The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
-2019 Printed in Germany
DOCUMENT CONTROL NOTE:
Document_standard_e_template_v05
Document ID: 58669036
Service Manual
►Manufacturer
Agfa NV
Published by
Agfa-Gevaert HealthCare GmbH
Tegernseer Landstraße 161
D - 81539 München
Germany
Copyright 2019 Agfa NV
All rights reserved.
Technical modifications reserved.
Agfa and the Agfa rhombus are trademarks of Agfa NV, Belgium, or its affiliates.
All other trademarks mentioned in this document are held by Agfa NV or the
respective owners and are used in an editorial fashion with no intention of
infringement.
Nothing contained in this legal notice nor in any text in this document shall be
construed as granting by implication, estoppel or otherwise, any license or right to
use any of the trademarks, service marks, trade names or logos appearing in this
document without the express prior written consent of their respective owner.
WARNING:
Improper operation or service activities may cause damage or injuries.
Read the "Generic Safety Directions" prior to attempting any operation, repair or
maintenance task on the equipment. Refer to Document ID 11849633
.
Strictly observe all safety directions within the "Generic Safety Directions" and on the
product.
IMPORTANT:
The installation and service of the product(s) described herein is to be performed
by qualified personnel who are employed by Agfa NV or one of its affiliates
or who are otherwise authorized by Agfa NV or one of its affiliates to provide such
services.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 2 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
LIST OF CONTENTS
0 ABOUT THIS MANUAL ......................................................................................................... 6
0.1 Purpose of this document ......................................................................................................... 6
0.2 Changes compared to previous revision .................................................................................. 6
13.1 DX-D Retrofit - Instant DR (self-triggering) – 2 x wireless ...................................................... 89
13.2 DX-D Retrofit - Instant DR (self-triggering) – 1 x wireless and 1 x wired................................ 90
13.3 DX-D Retrofit - Instant DR (self-triggering) – 2 x wired........................................................... 91
13.4 DX-D Retrofit – DR system with Generator control – 2 x wireless ......................................... 92
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 5 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
This document contains all information that
well as for corrective and preventive maintenance of the
It does
•
•
•
•
•
•
•
, that the network interface card cannot be
•
•
•
0 About this manual
0.1 Purpose of this document
service engineers need for installation as
not contain:
Spec ific service information for other target readers, e.g. Clinical Application
Specialists or Service Managers
Service Bulletins
0.2 Changes compared to previous revision
Corrected information for user training with respect to clicking another thumbnail
short after exposure. Refer to section
Added EPS detector variant in section 1.15 and section 4.
Adapted detector IP address setup in sections 1.10., 4.4.6. and 13.
Added table with information about Dual Plus and Dual Minus bandwidth
parameter. Refer to section
Removed information in section 1.10.1
used for other devices simultaneously (e.g. DR 600 Positioner or DR 14s
detector).
Added troubleshooting an unknown IP address using a Jig connector. Refer to
section
Added IRI 3.0 in section 10.5.
Added IRI upgrade instructions in section 11.1.
7.1.3.3.
4.12.
4.10.
DR 10e / DR 14e / DR 17e.
0.3 Referenced documents
Document Reference
Generic Safety Directions Document ID 11849633
Refer to the DR wireless
networking manual
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 6 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DR 10e / DR 14e / DR 17e User
Manual 0370
DX-D DR Detector Calibration Key
User Manual
System specific User Manual Refer to the Agfa Medimg Library
DOCUMENT CONTROL NOTE:
Document ID 58221971
Refer to the Agfa Medimg Library
Refer to the Agfa Medimg Library
Document ID: 58669036
Service Manual
Safety-relevant Notes
Icon
Signal Word
Situation
None-Safety-relevant Notes
Icon
Name
Type of Information
graphical user interface.
Highlighting of buttons, functions and names within a task
Install client or
Courier New bold
0.4 Explanation of notes
CAUTION:
WARNING:
DANGER:
-
-
IMPORTANT:
NOTE:
Hazardous situation which, if not avoided, can lead to a minor
injury to a user, engineer, patient or any other person.
Hazardous situation which, if not avoided, can lead to a potential
serious injury to a user, engineer, patient or any other person.
Direct, immediate danger: If not avoided, it can lead to a serious
injury to a user, engineer, patient or any other person
Instruction to avoid damage to equipment and/or environmental
pollution.
Prohibition to avoid damage to equipment and/or environmental
pollution.
Highlights very important actions which have to be carried out to
prevent malfunction.
•Indicates advice to facilitate the following step or action
without having a direct influence on the step or action.
• Highlights unusual points.
• Indicates background information.
• Can be used to explain or highlight displays of the
0.5 Conventions
Highlighting of tasks
Task number Task Description Remark
(1) Connect the cable.
(2) Switch the machine on.
(1) Press F9 or double-click the
Refresh button.
(2) If the
server? prompt appears,
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 7 of 92
03-2019 Agfa Company Confidential
type server.
DOCUMENT CONTROL NOTE:
Examples for working steps to be performed in
the listed sequence.
The bold typeface is used for menu topics, keyboard
keys, icons, device buttons, commands etc.
The
messages and prompts.
typeface is used for system
Document ID: 58669036
Service Manual
The intended use statement is listed in the
DR 10e /
1A
DR 10e C
1B
DR 14e C / G
1C
DR 17e C / G
innolux_DR14e.cdr
innolux_DR17e.cdr
1 Product description
1.1 Intended use
DR 14e / DR 17e DR Detector.
1.2 Components of the product
Following components are required to integrate the DR Detector into a DR system:
For how to obtain the different components as sales items refer to the DR system
specific sales information. Most parts are also available as spare parts.
Refer to section 12.
# Component / Purpose Picture
Available as CSI (Cesium iodide)
wireless DR Detector.
Captures X-ray images.
Dimension: 268 x 328 x 15 mm
Available as CSI (Cesium iodide) or GOS
wireless DR Detector.
Captures X-ray images.
Dimension: 384 x 460 x 15 mm
User Manuals of the
Available as CSI (Cesium iodide) or GOS
(Gadolinium oxysulfide) wireless DR
Detector.
Captures X-ray images.
Dimension: 460 x 460 x 15 mm
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 8 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
2
Battery charger
3
Additional battery
4
D-Link network switch DGS-105 (optional)
8 port switch DGS-108
5
DR Generator Sync Box (optional)
section 13, Wiring diagrams.
6
Access point (optional)
Refer to the DR wireless
ID 58221971
7
Standard, straight network cable CAT 5 (or
diagrams.
# Component / Purpose Picture
Provides power to two batteries for
simultaneous recharging.
Infor ms the user about battery status.
Includes an AC/DC adapter
Input voltage 100 to 240 V AC
Output voltage / current 16 V DC, 6.5 A
Input connector: C8
Output connector D-Sub 9 female
Can be used for DR 10e, DR 14e or DR 17e.
5 port unmanaged switch
Connects the different network devices.
Also supported:
Interface between Generator and NX for
exposure sync signals.
DR Detector control (Panel 1 to Panel 4) is
not connected. VARCAN interface(s) not
used.
Not required for Instant DR (self-triggering),
DX-D 100 and DX-D 300. For details refer to
CAT 6)
Up to three network cables are required,
depending on the DR system.
For details refer to section 13
, Wiring
networking manual, Document
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 9 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
8
PCIe Intel Gigabit CT desktop adapter
9
USB to Ethernet adapter (optional)
10
Powerbox (optional)
11
Registration cable
not be used for image transfer.
12
Detector specific CD
Rear view
Power
Ethernet
Detector
# Component / Purpose Picture
Image interface for the DR Detector. Can be
used for up to four DR detectors.
Not required for notebooks.
