V
‘‘CURR:TRIG 1.0’’Set the triggered current level to 1.0 A
‘‘TRIG:SOUR IMM’’Select the immediate trigger as a source
‘‘INIT’’Cause the trigger system to initiate
4
79
Chapter 4 Remote Interface Reference
Simplified Programming Overview
Power Supply Programming Ranges
The
SOURce
available programmingvalue for a parameter varies according to the desired output rangeof the power supply. The followingtable lists the programmingvalues available and MINimum,MAXimum, DEFault and reset valuesof the Agilient E3632A power supply.
Refer to this table to identify programming values when programming the power
supply.
Table 4-1. Agilent E3632A Programming Ranges
VoltageProgramming Range0 V to 15.45V0 V to 30.9 V
CurrentProgramming Range0 A to 7.21 A0 A to 4.12 A
subsystem requires parameters for programmingvalues. The
0 - 15V/7A Range0 - 30V/4A Range
MAX Value15.45 V30.9 V
MIN Value0 V0 V
DEFault Value0 V0 V
*RST Value0 V
MAX Value7.21 A4.12 A
MIN Value0 A0 A
DEFault Value7 A4 A
*RST7 A
80
Chapter 4 Remote Interface Reference
Using the APPLy Command
Using the APPLy Command
The
APPLy
command provides the most straightforward method to program the power supply overthe remote interface. You can select the output voltage and current in one command.
APPLy {<voltage>| DEF | MIN | MAX}[,{<current>| DEF | MIN | MAX}]
This command iscombinationof as the newlyprogrammed values are within the presently selected range, the output voltageand current are changed as soon as the command isexecuted.
The
APPLy
command changes the power supply’s output to the newly programmed values only if the programmed values are valid within the presently selected range. An execution error willoccurif the programmed values are not valid within the selected range.
You can substitute ‘‘MINimum’’,‘‘MAXimum’’, or ‘‘DEFault’’ in place ofa specific value for thevalues of ‘‘0’’ volts and ‘‘0’’ amps. MAXselects the highest valuesallowed for the selected range.
The
default
of the presentlyselected range.If you specify only one parameter of the
regards it asvoltage setting value.
values of voltage and currentare ‘‘0’’ volts and ‘‘7’’ amps regardless
voltage
and
See
VOLTage
current
and
CURRent
parameters. MIN selects the lowest
Table 4-1 for details of parameters.
APPLy
command, the power supply
commands. As long
4
APPLy?
This command queriesthe power supply’spresent values and returns a quoted string. The voltage and current arereturned in sequence as shown in the sample string below (the quotation marks are returned as part of the string).
"15.00000,4.00000"
In the above string, thefirst number 15.00000 is the voltage setting value and the second number 4.00000 isthe current settingvalue.
voltage
and
current
setting
81
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
Output Setting and Operation Commands
Thissection describes low-level commands used to program the power supply. Although the programthe power supply, the low-level output setting commandsgive youmore flexibility to change theindividual parameters.
CURRent{<current>|MINimum | MAXimum|UP|DOWN}
Thiscommand programs the immediate current level of the power supply. The immediate level isthe currentvalue ofthe outputterminals.
The
CURRent
programmed value regardlessof the output range presently selected.Youcan substitute ‘‘MINimum’’ or ‘‘MAXimum’’ in place of a specific value for
the current parameter.MIN selectsthe lowest current values of ‘‘0’’ amps. MAXselects the highest current values allowed for the selected range.
This command also increases or decreasesthe immediate current level using the ‘‘UP’’ or ‘‘DOWN’’ parameter by apredetermined amount. The command
CURRent:STEP
increment setting will cause anexecution error -222 (Data out of range) when the maximum or the minimum rated current isexceeded.
APPLy
command provides the most straightforward method to
command changes the output of the power supply to the newly
sets theamount of increase or decrease. Noticethat a new
CURRent
Example
The following programsegments showhow to use the command to increase or decrease the output current with the command.
"CURR:STEP 0.01"Set the step size to 0.01 A
"CURR UP" Increase the output current
"CURR:STEP 0.02" Set the step size to 0.02 A
"CURR DOWN" Decrease the output current
82
CURRUP
or
CURRDOWN
CURR:STEP
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
CURRent? [MINimum | MAXimum]
Thisquery returns the presently programmed current level of the power supply.
programmable
CURRent:STEP {<numeric value>|DEFault}
This command sets the stepsize for current programming with the
UP
Toset the step sizeto the minimum resolution, setthestep size to ‘‘DEFault’’.The minimum resolutionof the step size is approximately0.12 mA. The
CURR:STEP? DEF
immediate current level increases or decreasesby the value of the step size.For example, the outputcurrent will increase or decrease 10 mA if the step size is0.01.
This command isuseful when you program the powersupply to the minimum resolution. At resolution.
CURR?MAX
and
CURRentDOWN
and
CURR? MIN
currentlevels for the selected range.
commands. See the example in the previous page.
returns theminimum resolution ofyour instrument. The
*RST
return the highest and lowest
, the step size isthe value of the minimum
CURRent
allowed
CURRent:STEP? {DEFault}
This query returns the value of the step size currently specified. The returned parameter isanumeric value. ‘‘DEFault’’ gives theminimum resolution of the step size in unit of amps.
CURRent:TRIGgered {<current>| MINimum | MAXimum}
This command programs the pending triggeredcurrent level.The pending triggered current level isaterminals when a trigger occurs. A pending triggered level is not affected bysubsequent
CURRent:TRIGgered? [MINimum | MAXimum]
Thisquery returns the triggered current level presently programmed. If no triggered level is programmed,the
MAX
and
triggered current levels.
CURRent
CURR:TRIG? MIN
stored
commands.
return the highest and lowest
value that is transferred to the output
CURRent
levelis returned.
programmable
CURR:TRIG?
4
83
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
CURRent:PROTection {<current>|MINimum|MAXimum}
This command sets the current level at which the overcurrent protection (OCP) circuit will trip. If the peak output current exceeds theOCP level,thenthe outputcurrent is programmed to zero. TheQuestionableStatus register ‘‘OC’’ bit isset (seethe
CURR:PROT:CLE
is removed.
page101). Anovercurrent condition can be cleared with
command after the condition that caused the OCP trip
CURRent:PROTection? {MINimum|MAXimum}
This query returns the overcurrent protection triplevel presently programmed.
CURR:PROT? MAX
programmable overcurrent trip levels.
and
CURR:PROT? MIN
return the maximum and minimum
CURRent:PROTection:STATe {0|1|OFF|ON}
This command enablesordisables the overcurrent protection functionof thepower supply. An overcurrent condition can be cleared with the
CURR:PROT:CLE
removed. At
command after the condition that caused the OCP trip is
*RST
, thisvalue isset to‘‘ON’’.
CURRent:PROTection:STATe?
Thisquery returns the state of the overcurrent protection function. Thereturned parameter is ‘‘0’’(OFF) or ‘‘1’’ (ON).
CURRent:PROTection:TRIPped?
Thisquery returns a ‘‘1’’ if the overcurrent protection circuit is tripped and not cleared or a ‘‘0’’ if not tripped.
CURRent:PROTection:CLEar
This command causes the overcurrent protection circuit to be cleared.After thiscommand, the output current is restored to the state it was inbefore the current protection trippedand the OCP trip level remains unchanged to the value presently programmed. Before sending thiscommand, lower the output current below the trip OCP point, or raise the OCP trip level above the output setting.
84
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
VOLTage {<voltage>| MINimum | MAXimum|UP|DOWN}
This command programs the immediate voltage level of the power supply.Theimmediate level isthe voltage valueof the output terminals.
The
VOLTage
programmed value regardlessof the output range presently selected.Youcan substitute ‘‘MINimum’’ or ‘‘MAXimum’’ in place of a specific value for
the voltage parameter. MINselects the lowest voltage values of ‘‘0’’ volts.selects the highest voltage values allowed for theselected range.
Thiscommand also increases or decreases the immediate voltage level using the ‘‘UP’’ or ‘‘DOWN’’ parameter by apredetermined amount. The command
VOLTage:STEP
increment setting will cause anexecution error -222 (Data out of range) when the maximum or the minimum rated voltageis exceeded.
command changes the output of the power supply to the newly
MAX
sets the amount of increase or decrease. Notice that anew
VOLTage
ExampleVOLT DOWN
The following program segments show how to use the
VOLT:STEP
"VOLT:STEP 0.01" Set the step size to 0.01 V
"VOLT UP" Increase the output voltage
"VOLT:STEP 0.02" Set the step size to 0.02 V
"VOLT DOWN" Decrease the output voltage
VOLTage? [MINimum | MAXimum]
Thisquery returns the presently programmed voltage level ofthe power supply.
programmable
VOLT? MAX
VOLT UP
command to increase or decrease the output voltage with the command.
or
and
VOLT? MIN
voltage levels for the selected range.
return the highest and lowest
4
85
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
VOLTage:STEP {<numeric value>|DEFault}
Thiscommand sets the stepsize for voltageprogramming with the
VOLT DOWN
and To set the step size to the minimum resolution, setthe step size to ‘‘DEFault’’.
The minimum resolutionof the step size is approximately0.55 mV. The
VOLT:STEP? DEF
immediate voltage level increases or decreases by the value of thestep size. For example, the output voltage will increase or decrease 10 mV if the step sizeis 0.01.
This command isuseful when you program the powersupply to the minimum resolution. At resolution.
commands. See the above example in the previous page.
returns the minimumresolution of your instrument. The
*RST
, the step size is the value of the minimum
VOLT UP
allowed
VOLTage:STEP? {DEFault}
This query returns the value of the step size currently specified. The returned parameter is a numeric value. ‘‘DEFault’’ gives the minimum resolution step size in unit of volts.
VOLTage:TRIGgered {<voltage>| MINimum | MAXimum}
This command programs the pending triggeredvoltage level. The pendingtriggered voltage level isa terminals when a trigger occurs. A pending triggered level is not affected bysubsequent
VOLTage
stored
commands.
valuethat is transferred to the output
VOLTage:TRIGgered? [MINimum | MAXimum]
This query returnsthe triggered voltage level presently programmed. If no
VOLT
triggered levelis programmed, the
VOLT:TRIG? MIN
and voltage levels.
return the highest and lowest
level is returned.
VOLT:TRIG? MAX
programmable
triggered
VOLTage:PROTection {<voltage>|MINimum|MAXimum}
Thiscommand sets the voltage level at which the overvoltage protection (OVP)circuit willtrip. If thepeak output voltage exceeds the OVP level,then the power supply output isregister ‘‘OV’’ bit is set (see with the trip is removed.
VOLT:PROT:CLE
shorted
by an internalSCR. The Questionable Statuspage101). An overvoltage condition can be cleared command after the condition that caused the OVP
86
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
VOLTage:PROTection? {MINimum|MAXimum}
Thisquery returns the overvoltageprotection trip level presently programmed.
VOLT:PROT? MAX
programmable overvoltage trip levels.
VOLTage:PROTection:STATe {0|1|OFF|ON}
This command enablesor disablesthe overvoltage protectionfunction. Anovervoltage condition can be cleared with the after the condition that causedthe OVP trip is removed. Atset to ‘‘ON’’.
VOLTage:PROTection:STATe?
Thisquery returns the state of the overvoltage protection function. The returned parameter is ‘‘0’’(OFF) or ‘‘1’’ (ON).
VOLTage:PROTection:TRIPped?
Thisquery returns a ‘‘1’’ if the overvoltage protection circuit is tripped and not cleared or a ‘‘0’’ if not tripped.
VOLTage:PROTection:CLEar
This command causes the overvoltage protection circuit to be cleared. After this command, theoutput voltage is restored to the state it was inbefore the protection feature occurred and the OVP trip level remains unchanged to the value presently programmed. Before sending thiscommand, lower the output voltage below the trip OVP point, or raise the OVPtrip level above the output setting.
and
VOLT:PROT? MIN
return the maximum and minimum
VOLT:PROT:CLE
*RST
, this value is
command
4
VOLTage:RANGe {P15V|P30V||LOW|HIGH}
Thiscommand selects an output range to be programmed bythe identifier. When 15V/7A range isselected, the current are limited to 15.45 volts and 7.21 amps. When 30V/4A range isselected, the
maximum programmable
and 4.12amps. ‘‘P30V’’ or ‘‘HIGH’’ is the identifier for the 30V/4A range and ‘‘P15V’’ or ‘‘LOW’’ is for the 15V/7A range. At
VOLTage:RANGe?
Thisquery returns the currently selected range. The returned parameter is‘‘P30V’’ (HIGH) or ‘‘P15V’’(LOW).
maximum programmable
voltage and current arelimited to 30.09 volts
*RST
,the 15V/7A range is selected.
voltage and
87
Chapter 4 Remote Interface Reference
Output Setting and Operation Commands
MEASure:CURRent?
This command queries the current measured across the current sense resistorinside the power supply.
MEASure[:VOLTage]?
This command queriesthe voltage measured at the sense terminalsof the power supply.
88
Chapter 4 Remote Interface Reference
Triggering Commands
Triggering Commands
The power supply’striggering systemallows a change involtage and current when receiving a trigger,to select a trigger source, and to insert a trigger. Triggering the powersupply isa multi-step process.
•First, you mustspecify the source from which thepower supply will accept the trigger. The power supply will accept a bus (software) trigger or animmediate trigger from the remote interface.
•Then, you can setthetime delay between the detection of the trigger on the specified trigger source and the start of any corresponding output change.
Notice that the time delay is valid for only the bus trigger source.
•Finally, youmust provideansource isselected, the selected output is set to the triggered level immediately.But if the trigger source is the bus, the power supply is set to the triggeredlevelafter receiving the Group Execute Trigger (GET) orcommand.
Trigger Source Choices
INITiate
command. If the
IMMediate
*TRG
4
Youmustspecify the source from which the power supply willaccept a trigger.The trigger is stored insupply has been off or after a remote interface reset.
Bus (Software) Triggering
•To select the bustrigger source,send the following command.
TRIG:SOUR BUS
•To trigger thepower supply from the remote interface (GPIB or RS-232) after selecting the bus source,send the
*TRG
is sent, the trigger action starts after the specified timedelay if any
delay isgiven.
volatile
memory;the source is set tobus when the power
*TRG
(trigger) command. When the
89
Chapter 4 Remote Interface Reference
Triggering Commands
•Youcan also trigger the power supply from the GPIB interface by sendingthe IEEE-488 Group Execute Trigger(GET)message. The following statement shows how to send a GET from a Agilent Technologies controller.
TRIGGER 705(group execute trigger)
•To ensure synchronization when the bus source is selected, send the
*WAI
(wait) command. When the waits for all pending operations to complete before executing any additionalcommands. For example, the following command string guarantees that the first trigger is accepted and is executed before thesecond trigger isrecognized.
command isexecuted, the power supply
*WAI
TRIG:SOUR BUS;*TRG;*WAI;*TRG;*WAI
•You can usethe (operation complete) command to signal when the operation is complete. The
*OPC?
is complete. TheEvent register when the operation is complete.
Immediate Triggering
•To selecttheimmediate trigger source, send the followingcommand.
*OPC?
(operation completequery) command or the
command returns ‘‘1’’ to the outputbuffer when the operation
*OPC
command sets the ‘‘OPC’’bit (bit 0) in the Standard
*OPC
TRIG:SOUR IMM
•When the command immediately transfers the
VOLT
IMMediate
or
CURR
is selected as a trigger source, an
VOLT:TRIG
value. Any delay isignored.
or
CURR:TRIG
INITiate
value to
90
Chapter 4 Remote Interface Reference
Triggering Commands
Triggering Commands
INITiate
Thiscommand causes thetrigger system to initiate. This command completes one full trigger cycle when the trigger source is an immediate and initiates the trigger subsystem when the trigger source isbus.
TRIGger:DELay {<seconds>| MINimum | MAXimum}
This command sets the time delay between the detection of an event on the specified trigger source and the start of any corresponding trigger action on the power supply output. Select from 0 to 3600 seconds. MIN = 0 seconds. MAX
*RST
= 3600 seconds. At
TRIGger:DELay?
Thiscommand queries the trigger delay.
TRIGger:SOURce {BUS | IMMediate}
This command selects the source fromwhich the powersupply willaccept a trigger. Thepower supply will accept a bus (software) trigger or an internalimmediate trigger. At
, this valueis setto 0 seconds.
*RST
, the bus trigger source is selected.
4
TRIGger:SOURce?
Thiscommand queries the present trigger source. Returns ‘‘BUS’’ or ‘‘IMM’’.
*TRG
Thiscommand generates a trigger to the trigger subsystem that has selected a bus (software) trigger as its source the same effectas theGroup Execute Trigger (GET) command. For RS-232 operation, make sure the power supply isinthe remote interface mode by sending the
SYST:REM
command first.
(TRIG:SOUR BUS)
.The command has
91
Chapter 4 Remote Interface Reference
System-Related Commands
System-Related Commands
DISPlay {OFF | ON}
Thiscommand turns the front-panel display off or on. When the display isturned off, outputs are not sent to the display and all annunciators are disabledexcept the
The display state is automatically turned on when you return to the local mode. Press the
This command displaysa message on the front panel. The power supply willdisplay up to12 characters in a message; any additionalcharacters aretruncated. Commas, periods, and semicolons share a display spacewith the preceding character, and arenot considered individual characters.
ERROR
Local
annunciator.
key to return to the local state from the remote interface.
DISPlay:TEXT?
Thiscommand queries the messagesent to the front panel and returns a quoted string.
DISPlay:TEXT:CLEar
This command clears the message displayed on the front panel.
OUTPut {OFF | ON}
This command enables ordisables the outputs of the power supply. When the output is disabled, thevoltage valueis 0 V and the currentvalue is20 mA. At
*RST
, the output state isOFF.
OUTPut?
This command queries the output state of the power supply. The returned value is ‘‘0’’ (OFF) or ‘‘1’’ (ON).
92
Chapter 4 Remote Interface Reference
System-Related Commands
OUTPut:RELay {OFF | ON}
This command sets the state of two TTL signals on the RS-232 connector. These signals are intended for use with an external relay and relay driver. The TTL output is available on the RS-232connector pin 1and pin 9. When the
OUTPut:RELay
9 is low (0.5 V). The levels arereversed when the‘‘OFF’’. At
state is ‘‘ON’’, the TTL outputof pin 1 is high (4.5V) and pin
OUTPut:RELay
*RST
, the
OUTPut:RELay
state is OFF.
state is
Note
Note
TTL output of pin 1 or pin 9 of the RS-232 connector is available only afterinstallingtwo jumpersinside the power supply. See the Service Guide formore information.
Do not use the RS-232 interface if you have configured the power supply to output relaycontrol signals. Internalcomponents on the RS-232circuitrymay be damaged.
OUTPut:RELay?
This command returnsthe state of the TTL relay logic signals. See also
OUTP:REL
SYSTem:BEEPer
Thiscommand issues a single beep immediately.
SYSTem:ERRor?
Thiscommand queries the power supply’s error queue. When the front-panel
ERROR
errors have been detected. Up to 20 errors can be stored in the error queue.
See ‘‘Error Messages’’ for acomplete listing ofthe errorsin
•Errors are retrieved in first-in-first-out (FIFO) order. The first error returned is the first error that was stored. When you haveread all errors from the queue, the timean error isgenerated.
•If more than 20errors have occurred, the last error stored in the queue (themost recent error) is replaced with errorsare stored untilyou remove errorsfrom the queue. If no errors haveoccurred when you read the error queue, the power supply responds with
+0, ‘‘Noerror’’.
•The errorqueue is cleared when powerhas beenoff or aftera status) command has been executed. The clear the error queue.
command.
annunciator turns on, one or more command syntax or hardware
chapter 5.
ERROR
annunciator turns off. The power supplybeeps once each
-350
, ‘‘
Too many errors
*RST
(reset) command
’’. No additional
*CLS
(clear
does not
4
93
Chapter 4 Remote Interface Reference
System-Related Commands
SYSTem:VERSion?
Thiscommand queries the power supply to determine the present SCPIversion. The returned value isof a stringin the form YYYY.Vwhere the ‘‘Y’s’’represent the year of the version,andthe ‘‘V’’ represents a version number for that year(for example, 1995.0).
*IDN?
This query command reads the power supply’s identification string. The power supply returns four fields separated by commas.Themanufacturer’s name, the not used (always ‘‘0’’), and the three numbers. The first number isthe firmware revision number for the power supplyprocessor; the second is for the third isfor the
The command returns a string with the following format (be sure to dimensiona string variablewith at least
front-panel
second
field is the model number, the
fourth
processor.
40 characters
field isa revision code which contains
input/output
):
first
field is the
third
processor; and the
field is
main
HEWLETT-PACKARD,E3632A,0,X.X-X.X-X.X
*RST
This command resets the power supply to its power-on state as follows:
Commandstate
CURR
CURR:STEP
CURR:TRIG
CURR:PROT
CURR:PROT:STAT
DISP
OUTP
OUTP:REL
TRIG:DEL
TRIG:SOUR
VOLT
VOLT:STEP
VOLT:TRIG
VOLT:PROT
VOLT:PROT:STAT
VOLT:RANG
7 A
0.12 mA(typical value)7 A
7.5 AON
ONOFFOFF
0BUS0 V
0.55mV (typical value)0 V
32 VONP15V (Low)
94
Chapter 4 Remote Interface Reference
System-Related Commands
*TST?
Thisquery performs a the self-testpasses or ‘‘1’’ or any non-zero value if it fails. If the self-test fails,an error message is also generated with additional information on whythe test failed.
