ABB ACS380 User Guide

User Interface Guide
ACS380
Control panel
1. Status light
2. Local / remote
3. Status icons
4. Reference value
5. Actual value
6. Back / Options
1
6
7
Status light
green, steady: OK green, blinking: Warning red, steady: Fault red, blinking: Fault, turn power off
to reset
7. Stop
8. Edit value / Move in menus
9. OK / Select / Save / Menu
10. Start
2 43
5
9
8
10
1. Control location
2. Active fault
3. Active warnings
4. Forward / Reverse
1 4
2 5
3
5. Reference
Motor data
1. Motor type
• AsynM
• PMSM
• SynRM
2. Nominal power
3. Nominal voltage
4. Nominal speed
5. Phase order
Change direction without reconnecting motor cables
6. Unit selection
7. Control mode
Scalar or vector
8. Nominal current
9. Nominal frequency
10. Nominal torque
11. Nominal cos phi
1 7
2
3
4
5
6
Parameters
Direct access to all functions (advanced)
1. Complete list
2. Reset to factory defaults
3. Modied only
1
2
1. Start mode
2. Acceleration
3. Max.
4. Min. allowed
5. Stop mode
8
1. Active fault
2. Active
9
10
3. Fault history
4. Connection
11
1. Saved
2. Saved
3
3. Cost per
4. Saved
Motor control
Const time
Automatic
time
allowed speed
speed
Coast
Ramp
DC Hold
Diagnostics
warnings
status
Energy efciency
energy in kWh
energy in MWh
kWh
money
6. Deceleration time
7. Max. allowed current
1 5
2 6
3 7
4
1 3
2 4
5. Saved money x1000
1 4
2 5
3
Control macros
The menu content depends on the installed extension module.
I/O control:
1
1. I/O control macro
Fieldbus control:
1. Protocol
2. Address
1
2
settings
I/O control macros
Standard (2-wire)
AI1: Reference DI1: Start / Stop DI2: Forward / Reverse DI3: Constant speed sel1 DI4: Constant speed sel2 DIO1: Ramp pair selection DIO2: Ready run
ABB limited 2-wire
Integrated panel: Reference DI1: Start / Stop DI2: Constant speed sel1
For the full manual, go to:
3AXD50000022224 Rev. B EN
Alternate
AI1: Reference DI1: Start forward DI2: Start reverse
(if DI1 = DI2, stop) DI3: Constant speed sel1 DI4: Constant speed sel2 DIO1: Ramp pair selection DIO2: Ready run
Motor potentiometer
DI1: Start / Stop DI2: Forward / Reverse DI3: Reference up DI4: Reference down DIO1: Constant sel1 DIO2: Ready run
PID
PID
AI1: Setpoint AI2: Feedback DI1: Start / Stop DI2: Constant setpoint 1 DI3: Constant setpoint 2 DI4: Constant speed 1 DIO1: Ramp pair selection DIO2: Ready run
Fieldbus control macros
CANopen
EtherCAT
PROFIBUS
Pronet
Ethernet/IP
Modbus
Modbus TCP
TCP
Modbus
Modbus RTU
RTU
Start/stop/reference from the eldbus
DI1: Fault reset DI2: Not congured
Warnings/Faults
Warning Fault Description
A2A1 2281 Warning: Current calibration
A2B1 2310 Overcurrent. The output
A2B3 2330 Earth leakage. A load
A2B4 2340 Short circuit. There is a
A3A1 3210 DC link overvoltage. There
A3A2 3220 DC link undervoltage. There
A5A0 5091 Safe torque off. The Safe
AFF6 Identication run. The motor
is done at the next start. Fault: Output phase current measurement fault
current is more than the internal limit. This can be caused by an earth fault or phase loss.
unbalance that is typically caused by an earth fault in the motor or the motor cable.
short circuit in the motor or the motor cable.
3130 Input phase loss. The
intermediate DC circuit voltage oscillates.
3181 Cross connection. The
input and motor cable connections are incorrect.
is an overvoltage in the intermediate DC circuit.
is an undervoltage in the intermediate DC circuit.
3381 Output phase loss. All three
phases are not connected to the motor.
torque off (STO) function is on.
ID run occurs at the next start.
FA81 Safe torque off 1. The Safe
torque off circuit 1 is broken.
FA82 Safe torque off 2. The Safe
torque off circuit 2 is broken.
Loading...