Network interface to the hospital network for
notebooks. In this case the on-board network
interface is used for connection to the
detector.
Required for wired connection.
Cable length: 10 m
Provides power for the detector (battery can
remain inserted). For more details refer to
section 1.14.
259 mm (width) x 205 mm (depth) x 70 mm
(height).
Weight 3.2 kg
Connects the detector to the network card or
network switch. Does not provide power.
Length 80 cm.
• Required by the FSE during installation to
write system specific data to the detector.
• Required by the user to write wireless
networking data for detector sharing. May
Comes with each DR 10e, DR 14e and
DR 17e DR Detector.
Has a serial number label attached on the
cover.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 10 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
NOTE:
The detector does not have a power switch.
Reboot is done by taking out the battery for a few seconds.
innolux_009.cdr
Green
Battery status
Cable connector
READY
ON: Exposure possible
OFF: Not ready
Blinking 1/sec: Exposure*
Blinking 1/sec: Error occured*
POWER
ON: Power ON
OFF: Power OFF
ERROR
Blinking 1/sec: Error occurred*
OFF: Normal
LINK
ON: Connected
OFF: No ommunicationc
Blue
Orange
White
* If green, blue and red LED light up:
Defective battery is inserted.
1.3 Technical Data
The technical data are listed in DR 10e, DR 14e, DR 17e User Manual on the
Agfa Medimg Library
.
1.4 Connections and LEDs at the DR Detector
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 11 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Figure 1
Document ID: 58669036
Service Manual
Type Label
Battery
removed
Serial number (Example)
Located below battery
innolux_010 .cdrB
1.5 Serial number label and type label
The following figure shows the location of the serial number label.
Figure 2
The figure next page shows the type labels.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 12 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
innolux_010 .cdrA
0
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 13 of 92
03-2019 Agfa Company Confidential
Figure 3
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
NX Workstation
Instant DR (self-triggering)
innolux_017.cdr
NX
XRDI
SPM or
SDL or
SMS
RFBC*
* RFBC not installed in case of
USB connection between
Generator Sync Box and NX.
DR Generator
Sync Box
IRI
Generator
Generator
Control (optional)
Image & Control
DR 10e / DR 14e / DR 17e
DR 10e / DR 14e / DR 17e
DR 10e / DR 14e / DR 17e
NX Workstation
NX
XRDI
SPM or
SDL or
SMS
IRI
Control
Image & Control
Control
Control
RFBC = etro it ox ontrolR fB C
IRI = nnolux adiographic nterfaceIRI
XRDI = - ay evice nterfaceXr di
SPM = ell an Generator ComponentSp m
SDL = e eca Generator ComponentSd l
SMS = ie en Generator ComponentSm s
SSC = edecal oft onsoleSSC
THX = ec ni Generator ComponentT hx
SSC (DX-D 100/300)
THX (DR 100e) or
Generator
NX Workstation
DX-D 100 / DX-D 300 / DR 100e
NX
XRDI
IRI
Control
Image &
Control
DR systems with sync via DR Generator Sync Box
1.6 Software and hardware overview
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 14 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Figure 4
Document ID: 58669036
Service Manual
Software Components
Component Comment
XRDI X-ray device interface. Generic software component, which
interfaces between the NX application software and other, system
specific software interfaces.
RFBC Optional. Retrofit Box Control. Software interface for the control of
the DR Generator Sync Box via Ethernet.
SPM Optional. Spellman Generator Component. Software interface for the
control of the Spellman Generator.
SDL Optional. Sedecal Generator Component. Software interface for the
control of the Sedecal Generator.
SMS Optional. Siemens Generator Component. Software interface for the
control of the Siemens Generator.
SSC Optional. Sedecal Soft Console. Software interface for the control of
the Soft console on NX (r i ght par t of the GUI) and for control of the
Sedecal Generator.
THX Technix Generator Component. Software interface for the control of
the Technix (DR 100e) Generator.
IRI Innolux Radiographic Interface. Software interface for i mage and
control data of the DR 10e / DR 14e / DR 17e DR Detector.
1.7 Connection modes
Image transfer between detector and NX can be wireless or wired. For wired
connection the Power Box is required. A mix of wireless and wired connection in a
system is possible.
For example system wiring diagrams refer to section 13, Wiring diagram.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 15 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
The
example DR 100e, DX
For release status refer to the DR system specific
The released systems can also be looked up in the simplified ELMS DR Sub product
Interoperability Matrix, Document ID
where the IRI detector software component can be installed.
1.8 Exposure modes
The detector can be configured on NX for exposure control by the Generator or autotrigger mode. In auto-trigger mode the detector senses the X-ray beam, what is the
trigger to start image capture.
Generator control can be:
• Integrated, this means the detector gets the signal to start image capture by the
Generator. This is called router mode on the DR Generator Sync Box. In this mode
the Generator Sync Box is just routing the exposure signals through.
• Non-integrated, this means the DR Generator Sync Box sends the exposure signal
to the Generator. After the configured prepdelay, the detector starts image capture.
This is called retrofit mode on the DR Generator Sync Box.
1.9 Supported DR systems
DR 14e / DR 17e is initially supported in a limited number of Agfa DR systems, for
-D Retrofit and DR 400.
Service Manual.
35878296. This document lists these systems,
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 16 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
NOTE 1
The IRI
based on the following criteria:
1.10 Default and supported IP addresses
The following table lists the default IP address for a component from stock.
For recommended IP addresses in the system refer also to the wiring diagrams in
section 13.
DR 10e /
DR 14e /
DR 17e
Network
interface
in NX
DR
Generator
Sync Box
Access
point
Factory IP
address
Supported IP address
up to IRI 2.1
192.168.0.30 Automatically assigned
to 192.168.0.ZZZ with
ZZZ = 31 to 255 except
40.
See NOTE below.
Not defined 192.168.0.10
Adapter name: Eth1
Mandatory setting.
See 1.10.1.
192.168.100.30 192.168.0.ZZ
with ZZ < 30
Recommended
192.168.0.15
Depends on
access point
model
192.168.0.ZZ
with ZZ < 30
Recommended:
192.168.0.20
Supported IP address
as of IRI 3.0
Initial IP address
assignment like for
IRI ≤ 2.1. See NOTE
below. Subnet YYY of
IP address
192.168.YYY.ZZZ can
be adapted. See 0.
Initially 192.168.YYY.10
with YYY = 0.
Adapter name: Eth1
Mandatory setting.
See 1.10.1.
Initially 192.168.YYY.ZZ
with YYY = 0
and ZZ < 30
Recommended
192.168.0.15
192.168.YYY.ZZ
with YYY = 0
and ZZ < 30
Recommended:
192.168.0.20
• IP address range 192.168.0.31 to 192.168.0.255 except 192.168.0.40.
• IP address is calculated based on the detector serial number: When removing the
detector from the IRI Panel Installation Tool and configuring it again, the IP
address will be the same.
• If the calculated IP address is already assigned to another DR 10e, DR 14e or
DR 17e, automatically another IP address in the supported range is assigned.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 17 of 92
03-2019 Agfa Company Confidential
:
Panel Installation Tool assigns the IP address to the detector automatically
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
NOTE
As of NX 3.0.8950 the software looks for the network adapter name "Local Area
Connection XYZ"
Address of the network adapter on the PC's motherboard. In case of a different name
the licensing ser
For the
“Eth
licensing component on NX, which
For the network interface on NX the
following restrictions apply:
•
•
•
The IRI
these re
setup.
NOTE:
General rule for NIC (Network Interface Card) IP setup:
Each NIC on NX must be in its own subnet.
Example: If one NIC is set to 192.168.
192.168.
2:
(for example “Local Area Connection 2”) to determine the MAC
vice fails to retrieve the MAC address of that adapter.
DR 10e, DR 14e and DR 17e it is required to rename the network adapter to
1”. To prevent a failing licensing service, the IRI software also installs a new
does not have this restriction anymore.
1.10.1 Restrictions, specific for DR 10e, DR 14e, DR 17e network setup
The name of the network interface
must be Eth1. This name is case
sensitive.
The IP address must be
192.168.YYY.10
YYY = 0 for IRI ≤ 2.1
YYY = 0 to 255 for IRI ≥ 3.0
No second IP address must be
Figure 5
configured.
Panel Installation Tool checks
quirements at the end of the
0.10, the other must be for example on
100.10.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 18 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
As of software IRI 3.0 it is possible to
adjust the IP address 192.168.YYY.ZZZ.
This way it is possible to change the
default subnet 192.168.0
example
192.168.0 is already used by the
hospital.
Changing the IP address is done in the
IRI panel installation tool via dropdown.
1.10.2 Changing the IP address as of IRI 3.0
• YYY can be changed in the range of
0 to 255 (new with IRI 3.0).
• ZZZ is automatically assigned by the
IRI panel installation tool
(assignment mechanism
independent of IRI software).
to – for
– 192.168.1, if the subnet
Figure 6
Figure 7
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 19 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
NOTE:
If the IP address of a DR 10e, DR 14e, DR 17e is unknown, there are t
possibilities
to find it back:
•
•
•
Basic rules for IP address setup:
# Rule Example
1 Only change the subnet if
needed.
2 When changing the IP address
setup, label the detector with
the changed IP address.
3 Before starting the IRI panel
installation tool to install a new
detector, adapt the IP address
of the NIC to the detector
subnet.
4 When changing the NIC IP
address, restart the IRI panel
installation tool. Reason: IP
address is only checked at
startup of the tool.
5 When adding a second
detector to a system, where
the default IP address has
been changed, ignore
messages about differences in
the subnet. These messages
will be gone when the network
interface IP address is adapted
again.
192.168.0 is occupied by the hospital
network. Change subnet to 192.168.1.
Either use a sticker or write the changed IP
address (for example 192.168.1.170) on the
detector cover, below the battery.
Subnet is changed to 192.168.1.
To install a new detector, change IP
address of NIC temporarily back to default
192.168.0.
IP address is changed from 192.168.0.170
to 192.168.1.170.
NIC IP address is changed to 192.168.1.10.
Now the IRI panel installation tool needs to
be restarted to allow again connection to the
detector.
Figure 8
6 Detector sharing when the
default IP address has been
changed: The subnets for the
detector must be the same on
both NX.
Subnet for detector is 192.168.100.ZZZ.
When sharing the detector, change the
network interface on the other NX to
192.168.100.ZZZ before starting the IRI
Panel Installation Tool.
Possibility 1: Connect the registration cable to the detector. Start the IRI panel
installation tool: The IP address of the detector is shown.
Possibility 2: Look up the IP address of the NIC. This shows the correct subnet.
Possibility 3: Reset to default by using a Jig connector. For details refer to section
7.1.3.3.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 20 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
hree
Document ID: 58669036
Service Manual
IMPORTANT:
When adding a detector to a system, the calibration data on the detector are erased.
As a consequence:
•
•
1.11 Detector sharing
Detector sharing means: Using a DR Detector at different systems, e.g. DR 100e and
DX-D Retrofit.
When changing from one system to another, the user needs to register the DR
Detector at NX.
The registration workflow works as follows:
• User ensures that no active thumbnail is present for another DR 10e, DR 14e or
DR 17e configured at the system (as long as a thumbnail is active, registration
will not work).
• User connects the detector to the NX either via short registration cable or via
Power Box.
• After some seconds the detector switch shows the wired icon for this
detector.
• In case of wireless detector usage: Disconnect the registration cable.
• When changing from wireless to wired: Reboot detector by removing battery
and detector cable.
• When changing from wired to wireless: Reboot detector by removing and
inserting battery.
• Detector is ready.
During registration following data are written to the DR Detector:
• Access point SSID
• Access point PSK Key
In case the DR detectors are configured for different trigger mode on the two systems
(Exposync / Self Trigger Mode), a reboot of the DR Detector is required after having it
registered on another NX.
First add all detectors to all systems, then perform calibration at the main NX for
this detector.
If a detector is added later on to a system (e.g. customer bought an additional Agfa
DR system), detector calibration has to be redone at the main NX.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 21 of 92
03-2019 Agfa Company Confidential
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
Note that the procedure to
•
•
•
•
A video clip on the Agfa
ID
DR 17e.
register a detector differs for different detector brands:
The DR 10e / DR 14e / DR 17e is registering automatically by connecting the
registration cable or Power Box cable.
On the DX-D 30 / D X-D 35 DR Detector the user needs to press the power switch
in front of the IR data communication unit shortly to initiate registrat ion.
The DR 10s / DR 14s registers automatically as soon as the detector is close
enough to the IR data communication unit.
The DX-D 4 0 / DX-D 45 requires cable connection to the system control unit (SCU).
Medimg Library explains detector sharing. Refer to document
57923570. This video clip does not contain detector sharing for DR 10e / DR 14e /
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 22 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
1.12 Panel sleep mode
In the “IRI Panel Installation Tool” t wo parameters can be set to save battery power:
Parameter Description
Time out sleep
Default: 15 min.
Range:
15 to 99 min.
or Never
Time out shut
down
Default: 15 min.
Range:
15 to 99 min.
or Never
Both timers only work if both of the following conditions are fulfilled:
• The DR Detector is in WiFi range
• NX application is running
Reason: NX is the master for both timers.
The timers are also not used for following conditions:
• When a thumbnail is active for a DR 10e, DR 14e or DR 17e.
• During DR Detector calibration.
• In case of a detector related error message.
1.13 Recovery of images
For image recovery in case the image could not be sent to the NX e.g. due to WiFi
transmission problems, refer to the Application Note “DR image recovery on the NX
Workstation”, Document ID 43993890
Indicates the idle time after which the panel will go to sleep. In
sleep mode, the panel’s battery consumption is much less than
when not asleep. In sleep mode the DR Detector is only
listening to messages from the NX. The detector is not
operational.
The DR Detector wakes up again, when the user clicks a
thumbnail on NX for this DR Detector.
Indicates the time asleep after which the panel will
automatically shutdown. So this timer will only start after the
panel has been asleep for a while. For example, when both
values are on 15, then after 15 minutes idle time the DR
Detector will go asleep and 15 minutes later, the DR Detector
will shutdown. Any user actions in NX towards the DR Detector
will reset the timers.
In this mode the blue LED of the detector is still ON, but the
detector can only be started again by removing and reinserting the battery. The battery indicator on the detector rear
is off in this mode.
.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 23 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
Power status LED
Ethernet connection
C13 power input connector
10 m cable to detector
(non-detachable on Powerbox)
innolux_057.cdr
1.14 Powerbox connection
The Powerbox allows a permanent or temporary cabled connection between NX and
DR 10e, DR 14e or DR 17e.
This can be required for example, if in a retrofit solution the bucky design prevents a
reliable wireless connection.
Functions of the Powerbox:
• Provides power for the detector.
• Provides cabled connection for image transmission.
Figure 9
It is possible to use the Powerbox for different detectors, but only one detector at a
time. See also wiring examples in sections 13.2 and 13.3.
The Power Box is a simple device: It just adds power to the detector. The incoming
Ethernet cable is looped through. In fact the cable has the same functionality as the
regis tratio n cable, apart from the power supply.
As the Power Box gives power to the detector, a battery in the detector is not needed
during operation. The battery can also be left in during operation with the Powerbox. In
this case the battery is charged by the Powerbox. This might be usefull when using the
detector for cabled and wireless image transmission a t a system.
Due to its narrow operating temperature range (refer to section 1.14.1, Powerbox
technical data), the Powerbox is not suited to be built in a cabinet without additional
cooling.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 24 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
INLET
DC12V
AC100-240V
50-60Hz
MPS65A Board
GND Line
DC Line
AC Line
Signal
Board
Parts
2A
Signal
Signal
LED
LAN
conne
ctor
Power Box
NX
DR 10e / DR 14e /
DR 17e
innolux_021.cdr
Noise Filter
NFB
51A
Board
Power Supply
Pulse Transformer
LAN cable
~
1.14.1 Powerbox technical data
Operating conditions
Parameter Value
Temperature 15°C (15% RH) to 30°C (80% RH)
Humidity 15% RH (15°C) to 80% RH (30°C) no dew condensation
Atmospheric pressure 700 hPa – 1060 hPa
Power Supply Conditions
Parameter Value
Rated voltage 100 to 240 VAC
Input current 2.0 to 0.84 A
Frequency 50 to 60 Hz
Figure 10: Powerbox block diagram
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 25 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
205 mm
70 mm
259 mm
innolux_028.cdr
DR 14e
DR 10e
Connector
Connector
Connector
Rear view
Cover
Status lamps
Status lamps
Status lamps
DR 17e
innolux_029.cdr
Dimensions
Parameter Value
Widt h x depth x height 259 mm x 205 mm x 70 mm
Figure 11
Cable connection is at the detector front side. The cable outlet direction can be to the
left or to the right (default: right). The cable outlet direction can be changed by the Field
Service Engineer. Refer to instructions in section 4.3.3.1.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 26 of 92
03-2019 Agfa Company Confidential
Figure 12
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
NOTE:
EPS (Easy Payment Scheme) is a business model, where the customer buys a
time
The EPS
recognized by an EPS label in the rear
of the
There is no difference in installation,
troubleshooting and replacement
compared to a non
1.15 EPS variant of the DR 14e
-limited license for the detector, which can be renewed by the customer.
variant of the DR 14e can be
detector.
Restrictions:
• EPS detector only gets ready on NX, if the NX dongle contains a valid EPS license.
Typical payment scheme:
o The first 10 days after installation: Grace period, where detector also works
without license.
o The first 3 months no license fee must be paid.
o After 3 months, the customer needs to renew the license monthly by a payment
in the EPS customer portal.
o For details to licensing refer to the EPS for DR Detectors - Service Manual –
Document ID 67216623
• Only one EPS detector per NX.
• No mix EPS / non-EPS detector.
• Not possible to change EPS detector to a non-EPS detector by firmware update.
• Codemeter dongle required on NX. This needs to be ordered separately.
• At detector replacement, the new detector needs to be transferred to the license
(described in EPS for DR Detectors - Service Manual).
-EPS detector.
Figure 13
.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 27 of 92
03-2019 Agfa Company Confidential
DOCUMENT CONTROL NOTE:
Document ID: 58669036
Service Manual
IRI Panel installation tool adaptations for an EPS detector
The DR 14e EPS detector is supported as of IRI 3.0.
The IRI Panel Installation Tool is adapted as follows:
• An EPS detector can be recognized by “EPS” added to the “Panel Type”.
• A yellow text line indicates status messages.
• An orange text line indicates a problem with the detector or the EPS license.
• The Add Panel button is gray, as only one EPS detector is allowed per NX.
The controlled version of this document is available from the Agfa Me di m g Libr ar y. Any printed copy of this document is uncontrolled.
Edition 1, Revision 6 DR 10e / DR 14e / DR 17e Page 28 of 92
03-2019 Agfa Company Confidential
Figure 14
DOCUMENT CONTROL NOTE:
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.