*SAV { 1 | 2 | 3 }
Thiscommand stores the present state of the power supply to the specified location in
3) are available to store operating states of the power supply. The state storage
feature‘‘remembers’’ the states or values of the following commands:
CURR, CURR:STEP, CURR:TRIG, CURR:PROT, CURR:PROT:STAT DISP,
OUTP, OUTP:REL, TRIG:DEL, TRIG:SOUR, VOLT, VOLT:STEP, VOLT:TRIG,
VOLT:PROT, VOLT:PROT:STAT, and VOLT:RANG
To recall a stored state, you must use the same memory location usedpreviously to store the state.
*RCL { 1 | 2 | 3 }
This command recallsa previously storedstate. To recalla stored state,you must use the samememory location used previously to store the state.
non-volatile
complete
memory. Three memorylocations (numbered 1, 2 and
self-test ofthe power supply. Returns ‘‘0’’ if
4
Note DISP {OFF|ON}
Going tolocal mode automatically sets the display state to ON.
can bestoredand recalled in remote interface mode only.
95
Chapter 4 Remote Interface Reference
Calibration Commands
Calibration Commands
Seechapter 3 ‘‘CalibrationOverview’’, starting onpage66 for an overview of thecalibration features of the power supply. Formoredetaileddiscussion of the calibration procedures, see the Service Guide.
Note
When you calibrate the power supply, you should notset the OVP and OCPtoON state in order to preventOVP or OCP from tripping.
CALibration:COUNt?
Thiscommand queries the power supply to determine the number oftimes ithas been calibrated. Your power supply was calibrated before it left the factory. When you receive your power supply, read the count to determine its initialvalue. Since the value increments by onefor each calibration point, a complete calibration will increase thevalue by5 counts.
CALibration:CURRent <numeric value>
This command can only be used after calibration is unsecured and the output state is ON.It enters a current value that you obtained by reading an external meter.You must first select the minimum calibration level(
MIN
) for the valuebeingentered. You must then select themiddle and maximumcalibration levels () for the valuebeingentered. Three successive values mustbe selected and entered. The power supply then computes new calibration constants.Theseconstants are then stored in
This command can only be used after calibration is unsecured and the output state is ON. It sets thepower supply to a calibration point that isentered with
CAL:CURR
low-end point (MIN) must beselected and entered first.
command. Duringcalibration, threepoints must be entered and the
CAL:CURR:LEV MID
non-volatile
memory.
and
CAL:CURR:LEV
CAL:CURR:LEV MAX
CALibration:CURRent:PROTection
This command calibratesthe overcurrent protection circuit of the power supply.It takesabout 7 seconds to execute the command. The calibration must be unsecured and the output shorted before calibrating the overcurrent protection. The power supply automatically performs the calibration andstores the new overcurrentconstant in
current calibration precedes beforesending thiscommand.
96
nonvolatile
memory.
Notice that
Chapter 4 Remote Interface Reference
Calibration Commands
CALibration:DAC:ERRor
This command corrects the differential nonlinearity error of the internalDACwithout an external meter. You must send this command before calibrating the voltage. It takesabout 30 secondsto execute the command.
CALibration:SECure:CODE <new code>
Thiscommand enters a new security code. To change the security code, first unsecurethe power supply using theold security code. Then, enter the new code. The calibration code may contain up to 12 charactersover the remoteinterface but the first character must always be a
CALibration:SECure:STATe {OFF | ON},<code>
Thiscommand unsecures or secures the power supply for calibration. The calibration code may contain up to 12 characters over the remote interface.
CALibration:SECure:STATe?
Thiscommand queries the secured state for calibration of the power supply.The returned parameter is‘‘0’’ (OFF) or ‘‘1’’ (ON).
CALibration:STRing <quoted string>
Thiscommand records calibration information about your power supply. For example, you can store such information as the last calibration date, the nextcalibration due date, or the power supply’s serial number. The calibration message may contain up to40 characters.The power supply should be unsecured before sending a calibration message.
letter
.
4
CALibration:STRing?
Thiscommand queries the calibration messageand returns a quoted string.
CALibration:VOLTage[:DATA] <numeric value>
Thiscommand can only beused after calibration isunsecuredand the output state isON. It entersa voltage value that you obtained by reading an externalmeter.You must first select the minimum calibration level(
MIN
) for the valuebeingentered.You must then selectthe middle and maximum calibration levels (for the value being entered. Threesuccessive values must be selected andentered. The power supply thencomputes new voltage calibrationconstants.These constants are then stored in
CAL:VOLT:LEV MID
non-volatile
memory.
and
CAL:VOLT:LEV
CAL:VOLT:LEV MAX
97
)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.