ABB ACH580-31 Installation Instructions

ABB drives for HVAC
EN
USA
Quick installation guide
ACH580-31 drives
English . . . . . . . . 3
English - USA. . 11

List of related manuals

Drive manuals and guides Code (English)
ACH580 HVAC control program firmware manual 3AXD50000027537 Quick start-up guide for ACH580 HVAC control program 3AXD50000047658 ACH580-31 hardware manual ACH580-31 quick installation guide ACX-AP-x assistant control panels user’s manual
Option manuals and guides
ACS580, ACH580 and ACQ580 d rive module frame s R3, R5 to R9 for cabinet installation (options +P940 and +P944 supplement
ACS880-X1 and ACX580-31 +H358 gland plate installation guide
CDPI-01 communication adapter modul e user's manual FBIP-21 BACnet/IP adapter module FCAN-01 CANopen adapter module user's manual FCNA-01 ControlNe t adapter module user's manual FDNA-01 DeviceNet™ adapter module user's manual FECA-01 EtherCAT adapter modul e user's manual FENA-01/-11/-21 Ethernet adapter module user's manual 3AUA0000093568 FEPL-02 Ethernet POWERLINK adapter module user's manual 3AUA0000123527 FLON-01 L FPBA-01 PROFIBUS DP adapter module user's manual FSCA-01 RS-485 adapter module user's manual 3AUA0000109533
Tool and maintenance manuals and guides
Drive composer PC tool user's manual 3AUA0000094606 Converter module capacitor reforming instructions NETA-21 remote monitoring tool user's manual NETA-21 remote monitoring tool installation and start-up guide 3AUA0000096881
You can find manuals and other product documents in PDF format on the Internet. See section Document library on the
Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB
representative.
ONWORKS® adapter module user’s manual 3AUA0000041017
3AXD50000037066 3AXD50000048001 3AUA0000085685
3AXD50000210305
3AXD50000110711
3AXD50000009929 3AXD50000028468 3AFE68615500 3AUA0000141650 3AFE68573360 3AUA0000068940
3AFE68573271
3BFE64059629 3AUA0000096939
3AXD50000048001 B EN
EFFECTIVE: 2018-03-07 2018 ABB Oy. All Rights Reserved.
EN – Quick installation guide 3

EN – Quick installation guide

This guide briefly describes how to install the drive. For complete information on installation, see ACH580-31 drives hardware manual (3AXD50000037066 [English]). For start-up instructions, see ACH580 drives with HVAC control program quick start- up guide (3AXD50000047658 [English]).
To read a manual, go to www.abb.com/drives/documents number.
and search for the document

Obey the safety instructions

WARNING! Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur:
• Only qualified electrical professionals are allowed to install and maintain t ive.
dr
• Never work on the drive, motor cable or motor when main power is applied. If
the drive is already connected to the input power, wait for 5 minutes after disconnecting the input power.
• Never work on the control cables when power is applied to the drive or to t
ernal control circuits.
ext
• Do not connect the drive to a voltage higher than what is marked on the ty
ignation label.
des
• Always ground the drive, the motor and adjoining equipment to the protecti
ear
th (PE) bus of the power supply.
•Frames R6:
g device for lifting. Do not tilt the drive. Manual lifting, or overturning due to the
liftin tilting, can cause physical injury. Make sure that the wall and the fixing devices can carry the weight.
• Make sure that debris from drilling, cutting and grinding does not enter the drive.
• Make sure that the floor below the drive and the wall where the drive is install
ar
e non-flammable.
The drive module is heavy and its center of gravity is high. Use a
he
pe

Check if capacitors need to be reformed

he
ve
ed
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
If the drive has not been powered (either in storage or unused) for over three years, you must reform the capacitors.
You can determine the manufacturing date from the serial number, which you find on the type designation label attached to the drive. The serial number is of format MYYWWRXXXX. YY and WW tell the manufacturing year and week as follows:
4 EN – Quick installation guide
EN
DA
DEESFIFRIT
NL
PT
RU
SVTRCN
YY: 17, 18, 19, … for 2017, 2018, 2019, WW: 01, 02, 03, … for week 1, week 2, week 3,
For information on reforming the capacitors, see Converter module capacitor reforming instructions (3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents
.

Data

IEC ratings

ACH580-31-
3-phase UN = 400 V (380…415 V)
09A5-4 3×2.5+2.5 170M1561 226 12A7-4 3×2.5+2.5 170M1561 329 018A-4 3×2.5+2.5 170M1563 395 026A-4 3×6+6 170M1563 579 033A-4 3×10+10 170M1565 625 039A-4 3×10+10 170M1565 751 046A-4 3×16+16 170M1566 912 062A-4 3×25+16 170M1567 1088 073A-4 3×35+16 170M1568 1502 088A-4 3×50+25 170M1568 1904
Cable Cu (mm
2
) aR fuse Losses
(W)
3AXD00000586715

Select the power cables

See Data on page 4.

Ensure cooling

See Data on page 4. No condensation or frost is allowed. The allowed operating temperature range of the drive without derating is -15 to +40 °C.

Protect the drive and input power cable

See Data on page 4.

A – Install the drive on the wall

See figure A on page 19.

B – Remove the cover

Remove the cover/s. See figures B (R3) and B (R6)... on page 19.
EN – Quick installation guide 5

C – Check the compatibility with IT (ungrounded) and corner-grounded delta systems

See figure C on page 19.
WARNING! If the drive will be connected on an IT (ungrounded or high­resistance grounded) system or on a corner-grounded delta system,
disconnect the EMC filter and ground-to-phase varistor. See the drive hardware manual.
EN

D – Check the insulation of the power cables and the motor

Connect the motor cable at the motor end. For minimum radio frequency interference, ground the motor cable shield 360 degrees at the cable entry of the motor terminal box. See figure D on page 19.
Check the insulation of motor and motor cable. See figure D on page 19. Note: Moisture inside the motor casing will reduce the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement.
Check the insulation of the input cable before connecting it to the drive. Obey the local regulations.

E – Attach the warning stickers in local languages

See figure E on page 20.

F – Connect the power cables

Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor, make sure that is has sufficient conductivity for the PE.
Note for fr power cabling. See the hardware manual for more information.
Procedure:
1. Frame R6:
ame R3: Make sure that you have an additional PE conductor in the input
Remove the shroud on the power cable terminals. See figure F (R6)…
on page 20.
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
2. Remove the rubber grommets from the bottom plate for the cables to be connected. See figure …F… on page 20.
3. Cut an adequate hole into the rubber grommets. Slide the grommets onto the cables.
4. Prepare the ends of the cables. See figure …F… on page 20.
6 EN – Quick installation guide
EN
DA
DEESFIFRIT
NL
PT
RU
SVTRCN
The bare shield will be grounded 360 degrees. Mark the pigtail made from the shield as a PE conductor with yellow-and-green color.
Two alternative symmetrical three-conductor cable types are shown, and one four-conductor cable type. The four-conductor cable is only allowed for the input power cabling.
If you use aluminum cables, put grease to the peeled aluminum cable before connecting it to the drive.
5. Put the cables through the holes of the cable entry plate and attach the grommets to the holes.
6. Connect the cables (use the torques defined in the figure). See figures …F… on page 20:
Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable.
Connect the twisted shield of the cable to the grounding terminal.
Use a separate grounding PE cable (6a) or a cable with a separate PE
conductor (6b) if the conductivity of the shield does not meet the requirements for the PE conductor. If the protective PE conductor is smaller than 10 mm you must use a second earthing conductor. See the hardware manual for more information.
•Frame R3:
Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W
terminals and the phase conductors of the input cable to the L1, L2 and L3 terminals.
Connect the additional PE conductor of the input power cabling.
2
,
7. Frame R6 types bigger than -040A-x: cables.
8. Frames R6
(R6)… on page 21.
9. Secure the cables outside the drive mechanically.
: Install the shroud on the power cable terminals. See figure …F
Cut tabs in the shroud for the installed

G – Connect the control cables

Procedure:
1. Remove the front cover(s) if not already removed.
2. Frame R3
3. Cut an adequate hole into the rubber grommet and slide the grommet onto the cable. Slide the cable through a hole in the bottom plate and attach the grommet to the hole.
4. Route the cables. Frame R3: Frame R6:
: Lift the control panel holder up. See figure G (R3)… on page 21.
See figure …G (R3)… on page 21.
See figure …G (R6)… on page 21.
EN – Quick installation guide 7
5. Ground the outer shield of the cable 360 degrees under the grounding clamp. Keep the cable unstripped as close to the terminals of the control board as possible.
6. Secure the cables inside the drive mechanically.
7.
Ground the pair-cable shields and grounding wire at the grounding terminal (SCR) of the control unit.
8. Connect the conductors to the appropriate terminals of the control unit. See
Default IO connection diagram on page 8.
9. Wire the optional modules if included in the delivery. See the option module user's manual or installation guide.
10. Secure the cables outside the drive mechanically.
Note:
• Leave the other ends of the control cable shields unconnected.
• Keep any signal wire pairs twisted as close to the terminals as possible.

H – Reinstall cover(s)

See figures H (R3, R6).. on page 22.
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
EN
DA
DEESFIFRIT
NL
PT
RU
SVTRCN
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes: 0.14…2.5 mm
2
(26…14 AWG): All terminals
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
max. 500 ohm
1…10 kohm
X1 Reference voltage a nd analog inputs and outputs
1 SCR Signal cable shield (screen) 2 AI1 Output frequency/speed reference: 0…10 V 3 AGND Analog input circuit common 4 +10V Reference voltage 10 V DC 5 AI2 Actual feedback: 0…20 mA 6 AGND Analog input circuit common 7 AO1 Output frequency: 0…10 V 8 AO2 Motor current: 0…20 mA 9 AGND Analog output circuit common
X2 & X3 Aux. voltage output a nd programmable digital inputs
10 +24V Aux. voltage output +24 V DC, max. 250 mA 11 DGND Aux. voltage output common 12 DCOM Digital input common for all 13 DI1 Stop (0) / S tart (1) 14 DI2 Not configured 15 DI3 Constant frequency/speed selection 16 DI4 Start interlock 1 (1 = allow start 17 DI5 Not configured 18 DI6 Not configured
X6, X7, X8 Relay outputs
19 RO1C
Damper control
250 V AC / 30 V DC 2 A
20 RO1A 21 RO1B 22 RO2C
Running
250 V AC / 30 V DC 2 A
23 RO2A 24 RO2B 25 RO3C
Fault (-1)
250 V AC / 30 V DC 2 A
26 RO3A 27 RO3B
X5 Embedded fieldbus 29 B+
Embedded fieldbus, EFB (EIA-485)
30 A- 31 DGND
S4 TERM Termination switch S5 BIAS Bias resistors switch
X4 Safe torque off 34 OUT1
Safe torque off. Factory connection. Both circuits must be closed for the drive to start.
35 OUT2 36 SGND 37 IN1 38 IN2
X10 24 V AC/DC
40
24 V AC/DC+ in
Ext. 24V AC/DC input to power up cont rol unit when the main supply is
disconnected.
41
24 V AC/ DC- in
8 EN – Quick installation guide

Default IO connection diagram

Declaration of Conformity (EU)

EN – Quick installation guide 9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH